ML20237B443

From kanterella
Jump to navigation Jump to search
Rev 14 to AR-703, Ssf R Annunciator Response
ML20237B443
Person / Time
Site: Crystal River 
Issue date: 08/10/1998
From:
FLORIDA POWER CORP.
To:
References
AR-703, NUDOCS 9808180268
Download: ML20237B443 (67)


Text

- _ _ - - _ - - _ _ - _ _ _ - - _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ - _ _ - _ _

Document Transmittal #: 100388 Date: 8/10/98 To:

NRC (DC DESK)

MAC: NfA Holder 6: 1242 Destmaison De5wyuux:

Copy Totals Document:

Revlsion:

Comment:

INFO CNTL MSTR AR0703 14 1

0 0

O 1

i i

f i

Instructions to the Addressee:

Please verify the document (s) received agrees with the above information Operations department must attach old document (s) or portions of document (s) superseded by the above to this transmittal.

L The signature indicates acknowledgment of receipt of the above document (s) and that documents have been

'3 updated. Retum signed and dated transmittal to Document Control within 15 working days of transmittal gh date to mailcode:

1 NA1C Rorida Power Corporabon Document Control, NA1C CrystalRiver Energy Complex 15760 W. PowerLine St.

CrystalRiver, FL 34428-6708 Signature of Addressee:

Date:

9808190268 980810 l

PDR ADOCK 05000302 i

F PDR 2

Rev. 14 O

Effective Date [ O

[

I\\FORMAr N'

-- ONLY d%

t ANNUNCIATOR RESPONSE AR-703 ELORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 SSF R ANNUNCIATOR RESPONSE I

i I

i

)

1 l

APPROVED BY: Procedure Owner AZWAV (S'IdNATURE '6N FILCD '

M4!9$

DATE:

//~

Ol PROCEDURE OWNER: Manager, Nuclear Plant Operations L-

e TABLE OF CONTENTS SECTION PAGE l

1.0 PURPOSE......................................,,,,,,,,,,,,,,,,,,,,,,,,,,,,3 LQ._BE FE RE NCES..........................................................

2.1 IMPLEMENTING REFERENCES.............................................

1 2.2 DEVELOPMENTAL REFERENf15............................................

1 3.0 PERSONNEL INDOCTRINATION.,............................................

,,1 4.0 INSTRUCTIONS..............................................,,,,,,,,,,,,,,,3 5.0 FOLLOW-UP-ACTIONS..........................................,,,,,,,,,,,,,,1 ENCLOSURE 1

A n n u n ci at o r Re s po n s e.............................................. 2 1

,O i

%)

i 4

1 I

l O

.\\

l AR-703 Rev. 14 Page i l

1

_________a

1.0 PURPOSE V

1.1 Establish a reference document for each Annunciator Window on the SSF-A3 Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the SSF-A3 Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the SSF-A3 Lampbox.

2.0 REFERENCES

2.1 BELEMENTING REFERENCES 2.1.1 AP-660, Turbine Trip 2.1.2 E0P, Emergency Operating 2.1.3 AP-545, Plant Runback 2.2 DEVELOPMENTAL REFERENCES v

2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-049 3.0 PERSONNEL INDOCTRINATION 3.1 The Annunciator System is powered from VBDP-5 Breaker 28.

4.0 INSTRUCTIONS 4.1 Respond to alarms on the SSF-A3 Lampbox as indicated on Enclosure 1, Annunciator Response.

5.0 FOLLOW-UP-ACTIONS None O

AR-703 Rev. 14 Page 1

i I

ENCLOSURE 1 5

(Page 1 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-01 R-01-01 morrr I

I I

I BREAKER 1661 g

TRIP l

I I

I I

I l

EVENT POINT 0803 l

INDICATED CONDITION:

l o 500 KV BREAKER 1661 OPEN AND CONTROL SWITCH IN NORMAL AFTER CLOSED

!\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l l

o INFORMED BY DISPATCHER OF BKR 1661 TRIP CONDITION o GREEN LIGHT ON WITH RED FLAG ON BREAKER 1661 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o IE BKR 1662 IS OPEN, IllEN ENSURE MAIN TURBINE IS TRIPPED o POSITION CONTROL SWITCH TO OPEN TO PREVENT BREAKER CLOSING UPON RESTCMTION OF POWER o STABILIZE PLANT AS NECESSARY o NOTIFY SYSTEM DISPATCHER DISCUSSION:

