ML20202H720

From kanterella
Revision as of 10:48, 1 January 2021 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Rev 29 to AR-403, PSA H Annunciator Response
ML20202H720
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 12/05/1997
From:
FLORIDA POWER CORP.
To:
References
AR-403, NUDOCS 9712100347
Download: ML20202H720 (196)


Text

_ _ ._ . .m. . _ . . _ . _ _ . _ _ _ _ . . _ _ _ . _ _ _ _ . _ . _ _- . . ..

Document Transmittal #: 79081 Date: 12/5/97 Tc: NRC (DC DESK) MAC: N/A Destination:

Description:

Copy- Copy Totals Document: Revision: Comment: # INFO CNTL MSTR AR0403 ' 29 . 24 1- 0 0 l

4 4

i instructions to the Addressee:

-fC O I.4

/

e Please verify the document (s) received agrees with the above information.

Operations department must attach old document (s) or portions of document (s) superseded by the above

' to this transmittal.

Tha signature indicates acknowledgment of receipt of the above document (s) and that documents have be:n updated. Retum signed and dated transmittal to Document Control within 15 working days of transmittal date to mail code:

NA1C Florida Power Corporation Dxument Control, NA1C Crystal RNer Energy complex i l l

15760 W. Power une St. , , , i, 1,1 . l

,. - -- r Crystal RNer, FL 34428-6708 1 j u v o s)

Signature of Addressee: Date:

9712100347 971205 PDR ADOCK 05000302 F PDR a J

Rev.-29 Effective Date /M ' 6 47 l

INFORMAT:ON ONLY a ANNUNCIATOR RESPONSE t AR-403 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 O PSA H ANNUNCIATOR RESPONSE APPROVED BY; InterpretationCoQatt

) ,

li, l 4 l .

Vw] th '

(S{GNATUREONFILE) [ ['

DATE:

INTERPRETATION CONTACT: Manager Nuclear Plant Operations Support

_ _J

TABLE OF CONTENTS SECTION PAGE 1.0 PURP0SE................................................................. 1

2.0 REFERENCES

.............................................................. 1 2.1 IWLEMENTING REFERENCES............................................. 1 2.2 DEVELOPMENTAL REFERENCES............................................ 1 3 . 0 PE RSONNE L INDOCTRINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 4.0 INSTRUCTIONS............................................................ 2 5.0 FOLLOW-UP ACTION 5....................................................... 2 ENCLOSURE 1 An n u n c i a t o r R e s po n s e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 l'

\

L AR-403 Rev. 29 Page i  !

-1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the PSA-Z Lamp box.

1.2 Establish operator actions for valid Annunciator alarms on the PSA-Z Lamp box.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the PSA-Z Lamp box.

2.0 REFER @CES 2.1 IRLIMENTING REFERENCES 2.1.1 E0P,-Emergency Operating Procedure 2.1,2 AP-250, Radiation Monitor Actuation 2.1.3 AP-1050, Flooding 2.1.4 CP-138, Secondary Water Chemistry Guidelines 2.1.5 OP-103B, Heat-Up Cooldown Curves

.2.1.6 SP-146. EFIC Monthly Functional Test 2.1.7 OP-302, F.C Pump Operation 2.1.8 OP-301, Operation Of The Reactor Coolant System 2.1.9 AP-470. Loss of Instrument Air 2.1.10 OP-408, Nucicar Services Cooling System 2.1.11 OP-505, Radiation Monitoring System 2 1.12 CP-152, Primary to Secondary leakage-Operating Guideline 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 O

AR-403 Rev. 29 Page 1 J

I 3.0 PERSOf# DEL IlW0CTRINATION i

O 3.1-l

- The Annunciator System is powered i rom VBDP-5 Breaker 28.

4.0 INSTRUCTIONS 4.1 Respond to alarms on.the PSA-Z Lamp box as indicated on Enclosure 1 Annunciator Response.

S.0 FOLLOW-UP ACTIONS f

None O

O AR-403 Rev. 29 Page 2 m -

ENCLOSURE 1 O (Page 1 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l _

GAMMA l g RADIATION l j. HIGH I I I I EVENT POINT 1748 I INDICATED CONDITION:

o RM-G1 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O G REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G1 INDICATION AT RADIATION MONITORING PANEL.

o RM-G1 INDICATION AT DETECTOR.

o RM-G1 RED ALARM LIGHT.

o - RM-G1 HORN.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND-INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G1 MONITORS THE CONTROL ROOM. THE DETECTOR IS ON THE BACK WALL NEXT TO THE ES RELAY ACTUATION CABINETS. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

ORAWING 208-049-RM-22 SENSING ELEMENT: RADIATION MONITORING PANEL O

V AR-403 Pev. 29 Page 3

O ENCLQSURE 1 (Page 2 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 I I GAMMA RADIATION l l HIGH I I l- l EVENT POINT 1750 INDICATED CONDITION:

o RM-G2 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

A h REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G2 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G2 MONITORS THE CHEMICAL LABORATORY. THE DETECTOR IS LOCATED ON THE EAST WALL INSIDE THE CHEMICAL LABORATORY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-23 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 4 J

a 1

ENCLOSURE 1 (Page 3 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 GAMMA l l RADIATION g l HIGH I  !

l l EVENT POINT 1752 INDICATED CONDITION:

o RM-G3 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O (j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH.RA(,IATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G3 MONITORS THE PRIMARY SAMPLE ROOM. THE DETECTOR IS LOCATED ON THE SOUTH WALL INSIDE THE PRIMARY SAMPLE ROOM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-23 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 5

O ENCLOSilB L 1 (Page 4 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-01 H-01-01 i

i l i I l l GAMMA

, I i RADIATION l I HIGH I I l- l-EVENT POINT 1754 INDICATED CONDITION:

o RM-G4 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G4 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

i o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED APEA(S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505 RADIATION MONITORING SYSTEM.

I DISCUSSION:

RM-G4 MONITORS THE AUXILIARY BUILDING ENTRANCE HALLWAY. THE DETECTOR IS LOCATED ON THE WALL OPPOSITE THE PAX PHONE NEAR'THE ENTRANCE TO THE INTERMEDIATE INFORMATION.

BUILDING. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TRF.ND

REFERENCES:

DRAWING 208-049-RM-24 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 6

ENCLOSURE 1 O (Page 5 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 mrrrrrr I I GAMMA l l RADIATION l l HIGH I I I I EVENT POINT 1756 INDICATED CONDITION:

o RM-G5 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G5 INDICATION AT RADIATION M".4TORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-GS MONITORS THE WASTE GAS TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE 95' AB. ON THE WALL IN THE WASTE GAS VALVE ALLEY, AD]ACENT TO THE DETECTOR. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-045-RM-24

( SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 7

] ENCLOSURE 1 (Page 6 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 pyrrrrrr I I l

GAMMA RADIATION l l HIGH I I I I EVENT POINT 1758 INDICATED CONDITION:

o RM-G6 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-C6 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-C6 MONITORS THE MAKEUP TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE LOCKED CATE. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-25

_ SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 8

ENCLOSURE 1 (Page 7 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-01 H-01-01 P"F======

l l GAMMA l

l g ~ RADIATION l l HIGH ,

I I I l EVENT POINT 1760 I

INDICATED CONDITION:

[ o RM-G7 RADIATION LEVEL EXCEEDS HIGl1 SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G7 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G7 MONITORS TEE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE Wall.

NEAR THE ENTRANCE INSIDE THE LOCKED CATE ON THE 95* ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-25 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 9 m

ENCLOSURE 1 3 (Page 8 of 190)

PSA-Z ANNUNCIATOR-RESPONSE PSA-2-01-01 H-01-01

_I l l GAMMA

l RADIATION l l , HIGH I I I I EVENT POINT 1762 INDICATED CONDITION

o RM-G8 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

cO V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G8 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

! o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G8 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED CATE ON THE 119' ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 10

ENCLOSURE 1 (Page 9 of 190)

PSA-Z ANNUNCIATOR RESPONSE- PSA-Z-01-01 H-01-01 I I GAMMA l RADIATION y  ; HIGH I I I _I EVENT POINT 1764 INDICATED CONDITION:

o RM-G9 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-C9 INDICATION AT RADIATION MONITORING PANEL.

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORINC SYSTEM.

DISCUSSION:

RM-C9 MONITOR 5 THE AREA OUTSIDE THE PERSONNEL HATCH THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 119' ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

(

REFERENCES:

DRAWING 208-049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 11

ENCLOSURE 1 (Page 10 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l l GAMMA fI l

l RADIATION HIGH I I I I i

EVENT POINT 1766 INDICATED CONDITION:

o RM-G10 RADIATION LEVEL EXCEEDS HIGH SETPOINT, O(/ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G10 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G10 MONITORS THE MAKE-UP PUMP AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE TO THE 'C' MAKE-UP PUMP (SOUTH ENTRANCE). THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-27 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 12

~N ENCLOSURE 1 (Page 11 of 190)-

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 1

I GAMMA l RADIATION l HIGH

\ l -

EVENT POINT 1768 INDICATED CONDITION:

o RM Gil RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O

- (Q ' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Gil INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOP. A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTICY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

c OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO UP-5CS, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-Gil MONITORS THE DEBORATING DEMIN ROOM. THE DETECTOR IS LOCATED ON THE WALL INSIDE THE DEMIN ROOM ON THE 119 ELEVATION. THE REDAS 3YSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-27 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 13

ENCLOSURE 1 (Page 12 of 190) i PSA-Z ANNUNCIATOR RESPONSE '

PSA-Z-01-01 H-01-01 I

I I GAMMA l l RADIATION 4 l l HIGH I I I I EVENT POINT 1770 INDICATED CONDITION:

o RM-G12 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G12 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G12 MONITORS THE SPENT RESIN STORAGE 'ANK ROOM. THE DETECTOR IS LOCATED IN THE DECANT AND SLURRY PUMP ROOM JUST INSIDE THE LOCKED CATE ON THE WALL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-28 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 14 mi

l ENCLOSURE 1 (Page 13 of 190) l PSA-Z ANNUNCIATOR RESPONSE H-01-01 P5A-2-01-01 l i GAMMA RADIATION HIGH EVENT POINT 1772 INDICATED CONDITION:

o RM-G13 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Cl3 INDICATION AT PA.DIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5),

c OBSEi .

AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-C13 MONITORS THE DECONTAMINATION PIT AREA. THE DETECTOR IS LOCATED O THE 143' ELEVATION, CLOSE TO THE STAIRWELL BY THE ECSTs THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

P7.FERENCES : DRAWING 208-049-RM-28 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 15

_______..o

ENCLOSURE 1 (Page 14 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l

GAMMA y_ RADIATION g HIGH I

I EVENT POINT 1774 INDICATED CONDITION:

o RM-G14 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

((j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G14 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G14 MONITORS THE SPENT FUEL STORAGE AREA THE DETECTOR IS LOCATED ON THE 143' AB, ON THE WALL OF THE REACTOR BUILDING IN THE PASSAGEWAY TO ThE SPENT FUEL SYSTEM FILTERS. THIS DETECTOR IS THE ONLY S.T.S. AREA MONITOR AND IS COMMONLY REFERRED TO AS THE " SPENT FUEL CRITICALITY MONITOR". THE REDAS SYSTEM f AY ALSO BE USED TO OBSERVE TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-29 SENSING ELEMENT: RADIATION MONITORING PANEL i

AR-403 Rev. 29 Page 16

O ENCLOSURE 1 (Page 15 of 190) 4 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l I  !

I I I l GAMMA l l RADIATION I I HIGH I I I I EVENT POINT 1776 INDICATED CONDITION:

o RM-G15 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o RM-Gl$ INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

c INVESTIGATE CAUSE OF HICH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o IF FUEL MOVEMENT 15 IN PROGRESS, ENSURE FUEL !S PLACED IN A SAFE CONDITION PRIOR TO PERSONNEL EXIT.

o REFER TO OP-505, RADIATION MONITORINC SYSTEM.

DISCUSSION:

RM-C15 MONITORS THE SPENT FUEL AREA. THE DETECTOR IS LOCATED ON THE SPENT FUEL BRIDGE AND MOVES WITH THE BRIDGE. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-29 SENSING ELEMErlT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 17

l ENCLOSURE 1 O (Page 16 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01

{ZZZZZZ GAMMA g  ; RADIATION L

l l HIGH I I I I l EVENT POINT 1778 INDICATED CONDITION:

o RM-G16' RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G16 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FO't TREND INFORMATION.

o IF FUEL MOVEMENT IS IN PROGRESS, ENSURE FUEL IS PLACED IN A SAFE CONDITION PRIOR TO PERSONNEL EXIT.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-C16 MONITORS THE FUEL TRANSFER AREA. THE DETECTOR IS LOCATED ON THE MAIN FUEL BRIDGE AND MOVES WITH THE BRIDGE. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-30 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 18

~!

ENCLOSURE 1 (Page 17 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01 pmp-_ r r r r r l GAMMA g l RADIATION

[. l l HIGH l

l. ._

EVENT POINT 1780 INDICATED CONDITION:

o RM-G17 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

>O Q REDUNDANT INDIC&T*VN WHICH WILL VERIFY ALARM:

o RM-G17 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFOR%ATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-C17 MONITORS THE 119' ELEVATION OF THE REACTOR BUILDING. THE DETECTOR IS LOCATED ON THE STANCH 10N NEAR THE PERSONNEL HATCH. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-30 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 19

O ENCLOSURE 1 (Page 18 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-01 H-01-01 i

I

' GAMMA l  ; RADIATION l l HIGH I I l

1 I EVENT POINT 1782 INDICATED CONDITION:

o RM-G18 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G18 INDICATION AT RADIATION MONITORING PANEL.

'I OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G1B MONITORS THE INCORE PIT AREA. THE DETECTOR IS LOCATED IN THE PIT ON THE 164' ELEVATION NEAR THE TRANSFER CANAL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWIWG 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 20

O ENCLOSURE 1 (Page 19 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01

l. GAMMA g  ; RADIATION l l HIGH I I EVENT PO!NT 1784 INDICATED CONDITION:

o RM-G29/30 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

bb/ - REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G29/30 INDICATION ON HVAC SECTION OF MAIN CONTROL BOARD.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G29/30 ARE THE REACTOR BUILDINI. HIGH RANGE POST ACCIDENT MONITORS.

THE DETECTORS ARE LOCATED ON THE TOP OF EACH 'O' RING AT THE 180' ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

O

REFERENCES:

DRAWING 208-049-RM-32 V

SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 21

O, ENCLOSURE 1 (Page 20 of 190) j l

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 i

GAMMA MONITOR WARNING l

EVENT POINT 1749 I

l- INDI(.ATED CONDITION:

j .

o RM-G1 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G1 RADIATION MONITOR FAILED LOW.

A U REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G1 INDICATION AT RADIATION MONITORING PANEL,

-o RM-G1 INDICATION AT DETECTOR.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

g o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o o

NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREACS).

OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G1 MONITORS THE CONTROL ROOM. THE DETECTOR IS ON THE BACK WALL NEXT TO THE ES RELAY ACTUATION CABINETS. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-22 SENSING ELEMENT: RADIATION MONITORING PANEL L

AR-403 Rev. 29 Page 22

. ~ . ~ . .

ENCLOSURE 1 O

(Pago 21 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 9

GAMMA

~

MONITOR '

WARNING  ;

I EVENT POINT 1751 '

INDICATED CONDITION:

1 o RM-G2 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR, RM G2 P' 'ATION MONITOR FAILED LCW.

O REDJ' NDANT INDICATION WHICH WILL VERIFY ALARM:

o AM G2 INDICATION AT RADIATION MONITORING PANEL.

!- OPERATfsR ACTIONS - FOR A VALID ALARM:

o INVESTMATE CAUSE OF HIGH RADIATION OR, MO\lTOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (3).

o DBSERVE AREA MONITORS /REr. ORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM. ,

1 DISCUSSION!

RM-G2 MONIYORS THE CHEMICAL LABORATORY. THE DETECTOR IS LOCATED ON THE EtST WALL 1H5IDE THE CHEMICAL LABORATORY. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.- THE REDAS SYSTEM j ._ MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

4

REFERENCES:

DRAWING 208-049-RM-23 SENSING ELEMENTi RADIATION MONITORING PANEL AR-403 Rev. 29 Page 23

.._,_ , .m-, - . - - , . - - - . . , , - , , . , . - - - - ,- - . - . ~ . . . . - , - . , . . . - , - - - . . . . . . , , . . - , . . . , - - - - .

l i

O, ENCLOSURE 1 (Page 22 of 190)

PSA-Z ANNUNCIATOR RESPONSE l PSA-2-01-02 H-01-02 GAMMA MONITOR WARNING EVENT POINT 1753 INDICATED CONDITION:

o RM-G3 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR, o RM-G3 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G3 MONITORS THE PRIMARY SAMPLE ROOM. THE DETECTOR IS LOCATED ON THE WALL INSIDE THE PRIMARY SAMPLE ROOM. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

()

REFERENCES:

DRAWING 208-049-RM-23 SENSING ELEMENT: kADIATION MONITORING PANEL AR-403 Rev. 29 Page 24

m _ . . . . . _ _ _ _ _ _ _ . . _ . _ _ _ _ . .

I 1

i ENCLOSURE 1 O (Page 23 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 f

GAMMA MONITOR WARNING EVENT POINT 1755 INDICATED CONDITION:

o RM-C4 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR, o RM-G4 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-C4 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RAMATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, Rt.DIATION MONITORING SYSTEM.