I 1

l

REFERENCES:

DRAWING 208-079 5B-01 SENSING ELEMENT: 52W/1661 i

AR-703 Rev. 14 Page 2

_____________________________________--------------------------------------------------.--------------.__-------------.-----------------------_______u

l ENCLOSURE 1 (Page 2 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-02 R-01-02 l

i BREAKER 1661 TROUBLE EVENT POINT 0834 INDICATED CONDITION:

o BREAKER 1661 AIR PRESSURE LOW O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INFORMED BY DISPATCHER OF BKR 1661 TROUBLE ALARM

)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER l

l DISCUSSION:

THE AIR SYSTEM IS MOTIVE AIR FOR OPENING AND CLOSING BREAKER 1661.

THE QUENCH GAS IS A AN UNRELATED SYSTEM THAT USES SULPHUR HEXAFLUORIDE GAS.

REFERENCES:

DRAWING 208-079 SB-01; DRAWING S171-13490 (SUBSTATION)

SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT l

AR-703 Rev. 14 Page 3

ENCLOSURE 1 i

(Page 3 of 63) l SSF ANNUNCIATOR RESPONSE SSF A3-01-02 R-01-02 BREAKER 1661 TROUBLE EVENT POINT 0835 INDICATED CONDITION:

o ANY OF THE FOLLOWING CONDITIONS ASSOCIATED WITH BKR 1661:

HI GAS TEMP LOSS OF AC SOURCE POWER LOW GAS TEMP LOSS OF DC CONTROL POWER LOW GAS PRESSURE l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INFORMED BY DISPATCHER OF BKR 1661 TROUBLE CONDITION l

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER DISCUSSION:

THE GAS IS SULPHUR HEXAFLUORIDE CAS THAT IS USED FOR QUENCHING ARC EMISSIONS DURING BREAKER OPERATION.

REFERENCES:

DRAWING 208-079 SB-01 SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT l

l AR-703 Rev. 14 Page 4

t ENCLOSURE 1 (Page 4 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-04 R-01-04 l

500 KV SUBSTATION FEED DEAD EVENT POINT 0842 INDICATED CONDITION:

o 500 KV SUBSTATION PRIMARY POWER FEED IS DE-ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i (

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o SEND TURBINE BUILDING OPERATOR TO 500KV SUBSTATION BLOCKHOUSE TO VERIFY ABT TRANSFERRED TO UNIT #3 (ABT IS IN NORTHEAST CORNER OF BLOCKHOUSE) o INFORM UNIT #4 THAT UNIT #3 IS SUPPLYING 500KV SUBSTATION ALTERNATE POWER DISCUSSION:

SUBSTATION POWER IS 480VAC AND IS NECESSARY FOR OPERATION OF SUBSTATION l

SWITCH AND RELAY EQUIPMENT.

j UNIT #4 IS THE PRIMARY SOURCE OF POWER, WITH UNIT #3 AS ALTERNATE VIA "B" 480V TURBINE AUX BUS UNIT 2C.

l A LOSS OF UNIT #3 POWER TO THE SUBSTATION WILL RESULT IN AUTOMATIC TRANSFER OF THE SUBSTATION'S POWER TO UNIT #4 IF UNIT #3 WAS SUPPLYING POWER. THE ABT IS LOCATED IN THE SUBSTATION BLOCKHOUSE (NORTHEAST CORNER)

IN THE 500KV YARD.

REFERENCES:

DRAWING 208-079 SENSING ELEMENT: 500KV SUBSTATION LOCAL MULTIPLEXING UNIT l

l l

AR-703 Rev. 14 Page 5

l ENCLOSURE 1

(

)

(Page 5 of 63)

SSF ANNUNCIATOR RESPONSE SS F-A3-01-04 R-01-04 500 KV SUBSTATION FEED DEALD EVENT POINT 1528 INDICATED CONDITION:

o 500 KV SUBSTATION ALTERNATE POWER FEED IS DE-ENERGIZED b

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

\\-

o "B" 480V TURBINE AUX BUS BREAKER UNIT 2C (500KV SUBSTATION DISTRIBUTION PANEL FEEDER IS OPEN)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o SEND TURBINE BUILDING OPERATOR TO 500KV SUBSTATION BLOCKHOUSE TO VERIFY ABT IS SUPPLYING SUBSTATION POWER FROM UNIT #4 (ABT IS IN NORTHEAST CORNER OF BLOCKHOUSE) o INFORM UNIT #4 THAT 500KV SUBSTATION ALTERNATE POWER FROM UNIT #3 IS UNAVAILABLE DISCUSSION:

SUBSTATION POWER IS 480VAC AND IS NECESSARY FOR RELAYING AND SWITCH OPERATIONS.

UNIT #4 IS THE PRIMARY SOURCE OF POWER, WITH UNIT #3 AS ALTERNATE, VIA "B" 480V TURBINE AUX BUS UNIT 2C A LOSS OF UNIT #4 POWER TO THE SUBSTATION WILL RESULT IN AN AUTOMATIC TRANSFER OF THE SUBSTATION'S POWER TO UNIT #3. THE ABT IS LOCATED IN THE SUBSTATION BLOCKHOUSE (NORTHEAST CORNER) IN THE 500KV YARD.

REFERENCES:

DRAWING 208 AC-02

\\_ /

SENSING ELEMENT: 500KV SUBSTATION LOCAL MULTIPLEXING UNIT I

AR-703 Rev. 14 Page 6

O ENCLOSURE 1 (Page 6 of 63) l SSF-A3 ANNUNCIATOR RESPONSE SS F-A3-01-05 R-01-05 500KV SUBSTATION TROUBLE EVENT POINT 0831 INDICATED CONDITION:

o 500 KV SUBSTATION DC VOLTAGE LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY DISPATCHER OF LOW DC VOLTAGE OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER i

DISCUSSION:

REFERENCES:

DRAWING 208-079 5B-15 SENSING ELEMENT: 500KV SUBSTATION LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 7

( ~s ENCLOSURE 1 (Page 7 of 63) 1 SSF ANNUNCIATOR RESPONSE SSF-A3-01-05 R-01-05 l

500KV SUBSTATION TROUBLE EVENT POINT 0832 INDICATED CONDITION:

l o 500 KV SUBSTATION DIGITAL FAULT RECORDER TROUBLE REDUNDANT. INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY SYSTEM DISPATCHER OF DIGITAL FAULT RECORDER TROUBLE OPERATOR ACTIONS FOR A VALID ALARM:

q o NOTIFY SYSTEM DISPATCHER DISCUSSION:

THE DIGITAL FAULT RECORDER (DFR) IS A FAULT MONITORING SYSTEM THAT l

REPLACES THE OSCILLOGRAPH. THE DFR PERFORMS THE SAME FAULT RECORDING FUNCTIONS AS THE OSCILLOGRAPH DID.

t

REFERENCES:

DRAWING 208-079 SB-15 SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 8

ENCLOSURE 1 bv (Page 8 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-05 R-01-05 500KV SUBSTATION TROUBLE EVENT POINT 0838 INDICATED CONDITION:

o BREAKER 1660 TROUBLE O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY DISPATCHER OF BREAKER 1660 TROUBLE OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER r