DISCUSSION:

RM G4 MONITORS THE AUXILIARY BUILDING ENTRANCE HALLWAY. THE DETECTOR IS LOCATED ON THE WALL OPPOSITE THE PAX PHONE NEAR THE ENTRANCE TO THE INTERMEDIATE BUILDING.'EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL CIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-24 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 25

ENCLOSURE 1 O- (Page 24 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 l l

1 OfMMA l MONITOR WARNING )

EVENT POINT 1757 INDICATED CONDITION:

o RM-G5 RADIATION if. VEL EXCEEDS WARNING SETPOINT OR, o RM-G5 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G5 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM G5 MONITORS THE WASTE GAS TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE WALL OPPOSITE THE WASTE GAS COMPRESSOR ROOM. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS 'v5 TEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-24 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 26-

() ENCLOSURE 1 (Page 25 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 OAMMA MONITOR WARNING EVENT POINT 1759 i

INDICATED CONDITION:

o RM-G6 RAr>IATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-C6 kADIATION MONITOR FAILED LOW.

I

) REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G6 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION OR.

MONIT0r' LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505. RADIATION-MONITORING SYSTEM.

DISCUSSION:

RM-C6 MONITORS THE MAKEUP TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE LOCKED CATE. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL CIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE-TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-25

() SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 27

O ENCLOSURE 1 (Page 26 of 190)

PSA+2 ANNUNCIATOR RESPONSE PSA Z-01-02 H-01-02 i

GAMMA MONITOR WARNING q

l EVENT POINT 1761 INDICATED CONDITION:

o RM-C' RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G7 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM G7 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR.

MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM G7 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 95' ELEVATION. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-25 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 28

l ENCLOSURE 1 I( ) (Page 27 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 GAMMA MONITOR l WARNING l EVENT POINT 1763 INDICATED CONDITION:

o RM-CB RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G8 RADIATION MONITOR FAILED LOW.

r REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G8 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP 505. RADIATION MONITORING SYSTEM.

DISCUSSION:

RM*C8 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 119' ELEVATION. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWINC 208 049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL

.AR-403 Rev. 25 Page 29

EELD1UEE_l (Page 28 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 GAMMA MONITOR WARNING- -

t EVENT POINT 1765 INDICATED CONDITION:

o RM-G9 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM G9 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G9 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5). .

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G9 MONITORS THE PERSONNEL HATCH. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED CATE ON THE 119' ELEVATION. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 30

ENCLOSURE 1 I (Page 29 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 l l

l GAMMA MONITOR WARNING EVENT POINT 1767 INDICATED CONDITION:

o RM-G10 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G10 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-CIO INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).  !

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-CIO MONITORS THE MAKE-UP PUMP AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE TO 1HEC' MAKE 'JP PUMP (SOUTH ENTRANCE), EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-27 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 31

i i

O 5

ENCLOSURE 1 (Page 30 of 190) 1 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA h40NITOR l VVA,RNING 1-

)

EVENT POINT 1769 INDICATED CONDITION:

o RM-Gil RADIATION LEVEL EXCEEDS WARNING SETPOINT OR j o RM-Gil RADIATION MONITOR FAILED LOW.

I i {'Ss/

g REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Gil INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING. *

' o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

$ RM-CII MONITORS THE DEBORATING DEMIN ROOM. THE DETECTOR 15 LSCATED ON THE WALL INSIDE THE DEMIN ROOM ON THE 119' ELEVATION. EITHER WARNING SETPOINT i

EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-27

) SENSING ELEMENT: RADIATION MONITORING PANEL 1

AR-403 Rev. 29 Page 32

i ENCLOSURE 1 O (Page 31 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 GAMMA MONITOR WARNING I

EVENT POINT 1771 INDICATED CONDITION:

o RM-G12 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G12 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G12 INDICATION AT RADIATION MONITORING PANEL.

t OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-G12 MONITORS THE SPENT RESIN STORAGE TANK ROOM. THE DETECTOR IS LOCATED IN THE DECANT AND SLURRY PUMP ROOM JUST INSIDE THE LOCKED GATE. EITHER LWARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-28

) SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 33

l 1

() ENCLOSURE 1 (Page 32 of 190) i PSA-Z ANNUNCIATOR RESPONFE PSA-2-01-02 H-01-02 s

F GAMMA MONITOR WARNING EVENT POINT 1773 INDICATED CONDITION:

o RM-G13 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G13 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G13 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR k VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR.

M0?.Il0R LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR A,tFECTED AREA (5),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATI0F o REFER TO OP-$05, RADIATION MONITORINC= SYSTEM.

DISCUSSION:

RM-G13 MONITORS THE DECONTAMIhATION PIT AREA. THE DETECTOR IS LOCATED ON THE 143' ELEVATION. CLOSE TO THE STAIRWELL BY THE ECSTs. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-28

) SENSING ELEMENT: RADIATION MONITORING PANEL l

AR-403 Rev. 29 Page 34 n .

ENCLOSURE 1 (Page 33 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02

_ l il GAMMA MONITOR WARNING EVENT POINT 1775 INDICATED CONDITION:

o RM-G14 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G14 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATI0F WHICH WILL VERIFY ALARM:

o RM-CI4 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH RADIATION OR, MONITOR LOW READING.

o NOTIPY HEALTH PHYSICS TO MONITOR AFFECTED AREACS).

o OBSFRVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

' DISCUSSION:

RM-G14 MONITORS THE SPENT FUEL STORAGE AREA. THE DETECTOR IS LOCATED ON THE 143' AB. ON THE WALL OF THE REACTOR BUILDING IN THE PASSAGEWAY TO THE SPENT FUf'. SYSTEM FILTERS. THIS DETECTOR IS COMMONLY REFERRED TO AS THE

" SPENT 'UEL CRITICALITY MONITOR". THE REDAS SYSTEM MAY ALCO BE USED TO OBSEP',E TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM '

SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 35

fEL01UBL1 O (Page 34 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 a

i I

.i GAMMA MONITOR 3 WARNING 4

EVENT POINT 1777 i

l INDICATED CONDITION: I o RM-G15 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR 1 o RM-G15 RADIATION MONITOR FAILED LOW.

b V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l' o RM-G15 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

-RM-f15 MONITORS THE SPENT FUEL AREA. THE DETECTOR IS LOCATED ON THE SPENT FUEL BRIDGE AND MOVES WITH THE BRIDGE. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL CIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWINC 208-049-RM-29 SENSING ELEMENT: RADIATION MONITORING PANEL

AR-403 Rev. 29 Page 36

1 I

ENCLOSURE 1 (Page 35 of 190) i PSA-Z ANNUNCIATOR RESPONSE PSA-7-01-02 H-01-02 l l 1

GAMMA l MONITOR WARNING EVENT POINT 1779 INDICATED CONDITION:

o RM-G16 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G16 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G16 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

I DISCUSSION:

RM G16 MONITORS THE FUEL TRANSFER AREA. THE DETECTOR IS LOCATED ON THE MAIN FUEL BRIDGE AND MOVES WITH THE BRIDGE. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WI' L GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-30

() SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 37

l l

() ENCLOSURE 1 (Page 36 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 GAMMA MONITOR -

WARNING l

EVENT POINT 1781 INDICATED CONDITION:

o RM-G17 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G17 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM G17 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE-CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5),

o . 0BSERVE AREA MONITORS /h: CORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM GI7. MONITORS THE '119' ELEVATION OF THE REACTOR BUILDING. THE DETECTOR IS LOCATED ON THE STANCHION NEAR.THE PERSONNEL HATCH. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-30 O SENSING ELEMENT: RADIATION MONITORIN PANEL AR-403 Rev. 29 Page 38

! i I

~

ENCLOSURE 1

  • (Page 37 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 ,

OAMMA MONITOR '

WARNING l

l l

EVENT PO!NT 1783 ,

INDICATED CONDITION:

t i o RM-G18 RADIATION LEVEL' EXCEEDS WARNING SETPOINT OR o RM-G18 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 RM-G18 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

l l

o INVESTICATE CAUSE OF HIGH RADIATION OR.

MONITOR LOW READING.

  • o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED -ikEA(5),

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT.

o REFER TO OP-505 RADIATION MONITORING SYSTEM.

DISCUSSION:

RM G18 MONITORS THE INCORE PIT AREA. THE DETECTOR IS LOCATED IN THE PIT ON THE 164' ELEVATION NEAR THE TRANSFER CANAL. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.- THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 39

-i

(

O ENCLOSURE _1 (Page 38 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA MONITOR WARNING I

EVENT POINT 1785 INDICATED CONDITION:

4 o

RM-C29/30 RADIATION LEVEL EXCEEDS WARNING SETPOINT(S) OR o RM-G29/30 RADIATION MONITOR (S) FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-C29/30 INDICATION ON HVAC SECTION OF MAIN CONTROL BOARD.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CA'ISE OF HIGH RADIATION OR MONITOR (S) LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT. '

o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-C29/30 ARE THE REACTOR BUILDING HIGH RANGE POST ACCIDENT MONITORS.

THE DETECTORS ARE LOCATED ON THE TOP OF EACH 'O' RING AT THE 180' ELEVATION. EITHER WARNING SETPOINT(S) EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 40 J

O ENCLOSURE 1 (Page 39 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-05 H-01-05 l

MN SYM LINE l

A/B HIGH RAD MONITOR Fall l

EVENT POINT 1977 l

l INDICATED CONDITION:

o RM-G25/26/27/28 RADIATION LEVEL EXCEEDS ALARM SETPOINT OR o RM G25/26/27/28 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G25/26/27/28 INDICATION ON HVAC SECTION OF MAIN CONTROL BOARD.

o AUDIBLE INDICATION ON RADIATION MONITOR (5) o SPDS ALPHA PACE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR LOW MONITOR READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (5).

o REFER TO E0P-06, STEAM CENERATOR TUBE RUPTURE.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM G25/28 MONITOR THE ATMOSPHERIC DUMP LINES MSV-25/A1 AND MSV-26/B2.

RM-G26/27 MONITOR THE MAIN.5 TEAM LINES B1 AND A2 RESPECTIVELY. THE DETECTORS ARE ALL LOCATED ON THE 119' ELEVATION OF THE INTERMEDIATE BUILDING ON THEIR RESPECTIVE STEAM LINE. EITHER RADIATION SETPOINT EXCEEDED O_R A DETECTOR FAILED LOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-47 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 41

l l

l EEtointi (Page 40 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-07 H-01-07 DO STOR TANK LEVEL HIGH/ LOW EVENT POINT 1512 INDICATED CONDITION:

o DO STORACE TANK LEVEL >97" H,0 AS SENSED BY DO-4-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o-INVESTICATE CAUSE OF HIGH LEVEL.

o NOTIFY SECONDARY PLANT OPERATOR TO OBSERVE LOCAL LEVEL INDICATOR.

DISCUSSION:

THE DO STORACE TANK HAS AN AUTO FILL FEATURE IF THE LEVEL IS HIGH AND RISING THE FILL VALVE MAY BE STUCK OPEN.

REFERENCES:

DRAWING 208-022-00-07 V.- SENSING ELEMENT: DO-A-LS AR-403 Rev. 29 Page 42

l ENCLOSURE 1 (Page 41 of 190)

PSA-2 ANNUNCIATOR RESPONSE PSA-2-01-07 H-01-07 I l

DO STOR TANK LEVEL l HIGH/ LOW EVENT POINT 1520 INDICATED CONDITION:

o DO STORAGE TANK LEVEL <33' H,0 AS SENSED BY DO-3-LS O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS F0r, A VALIO ALARM:

o . INVESTIGATE CAUSE OF LOW LEVEL.

o NOTIFY SECONDARY PLANT OPERATOR TO 0BSERVE LOCAL LEVEL INDICATOR, DISCUSSION:

THE DO STORAGE TANK HAS AN AUTO FILL FEATURE. IF THE LEVEL IS LOW AND NOT RISING THE FILL VALVE MAY BE STUCK CLOSED, OR DO WATER FROM UNITS 1/2 WATER TREATMENT BUILDING IS NOT AVAILABLE. CONTACT UNITS 1/2 TO INVESTICATE.

.REFEkENCES: . DRAWING 208-022-00-07 SENSING ELEMENT: 00 3-LS

-AR-403 Rev. 29 Page 43

I i

ENCLOSURE 1 (Page 42 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l

i l . _ _

l l l. ATMOSPHCHIC l l RADIAT;ON l } H10H i l I i l l EVENT POINT 1712 INDICATED CONDITION:

o RM-Al RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Al INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PACE.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-250, o INVESTIGATE CAUSE OF HICH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RW Al MONITORS THE REACTOR BUILDING PURCE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED. PARTICULATE, IODINE AND CAS ANY ONE OF THESE CHANNELS CAN INFORMATION,CIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND

REFERENCES:

DRAWING 208-049-RM-16 N SENSING ELEMENT: RADIATION MONITCRING PANEL AR-403 Pev. 29 Page 44 m

l l

! ENCLOSURE 1 (Page 43 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 i

I

, ATMOSPHERIC l RADIATION l NIGH

- I EVENT POINT 1715 INDICATED CONDITION:

o RM-A2 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM.A2 INDICATION AT RADI ATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOP. ACTIONS FOR A VALID ALARM:

)

o REFER -TO AP 250.

o INVESTICATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS COR TREND INFORMATION o REFEP TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION: I RM-A2 MONITORS THE AUXILIARY BUILDING PURCE EXHAUST DUCT. THRLE DIFFERENT DETECTORS ARE USED, PARTICULATE. IODINE AND CAS. ANY ONE OF THESE CHANNELS CAN CIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL

.AR-403' Rev. 29 Page 45

! ENCLOSURE 1-(Page 44 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l l ATMOSPHERIC

; RADIATION l [ HIGH I I I I EVENT POINT 1718 INDICATED CONDITION

o RM-A3 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-250.

o INVESTICATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A3 MONITORS AUXILIARY BUILDING EXHAUST FROM SAMPLE AREA 'D', THE WASTE CAS COMPRESSOR ROOM, THE WASTE CAS VALVE ALLEY, AND AD3OINING AREAS.

THIS DETECTOR ONLY HAS A GAS CHANNEL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM 17 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 46

fE Loss n _1 (Page 45 of 190) -

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l

l ZZZZZ l I

l ATMOSPHERIC l l RADIATION l l HIGH I I I I EVENT POINT 1721 INDICATED CONDITION

o RM-A4 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM- A4 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-250, o INVESTICATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505. RADIATION MONITORING SYSTEM.-

DISCUSSION: '

RM A4 MONITOR 5 THE SPENT FUEL AREA EXHAUST. THIS DETECTOR ONLY HAS A GAS CHAMEL. THF REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-17 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 47

lE ENCLOSURE 1 l

(Page 46 of 190) i PSA-Z ANNUNCIATOR RESPONSE lPSA-2-02-01 H-02-01 ATMOSPHERIC l RADIATION HIGH 1

1 1

EVENT POINT 1724 IND7'.ATED CONDITION:

\ o RM-A5 RADIATION LEVEL EXCEEDS HIOt SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A5 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PACE.

r OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-250.

o INVESTICATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

. DISCUSSION:

RM-A5 MONITORS THE CONTROL COMPLEX RETURN DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE. IODINE AND CAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-18 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 48

I

( ENCLOSURE 1 (Page 47 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l

~

1 I I I

, , ATMOSPHERIC l l RADIATION l l l HIGH I I I I I EVENT POINT 1727 INDICATED CONDITION:

o RM-A6 RADIATION LEVEL EXCEEDS HICH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A6 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE. SAMPLE POINTS ARE EITHER AHF-38 DUCT, OR THE RB ATMOSPHERE DIRECTLY.

IT IS NORMALLY LINED UP TO THE DUCT OF AHF-38. IT CAN ALTERNATELY BE LINED UP TO SAMPLE THE RB ATMOSPHERE DIRECTLY PER OP-417. TWO DIFFERENT DETECTORS ARE USED, PARTICULATE / BETA AND CAS. ANY ONE OF THESE CHANNELS CAN CIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

(D V

REFERENCES:

DRAWING 208-049-RM-18 SENSING ELEMENT: RADIATION MONITORING PANEL lAR-403 Rev. 29 Page 49

ENCLOSURE 1 (Page 48 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-01 H-02-01 I

l I i I ATMOSPHERIC RADIATION l HIGH l

1 EVENT POINT 1730 INDICATED CONDITION:

o RM-A7 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A7 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A7 MONITORS THE AHF-44A/B DISCHARCE AIR, THEREFORE THE ATMOSPHERES OF-THE PRIMARY SAMPLE ROOM, PRIMARY SAMPLE ROOM SAMPLE HOOD, RADIO CHEMISTRY LAB SAMPLE HOODS, AND/OR PASS SYSTEM VALVE ALLEY MAY HAVE HICH CASE 005 ACTIVITY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208+049-RM-19 O SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 50-

i l

l6 ENCLOSURE 1 lt 4 (Page 49 of 190)

'PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 ATMOSPHERIC RADIATION i

HIGH EVENT POINT 1733 INDICATED CONDITION:

l .

} o RM-A8 RADIATION LEVEL EXCEEDS HIGH SETPOINT, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A8 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR /, VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A8 MONITORS THE AUXILIARY BUILDING EXHAUST UPSTREAM OF THE PENETRATION FOR THE FbEL HANDLING FLOOR t"HAUST. iHE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION. ,

j

REFERENCES:

DRAWING 208-049-RM-19 V SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 51 7's ~

i

(g ENCLOSURE 1 1

(j (Page 50 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 k 2-01 l

l l l I I ATMOSPHERIC I I RADIATION I l - HIGH I -l '

I I EVENT POINT 1736 INDICATED CONDITION:

o RM-All RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-All INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o IPT.'ESTICATE CAUSE OF HIGH RADIATION. '

o If~?ASTE GAS RELEASE IN PROGRESS, NOTIFY FtIMARY PLANT OPERATOR TO ENWRE _WCDT RECYCLE VALVES AND RELEASE VALVE ARE CLOSED.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM All MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR THE WASTE GAS RELEASE PATH. THE WCDT RECYCLE VALVES ARE WDV 393/394/355 AND THE RELEASE VALVE IS WDV-439. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-20 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 52-I

. )

l ENCLOSURE 1 (Page 51 of 190) i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 i.