DISCUSSION:

i i

REFERENCES:

DRAWING 208-079 5B-10 SENSING ELEMENT: 500KV SUBSTATION LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 9 u_-__-____-._---__..__--__---

ENCLOSURE 1

(

(Page 9 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-05 R-01-05 L

500KV SUBSTATION TROUBLE EVENT POINT 0839 INDICATED CONDITION:

o BREAKER 1891 TROUBLE O

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY DISPATCHER OF BREAKER 1891 TROUBLE OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER DISCUSSION:

l f

I

REFERENCES:

DRAWING 208-079 SB-10 SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT l

i AR-703 Rev. 14 Page 10

l ENCLOSURE 1 (Page 10 of 63)

SSF-ANNUNCIATOR RESPONSE SSF-A3-01-05 R-02-05 500KV SUBSTATION TROUBLE EVENT POINT 0840 INDICATED CONDITION:

l o 500 KV SUBSTATION RELAY SYSTEM LOSS OF DC POWER O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY DISPATCHER OF 500 KV RELAY SYSTEM LOSS OF DC POWER.

1 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o NOTIFY TURBINE BUILDING OPERATOR TO GO TO THE 500KV BLOCKHOUSE AND READ i

THE FAULT INFORMATION RECORDED ON THE SUBSTATION EVENTS RECORDER PAPER l

PRINTOUT, REPORT THIS INFORMATION TO THE SYSTEM DISPATCHER l

DISCUSSION:

i

REFERENCES:

DRAWING 208-079 58-14

(

SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 11

ENCLOSURE 1 (Page 11 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-05 R-01-05 t

1 500KV SUBSTATION TROUBLE EVENT POINT 0841 INDICATED CONDITION:

o 500 KV SUBSTATION BATTERY CHARGER TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY SYSTEM DISPATCHER OF 500 KV SUBSTATION BATTERY CHARGER TROUBLE OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o NOTIFY TURBINE BUILDING OPERATOR TO GO TO THE 500KV BLOCKHOUSE TO INSPECT BATTERY CHARGERS FOR PROPER OPERATION DISCUSSION:

BATTERY CHARGERS ARE LOCATED IN THE 500KV BLOCKHOUSE, NORTH END - AD]ACENT TO THE BATTERIES. THE CHARGERS HAVE VOLTAGE INSTRUMENTATION, POWER AVAILABLE, AND FAULT LIGHTS TO DETERMINE THEIR STATUS.

I

REFERENCES:

DRAWING 208-079 5B-14 SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT I

AR-703 Rev. 14 Page 12

i ENCLOSURE 1 (Page 12 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3 05 R-01-05 i

500KV SUBSTATION TROUBLE j

EVENT POINT 0844 i

1 INDICATED CONDITION:

o 500 KV SUBSTATION MULTIPLEXER FAILURE O'

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY DISPATCHER OF 500 KV SUBSTATION MULTIPLEXER FAILURE OPERATOR ACTIONS FOR A VALID ALARM:

i o NOTIFY SYSTEM DISPATCHER i

DISCUSSION:

THIS DEVICt: ACTS AS AN INTERFACE BEWEEN SUBSTATION FAULT ALARMS AND THE UNIT #3 CONTROL ROOM ALARM SYSTEM. THE MULTIPLEXER MONITORS VARIOUS SUBSTATION PARAMETERS, AND THE ALARM INDICATES IT HAS FAILED.

SUBSTATION FAULT CONDITIONS MAY NOT ALARM IF THE MULTIPLEXER IS INOPERABLE.