ATMOSPHERIC -

; RADIATION l l - HIGH I -1 I I EVENT POINT 1738 INDICATED CONDITION

o RM-A12 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A12 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

o MAIN STEAM LINE RAD MONITORS RMG-25, RMG-26, RMG-27,' AND /OR RMG-28 READ HIGHER THAN NORMAL.

OPERATOR ACTIONS FOR A VALID ALARM:  :

o REFER TO E0P-06, STEAM GENERATOR TUBE RUPTURE.

o INVESTICATE CAUSE OF HIGH RADIATION. t o

OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.  ;

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A12 MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR SECONDARY PLANT CONDENSER OFF GAS. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-20 b SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 53

. s

ENCLOSURE 1 j (Page 52 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l l ATMOSPHERIC

l RADIATION i j l .

HIGH I I I I EVENT POINT 1742 INDICATED CONDITION:

o RM-A14 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

l

)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A14 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A14 IS A PORTABLE MONITOR, NORMALLY LOCATED NEAR THE PRIMARY SAMPLE LABORATORY. THIS MONITOR IS NOT NORMALLY ENERGIZED. THC REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES. DRAWING 208-049-RM-21 SENSING ELEMENT: RADIATION MONITORING PANEL l

AR-403 Rev. 29 Page 54

l ENCt_05URE 1 (Page 53 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 K ZZZZZ l ATMOSPHERIC l l RADIATION l l HIGH I I I I EVENT POINT 1745 INDICATED CONDITION:

o RM-A15 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A15 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A15 IS A PORTABLE MONITOR,

..T MALLY LOCATED NEAR THE DECONTAMINATION PIT ON THE SPENT FUEL FLOOR. TetIs MONITOR IS NOT NORMALLY ENERGIZED. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-22 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 55

ENCLOSURE 1 (Page 54 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-02 H-02-02 5

L ATMOSPHERIC -

MONITOR WARNING ll EVENT POINT 1713 INDICATED CONDITION:

o RM Al RADIATION LEVEL EXCEED 3 WARNING SETPOINT, OR o RM-Al RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Al INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION. OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-Al MONITORS THE REACTOR BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND CAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED--

LOW. THE-REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16

) SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 56

ENCLOSURE 1

, (Page 55_of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1714 INDICATED CONDITION:

o RM-Al RADIATION 40NITOR PUMP FLOW AROVE NORMAL QR LESS THAN 5 SCFM.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ' RM-Al FLOW INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-AI MONITORS THE REACTOR BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS APE USED, PARTICULATE, IODINE AND CAS. EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING - 208-049-RM-01 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 57

iG ENCLOSURE 1

() (Page 56 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1716 INDICATED CONDITION:

9 o RM-A2 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A2 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A2 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A2 MONITORS THE AUXILIARY BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND CAS. ANY ONE OF THESE CHANNELS CAN CIVE THIS ALARM, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED LOW. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 58

( ENCLOSURE 1 (Page 57 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 l

ATMOSPHERIC MONITOR l- WARNING EVENT POINT 1717 INDICATED CONDITION:

o RM-A2 RADIATION MONITOR PUMP FLOW ABOVE NORMAL QB LESS THAN 5 SCFM.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A2 FLOW INDICATION AT RADIATION MONITORIFG PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A2 MONITORS THE AUXILIARY BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND CAS. EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-02

( SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 59

ENCLOSURE 1 (Page 58 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 L

ATMOSPHERIC MONITOR WARNING EVENT POINT 1719 INDICATED CONDITION:

o RM-A3 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A3 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A3 MONITORS AUXILIARY BUILDING EXHAUST FROM SAMPLE AREA'D', THE WASTE GAS COMPRESSOR ROOM, THE WASTE GAS VALVE ALLEY, AND ADJOINING AREAS. THIS DETECTOR ONLY HAS A CAS CHANNEL AND EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 60

O ENCLOSURE 1 (Page 59 of 190) i PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-02 H-02-02 I

I l

i l -

ATMOSPHERIC MONITOR WARNING EVENT POINT 1720 INDICATED CONDITION:

o RM-A3 RADIATION MONITOR PUMP FLOW ABOVE NORMAL QB LESS THAN 5 SCFM.

O-V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A3 FLOW INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

015CU55 ION:

RM-A3 MONITORS AUXILIARY BUILDING EXHAUST FROM SAMPLE AREA 'D', THE WASTE GAS COMPRESSOR ROOM, THE WASTE GAS VALVE ALLEY, AND ADJOINING AREAS. THIS

- THIS DETECTOR ALARM.

ONLY HAS A GAS CHANNEL AND EITHER A HIGH OR LOW FLOW CAN GIVE g

REFERENCES:

DRAWING 208-049-RM-03 b SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 61

() ENCLOSURE 1 (Page 60 of 190)

PSA-Z ANNUNCIATOR RESPONSE -PSA-2-02-02 H-02-02 i

ATMOSPHERIC MONITOR VVARNihH3 EVENT POINT 1722 INDICATED CONDITION:

o RM-A4 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A4 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A4 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR i

LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TC' OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A4 MONITORS THE SPENT FUEL AREA EXHAUST. THIS DETECTOR ONLY HAS A GAS CHANNEL AND EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL

-GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND LNFORMATION.

REFERENCES:

DRAWING 208-049-RM-17 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 62

ENCLOSURE 1 (Prje Al of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H ' bO2 l

ATMOSPHERIC MONITOR WARNING EVENT POINT 1723 I INDICATED CONDITION:

o RM-A4 RADIATION MONITOR PUMP FLOW ABOVE NORMAL QE LESS THAN 5 SCFM.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A4 FLOW INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS OR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

f DISCUSSION:

RM-A4 MONITORS THE SPENT FUEL AREA EXHAUST. THIS DETECTOR ONLY HAS A CAS CHANNEL AND EITHER A HIGH OR LOW FLOW CAN CIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-04 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 63

ENCLOSURE 1 (Page 62 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING l.

EVENT POINT 1725

)

f INDICATED CONDITION:

o RM-A5 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A5 RADIATION MONITOR FAILED LOW

,O

/  !

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: 1 o - RM-A5 INDICATION AT RADIATION MONITORING PANEL'.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER'TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A5 MONITORS THE CONTROL COMPLEX RETURN DUCT. THREE DIFFERENT DETECTORS ARE USED. PARTICULATE, IODINE AND CAS. ANY ONE OF TiiESE CHANNELS CAN GIVE THIS ALARM, EITHER WARNING SETPOINT EXCEEDED, OR- DLTECTOR FAILED LOW. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-18 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 64

ENCLOSURE 1 j (Page 63 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 I

ATMOSPHERIC MONITOR WARNING EVENT POINT 1726 INDICATED CONDITION:

o RM-A5 RADIATION MONITOR PUMP FLOW AB0VE NORMAL DE LESS THAN 5 SCFM.

D (Nj REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A5 FLOW INDICATION AT RADIATION MONITOR.JG PANEL.

CDERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A5 MONITORS THE CONTROL COMPLEX RETURN DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE IODINE AND CAS. EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM- )5 1

%./ SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 65

() ENCLOSURE 1 (Page 64 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING t

EVENT. POINT 1728 INDICATED CONDITION:

o RM-A6 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A6 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A6 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PACE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE. SAMPLE POINTS ARE EITHER AHF-3B DUCT OR THE RB ATMOSPHERE DIRECTLY. IT IS NORMALLY LINED UP TO THE DUCT' 0F AHF-3B.

IT CAN ALTERNATELY BE LINED UP TO SAMPLE THE RB ATMOSPHERE DIRECTLY PER OP-417.

] TWO DIFFERENT DETECTORS ARE USED, PARTICULATE / BETA AND CAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM.

O THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REF:RENCES: DRAWINC 208-049-RM-18 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 66 a

.A ENCLOSURE 1

() (Page 65 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-02 H-02-02 ATMOSPHERIC MONITOR l WARNING l

l EVENT POINT 1729 INDICATED CONDITION:

o RM-A6 RADIATION MONITOR PUMP FLOW ABOVE NORMAL, LESS THAN 5 SCFM, ,

QB RMA-6 BACKUP SAMPLE PUMo IS RUNNING.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A6 FLOW INDICATION AT RADIATION MONITORING PANEL.

! OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

EITHER A HIGH OP LOW FLOW CAN GIVE THIS ALARM.

RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE. SAMPLE POINTS ARE EITHER AHF-3B DUCT. OR THE RB ATMOSPHERE DIRECTLY. IT IS NORMALLY LINED UP TO TrtE DUCT OF AHF-38. IT CAN ALTERNATELY BE LINED UP TO SAMPLE THE RB ATMOSPHERE DIRECTLY PER OP-417.

l TWO DIFFERENT DETECTORS ARE USED, PARTICULATE / BETA AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM.

p THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

b)

REFERENCES:

DRAWING 208-049-RM-06 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 67

() ENCLOSURE 1 (Page 66 of 190)_

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1731 INDICATED CONDITION:

o RM-A7 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A7 RADIATION MONITOR FAILED LOW

) REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A7 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A7 MONITORS THE AHF-44A/B DISCHARGE AIR, THEREFORE THE ATMOSPHERES OF THE PRIMARY SAMPLE ROOM, PRIMARY SAMPLE ROOM SAMPLE HOOD, RADIO CHEMISTRY LAB SAMPLE HOODS, AND/0R PASS SYSTEM VALVE ALLEY MAY HAVE HIGH GASEOUS ACTIVITY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-19 SENSING ELEMENT: RADIATION MONITORING PANEL (J'T 4

AR-403 Rev. 29 Page 68

O ENCLOSURE _,1 (Pace 67 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA 02-02 H-02-02 l ATMOSPHERIC MONITOR WARNING EVENT POINT 1732 INDICATED CONDITION:

o RM-A7 RADIATION MONITOR PUMP FLOW ABOVE NORMAL DE LESS THAN 5 SCFM.

f}

h REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A7 FLOW INDICATION AT RADIATION MONITORING PANEL, OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM. RM-A7 MONITORS THE AHF-44A/B DISCHARGE AIR, THEREFORE THE ATMOSPHERES OF THE PRIMARY SAMPLE ROOM, PRIMARY SAMPLE ROOM SAMPLE HOOD, RADIO CHEMISTRY LAB SAMPLE HOODS, AND/OR PAS 5 SYSTEM VALVE ALLEY MAY HAVE HIGH GASEOUS ACTIVITY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-07 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403- Rev. 29 Page 69

~ .

() ENCLOSURE 1 (Page 68 of 190)

I PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 i

ATMOSPHERIC MONITOR WARNING EVENT POINT 1734 INDICATED CONDITION:

o RM-A8 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A8 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A8 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TRrND INFORMATION.

o REFER TO OP-505, RADIATION MONITC~.iNG SYSTEM.

DISCUSSION:

RM-A8 MONITORS THE AUXILIA.f BUILDING EXHAUST UPSTREAM OF THE PENETRATION FOR THE FUEL HANDLING FLOOR EXHAUST. THIS DETECTOR ONLY HAS A CAS CHANNEL AND. EITHER WARNING SEfPOINT EXCEEDED, OR DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16

\s_/ SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 70

O ENCLOSURE 1 (Page 69 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1735 INDICATED CONDITION:

o RM-A8 RADIATION MONITOR PUMP FLOW ABOVE NORMAL QB LESS THAN 5 SCFM.

O

i. j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A8 FLOW INDICATION AT RADIATION.MONITORINC PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-A8 MONITORS THE AUXILIARY BUILDING EXHAUST UPSTREAM OF THE PENETRATION FOR THE FUEL HANDLING FLOOR EXHAUST. THIS DETECTORS ONLY HAS A GAS CHANNEL AND, EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-08 I

SENSING ELEMENT: RADIATION MONITORING PANEL t

AR-403 Rev. 29 Page 71

O ENCLOSURE 1 (Page 70 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 l

l ATMOSPHERIC l

' MONITOR WARNING EVENT POINT 1737 INDICATED CONDITION:

o RM-All RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-All RADIATION MONITOR FAILED LOW

,O\

Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:.

o RM-All INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

RM-All MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR THE WASTE GAS RELEASE PATH. THIS DETECTOR ONLY HA5 A CAS CHANNEL AND, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED LOW CAN GIVE THIS ALARM. ThE REDA5 SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWINC 208-049-RM-20 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 72

ENCLOSURE 1 (Page 71 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 l ~

l ATMOSPHERIC MONITOR WARNING t

EVENT POINT 1739 i

INDICATED CONDITION:

o RM-A12 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A12 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A12 INDICATION AT RADIATION MCNITORING PANEL.

o MAIN STEAM LINE RAD MONITORS RMG-25, RMG-26, RMG-17, AND/OR RMG-28 READ HIGHER THAN NORMAL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION MONITOR PROBLEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM. '

o CHECK ARV-26/27 FOR PROPER POSITION (ARP-1A/1B 3-WAY VALVES) o REFER TO CP-152, PRIMARY TO SECONDARY LEAKAGE OPERATING GUIDELINE DISCUSSION:

RM-A12 MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR SECONDARY PLANT CONDENSER OFF GAS. THIS DETECTOR ONLY HAS A CAS CHANNEL AND, EITHER t

WARNING SETPOINT EXCEEDED OR DETECTOR FAILED LOW CAN GIVE TilIS ALARM, CHECK FOR SUPPORTING INDICATIONS OF OTSC TUBE LEAKAGE.

REFERENCES:

DRAWING 208-049-RM-20

, SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 73

ENCLOSURE 1 (Page 72 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-04 H-02-04 EDAS SYSTEM TROUBLE l

t EVENT POINT 2045 INDICATED CONDITION:

o LOSS OF MULTIPLEXER POWER.

o PRIMARY METEOROLOGICAL TOWER ON BACKUP POWER.

o PRIMARY METEOROLOGICAL TOWER BACKUP POWER OUT OF SYNCHRONIZATION.

o PRIMARY METEOROLOGICAL TOWER SIGNAL FAILURE, k' o PRIMARY METEOROLOGICAL TOWER BUILDING TEMPERATURE HIGH/ LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o PRIMARY METEOROLOGICAL ALARM PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-070-MM-01 SENSING ELEMENT: MMP 3 METEOROLOGICAL ALARM PANEL AR-403 Rev. 29 Page 74

i ENCLOTURE 1 (Page 73 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-05 H-02-05 COND PUMP PIT i

SUMP LEVEL HIGH EVENT POINT 1329 INDICATED CONDITION:

o CONDENSATE PUMP PIT SUMP A LEVEL >88.6' ELEVATION AS SENSED BY SD-31-LS.

.c REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-1050.

o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-072-50-07 SENSING ELEMENT: SD-31-LS

)

AR-403 Rev. 29 Page 75 i nr '

ERCLOSURE 1 k (Page 74 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-05 H-02-05 COND PUMP PIT SUMP LEVEL HIGH EVENT POINT 1317 INDICATED CONDITION:

o CONDENSATE PUMP PIT SUMP B LEVEL >88.6' ELEVATION AS SENSED BY SD-32-LS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-1050.

o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-072-50-08 SENSING ELEMENT: SD-32-LS

R-403 Rev. 29 Page 76

ENCLOSURE 1 O- .

(Paca 75 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-06 H-02-06 AUX BLDG SUMP LEVEL HIGH EVENT POINT 1292 INDICATED CONDITION:

o DECAY HEAT PIT SUMP A LEVEL >74' ELEVATION AS SENSED BY WD-133-LS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-060-wD-09

,. SENSING ELEMENT: WD-133-LS AR-403 Rev. 29 Page 77

O ENCLOSURE 1 (Page 76 of 190)

PSA-Z ANNUNCIATOR RESPONSE- PSA-2-02-06 H-02-06 h

AUX BLDG SUMP LEVEL HIGH EVENT POINT 1305 INDICATED CONDITION:

o DECAY HEAT PIT SUMP B LEVEL >74' ELEVATION AS SENSED BY WD-134-LS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

l DISCUSSION:

l~

REFERENCES:

DRAWING 208-060-WD-10 SENSING ELEMENT: WD-134-LS AR-403 Rev. 29 Page 78

ENCLOSURE 1 (Page 77 of 190)

FSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-06 H-02-06 I AUX BLDG SUM

  • LEVEL H10H EVENT POINT 1300 I

INDICATED CONDITION:

4 o AUXILIARY BUILDING SUMP LEVEL >92.5' ELEVATION AS SENSED BY WD-132-15.

O kEDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-060-wD-12 SENSING ELEMENT: WD-132-L5 AR-4J3 Rev. 29 Pt.ge 79

I ENCLOSURL1 O (Page 78 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-06 H-02-06 AUX BLDG SUMP LEVEL HIGH EVENT PO!NT 1809 INDICATED CONDITION:

o NUCLEAR SERVICE COOLER AREA SUMP >93'1" ELEVATION AS SENSED BY SD-5-LS.

O REDUNDANT INDICATION W3ICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o THIS LEVEL SWITCH 15 A MECHANICAL ALTERNATOR WHICH OPERATES BOTH SDP-2A AND 2B.

SWITCH #1 STARTS THE LEAD PUMP AT 93'0" AND SWITCH #2 STARTS THE LAG PUMP AT 93'1" AND INITIATES THE HIGH LEVEL ALARM.

REFERENCES:

ORAWING 208 072-50-03

/ SENSING ELEMENT: SD-5-L5 AR-403 Rev 29 Page 80 m

f ENCLOSURE 1 Os (Page 79 of 190) .

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-06 H-02-05 I

AUXBLDG SUMP LEVEL HIGH EVENT POINT 1810 INDICATED CONDITION:

o TENDON ACCESS GALLERY SUMP >71'1" ELEVATION AS SENSED BY SD-6-LS.

O ,

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o THIS LEVEL SWITCH IS A MECHANICAL ALTERNATOR WHICH OPERATES BOTH SDP-3A AND 38. SWITCH #1 STARTS THE LEAD PUMP AT 71'0" AND SWITCH #2 STARTS THE LAC PUMP AT 71'1" AND INITIATES THE HICH LEVEL ALARM.

REFERENCES:

DRAWINC 208-072-5D-05 -

A SENSINC ELEMENT: SD-6-LS O

AR-403 Rev. 29 Page 81

i ENCLOSUBl J l (Page 80 of 190)

PSA-ZANbCIATORRESPONSE PSA-2-02-07 H-02-07

)

BLDG SUMPS SUMP PUMP l TROUBLE I EVENT POINY 1196  ;

I INDICATED CONDITION:

o DIESEL GENERATOR SUMP A/B LEVEL HIGH AS SENSED BY EG-027-LS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALIO ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTICATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-027-EG-17 SENSING ELEMENT: EG-027-LS.

AR-403 Rev. 29 Page 82

O ENCLOSURE 1 (Page 81 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z vs-07 H-02-07 BLDG SUMPS SUMP PUMP TROUBLE EVENT POINT 1586 INDICATE l: CONDITION:

o DECAY HEAT PIT SUMP PUMP AUTO START.

o DECAY HEAT PIT SUMP PUMP TRIP.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDI110N.

DISCUSSION:

THIS ALARM MAY INDICATE AN AUTO SHUT DOWN IF THE PRIMARY PLANT OPERATOR MANUALLY STARTED THE DECAY HEAT PIT SUMP PUMP. THE ALARM IS BASED ON THE PUMD CONTROL SWITCH CONTACTS (NORMAL AFTER START OR NORMAL AFTER STOP)

IN SERIES WITH THE SilMP LEVEL SWITCH.

[

REFERENCES:

DRAWING 208-060-WD-09, WD-10 WD-134 SENSING ELEMENT: WD-133-LS, WD-134-LS, WDP-3A/38 CONTROL SWITCH CONTACTS.

-AR-403 Rev. 29 Page 83

ENCLOSURE 1 1 (Page 82 of 190) i PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-07 H-02-07  ;

i BLDG SUMP 8 8 UMP PUMP

, TROUBLE EVENT POINT 1587  :

4 INDICATED CONDITION:

o AUXILIARY BUILDING SUMP PUMP AUTO START.

o AUXILIARY BUILDING SUMP PUMP TRIP.

o WASTE GAS COMPRESSOR SEAL LEAKAGE DRAIN TANK LOW LEVEL'.  !

O ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o DURING NORMAL OPERATING CONDITIONS THIS IS AN EXPECTED ALARM WHENEVER -

THE AUX. BLDC. SUMP PUMP AUTO STARTS; IF ALARM DOES NOT CLEAR WITHIN 3-5 MINUTES, THEN NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.-  ;

c: ENSURE WDV-1030-SV HAS CLOSED-(SEAL TANK DRAIN POT DRAIN VALVE).

DISCUSSION:

THIS ALARM MAY INDICATE AN AUTO SHUT DOWN IF THE PRIMARY PLANT OPERATOR MANUALLY STARTED THE AUXILIARY BUILDING SUMD PUMP (S). THE ALARM IS BASED ON THE PUMP CONTROL SWITCH CONTACTS (NORMAL AFTER STARLSTOP) IN SERIES WITH -THE SUMP LEVEL SWITCH. THE WASTE GAS COMPRESSM SEAL LEAKAGE DRAIN

-TANK CAN GIVE THIS ALARM BY OPERATING WDV-1030 SV TO LOWER THE DRAIN TANK LEVEL UNTIL THE LOW LEVEL SWITCH CONTACT OPENS. (SEE DRAWING WD-175)

REFERENCES:

DRAWING 208-060-WD-11, WD-12, WD-135, WD-175 SENSING ELEMENT: WD-132-LS. WD-357-LS2, WDP-4A/4B CONTROL SWITCH CONTACTS.

AR-403 Rev. 29 Page 84

i ENCLOSURE 1 O- (Page-83 of 190)

PSA Z ANNUNCIATOR RESPONSE PSA Z-02-07 H-02-07 BLDG SUMPS SUMP PUMP TROUBLE i

EVENT POINT 1589 i INDICATED CONDITION:

o LAUNDRY AND SHOWER SUMP PUMP AUTO START.

o LAUNDRY AND SHOWER SUMP PUMP TRIP.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALIO ALARM:

DISCUSSION:

REFERENCES:

SENSING ELEMENT:

AR-403 Rev. 29 Page 85

O ENCLOSURE 1 (Page 84 of 190) ,

i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 BLDG SUMPS SUMP PUMP TROUBLE EVENT POINT 1806 INDICATED CONDITION:

o DIESEL GENERATOR ROOM 'A' SUMP LEVEL HIGH AS SENSED BY SD-19-LS, O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF HIGH LEVEL.

DISCUSSION:

REFERENCES:

DRAWING 208-072-50-15.

SENSING ELEMENT: 50-19-LS AR-403 Rev, 29 Page 86

i ENCLOSURE 1 (Page 85 of 190)  :

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-D2 H-02-07 BLDG SUMPS SUMP PUMP -

TROUBLE EVENT POINT 1807 INDICATED CONDITION:

o DIESEL GENERATOR ROOM 'B' SUMP LEVEL HIGH AS SENSED BY SD-20-LS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF-HIGH LEVEL.

DISCUSSION:

REFERENCES:

DRAWING 208-072-5D-16.

SENSING ELEMENT: SD-20-LS AR-403 Rev. 29 Page 87

(

ENfLOSURE 1 (Page 86 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 i

BLDG SUMPS SUMP PUMP TROUBLE l

EVENT POINT 1811 INDICATED CONDITION:

o INTAKE ELECTRIC VAULT SUMP LEVEL HIGH AS SENSED BY SD-14-LS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY PLANT OPERATOR TO INVESTICATE CAUSE OF HIGH LEVEL.

DISCUSSION:

REFERENCES:

DRAWINC 208-072-SD-09.

SENSING ELEMENT: SD-14-LS AR-403 Rev. 29 Page 88

ENCLOSURE 1 (Page 87 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-07 H-02-07 i

RLDS i JMPS LUMPFUMP l

TROUBLE l

EVENT POINT 1880 l

INDICATED CONDITION:

5

< o TURBINE ROOM SUMP LEVEL HIGH AS SENSED BY SD-24-LS os o OILY WATER SEPARATOR TROUBLE O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY PLANT. OPERATOR TO INVESTIGATE CAUSE OF HIGH LEVEL ANJ/OR OILY l WATER SEPARATOR PROBLEM DISCUSSION:

OILY WATER SEPARATOR TROUBLE MAY BE CAUSED BY ANY OF THE FOLLOWING:

HIGH/ LOW VACUUM PRE-FILTER HIGH AP OIL DISCHARGE EMERGENCY STOP WHEN IN-AUTO THE ALARM WINDO# DOES NOT TYPE "0ILY WATER SEPARATOR TROUBLE" BUT IN FACT IS LABELED " TURBINE BUILDING SUMP LEVEL HIGH".

REFERENCES:

DRAWING 208-072 S0-01, 50-17.

SENSING ELEMENT: SD-24-LS, SD-24-DPIS, SD-26-PIS AR-403 Rev. 29 Page 89

ENCLOSURE 1 O (Page 68 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-07 H-02-07 BLDG SUMPS SUMP PUMP TROUBLE EVENT POINT 1913 INDICATED CONDITION:

o SEWAGE PUMP SUMP LEVEL HIGH AS SENSED BY LOCAL CIRCUIT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SEP-1A AND/0R SEP-1B RUNNING.

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY TURBINE BUILDING OPERATOR TO ENSURE LEVEL DOES NOT OVERFLOW ONTO TURBINE BUILDING FLOOR AND THAT SEP-1A AND OR SEP-18 ARE RUNNING TO LOWER LEVEL.

DISCUSSION:

1

REFERENCES:

DRAWING 208-064 ME-10 O SENSING ELEMENT: R1.

AR-403 Rev. 29 Page 90

l l

ENCLOSURE 1 (Page 89 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-08 H-02-08 SEC SAMPLE 4 SYSTEM i ALARM EVENT POINT 0798 INDICATED CONDITION:

o HOTWELL/ CONDENSATE CONDUCTIVITY HIGH.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SS-141-CIR, CONDUCTIVITY RECORDER ON HVAC SECTION OF MCB.

o COMPUTER POINTS A-100 TO A-104 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY CHEMISTRY TO INVESTIGATE CAUSE OF HIGH CONDUCTIVITY.

o REFER TO CP-138 015CUSSION:

REFERENCES:

DRAWING 208-054-55-10 SENSING ELEMENT: SS-141-CIR O

AR-403 Rev. 29 Page 91

, e ENCLOSURE 1 (Page 90 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-08 H-02-08 SEC SAMPLE SYSTEM ALARM t

1 EVENT POINT 0887 INDICATED CONDITION:

o SECONDARY CYCLE SAMPLE ANALYSIS ALARM, O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY CHEMISTRY TO INVESTICATE CAUSE OF SAMPLE ALARM.

DISCUSSION:

THIS ALARM INDICATES AN ALARM HAS NOT BEEN ACKNOWLEDGED IN THE SECONDARY CHEMISTRY LAB 0LTORY WITHIN AN ADJUSTABLE TIMER SETTING.

REFERENCES:

DRAWING 208-054-55-11 SENSING ELEMENT: SSCP-1 (SECONDARY CYCLE SAMPLE ANALYZER PANEL)

V l

AR-403- Rev. 29 Page 92

. . . - ..--- - -.-,- -.-_-. ..- .~_.._- --._ -_.- ..-.. ..~_.- . -

i ENCLOSURE 1

(Page 91 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-01 H-03-01 l

ZZ{ZZZZ u ouio l

l RADIATION l HIGH I

l EVENT POINT 1786 INDICATED CONDITION: ,'

o RM-L1 RADIATION LEVEL EXCEEDS HICH SETPOINT, O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM L1 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM, o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 93

l O ENCLOSURE 1 (Page 92 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-01 H-03-01 x x l l xxxx LlOUID l l RADIATION l l HIGH I I I I EVENT POINT 1788 l

l INDICATED CONDITION:

o RM-L2 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L2 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PACE OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATI'1 o

NOTIFY PRIMARY PLANT OPERATOR TO ENSURE WDV-891 AND WDV-892 CLOSED.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

o CONTACT CHEMISTRY FOR EVALUATION OF MONITOR PRIOR TO MONITOR FLUSH.

DISCUSSION:

WDv-891 AND WDV-392 ARE PRIMARY LIQUID RELEASE VALVES.

REFERENCES:

DRAWING 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403_ Rev. 29 Page 94

O ENCLOSURE 1 (Page 93 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-01 H-03-01 rw xrrr l l LIQUID l l RADIATION l l H10H I I I I ,

EVENT POINT 1792 INDICATED CONDITION:

9 o RM-L3 RADIATION LEVEL EXCEEDS HIGH SETPOINT, O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH RADIATION, o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

o REFER TO OP-408. NUCLEAR SERVICES COOLING SYSTEM TO CONNECT SW SURGE TANK-TO WASTE CAS HDR o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

=

REFERENCES:

ORAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 95

ENCLOSURE 1 O (Page 94 of 190)

PSA-Z ANNUNt mf0R RESPONSE PSA-Z-03-01 H-03-01 i

I I LIQUID l l RADIATION l l ., HIGH I I I I EVENT POINT 1794 ,

INDICATED CONDITION:

o!

o RM-L5 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L5 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP 301, OPERATION OF THE REACTOR COOLANT SYSTEM.

o REFER TO OP-505 RADIATION MONITORING SYSTEM.

DISCUSSION:

=

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 96

i ENCLOSURE 1 (Page 95 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 r y rrrr l l LIQUID l  ; RADIATION

-j l HIGH I I I I EVENT POINT 1796 INDICATED CONDITION:

o RM-L6 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM L6 INDICATION AT RADIATION MONITORING PANEL.

ODERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

o REFER TO OP-505. RA0!ATION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 97

\1 a

O ENCLOSURE 1 (Page 96 of 190) l l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 LIQUID RADIATION HIGH k

EVENT POINT 1798 l

INDICATED CONDITION:

o RM-L7 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O REDUNDANT INDICATION WHICH Will VERIFY ALARM:

o RM-L7 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY PRIMARY PLANT OPERATOR TO ENSURE SDV-90 CLOSED.

o CONTACT CHEMISTRY FOR EVALUATION OF MONITOR PRIOR TO MONITOR FLUSH.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

SDV-90 IS THE SECONDARY LIQUID RELEASE VALVE.

REFERENCES:

DR\ WING 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 98 J

  • l p ENCLOSURE 1 Q (Page 97 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 l

l LIQUID MONITOR WARNING 1

EVENT POINT 1787 INDICATED CONDITION:

o RM-L1 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-LI INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM. $

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Fage 99

ENCLOSURE 1 (Page 98 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-02 H-03-02 l

l LIQUID MONITOR WARNING I

l EVENT POINT 1789 l

INDICATED CONDITION:

o RM-L2 RADIATION LEVEL EXCEEDS WARNING SETPOINT, O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L2 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PACE OPERAVOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH RADIATION.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWINC 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 100

ENCLOSURE 1 (Page 99 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-02 H-03-02 I

LIQUID MONITOR WARNING EVENT POINT 1791 INDICATED CONDITION:

o RM-L3 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

n v

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

o REFER TO OP-505, RADIAlION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 101

ENCLOSURE 1 (Page 100 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 I

LIQUID MONITOR ,

WARNING EVENT POINT 1795 INDICATED CONDITION:

4 o RM-L5 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM L5 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301. OPERATION OF THE REACTOR COOLANT SYSTEM.

o REFER TO OP-505, RADIATION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 29 Page 102

k r

ERCLOSURE 1

,O* (Page 101 of 190) i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 d

9 f

l LIQUID i

MONITOR WARNING l

I.

EVENT POINT 1797 INDICATED CONDITION:

o RM-L6 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L6 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

o REFER TO OP-505, RADIATION MONITORINC SYSTEM. ,

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL ,

-AR-403 Rev. D Page 103

O ENCLOSURE 1 (Page 102 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 I

LIQUID MONITOR WARNING EVENT POINT 1799 INDICATED CONDITION: l ,j o RM-L7 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L7 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PACE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HICH RADIATION.

o REFER TO OP-505. RADIATION MONITORING SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049 RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL

-AR-403 Rev. 29 Page 104

ENCLOSURE 1 (Page 103 of 190) s PSA-2 ANNUNCIATOR RESPONSE PSA-2-03-03 H-03-03 1

RM L2/7 INTERLOCK BYPASSED EVENT POINT 2044 INDICATED CONDITION:

o INTERLOCK BEWEEN SDV-90 AND RWP-3A/3B DEFEATED.

o INTERLOCK BETWEEN WDV-892 AND RWP-1, RWP-2A/2B DEFEATED.

RF.DUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L2/7 BYPASS KEY INSTALLED AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

BYPASSING THE RM-L2/7 INTERLOCK ALLOWS OPENING OF SDV-90 WITH EITHER RwP-1, RWP-2A OR RWP-2B RUNNING INSTEAD OF RWP-3A GR RWP-38. ALSO WDV-892 MAY BE OPENED WITH RWP-3A OR RWP-3B RUNNING INSTEAD OF RWP-1, RWP-2A OR RWP-28.

REFERENCES:

DRAWING 208-060-WD-60 SENSING ELEMENT: RADIATION MONITORING PANEL BYPASS INTERLOCK KEY SWITCH AR-403 Rev. 29 Page 105

t ENCLOSURE 1 h

D (Paga 104 of 190)

PSA-2 ANNUNCIATOR RESPONSE- PSA-2-04-01 H-04-01 I

MAKEUP TANK j  ; LFVEL l l LOW Low I I I I EVENT POINT 0792 INDICATED CONDITION:

o MAKEUP TANK LEVEL <18' AS SENSED BY MU14-LYI-4, MU14-LY2-4.

U REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o Mue014 LIR1, MUT LEVEL / PRESSURE RECORDER.

o MU-14-LI1, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

o MU-14-LI2, MUT LEVEL INDICATION-(REDUNDANT INSTRUMENT PANEL).

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MUV-58, AND MUV-73 OPEN.

o RESTORE MAKEUP TANK LEVEL TO NORMAL BAND.

DISCUSSION:

~

REFERENCE 5: DRAWINC 208-041-MU-17,MU-18 l SENSING ELEMENT: MU14-LY1-4,MU14-LY2-4 AR-403 Rev. 29 Page 106

G ENCLOSURE 1 (Page 105 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-02 H-04-02 MAKEUP TANK LEVEL HIGH/ LOW t

EVENT POINT 1064 INDICATED CONDITION:

o MAKEUP TANK LEVEL >1M" AS SENSED BY MU-14-LY3.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

o MU-14-LI1, MUT LEVEL ZNDICATION (REDUNDANT INSTRUMENT PANEL).

o MU-14-LI2, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

o COMPUTER POINT X359 OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE MAKEUP TANK LEVEL TO NORMAL BAND.

DISCUSSION:

IF HUP (S) ARE ALIGNED TO BWST & RECIRC FLOW TO MUT IS CAUSING HIGH LEVEL IN

- THEN CONSIDER ALIGNING MUP SUCTION FROM MUT ONLY.

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-14-LY3.

.%R-403 Rev. 29 Page 107

ENCLOSURE 1 (Page 106 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSa-2-04-02 H-04-02

.m MAKEUP TANK LEVEL HIGH/ LOW EVENT POINT 1065 INDICATED CONDITION:

o MAKEUP TANK LEVEL <55" AS SENSED BY MU-14-LY3.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o. MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

o MU-14-LII, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

o MU-14-LI2, MUT LEVEL INDICATION (REDUNDANT 'NSTRUMENT PANEL) .

o COMPUTER POINT X359.

OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE MAKEUP TANK LEVEL TO NORMAL BAND.