REFERENCES:

DRAWING 208-079 SB-15 SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT i

l AR-703 Rev. 14 Page 13

i ENCLOSURE 1 (Page 13 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-01-05 R-01-05 500KV SUBSTATION TROUBLE EVENT POINT 0849 INDICATED CONDITION:

o 500 KV SUBSTATION DIGITAL FAULT RECORDER ALARM O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY DISPATCHER OF 500 KV DIGITAL FAULT RECORDER ALARM OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER t

l DISCUSSION:

THE DIGITAL FAULT RECORDER (DFR) IS A FAULT MONITORING SYSTEM THAT REPLACES THE OSCILLOGRAPH. THE DFR PERFORMS THE SAME FAULT RECORDING FUNCTIONS AS THE OSCILLOGRAPH DID.

REFERENCES:

DRAWING 208-079 SB-14 SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 14

l I

l I

ENCLOSURE 1 (Page 14 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-02-01 R-02-01 i

r v-r I

l l

BREAKER 1662 g

TRIP l

1 l

EVENT POINT 0804 l

INDICATED CONDITION:

o 500 KV BREAKER 1662 OPEN AND CONTROL SWITCH IN NORMAL AFTER CLOSED O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

t o INFORMED BY DISPATCHER OF BKR 1662 TRIP CONDITION o CREEN LIGHT ON WITH RED FLAG ON BREAKER 1662 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o IE BKR 1661 IS OPEN, IllEN ENSURE MAIN TURBINE IS TRIPPED o POSITION CONTROL SWITCH TO OPEN TO PREVENT BREAKER CLOSING UPON RESTORATION OF POWER l

o STABILIZE PLANT AS NECESSARY l

o NOTIFY SYSTEM DISPATCHER

REFERENCES:

DRAWING 208-079 SB-02 SENSING ELEMENT: 52W/1662 t

l AR-703 Rev. 14 Page 15

I I

ENCLOSURE 1 (Page 15 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-02-02 R-02-02 BREAKER 1662 TROUBLE EVENT POINT 0836 INDICATED CONDITION:

o BREAKER 1662 LOW AIR PRESSURE O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INFORMED BY DISPATCHER OF BKR 1662 LOW GAS PRESSURE CONDITION OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER l

l DISCUSSION:

THE AIR SYSTEM IS MOTIVE AIR FOR OPENING AND CLOSING BREAKER 1662.

THE QUENCH GAS IS A AN UNRELATED SYSTEM THAT USES SULPHUR HEXAFLUORIDE GAS.

l

REFERENCES:

DRAWING 208-079 5B-02; DRAWING S171-1350D (SUBSTATION)

SENSING ELEMENT: 500 KV LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 16

)

ENCLOSURE 1 (Page 16 of 63) l SSF ANNUNCIATOR RESPONSE SSF-A3-02-02 R-02-02 l

BREAKER 1662 TROUBLE EVENT POINT 0837 INDICATED CONDITION:

o ANY OF THE FOLLOWING CONDITIONS ASSOCIATED WITH BKR 1662:

HI GAS TEMP LOSS OF AC SOURCE POWER f

LOW GAS TEMP LOSS OF DC CONTROL POWER LOW GAS PRESSURE t

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o INFORMED BY DISPATCHER OF BKR 1662 TROUBLE CONDITION I

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER l

DISCUSSION:

THE GAS IS SULPHUR HEXAFLUORIDE GAS THAT IS USED FOR QUENCHING ARC EMISSIONS DURING BREAKER OPERATION.

REFERENCES:

DRAWINC 208-079 58-02 O

SENSING ELEMENT: 500 KV SUBSTATION LOCAL MULTIPLEXING UNIT V

t AR-703 Rev. 14 Page 17 I

I______________--______---.---.-_-_-___------------_-------_-

1 q

ENCLOSURE 1 Q

(Page 17 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-02-04 R-02-04 500 KV YARD MTR OPERATED l