DISCUSSION:

REFERENCES:

PVWING 208-041-MU-47.

SENSING ELEMENT: MU-14-LY3.

AR-403 Rev. 29 Page 108

ENCLOSt%E__1 (Par ~~

  • 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-03 t-

,i.

MAKEUP FLOW HIGH EVENT POINT 1066 l

INDICATED CONDITION:

o MAKEUP FLOW >160 GPM THROUGH MVV-31 AS SENSED BY MU-24-FS.

O V

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-24-FI OPERATOR' ACTIONS FOR A VALID ALARM:

o DETERMINE CAUSE OF HIGH FLOW ALARM.

o CBSERVE LTOP CONCERNS o REFER TO OP-301 DISCUSSION:

THE HICH cLOW ALARM WAS ESTABLISHED FOR LTOP CONDITIONS TO PROVIDE INDICATILt. SHOULD MUV-31 FAIL WIDE OPEN. THE INTENT WAS TO PROVIDE AT LEAST 10 MINUTES FOR OPERATOR CORRECTIVE ACTION FOR THIS TRANSIENT.

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-24-FS.

AR-403 Rev. 29 Page 109

ENCLOSURE 1 (Page 108 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-04 H 04-04 LETDOWN TEMP HIGH EVENT POINT 1027 INDI 3TED CONDITION:

o LETDOWN TEMPERATURE TO PRE-FILTERS >130*F AS SENSED BY MU-5-TS.

bv REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-5-TI OPERATOR ACTIONS FOR A VALID ALARM:

o REDUCE LETDOWN FLOW WITH MUV-51 FLOW CONTROL VALVE.

o NOTIFY PRIMARY PLANT OPERATOR TO VERIFY SW THROTTLE VALVES TO LETDOWN COOLERS ' SEALED'.

DISCUSSION:

IF LETDOWN HAS ISOLATED VIA MUV-49 REFER TO OP-402 FOR LETDOWN RECOVERY.

IF HICH LETDOWN FLOW IS DESIRED THEN CONSIDER STACTING SWP-1A GR SWP-1B TO PROVIDE ADDITIONAL COOLING WATER TO THE LETDOWN COOLERS.

REFERENCES:

DRAWING 208-041-MU-33.

SENSING ELEMENT: MU-5-TS.

AR-403 Rev. 29 Page 110

ENCLOSURE 1 O (Page 109 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-05 H-04-05 RC PUMP SEAL BLEED OFF HIGH EVENT POINT 1075 INDICATED CONDITION:

o RC PUMP 1A CONTROL BLEED 0FF >1.75 GPM AS CALCULATED BY PLANT COMPUTER.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-922.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302 'RC PUMP OPERATION'.

DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 78 CONTAINS ADDITIONAL DATA FOR RCP-1A.

REFERENCES:

DRAWING 208-047 RC-05.

SENSING ELEMENT: RX00/RC-19A-PTl AR-403 Rev. 29 Page 111

O ENCLOSURE 1 (Page 110 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-05 H-04-05 RC PUMP SEAL BLEED OFF HIGH EVENT POINT 1076 INDICATED CONDITION:

o RC PUMP IB CONTROL BLEED 0FF >1.75 GPM AS CALCULATED BY PLANT COMPUTER, bG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-923.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302 'RC PUMP OPERATION'.

DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 79 CONTAINS ADDITIONAL DATA FOR RCP-18.

REFERENCES:

DRAWING 208-047 RC 06.

O' v SENSING ELEMENT: RX01/RC-19A-PT2 AR-403 Rev. 29 Page 112 4 -

O ENCLO1URL1 (Page 111 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-05 H-04-05 RC PUMP SEAL BLEED OFF HIGH t

EVENT POINT 1077 INDICATED CONDITI0t': l o RC PUMP 1C CONTROL--BLEED 0FF >1.75 GPM AS CALCULATED BY PLANT COMPUTER.

O --

'V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-924.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO 0F-302 'RC PUMP OPERATION'.

DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 80 CONTAINS ADDITIONAL DATA FOR RCP-1C.

REFERENCES:

DRAWING 208-047 RC-07.

SENSING ELEMENT: RX02/RC-198-PT1.

v AR-403 Rev. 29 Page 113

ENCLOSURE 1 O (Page 112 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-05 H-04-05 l

.).

RC PUMP SEAL BLEED OFF HIGH 3

EVENT POINT 1078 INDICATED CONDITION:

o RC PUMP 1D CONTROL BLEED 0FF >1.75 GPM AS CALCULATED BY PLANT COMPUTER.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-925.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302 'RC PUMP OPERATION'.

DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 81 CONTAINS ADDITION.AL DATA FOR RCP-1D.

REFERENCES:

DRAWING 208-04:' RC-08.

SENSING ELEMENT: RX-08/RC-198-PT1.

AR-403 Rev. 29 Page 114

()

-s ENCLOSURE 1 (Page 113 of 190' PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-06 H-04-06 i

MAKEUP TANK PRESS HIGH/ LOW EVENT POINT 1062 INDICATED CONDITION:

o MAKEUP TANK PRESSURE 1 THE OVERPRESSURE VALUE CALCULATED BY THE PLANT COMPUTER.

i O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

o COMPUTER POINTS X359 AND.X401.

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MUV-141, MUV-143 CLOSED o

IMMEDIATELY REDUCE PRESSURE WITHIN THE LIMITS OF MAKEUP TANK PRESSURE / LEVEL OF CURVE 8 0F OP-103B.

DISCUSSION:

THE VALUES OF THE COMPUTER POINTS ARE INPUT TO A CALCULATION WHICH ACTUATES THIS EVENT POINT WHEN MUT LEVEL / PRESSURE COMBINATION ARE BEING OPERATED IN THE RESTRICTED REGION OF CURVE 8 OP-103B.

REFERENCES:

DRAWING 208-041-MU-47.

fs V

SENSING ELEMENT: CX82 AR-403 Rev. 29 Page 115-

ENCLOSURE 1 (Page 114 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-06 H-04-06 MAKEUP TANK PRESS HIGH/ LOW EVENT POINT 1063 INDICATED CONDITION:

o MAKEUP TANK PRESSURE <3 PSIG AS SENSED BY MU-17-PS, '

O I

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MVV-134 CLOSED o

INCREASE PRESSURE WITHIN LIMITS OF MAKEUP TANK PRESSURE / LEVEL CURVE OF OP-103B.

DISCUSSION:

MUT PRESSURE MAY BE TEMPORARILY REDUCED BELOW 3 PSIG DURING VENTING EVOLUTIONS, BUT SHOULD BE MAINTAINED ABOVE O PSIG.

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-17-PS.

AR-403 Rev. 29 Page 116

ENCLOSURE 1 (Page 115 of 1901 PSA-Z ANNUNCIATOR RESPONSE PSA-2-04-07 H-04-07 RC PUMP SEAL RTN (MUV 253)

, NOT FULL OPEN l

EVENT POINT 1036 INDICATED CONDITION: '

o MUV-253 NOT FULL OPEN.

O REDUNDANT INDICATION WI,fCH WILL VERIFY ALARM:

o MUV-253 VALVE INDICATION ON PSA SECTION AND E.S. LIGHT MATRIX, o COMPUTER POINT P064.

OPERATOR ACTIONS FOR A VALID ALAP.M:

o REOPEN MUV-253.

o MONITOR RCP SEALS TEMPERATURE / PRESSURE DISCUSSION:

IF MUV-253 CANNOT BE REOPENED THEN REFER TO OP-302.

RCP DATA CAN BE OBSERVED ON COMPUTER GROUPS 78.79,80 AND 81.

REFERENCES:

DRAWING 208-041-MU-44.

(,) SENSING ELEMENT: RELAY 3MUV-2530.

l AR-403 Rev. 29 Page 117

__o

i ENCLOSURE 1 (Page 116 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-08 H-04-08 i

MAKEUP VALVES AIR FAILURE EVENT POINT 1094 INDICATED CONDITION:

o LETDOWN FLOW CONTROL VAL 5" MUV-51 LOCKED.

3 (V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MUV AIR FAILURE PUSH-BUTTON ILLUMINATED.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o

INVESTICATE LOSS OF INSTRUMENT AIR PRESSURE TC MUV-51.

DISCUSSION:

TWO PRESSdRE SWITCHES SUPPLY PRESSURE INFORMATION TO ThE CONTROL CIRCUITS FOR MUV-51. MU-3-PSI SET FOR 32 PSIC AND MU-3-PS2 SET FOR 28 PSIG. IF EITHER MU-3-PS1 OR MU-3-PS2 IS ACTUATED, THE VALVE POSITION WILL BE LOCKED "A5 IS" BY THE ISOLATION OF THE AIR LINE FROM THE POSITIONER TO THE VALVE DIAPHRACM. OPERATION OF THE VALVE BY DEPRESSING THE AIR FAILURE RESET PUSH-BUTTON IS NOT CERTAIN AT THIS LOW AIR PRESSURE.

REFERENCES:

DRAWING 208-041-MU-54.

SENSING ELEMENT: MU-3-PS1, MU-3-PS2.

AR-403 Rev. 29 Page 118

ENCLOSURE 1 q (Page 117 of 190) 1 PSA-Z ANNbNCIATOR RESPONSE PSA-2-04-08 H-04-08 i

MAKEUP VALVES AIR FAILURE EVENT POINT 1095 l

INDICATED CONDITION:

o MAKEUP CONTROL VALVE MUV-31 LOCKED.

b

.V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o NNI-AR3 LIGHT 31 IN NNI CABINET 2 o MUV-31 AIR FAILURE PUSH-BUTTON ILLUMINATED.

o MUV-31 CONTROL STATION IN ' HAND' .

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-31.

DISCUSSION:

MUV-31 WILL LOCK IN POSITION ON AIR / ELECTRICAL FAILURE.

THE VALVE WILL FAIL CLOSED ON LOSS OF AIR TO THE DIAPHRAGM.

REFERENCES:

DRAWING 208-041-MU-54.

SENSING ELEMENT: MU-25-PS1 AR-403 Rev. 29 Page 119

G ENCLOSURE 1 (Page 118 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-08 H-04-08 l

3  !

MAKEUP VALVES Atti FAILURE EVENT POINT 1096

] INDICATED CONDITION:

o MAKEUP CONTROL VALVE Mv.-16 LOCKED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o NNI-AR4 LIGHT 16 IN NNI CABINET 2.

o MUV-16 AIR FAILURE PUSH-BUTTON ILLUMINATED.

o MUV-16 CONTROL STATION IN ' HAND'.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o

INVESTICATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-16.

DISCUSSION:

MUV-16 WILL LOCK IN POSITION ON AIR /ELEGRICAL FAILURE.

THE VALVE WILL FAIL OPEN ON LOSS OF AIR TO THE DIAPHRACM.

REFERENCES:

DRAWING 208-041-MU-54.

O SENSING ELEMENT: MU-15-PS1 AR-403 Rev. 29 Page 120

ENCLOSURE 1 (Page 119 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-08 H-04-08 l 1

MAKEUP VALVES AIR FAILURE EVENT POINT 1102 INDICATED CONDITION:

o RC PUMP SEAL BLEED 0FF VALVE MUV-253 AIR SUPPLY PRESSURE <80 PSIG AS SENSED BY MU-253-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

r OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o

INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-253.

DISCUSSION:

OPERATION OF THE VALVE IS NOT CERTAIN AT THIS LOW AIR PRESSURE. MUV-253 FAILS CLOSED IF THE AIR PRESSURE IS INSUFFICIENT AGAINST-THE CLOSURE SPRING OF THE VALVE OPERATOR.

REFERENCES:

DRAWING 208-041-MU-54.

SENSING ELEMENT: MU-15-PS1, MU-15-PS2.

AR-403 Rev. 29 Page 121

ENCLOSURE 1 (Page 120 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-01 '

H-05-01 rrr r I I rr STM GEN A MAIN STEAM ISO l l l ACTUATED l l I I EVENT POINT 2007 INDICATED CONDITION:

I o EFIC CHANNEL "A", STEAM CENERATOR "A" MAIN STEAM LINE ISOLATION BUS 1 OR BUS 2 TRIPPED.

O REDUNDANT-INDICATION WHICH WILL VERIFY ALARH:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN STEAM LINE ISOLATION.

o MS-106-PI, CHANNEL "A", OTSG A PRESSURE ' INDICATION.

o MS-106-PIR, CHANNEL "A", OTSC A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIC. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 122

h 9 ENCLOSURE 1 (Page 121 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-01 H-05-01 3

f  :

I STM GEN A MAIN STEAM ISO l ACTUATED 1

i EVENT POINT 2015 INDICATED CONDITION:

o EFIC CHANNFL "B", STEAM GENERATOR "A" MAIN STEAM LINE ISOLATION BUS 1 OR BUS 2 TRIPPED.

O REDUNDANT INDICATION WHICh WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN STEAM LINE ISOLATION.

o MS-107-PI, CHANNEL "B",

OTSG A PRESSURE INDICATION.

o MS-IO7-PIR, CHANNEL "B",

OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05, EXCESSIVE HEAT TPANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 SENSING ELEMENT:

AR-403 Rev. 29 Page 123

_ _ _ _ _ _ _ _ _ _ . _ . _ _ _ . _ . . . . . .. _O

ENCLOSURE 1 O (Page 122 of 190) 4 PSA-Z ANNUNCIATOR RESPONSE PSA-2-05-02 H-05-02 i

STM GEN A FEEDWATER ISO ACTUATED.

l EVENT POINT 2009 INDICATED CONDITION:

o EFIC CHANNEL "A. STEAM GENERATOR "A" MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED.

.f)

\j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN FEEDWATER ISOLATION.

o MS-106-PI, CHANNEL "A",

OTSG A PRESSURE INDICATION.

o MS-106-PIR, CHANNEL "A", OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MPdi AClUATION SETPOINT IS OTSG PRESSURE <600 PSIC. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSLRVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 124

('

CNCLOSURE 1 (Page 123 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-05-02 H-05-02 STM GEN A FEEDWATER ISO ACTUATED EVENT POINT 2017 INDICATED CONDITION:

o EFIC CHANNEL "B", STEAM CENERATOR 'A' MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED, O

REDUNDANT INDICATION WHICH WILL VcRIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN FEEDWATER ISOLATION.

o MS-107-PI, CHANNEL "B", OTSG A PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MFWI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST SBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

N3 ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 SENSING ELEMENT:

AR-403 )

Rev. 29 Page 125 m

ENCLOSURE 1 (Page 124 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-03 H-05-03 MAIN STEAM ISO VALVE 4 AIR FAILURE EVENT POINT 0956 INDICATED CONDITION:

o MSV-413 AND MSV-414 AIR SUPPLY PRESSURE <80 PSIG AS SENSED BY MS-99-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o

INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MSIVs.

DISCUSSION:

ON A LOSS OF INSTRUMENT AIR, THE ACCUMULATORS SHOULD MAINTAIN THE MSIVs OPEN FOR AT LEAST 1 HOUR DEPENDENT ON ACTUATOR LEAKAGE. DEGRADATION OF THE ACCUMULATOR PRESSURE WILL BE INDICATED BY THE ILLUMINATION OF THE SV-1/SV-2 WHITE TEST LIGHT ON THE PSA PANEL.

REFERENCES:

ORAWING 208-039 MS-14 SENSING ELEMENT: MS-99-PS AR-403 Rev. 29 Page 126 I

O ENCLOSURE 1 (Page 125 of 190)

PSA-2 ANNUNCIATOR RESPONSE PSA-2-05-03 H-05-03 MAIN STEAM <

ISO VALVE AIR FAILURE EVENT POINT 0959 INDICATED COGiTION:

4 o

MSV-411 AND MSV-412 AIR SUPPL l( PRESSURE <80 PSIG AS SENSED BY MS-98-PS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I OPERATOR ACTIONS FOR A VALIO ALARM:

o REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUPENT AIR PRESSURE TO MSIVs.

DISCUSSION:

ON A LOSS OF INSTRUMENT AI.1, THE ACCUMULATORS SHOULD MAINTAIN THE MSIVs l

OPEN FOR AT LEAST 1 HOUR DEPENDENT ON ACTUATOR LEAKAGE. DEGRADATION OF {

THE ACCUMULATOR PRESSURE WILL BE INDICATED SY THE ILLUMINATION OF THE SV-1/SV-2 WHITE TEST LIGHT ON THE PSA PANEL.

REFERENCES:

DRAWING 208-039 MS-14

'%) SENSING ELEMENT: MS-98-PS AR-403 Rev. 29 Page 127

A ENCLOSURE 1 d (Page 126 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-04 H-05-04 l

I LETDOWN PRESSURE HIGH EVENT POINT 1060 INDICATED CONDITION:

e o

LETDOWN PRESSURE AFTER BLOCK ORIFICE >145 PSIG AS SENSED BY MU-6-PS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o COMPUTER POINT X002.

OPERATOR' ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF HICH PRESSURE CONDITION.

o REDUCE LETDOWN FLOW.

DISCUSSION:

A POSSIBLE CAUSE OF HICH PRESSURE AT THIS POINT IN THE SYSTEM IS ISOLATION OF DOWNSTREAM COMPONENTS OR ANY FLOW RESTRICT'.ONS IN THE PRE-FILTERS, POST-FILTERS OR MAKEUP DEMINS. IF THE HICH PRESSURE CONDITION EXISTS AND ITS CAUSE CANNOT BE DETERMINED THEN CLOSURE OF MUV-49 MAY BE REQUIRED TO PREVENT POSSIBLE RELIEF VALVE OPERATION TO THE A.B. SUMP.

REFERENCES:

DRAWING 208-041 MS-47 SENSING ELEMENT: MS-6-PS AR-403 Rev. 29 Page 128

ENCLOSURE 1 O (Page 127 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-05 H-05-05 l

1 MAKEUP FILTERS A PRESS HIGH I

EVENT POINT 1061 l

l INDICATED CONDITION:

o MAKEUP POSTFILTER DIFFERENTIAL PRESSURE >25 PSIG AS SENSED BY MU-18-DPS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MAKEUP POSTFILTER DIFFERENTIAL PRESSURE MU-18-DPI.

OPERATOR- ACTIONS FOR A VALID ALARM:

o PLACE "A" AND "B" POST-FILTERS IN SERVICE.

o REDUCE LETDOWN FLOW.

DISCUSSION:

o DO NOT INITIATE FILTER CHANGE OUT UNTIL STEADY STATE DP REACHES 25 PSID, AS INDICATED ON MU-18-DPI

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-18-DPS AR-403 Rev. 29- Page 129

ENCLOSURE 1 (Page 128 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-05 H-05-05 MAKEUP FILTERS A PRESS HIGH I

l  !

EVENT POINT 1082 INDICATED CONDITION:

o HAKEUP PRE-FILTER DIFFERENTIAL PRESSURE >12 PSIG AS SENSED BY MU-81-DPS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MAKEUP PRE-FILTER DIFFERENTIAL PRESSURE INDICATION MU-81-DPl.

OPERATOR ACTIONS FOR A VALID ALARM:

o PLACE "A" AND "B" PRE-FILTERS IN SERVICE.

o REDUCE LETDOWN FLOW.

DISCUSSION:

o DO NOT INITIATE FILTER CHANGE OUT UNTIL STEADY STATE DP REACHES 12 PSID, AS INDICATED ON MU-81-DPI

REFERENCES:

DRAWING 208-041 MU-47 lSENSINGELEMENT: MU-81-DPS AR-403 Rev. 29 Page 130

O ENCLOSURE _1 (Page 129 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-06 H-05-06 D

MAKEUP DEMIN A PRESS HIGH EVENT POINT 1083 INDICATED CONDITION:

o MAKEUP DEMIN DIFFERENTIAL PRESSURE >14 PSIG AS SENSED BY MU-75-DPS.

REDUNDANT INDICATION WHICH kGLL VERIFY ALARM:

o MAKEUP DEMIN DIFFERENTIAL PRESSURE INDICATION MU-75-DPI.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-402 o BYPASS DEMINERALIZERS OR PLACE ALTERNATE DEMIN IN SERVICE o REDUCE LETDOWN FLOW DISCUSSION:

CONSIDERATION SHOULD BE CIVEN TO THE AFFECT ON THE RCS OF PLACING THE ALTERNATE DEMIN IN SERVICE. IF IT IS NOT SATURATED AT THE SAME LEVEL A3 THE RCS IS AT THE TIME THE ALTERNATE DEMIN IS PLACED IN SERVICE THERE WILL DE A SIGNIFICANT CHANGE IN CORE REACTIVITY THAT MAY CAUSE A SIGNIFICANT 3 OPERATIONAL EXCURSION OR REDUCTION OF THE SHUTDOWN MARGIN.

-s

REFERENCES:

DRAWING 208-041 MU-47

\s / SENSING ELEMENT: MU-75-DPS t-AR-403 Rev. 29 Page 131

O ENCLOSURE 1 (Page 130 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05 H-05-07 RC PUMP SEAL FLOWS HIGH/ LOW EVENT POINT 1079 INDICATED CONDITION:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW >42 GPM AS SENSED BY MU-27 -FS, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW INDICATION MU-27-FI, OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW, DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47

{

SENSING ELEMENT: MU-27-FS l

AR-403 Rev. 29 Page 132

ENCLOSURE 1

( (Page 131 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-05-07 H-05-07 RC PUMP SEAL FLOWS HIGH/ LOW  !

EVENT POINT 1080 I

INDICATED CONDITION:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW <22 GPH AS SENSED BY MU-27-FS.

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW INDICATION MU-27-FI.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302, o REESTABLISH NORMAL SEAL FLOW.

DISCUSSION:

REFEREN ES: DRAWINC 208-041 MU-47 lSENSINGELEMENT: MU-27-FS AR-403 Rev. 29 Page 133-

A ENCLOSURE 1 t,j (Page 132 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05 H-05-07 I I RC PUMP SEAL FLOWS HIGHILOW -

Ei!5ivT POINT 1084 INDICATED CONDITION:

o REACTOR COOLANT PUMP 1A SEAL FLOW <3 GPM AS SENSED BY MU-7-FS1, O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP 1A SEAL FLOW INDICATION MU-7-FIl.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-7-FS1 AR-403 Rev. 29 Page 134

l 1

ENCLOSUAE_1 1

O. (Page 133 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-05-07 H-05-07 RC F3JMP SEAL FLOWS HIGH/ LOW EVENT POINT 1085 INDICATED CONDITION:

9 o REACTOR COOLANT PUMP IB SEAL FLOW <3 GPM AS SENSED BY MU-7-FS2, O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOL. ANT PUMP 18 SEAL FLOW INDICATION MU-7-FI2.

OPERATOP, ACTIONS FOR A VALID ALARM:

o REFER TO OP-302, o REESTABLISH NORMAL SEAL FLOW.

DISCUSSION:

=._

REFERENCES:

DRAWINC 208-041 MU-47 SENSING ELEMENT: MU-7-FS2 AR-403- Rev. 29 Page 135

l ENCLOSUREj O. (Page 134 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-07 -H-05-07 RC PUMP SEAL FLOWS HIGH/ LOW EVENT POINT 1086 INDICATED CONDITION:

o REACTOR COOLANT PUMP IC SEAL FLOW <3 GPM AS SENSED BY MU-7-FS3. ,

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP 1C SEAL FLOW INDICATION MU-7-FI3. -

OPERATOR ACTIONS FOR A VALID ALARM:

i 2

o REFER TO OP 30.:.

) o REESTABLISH NORK*.L SEAL-FLOW.

1

^

DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-7-FS3 s

AR-403 Rev. 29 Page 136

l ENCLOSURE 1 (Page 135 of 190).

PSA-Z ANNUNCIATOR RES"0NSE PSA-2-05-07 H-05-07_

=-+ RC PUMP SEAL FLOWS HIGH/ LOW EVENT POINT 1087 I

INDICATED CONDITION:

o REACTOR COOLANT PUMP 10 SEAL FLOW <3 GPM AS SENSED BY MU-7-F54 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: <

o REACTOR COOLANT PUMP 10 SEAL FLOW INDICATION MU-7-FI4.

OPERATOR ACTIONS FOR A VALIO ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

DISCUSSION:

REFERENCES:

DRAWING 208-041 PM-47 SENSING ELEMENT: MU-7-F54 AR-403- Rev. 29 Page 137

ENCLOSURE 1 (Page 136 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-05-08 H-05-08 BWST VLV INTERLOCK BYPASSED

____ ___l EVENT POINT 2048 INDICATED CONDITION:

o MAKEUP TANK LOW-LOW LEVEL INTERLOCK DEFEATED FOR MUV-50 AND/OR MUV-73 n

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

SWITCH POSITIONS IN "A" AND "B" REMOTE SHUTDOWN AUXILIARY CABINETS.

OPERATOR ACTIONS FOR A vat.ID ALARM:

DISCUSSION:

THE SWITCH FOR MUV-73 INTERLOCK IS LOCATED IN THE "A" REMOTE SHUTDOWN AUXILIARY CAdINET IN THE "A" ES 4160V SWITCHGEAR ROOM. THE SWITCH FOR MUV-58 INTERLOCK IS LOCATED IN THE "B" REMOTE SHUTDOWN AUXILIARY CABINET IN THE "B" ES 4160V SWITCHCEAR ROOM. USE 5500 KEY 47 TO ACCESS THE AUXILIARY CABINETS.

= _ _

REFERENCES:

DRAWING 205-041 MU-07 SENSING ELEMENT: ZZ SS/BYP, RS-AUX A/B AR-403 Rev. 29 Page 138

n

! ENCLO51!BL1 (Page 137 of 190) i l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-01 H-06-01 I I

! STM GEN 8 l l MAIN STEAM 180 l l ACTUATED  ;

!- 1 I i l I EVENT POINT 2008 INDICATED CONDITION:

o EFIC CHANNEL "A", STEAM GENERATOR "B" MAIN STEAM LINE ISOLATION BUS 3 OR BUS 2 TRIPPED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN STEAM LINE ISOLATION.

o MS-110-PI CHANNEL "A" OTSG B PRESSURE INDICATION.

o- MS 106-PIR, CHA.NNEL "A". OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05. EXCESSIVE HEAT TRANSFER, o INVEbTICATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSC PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM. A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 139

, , , _ . - _. - _-.-,,m.,., . , _ _ _ _ . . _ . , __ , _.,,,,,.c._.#_, .yy --nee , . . _ . - -w. y

l l

ENCLOSURE 1 C) (Page 138 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-01 H-06-01 I I I I STM GEN B j MAIN STEAM ISO l

l l ACTUATED

I l I l EVENT POINT 2016 INDICATED CONDITION:

o EFIC CHANNEL "B", STEAM GENERATOR "B" MAIN STEAM LINE ISOLATION BUS 1 OR BUS 2 TRIPPED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN STEAM LINE ISOLATION.

o MS-111-PI, CHANNEL "B", OTSG A PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSG A/B PRESSURE RECORDER.

, OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

l DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIC. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

'(

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 f SENSING ELEMENT:

AR-403 Rev. 29 Page 140

MCLOSURE_1 g (Page 139 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-02 H-0G-02 STM GEN B FEEDWATER 180 ACTUATED b

EVENT POINT 2010 INDICATED CONDITION:

o EFIC CHANNEL "A", STEAM GENERATOR "B" MAIN FEEDWATER ISOLATION BUS-1 OR q BUS 2 TRIPPED.

!O 4 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN FEEDWATER ISOLATION.

o M5-110-PI, CHANNEL "A", OT5G B PRESSURE INDICATION.

o'MS-106-PIR, CHANNEL "A", OTSG A/B PRES 5URE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-0$, EXCESSIVE HEAT TRANSFER.

o INVESTICATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MFWI ACTUATION SETPOINT 15 OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM. A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPFRATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL-ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

O V

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 141

V y

ERCLOSURE 1 V)

(

(Page 140 of 190)

PSA-Z ANNUNCIATOR RESPONSE

)

PSA-Z-06-02 H-06-02 STM GEN B /

FEEDWATER ISO ACTUATED EVENT POINT 2018 INDICATED CONDITION: 6Y o EFIC CHANNEL "B", STEAM CENERATOR "B" MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED.

p 4.9 -

Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN FEEDWATER ISOLATION.

o MS-111-PI, CHANNEL "B", OTSC B PRESSURE INDICATION. /

o MS-107-PIR, CHANNEL "B",

OTSC A/B PRESSURE RECORDER.

LM OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTICATE CAUSE OF TRIP CONDITION. y DISCUSSION:

/

MFWI ACTUATION SETPOINT IS OTSC PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST ;9 OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS. 0 NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS. @

g9 00 O\ /

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 '

4 1*h SENSING ELEMENT:

AR-403

/

Rev. 29 Page 142 i 1

3 o u or - - w _ a >o

1 1

MCLOSURE 1 (Page 140 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z 06-02 H-06-02 STM GEN B FEEDWATER ISO ACTUATED EVENT POINT 2018 INDICATED CONDITION:  !

o EFIC CHANNEL "B". STEAM CENERATOR "B" MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED.

lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN FEEDWATER ISOLATION.

t o MS-111-PI, CHANNEL "B", OTSC B PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSC A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-05. EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

I i

DISCUSSION:

MFWI ACTUATION SETPOINT IS OTSC PRESSURf <600 PSIG. WITH THIS EVENT POINT

~

IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

4

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 SENSING ELEMENT:

, AR-403 Rev. 29 Page 142

O ENCLOSURE 1 (Page 141 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-03 H-06-03

(

EMERG FW ACTUATION EVENT POINT 2006 INDICATED CONDITION:

o EFIC CHANNEL "A", EMERGENCY FEEDWATER BUS 1 OR BUS 2 TRIPPED.

O REDbNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" EMERGENCY FEEDWATER ACTUATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P.

o INVESTIGATE CAUSE OF TRIA CONDITION.

DISCUSSION:

WITH THIS EVENT POINT IN ALARM A HALF TRIP OR FULL TRIP CONDITION EXISTS.

THE OPERATOR MUST OBSERVE THE EFIC PUSH-BUTTONS TO DETERMINE EFIC ACTUATION STATUS. EFIC ACTUATES BY ANY OF THE FOLLOWING CONDITIONS:

EITHER OTSG <600 PSIG EITHER OTSG APPROACHING 0" MANUAL ACTUATION LOSS OF ALL RCPs NI POWER >45% W/FW <17% HPI A AND B ACTUATION LOSS OF BOTH MFPs W/RPS NOT IN S/D BYPASS

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403. Rev. 29 Page 143 C s

I l

MCLOSURE 1 (Page 142 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-03 H-06-03

  • _ i EMERO FW ACTUATION EVENT POINT 2014 INDICATED CONDITION:

o EFIC CH*

"B", EMERGENCY FEEDWATER BUS 1 OR BUS 2 TRIPPED.

REDUNDANT INDICATION WHICH WILL VERIFY At. ARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" EMERGENCY FEEDWATER ACTUATION.

?

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P.

o INVESTICATE CAUSE OF TRIP CONDITION.

  • DISCUSSION:

WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS.

THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS. - EFIC ACTUATES BY ANY OF THE FOLLOWING CONDITIONS:

EITHER OTSG <600 PSIG EITHER OTSG APPROACHING 0" MANUAL ACTUATION LOSS OF ALL RCPs NI POWER >45% W/FW <17% HPI A AND B ACTUATION LOSS OF BOTH MVPs W/RPS NOT IN S/D BYPASS

(

REFERENCES:

VITRO DRAWING-3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 144

Et4 CLOSURE 1 (Page 143 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-04 $1-06-04 I

l EF PUMP 1 TRIP DEFEATED EVENT POINT 1179 INDICATED CONDITIP.4:

EFP-1 TRIP DEFEAT CONTROL SWITCH IS IN " DEFEAT"' POSITION O

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

VISUAL OBSERVATION OF ONL TWO, OR THREE EFP-1 TRIP DEFEAT CONTROL SWITCHES IN DEFEAT POSITION. ES ACTUATION TEST CABINETS 1, 2 AND 3 EACH CONTAIN ONE CONTROL SWITCH.

OPERATOR ACTIONS FOR A VALID ALARM:

VERIFY THE REQUIREMENTS FOR PLACING CONTROL SWITCH TO " DEFEAT" ARE MET:

EFP-2 NOT AVAII.ABLE. FEEDWATER IS REQUIRED, A LOSS OF OFFSITE POWER EVENT IS IN PROGRESS AND LPI INITIATION IS IMMINENT OR HAS OCCURED DISCUSSION:

ESAS GENERATES A TRIP SIGNAL TO EFP-1 WHEN AS RCS LOW LOW ESAS INITIATION SIGNAL COINCIDENT WITH A LOOP IS PRESENT.- THIS IS PART OF THE LOAD MANAGEMENT SCHEME COR EDG-1A, THE TRIP CAN BE DEFEATED IF EFP-2-IS UNAVAILABLE AND FEEDWATER IS REQUIRED. DEFEATING THE TRIP.IS ACCOMPLISHED BY

3. PLACING THE CONTROL SWITCH TO DEFEAT IN ES ACTUATION CABINETS 1. 2. AND.

OPERATION OF ANY ONE SWITCH CAUSES ANNUNCIATION OF THIS ALARM.

OPERATION OF THE-REMAINING SWITCHES CAUSE THIS ALARM REFLASH.

REFERENCES:

DRAWING 211-028 ES-A35 SENSING ELEMENT:

'AR-403 Rev. 29 Page 145

ENCLOSURE 1 (Page 144 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-04 H-06-04 I

EF PUMP 1 TRIP DEFEATED EVENT POINT 1181 INDICATED CONDITION:

EFP-1 TRIP DEFEAT CONTROL SWITCH IS IN "O* FEAT" POSITION REDUNDAh ' CATION WHICH WILL VERIFY ALARM:

VISUAL OBSERVATION OF ONE, TWO, OR THREE EFP-1 TRIP DEFEAT CONTROL SWITCHES IN DEFEAT POSITION. ES ACTUATION TEST CABINETS 1,.2 AND 3 EACH CONTAIN ONE CONTROL SWITCH.

OPERATOR ACTIONS FOR A VALID ALARM:

VERIFY THE REQUIREMENTS FOR PLACING CONTROL SWITCH TO " DEFEAT" ARE MET:

EFP-2 NOT AVAILABLE, FEEDWATER IS REQUIRED, A LOSS OF OFFSITE POWER EVENT IS IN PROGRESS AND LPI INITIATION IS IMMINENT OR HAS OCCURR 9 DISCUSSION:

ESAS GENERATES A TRIP SIGNAL TO EFP-1 WHEN AS RCS LOW LOW ESAS INITIATION SIGNAL COINCIDENT WITH A LOOP IS PRESENT. THIS IS PART OF THE LOAD MANAGEMENT SCHEME FOR EDC-1A. THE TRIP CAN BE DEFEATED IF EFP-2 IS UNAVAILABLE AND FEEDWATER IS REQUIRED. DEFEATING THE TRIP IS ACCOMPLISHED BY PLACING THE CONTROL SWITCH TO DEFEAT IN ES ACTUATION CABINETS 1, 2, AND

3. . OPERATION OF ANY ONE SWITCH CAUSES ANNUNCIATION OF THIS ALARM.

OPERATION OF THE REMAINING SWITCHES CAUSE THIS ALARM REFLASH.

REFERENCES:

DRAWING 211-028 ES-A36

, SENSING ELEMENT:

AR-403 Rev. 29 Page 146

)

1 ENCLOSURE 1 i (Page 145 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-04 H-06-04 1

EF PUMP 1 ,

j TRIP DEFEATED i

i i

EVENT POINT 1301 4

i INDICATED CONDITION:

EFP-1 TRIP DEFEAT COVTROL SWITCH IS IN " DEFEAT" POSITION

!O i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i VISUAL OBSERVATION OF ONE. TWO, OR THREE EFP-1 TRIP DEFEAT CONTROL' SWITCHES IN DEFEAT POSITION. ES ACTUATION TEST CABINETS 1, 2, AND 3 EACH CONTAIN ONE CONTROL SWITCH.

CoERATOR ACTIONS FOR A VALID ALARM:

VERIFY THE REQUIREMENTS FOR PLACING CONTROL SWITCH TO " DEFEAT" ARE MET:

i EFP-2 NOT AVAILABLE, FEEDWATER IS REQUIRED, A LOSS OF OFFSITE POWER EVENT l IS IN FROGRESS AND LPI INITIATION IS IMMINENT OR HAS OCCURED DISCUSSION:

! ESAS GENERATES A TRIP SIGNAL TO EFP-1 WHEN AS RCS LOW LOW ESAS INITIAFION SIGNAL COINCIDENT WITH A LOOP IS PRESENT. THIS IS PART OF THE LOAD MANAGEMENT SCHEME FOR EDG-IA. THE TRIP CAN BE DEFEATED IF EFP-2 IS

UNAVAILABLE AND FEEDWATER IS REQUIRED. DEFEATING THE TRIP IS ACCOMPLISHED BY PLACING THE CONTROL SWITCH TO DEFEAT IN ES ACTUATION CABINETS 1, 2 AND
3. OPERATION OF ANY ONE WHICH CAUSES ANNUNCIATION OF THIS ALARM. OPERATION OF'THE REMAINING SWITCHES CAUSE THIS ALARM REFLASH.

j

REFERENCES:

DRAWING 211-028 ES-A37 SENSING EliMENT:

AR-403 Rev. 29 Page 147

(.-,.. . . ~ . - _ . , _.-- _,, ., _ . . _ . . , - - - , - . _ . - -

ENCLOSURE 1 (Page 146 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 EFIC BYPASS EVENT POINT 2012 INDICATED CONDITION:

4 o EFIC CHANNEL A IN MAINTENANCE BYPASS.

o ANY EFIC CHANNEL A TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL A CIRCUIT BREAKER OPEN.

O- o ANY EFIC CHANNEL A MODULE WITHDRAWN.

o EFIC CHANNEL A CABINET POWER SUPPLY FAILURE.

o EFIC CHANNEL A MAINTENANCE BYPASS ISOLATOR FAILURE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o MAINTENANCE BYPASS DIGITAL ISOLATOR FAILURE IS INDICATED ' MAINTENANCE BYPASS ALARM WITHOUT THE LOCAL CHANNEL MAINTENANCE BYPAS5 a.ED FLASHING.

REFERENCES:

-VITRO ORAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 148 6

ENCLOSURE 1 (Page 147 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 l

EFIC 8YPASS EVENT POINT 2020 INDICATED CONDITION:

o EFIC CHANNEL B IN MAINTENANCE BYPASS.

o ANY EFIC CHANNEL B TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL B CIRCUIT GREAKER OPEN.

A o ANY EFIC CHANNEL B MODULE WITHDRAWN.

U o EFIC CHANNEL B CABINET POWER SUPPLY FAILURE.

o EFIC CHANNEL B MAINTENANCE BYPASS ISOLATOR FAILURE.

RE0VNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o MAINTENANCE BYPASS DIGITAL ISOLATOR FAILURE IS INDICATED BY MAINTENANCE BYPASS ALARM WITHOUT THE LOCAL CHANNEL MAINTENANCE BYPASS LED FLASHING.

c

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 SENSING ELEMENT:

AR-403 Rev. 29 Page 149

i O EBCLOSURE 1 (Page 148 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-06 H-06-06

(

l l

EFIC BYPASS

} __

EVENT POINT 2025 INDICATED CONDITION:

o FFIC CHANNEL C IN MAINTENANCE BYPASS.

o AnY EFIC CHANEL C TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL C CIRCUIT BREAKER OPEN.

O o ANY EFIC CHANNEL C MODULE WITHDRAWN.

o EFIC CHANNEL C CABINET POWER SUPPLY FAILURE.

o EFIC CHANNEL C MAINTENANCE BYPASS DIGITAL ISOLATOF, FAILURE.

REDUND%NT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o MAINTENANCE BYPASS DICITAL ISOLATOR FAILURE IS INDICATED BY MAINTENANCE BYPASS ALARM WITHOUT THE LOCAL CHANNEL MAINTENANCE BYPASS LED FLASHING.

- ('i '

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 3 SENSING ELEMENT:

AR-403 Rev. 29 Page 150 1*" v -

l ERCLOSURE 1 (Page 149 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-06 H-06-06 EFIC GYPASS EVENT POINT 2029 INDICATED COND1 TION:

o EFIC CHANNEL D IN MAINTENANCF. BYPASS.

o ANY EFIC CHANNEL -D TEST SWITCH -NOT IN NORMAL.

o ANY EFIC CHANNEL D CIRCUIT BREAKER OPEN.

O o ANY EFIC CHANNEL D MODULE WITHDRAWN.

o EFIC CHANNEL D CABINET POWER SUPPLY FAILURE.

o EFIC CHANNEL D MAINTENANCE BYPASS DIGITAL ISOLATOR FAILURE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o MAINTENANCE BYPASS DIGITAL ISOLATOR FAILURE IS INDICATED BY MAINTENANCE BYPASS ALARM WITHOUT THE LOCAL CHANNEL MAINTENANCE BYPASS LED FLASHING.

REFERENCES:

VITRO DPJWING 3801-3005 SHEET 4 SENSING ELEMENT:

AR-403 Rev. 29 Page 151

ENCLOSURE 1 (Page 150 of 190) l PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-06 H-06-06 EFIC BYPASS EVENT POINT 2030 INDICATED CONDITION:

o EFIC CilANNEL A EFW TEST SWITCH IN " TEST" POSITION.

o "M.S.

ISOLATION VALVES AIR SUPPLY TEST A" SWITCH SELECTED TO NUMBER 2 "MSI SV-2 EFIC HALF / TRIP" OR NUMBER 1, "MS & FW ISOLATION".

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o KEY OPERATED TEST SWITCH-IN RELAY RACK RR3A IS SELECTED TO THE " TEST" POSITION. (CRD ROOM)

OPERATOR ACTIONS FOR A VALIO ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

o NOTIFY S500 0F KEY SWITCH POSITION.

DISCUSSION:

o SELECTING THE " TEST" POSITION BLOCKS THE OUTPUT OF "A" EFW BUS 1 AND BUS 2.

REFERENCES:

DRAWING 208-032-FW 47, 208 026-EF-15 SENSING ELEMENT:

AR-403 Rev. 29 Page 152

fRC1.050RE 1 (Page 151 of 190)

PSA-Z ANNUNCIATOR RESPCNSE PSA-2-06-06 H-06-06 7

(

EFIC BYPASS EVENT POINT 2031 l

l INDICATED CONDITION:

o EFIC CHANNEL B EFW TEST SWITCH IN TEST POSITION.

o "M.S.

ISOLATION VALVES AIR SUPPLY TEST B" SWITCH SELECTED TO NUMBER 2 "MSI SV-1 EFIC HALF TRIP" OR NUMBER 1, "MS & FW ISOLATION".

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o KEY OPERATED POSITION. TEST SWITCH IN "ELAY RACK RR5B1 IS SELECTED TO THE " TEST" (EFIC ROOM B)

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF ALARM CONDITION.

o NOTIFY 5500 0F KEY SWITCH POSITION.

DISCUSSION:

o SELECTING THE " TEST" POSITION BLOCKS THE OUTPUT "B" EFWOFBUS I AND BUS 2.

REFERENCES:

DRAWING 208-032-FW-46, 208-026-EF-16 SENSING ELEMENT:

AR-403 Rev. 29 Page 153

l EELOSURE_1 (Page 152 of 190)

.-06-06 l PSA-Z ANNUNCIATOR RESPONSE P'06-06

~

l EFIC BYPASS EVENT POINT 2032 INDICATED CONDITION:

o EFIC AUXILIARY RELAY BOX 1C TEST SWITCH IN TEST.

O REDUNDANT. INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALIO ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION, DISCUSSION:

o AUT04.ATIC TEST, REPOSITIONING OF EFV-11 AND EFV-32 BY EFIC IS BLOCKED WHEN IN O

REFERENCES:

DRAWING 208-026-EF 11 SENSING ELEMENT:

AR-403 Rev. 29 Page 154

__.m.. .- _ ,_ _._ ._._.._.._.__- ._____ _ _..___ _ . . _ _ _ _ _._. _ ...._ ___.

I ENCLOSURE 1 O. .

(Page 153 of 190)

~

PSA-Z ANNUNCIATOR RESPONSE' PSA-Z-06-06 H-06-06 EFIC BYPASS

- 2E

~

..i _ . . >

EVENT POINT 2033 ,

INDICATED CONDITION:

o EFIC AUXILIARY RELAY BOX 10 TEST SWITCH IN TEST.

O t

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALIO ALARM: .

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

o' AUTOMATIC REPOSITIONING OF EFV-14 AND EFV-33 BY EFIC IS BLOCKED WHEN IN TEST.

REFERENCESi DRAWING 208-026-EF-22 SENSING ELEMENT: i AR-403' Rev. 29 Page 155

- . - - . - - - . . - = . - . . . . . _ . - . _ - . ~ . - - - . _ _ - - . - - . . - . - . - -

F l ENCLOSURE.1 (Page 154 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-06 H-06-06 1

EFIC BYPAS$

i EVENT POINT 2034 INDICATED CONDITION:

o EFIC ES-A BYPASS / TESTING.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF ALARM CONDITION.

DISCUSSION:

THIS EVENT POINT IS RECEIVED DURING EFIC TESTING BY PLACING THE SPRING -

RETURN TO NORMAL SWITCH TO EITHER TEST 1 OR TEST 2 POSITION IN THE ES-A MANUAL ACTUATION CABINET 4D. THESE TEST POSITIONS SIMULATE AN ES "A" SIGNAL TO EFIC CHANNELS "A" OR "B". THIS SWITCH DOES NOT BYPASS ANY ACTUATION SIGNAL FROM ENGINEERED SAFEGUARDS.

REFERENCES:

DRAWING 208-028-ES-A65 SENSING ELEMENT:

AR-403 Rev. 29 Page 156

ENCLOSURE 1 (Page 155 of 190) l-PSA-Z ANNUNCIATOR RESPONSE- PSA-Z-06-06 H-06-06 l

l EFIC BYPASS j

EVENT POINT 2035 INDICATED CONDITION:

o EFIC ES-B BYPASS / TESTING.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

THIS EVENT POINT IS RECEIVED DURING EFIC TESTING BY PLACING THE SPRING RETURN TO NORMAL SWITCH TO EITHER TEST 1 OR TEST 2 POSITION IN THE,ES-B MANUAL ACTUATION CABINET 50. THESE TEST POSITIONS- SIMULATE AN ES"B" SIGNAL TO EFIC CHANNELS "A" OR "B" THIS SWITCH DOES NOT SYPASS ANY ACTUATION SIGNAL FROM ENGINEERED SAFEGUARDS.

REFERENCES:

DRAWING 208-028-ES-B65 SENSING ELEMENT:

AR-403 Rev. 29 Page 157

i ENCLOSURt_1

(Page 156 of 190)

PSA-Z ANNUNCIA10R RESPONSE PSA-2-06-07 H-06-07 EFIC SHUTDOWN  ;

BYPASS i EVENT POINT 2013 3

INDICATED CONDITION:

i I

, o EFIC CHANNEL "A" MAIN STEAM ISOLATION ACTUATION BYPASSED.

j O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "A" s725 PSI STM CEN PRESS EFIC ACT BYPASS' PUSH-BU1 TON ILLUMINATED.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS EVENT POINT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING 0F MSLI/Mn'FI ACTUATION, AND THE BYPASS PUSH-Bi)TTON HAS BEEN DEPRESSED. THE ACTUATION SETPOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPROXIMATELY <725 PSIC.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 29 Page 158

ENCLOSURE 1 (Page 157 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA 2-06-07 H-06-07 l - - -- --

EFlC SHUTDOWN BYPASS EVENT POINT 2021 l

INDICATED CONDITION:

o EFIC CHANNEL "B" MAIN STEAM ISOLATION ACTUATION BYPASSED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "B" <725 PSI STM GEN PRESS EFIC ACT BYPASS' PUSH-BUTTON ILLUMINATED.

l OPERATOR ACTIONS FOR A VALID ALARMt DISCUSSION:

THIS EVENT POINT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING OF MSLI/MdFI ACTUATION, AND THE BYPASS PUSH-BUTTON HAS BEEN DEPRESSED. THE ACTUATION SETFOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPR0XIKATELY <725 PSIG.

REFERENCES:

VITRO DRAWING 3803-3005 SHEET 2 SENSING ELEMENT:

AR-403 Rev. 29 Page 159

)

i ENCLOSURE 1 O (Page 158 of 190)

I PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-07 H-06-07 EFIC SHUTDOWN BYPASS I

EVENT POINT 2024 INDICATED CONDITION:

o ' EFIC CHANNEL "C" MAIN STEAM ISOLATION ACTUATION BYPASSED.

O _

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "C" <725 PSI STM GEN PRESS EFIC ACT BYPASS' PUSH-BUTTON ILLUMINATED.

OPERATOR ACTIONS FOR A VALID ALARM:.

DISCUSSION:

THIS EVENT POINT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING OF MSLI/ W FI ACTUATION, AND THE BYPASS PUSH-BUTTON HAS BEEN DEPRESSED. THE ACTUATION SETPOINT IS <600 PSIC AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPROXIMATEl.Y <723 PSIC.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 3 SENSING ELEMENT:

AR-403 Rev. 29 Page 160

O ,

ENCLOSURE 1 (Page 159 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-07 H-06-07 EFIC SHUTDOWN BYPASS l

EVENT POINT 2028 -

INDICATED CONDITION:

o EFIC CHANNEL "D" MAIN STEAM ISOLATION ACTUATION BYPASSED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "D" <72$ PSI STM GEN PRESS EFIC ACT BYPASS' PUSH-BUTTON

!LLUMINATED.

4 OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS EVENT POIMT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING OF MSLI/WFI ACTUATION, AND ~HE BYPASS PUSH-BUTTON HAS BEEN DEPRESSED. THE ACTUATION SETPOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPROXIMATELY <725 PSIC.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 4 SENSING ELEMENT:

AR-403 Rev. 29 Page 161

ENCLOSURE 1

-(Page 160 of 190)

PSA-Z ANNUNCIATOR RESPONSE lPSA-Z-06-08 H-06-08 M

EFIC AH t

SYSTEM TROUBLE EVENT POINT 0767 INDICATED CONDITION:

o AHF-54A/AHF-54B DUCT, SM0KE DETECTED, OR TROUBLE AS SENSED BY PYROTRONIC SMOKE DETECTION MODULES AH-934-CE1 OR AH-934-CE2.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

~)ERATOR ACTIONS FOR A VALID ALARM

o INVESTIGATE CAUSE OF SMOKE DETECTED OR TROUBLE ALARM.

~

r DISCUSSION:

REFERENCES:

DRAWING 208-004-AH-185 SENSING ELEMENT: AH-934-CE1, AH-934-CE2 AR-403 Rev. 29 Page 162

s

]e EhdOSURE1 (Page 161 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-08 H-06-08 EFIC AH SYSTEM TROUBLE EVENT POINT 0768 INDICATED CONDITION:

o AHF-54A/AHF-54B DUCT, TEMPERATURE >85* AS SENSED BY AH-932-TS1/TS2.

O REDUNDANT INDICATION k'HICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF DUCT HIGH TEMPERATURE ALARM.

DISCUSSION:

REFERENCES:

DRAWING 208-005-AH-185 SENSING ELEMENT: AH-932-TS1, AH-932-TS2 AR-403 Rev. 29 Page 163

sNCLOSURE 1 (Page 162 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-08 H-06-08 tiFIC AH SYSTEM TROUBLE t ___ __

EVENT POINT 0774

[.

INDICATED CONDIFION:

o AHF-54A/AHF-54B DUCT, FLOW LOW AS SENSED BY AH-933-FS1/FS2.

V,O REDUNDANT INDICATION WHICH WILL VERIFY ALARM; OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW AIRFLOW ALARM.

DISCUSSION:

THIS ALARM POINT IS ACTUATED WHEN EFIC DUCT AIRFLOW IS LESS THAN 70%

OF DESIGN AIRFLO4

REFERENCES:

DRAWING 208-005-AH-185 lSENSINGELEMENT: AH-933-FS1, AH-933-FS2 AR-403 Rev. 29 Page 164

ENCLOSURE 1 (Page 163 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-08 H-06-08 f

EFIC AH SYSTEM i , TROUBLE l

i EVENT POINT 0775 INDICATED CONDITION:

o EFIC ROOM (S) TEMoERATURE HIGH/ LOW AS SENSED BY AH-944-TS1/TS2/TS3/TS4.

O L,]

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF EFIC ROOM TEMPERATURE ALARM.

DISCUSSION:

THIS ALARM POINT IS ACTUATED WHEN ANY EFIC ROOM TEMPERATURE IS LESS THAN 60'F OR GREATER THAN 8' '" "NE DETECTOR IS LOCATED IN EACH EFIC ROOM MOUNTED ON THE WALL A'-

t.1MATELY 4' FRO'i THE FLOOR. IF ALARM IS IN FOR NO APPARENT REASON ENGINEERING CAN ADJUST DAMPER AND/OR DUCT REGISTER POSITIONS TO BETTER DISTRIBUTE AIR FLOW THROUGHOUT THE ROOMS.

s O

-( j

REFERENCES:

DRAWING 208-005-AH-185 SENSING ELEMENT: AH-944-TS1, AH-944-TS2, AH-944-TS3, AH-944-TS4 AR-403 Rev. 29 Page 165

f ENCLOSURE 1 (Page 164 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-01' H-07-01

l. EF TANK
; LEVEL l l LOW LOW l l I I EVENT POINT 0815 INDICATED CONDITION

-l o EFT-2 LEVEL < 7' - 7" AS SENSED BY EF-98-LT, O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

. o ' EF-98-LII, EMERCENCY FEED TANK LEVEL INDICATION, o sEF-99-LII, EMERGENCY FEED TANK LEVEL INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P.

._= .

DISCUSSION:

I REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 20 5-026- E F-05 SENSING ELEMENT: EF-98-LT

'AR-403 Rev. 29 Page 166

)

p)

(

ENCLOSURE 1 (Page 165 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-02 H-07-02 EF PUMP 1 AUTO START EVENT POINT 1681 INDICATED CONDITION:

o EFP-1 MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION, s

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

. o RED LIGHT ON WITH A GREEN FLAG ON EFP-1 CONTROL STATION.

OPERAFOR ACTIONS FOR A VALID ALARM:

~

o REFER TO EOP.

DISCUSSION:

a

REFERENCES:

DRAWING 208-026-EF-01B SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/ST, CS/0 {

AR-403 Rev. 29 Page 167 I

M

q ENCLOSURE 1 Q (Page 166 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-03 H-07-03 EF PUMP 1 START l

FAILL'RE l

EVENT POINT 1680 INDICATED CONDITIO":

o EFP-1 A0 TOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION, AND 50 SECONDS HAVE ELAPSED WIT 11 AN ACTUATION SIGNAL PRESENT.

)

\_/

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o- REFER TO E0P.

o MANUALLY START EFP-1 DISCUSSION:

IF EFP-I FAILED TO START FROM A VALID ACTUATION SIGNAL, BUT WAS MANUALLY STARTED 1 HEN THIS ALARM WILL NOT ACTUATE DUE TO THE 50 SECOND TIME DELAY RELAY CIRCUIT. THE C0f(TROL SWITCH MUST BE IN THE NORMAL AFTER STOP POSITION TO ACTUATE THIS ALARM.

REFERENCES:

DPAWING 208-026-EF-01B SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/ST, CS/0 AR-403 Rev. 29 Page 168

ENCLOSURE 1 (Page 167 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-03 H-07-LJ l

1 l

EF PUMP 1 START FAILURE l

l l

EVENT POINT 1682 INDICATED CONDITION:

o EFP-1 DISCHARGE PRESSURE <1100 PSIG AS SENSED BY EF-17-PS WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

O

\j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO EOP.

o INVESTICATE CAUSE OF LOW DISCHARGE PRESSURE, DISCUSSION:

THE CONTROL SWITCH MUST BE IN THE NCRMAL AFTER START POSITION TO ACTUATE THIS EVENT DOINT.

i

REFERENCES:

DRAWING 208-026-EF-01B SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/SC, CS/0, EF-17-PS AR-403 Rev. 29 Page 169-

I..

ENCLOSURE 1 (Page 168 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-04 H-07-04 EF PUMP 1 TRIP

't -

EVENT POINT 1261 INDICATED CONDITION:

o EFP-1 MOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON EFP-1 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO EOP.

o INVESTIGATE CAUSE OF BREAKER TRIP.

DISCUSSION:

THE CONTROL SWITCH MUST BE IN THE NORMAL AFTER START POSITION TO ACTUATE THIS EVENT POINT.

REFERENCES:

DRAWING 208-026-EF-01 SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/SC, CS/6 AR-403 Rev. 29 page 170

ENCLOSURE 1 (Page 169 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-07-05 H-07-05 EF PUMP 1 OUT OF SERVICE l __

EVENT POINT 1191

. INDICATED CONDITION:

o EFP-1 CONTROL SWITCH IN PULL TO LOCK POSITION O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN AND RED LIGHTS EXTINGUISHED ON CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

REFERENCES:

DRAWING 208-026-EF-01 SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/PTL AR-403 Rev. 29 Page 171

ENCLOSURE 1 (Page 170 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-05 H-07-05 EF PUMP 1 OUT OF SERVICE EVENT POINT 1257 INDICATED CONDITION:

o EFP-1 CIRCUIT BREAKER NOT RACKED IN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN AND RED LIGHTS EXTINGUISHED ON CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

REFERENCES:

DRAWING 208-026-EF-01 s

SENSING ELEMENT: EFP-1 BREAKER 52H/B CONTACTS AR-403 Rev. 29 Page 172

(

ENCLOSURE 1 (Page 171 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-05 H-07-05 EF PUMP 1 OUT OF SERVICE O

EVENT POINT 1259 INDICATED CONDITION:

o EFP-1 CIRCUIT BREAKER LOSS OF DC CONTROL POWER.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN AND RED LIGHTS EXTINGUISHED ON CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

REFERENCES:

DRAWING 208-026-EF-01 SENSING ELEMENT: EFP-1 BREAKER CONTROL CIRCUIT 27 RELAY AR-403 Rev. 29 Page 173

ENCLOSURE 1 O (Page 172 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-06 H-07-06 EF PUMP 1 MOTOR i OVERLOAD I

EVENT POINT 1260 INDICATED CONDITION:

o EFP-1 MOTOR AMPS >115% RATED LOAD.

p.

b -

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS.

o EFP-1 BREAKER TRIP.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P.

o START- EFP-2.

o REDUCE EMERGENCY FEEDWATER FLOW FROM EFP-1 IF STILL RUNNING.

DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

ORAWING 208-026-EF-01 SENSING ELEMENT:

EFP-1 BREAKER 51 RELAY (INSIDE 4160 BREAKER CUBICLE)

AR-403 Rev. 29 Page 174

ENCLOSURE 1 (Page 173 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-07 H-07-07

_)

FWP-7  !

TRIP 3

EVENT POINT 0819 INDICATED CONDITION:

o FWP-7 MOTOR NOT ENERGIZED WITH CONTROL STATION IN NORMAL AFTER START POSITION.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON FWP-7 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF BREAKER TRIP, DISCUSSION:

REFERENCES:

DRAWING 208-032 FW-55 SENSING ELEMENT: CS/SC, CS/0 AR-403 Rev. 29 Page 175-

ENCLOSURE 1 (Page 174 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-07-08 H-07-08 FWP7 OVERCURRENT M

EVENT POINT 0780 INDICATED CONDITION:

o FWP-7 MOTOR AMPS >115% RATED LOAD O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS o FWP-7 BREAKER TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o REDUCE FEEDWATER FLOW FROM FWP-7 IF STILL RUNNING DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP

REFERENCES:

DRAWING 208-032 FW-55 SENSING ELEMENT:

FWP-7 BREAKER 51 RELAY (INSIDE 4160 BREAKER CUBICLE)

AR-403 Rev. 29 Page 176

1 ENCLOSURE 1 (Page 175 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-08 H-08-01 l

rrrrrrm EF TANK l g LEVEL.

,j l HIGH/ LOW I I l l 1 EVENT POINT 0816 INDICATED CONDITION:

o l EFT-2 LEVEL > 37' - 10" AS SENSED BY EF-98-LT.

5 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EF-98-LIl EMERGENCY FEED TANK LEVEL INDICATION.

o EF-99-LIl EMERGENCY FEED TANK LEVEL INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE TANK LEVEL TO NORMAL OPERATING 8AND.

DISCU5SION:

1

REFERENCES:

DRAWING 205-026 EF-05 SENSING ELEMENT: EF-98-LT AR-403 Rev. 29 Page 177

ENCLOSMRL1 (Page 176 of 190)-

PSA-Z ANNUNCIATOR RESPONSE PSA-2-08-01 H-08-01 I

EF TANK LEVEL l HIGHILOW ' '

t l ~ i l

L i

EVENT POINT 0817 INDICATED CONDITION:

l o EFT-2 LEVEL <32'-11" AS SENSED BY EF-99-LT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EF-98-LIl EMERCENCY FEED TANK LEVEL INDICATION.

o EF-99-LIl EMERGENCY FEED TANK LEVEL INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE TANK level TO NORMAL OPERATING BAND.

DISCUSSION:

THE LOW LEVEL ALARM SETp0 INT IS > THAN TECH. SPEC. LIMIT OF 150,000 I CALLONS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWINC 205-026 EF-05 i SENSING ELEMENT: EF-99-LT AR-403 Rev. 29 Page 178

O ENCLOSURE 1 (Page 177 of 190) 4BuuBO +

PSA-Z ANNUNCIATOR RESPONSE PSA-2-08-02 H-08-02 i

EF PUMP 2

, AUTO START EVENT POINT 1707 INDICATED CONDITION:

o EFP-2 DISCHARGE PRESSURE >1100 PSIG AS SENSED BY EF-18-PS, ANA 50 SECONDS l' AVE ELAPSED WITH AN ACTUATION SIGNAL PRESENT.

(%),

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO EOP.

DISCUSSION:

REFERENCES:

DRAWING 208-008 AS-01 SENSING ELEMENT: EF-18-PS AR-403 Rev. 29 Page 179 i

U

ENCLOSURE 1 (Page 178 of 190) .

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-03 H-08-O' l

EF PUMP 2 START FAILURE i

EVENT POINT 1706 INDICATED CONDITION:

o EFP-2 DISCIIARGE PRESSURE <1130 PSIG AS SENSED BY EF-18-PS, MQ 50 SECONDS HAVE ELAPSED WITH AN ACT1JATION SIGNAL PRESENT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P.

DISCUSSION:

REFERENCES:

DRAWING 208-008 AS-01 SENSING ELEMENT: EF-18-PS AR-403 Rev. 29 Page 180

ENCLOSURE 1 (Page 179 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-08-04 H-08-04 EF PUMP 2 TRIP EVENT POINT 0326 INDICATED CONDITION:

o

-- TURBINE DRIVEN EMERGENCY FEEDWATER PUMP STEAM SUPPLY VALVE ASV-50 NOT OPEN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO RESET ASV-50 DISCUSSION:

REFERENCES:

DRAWING 208-008 AS-01 l SENSING ELEMENT: 33C/ASV-50 AR-403 Rev. 29 Page 181

ENCLOSURE 1

( .(Page 180 of 190) f PSA-Z AdNUNCIATOR RESPONSE-- PSA-Z-08-05 H-08-05 I

EF PUMP 2 OUT OF SERVICE l

u EVENT POINT 0100 INDICATED CONDITION:

o ASV-5 CLOSED, WITH Du CONTROL POWER NOT AVAILABLE FOR >5 SECON05.

o MSV-55 CLOSED.

o MSV-56 CLOSED.

O REDUNDANT ILDICATION WHICH WILL VERIFY ALARM.

o ASV-5 POSITION INDICATION.

o MSV-55 POSITION INDICATION.

o MSV-56 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE LOSS OF CONTROL-POWER TO ASV-5.

o INVESTICATE CLOSURE OF MSV-55 OR MSV-56.

DISCUSSION:

IF THIS ALARM IS DUE TO THE ASV-5 CIRCUITRY THEN IT MEANS ASV-5 IS CLOSED WITH NO CONTROL POWER AVAILABLE TO ALLOW AN AUTO OPEN DURING AN EFW ACTUATION.

THE MSV-55 AND MSV-56 ALARMS ARE D'JE TO FULLY CLOSED LIMIT SWITCHES.

CONTROL POWER FOR ASV-5 IS SUPPLIED FROM DPDP-83 FUSE #6.

REFERENCES:

DRAWING 208-008 AS-01 SENSING ELEMENT: ASV-5 LS(13), 2ASV-5 RELAY, MSV-55 LS(5), MSV-56 LS(14)

AR-403 Rev. 29 Page 182

ENCLOSURE 1

-Of (Page 181 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-05 H-08-05 EF PUMP 2 l OUT OF SERVICE EVENT POINT 1521 INDICATED CONDITION:

4 o ASV-204 CLOSED, WITH DC CONTROL POWER NOT AVAILABLE.

O

.,EDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ASV-204 PC ' TION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE LOSS OF CONTROL POWER TO ASV-204.

DISCUSSION:

THIS ALARM ME/"c ASV-204 IS CLOSED WITH NO CONTROL POWER AVAILABLE TO ALLOW AN AUTO OPEN DURING AN ACTUATION. CONTROL POWER FOR ASV-204 IS SUPPLIED FROM DPDP-8A FUSE #15.

g

REFERENCES:

DRAWING 208-008 AS-07 SENSING ELEMENT: ASV-204 LS(13), 27ASV-204 RELAY AR-403 Rev. 29 Page 183

ENCLOSURE 1

( (Page 182 of 190)-

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06

' EMERG FW VALVE NOT FULL OPEN l

l EVENT POINT 1192 INDICATED CONDITION:

o EFV-32 NOT FULL OPEN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-32 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CLOSURE OF EFV-32.

DISCUSSION:

REFERENCES:

DRAWING 208-026 EF-10 SENSING ELEMENT: EFV-32 FULL OPEN LIMIT SWITCH AR-403 Rev. 29 Page 184

ENCLOSURE 1

-y (Page 183-of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-08-06 H-08-06 EMERG FW VALVE

-, NOT FULL OPEN EVENT POINT 1193 l

INDICATED CONDITION:

o EFV-11 NOT FULL OPEN.

j9

.w)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-11 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-11.

DISCUSSION:

REFERENCES:

DRAWING 208-026 EF-08 JENSINGELEMENT: EFV-11 FULL OPEN LIMIT SWITCH AR-403 Rev. 29 Page 185

ENCLOSURE 1 (Page 184 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06

' EMERG FW VALVE NOT FULL OPEN EVENT POINT 1194 l-INDICATED CONDITION:'

o EFV-14 NOT FULL OPEN.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i o EFV-14 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-14.

DISCUSSION:

REFERENCES:

DRAWING 208 026 EF-9 SENSING ELEMENT: EFV-14 FULL OPEN LIMIT SWITCH AR-403 Rev. 29 Page 186

ENCLOSURE 1 (Page 185 of 190)

PSA-Z ANNUNCIATOR RESPON5E PSA-Z-08-06 H-08-06 EMERG FW VALVE NOT FULL OPEN EVENT POINT 1196

! INDICATED CONDITION:

o EFV-33 NOT FULL OPEN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-33 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-33.

DISCUSSION:

REFERENCES:

DRA'VING 208-026 EF-11 SENSING ELEMENT: EFV-33 FULL OPEN LIMIT SWITCH AR-403 Rev. 29 Page 187

ENCLOSURE 1 (Page 186 of 190)

PSA-Z ANNUNrIATOR RESPONSE PSA-Z-08-06 H-08-05 EMERG FW VALVE NOT FULL OPEN -

EVENT POINT 1255

-INDICATED CONDITION:

o EFV-3 NOT FULL OPEN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-3 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-3.

DISCUSSION:

REFERENCES:

DRAWING 208-026 EF-02 SENSING ELEMENT: EFV-3 FULL OPEN LIMIT SWITCH AR-403' Rev. 29 Page 188

ENCLOSURE 1 (Page 187 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 EMERG FW VALVE NOT FULL OPEN EVENT POINT 1256 g INDICATED CONDITION:

o EFV-4 NOT FULL 0 PEN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-4 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CLOSURE OF EFV-4.

REFERENCES:

DRAWINC 208-026 EF-03 SENSING ELEMENT: EFV-4 FULL OPEN LIMIT SWITCH AR-403 Rev. 29 Page 189

EHCLOSURE_1 (Page 188 of 190).

i PSA-Z ANNUNCIATOR RE5FONSE P5A-2-08-06 H-08-06 EMERG FW VALVE NOT FULL OPEN EVENT POINT 1262 INDICATED CONDITION:

o EFV-7 NOT FULL OPEN.

l

f. REDUNDAN's INDICATION WHICH WILL VERIFY ALARM:

0-EFV 7 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CLOSURE OF EFV -7, DISCUSSION:

_=

REFERENCES:

ORAWING 208-026 EF-04 SENSING ELEMENT: EFV-7 FULL OPEN LIMIT SWITCH AR-403 Rev. 29 Page 190-Y Y M+JJ '

i l

ENCLOSURE 1 (Page 189 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 EMERG FW VALVE NOT FULL OPEN EVENT POINT 1263 INDICATED CONDIT N o EFV-8 NOT FULL OPEN.

(O J

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-8 POSIT!ON INDICATION.

OPERATOR ACTIONS FOR A VALID ALAI 4:

o INVESTIGATE CLOSURE OF EFV-8.

i DISCUSSION:

REFERENCES:

DRAWING 208-026 EF-05 SENSING ELEMENT: EFV-8 FULL OPEN LIMIT SWITCH 8N AR-403 Rev. 29 Page 191

i r ENCLOSURE 1 l (Page 190 of 190)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-08-07 H-08-07 i

EFV 12 l EF CROSS TIE

' OPEN  :

i
EVENT POINT 1266 y 2

INDICT.TED CONDIT. TON:

i o EFV-12 OPEN.

O '

2 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT LIT ON EFV-12 CONTROL STATION, EfV-12-MST IN "A" ES 480v i SW.TTCHCEAR ROCE,124" ELEV CC.

o FLOW INDICATED ON EF-62-FI, LOCATED ON PSA SECTION OF MCB (TO BE  !

1 INSTALLED BY MAR 97-01-04-01 '

OPERATOR ACTIONS FOR A-VALID ALARM:  !

j o VERIFY CROSS-FLOW VIA "A" SIDE EFIC FLOW INDICATORS.

]

DISCUSSION
EFV-12 POWERED FROM DPDP-8C, BKRS 5 (POWER) & 6 (CONTROL) 4 f

REFERENCES:

DRAWING 208-026 EF-24 SENSING' ELEMENT: LIMIT SWITCH CONTACT #9 AR-403 Rev. 29 Page 192 (LAST PAGE)

- , - . . ._ -. - . - _ . - - , - - .,- . . - - . - .-- .-_ --