SWITCH OPEN I

i EVENT POINT 0833 INDICATED CONDITION:

l o ANY OF TlE FOLLOWING 500 KV MOTOR OPERATED SWITCHES NOT FULLY CLOSED l

1661 NORTH 1662 NORTH 1873 1661 SOUTH 1662 SOUTH REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

CONTROL BOARD INDICATING LIGHTS INDICATE MOTOR OPERATED SWITCH NOT FULLY o

CLOSED OPERATOR ACTIONS FOR A VALID ALARM:

I o ENSURE APPLICABLE MOTOR OPERATED SWITCH IS REQUIRED TO BE OPEN l

l o NOTIFY SYSTEM DISPATCHER l

l DISCUSSION:

REFERENCES:

DRAWING 208-079 SB-07 SENSING ELEMENT: 500 KV LOCAL MULTIPLEXING UNIT AR-703 Rev. 14 Page 18

ENCLOSURE 1 (Page 18 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-02-05 R-02-05 PRIMARY RELAYING ALARM EVENT POINT 0781 INDICATED CONDITION:

o UNIT #5 PILOT WIRE RELAYING ALARM f%)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o NOTIFIED BY SYSTEM DISPATCHER OF RELAY ALARM OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT SYSTEM DISPATCHER o RESET ALARM AS REQUESTED BY DISPATCHER DISCUSSION:

i THIS ALARM INDICATES A PROBLEM WITH UNIT #5 INPUT TO THE 500 KV GRID.

REFERENCES:

DRAWING S171 (SUBSTATION)

SENSING ELEMENT: 500 KV LOCAL MULTIPLEXING UNIT O

AR-703 Rev. 14 Page 19 L___-__-_-___-_____

l j

ENCLOSURE 1 l

(Page 19 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A 05 R-02-05 PRIMARY RELAYING ALARM EVENT POINT 0782 INDICATED CONDITION:

o CENTRAL FLORIDA TRANSFER TRIP AND LINE PROTECTION RELAYING ALARM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY SYSTEM DISPATCHER OF PRIMARY RELAY ALARM OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT SYSTEM DISPATCHER o RESET ALARM AS REQUESTED BY DISPATCHER DISCUSSION:

THIS ALARM INDICATES A PROBLEM ON THE CENTRAL FLORIDA LINE, l

l

REFERENCES:

DRAWING S171 (SUBSTATION) i SENSING ELEMENT: 500 KV LOCAL MULTIPLEXING UNIT O

AR-703 Rev. 14 Page 20 w_-_______-_________-_-_-__

l l O ENCLOSURE 1 U

(Page 20 of 63)

SSF ANNUNCIATOR RESPONSE SS F-A3-02-05 R-02-05 PRIMARY RELAYING ALARM EVENT POINT 0867 INDICATED CONDITION:

-o BROOKRIDGE TRANSFER TRIP AND LINE PROTECTION RELAYING ALARM I

O

, U REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFIED BY SYSTEM DISPATCHER OF PRIMARY RELAY ALARM OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT SYSTEM DISPATCHER o RESET ALARM AS REQUESTED BY DISPATCHER i

i DISCUSSION:

THIS ALARM INDICATES A PROBLEM ON THE BROOKRIDGE LINE i

REFERENCES:

DRAWINGS S171 (SUBSTATION)

SENSING ELEMENT: 500 KV LOCAL MULTIPLEXING UNIT l

9

t ENCLOSURE 1 (Page 21 of 63) l SSF ANNUNCIATOR RESPONSE SSF-A-03-02 R-03-02 l

l STEPUP XFMR MAJOR ALARM l

EVENT POINT 0736 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" TOP OIL TEMPERATURE >90* C.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

,l ('N

'(

o RED LIGHT IS ON, LOCATED ON "A" STEP UP XFMR (3-3) ALARM PANEL o COMPUTER POINT A-313 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "A" STEP UP TRANSFORMER OIL PUMPS AND FANS OPERATING FOR VALID ALARM REDUCE ELECTRICAL LOAD UNTIL ALARM CLEARS (100 MW LOAD o

REDUCTION INCREMENTS PER HALF HOUR RECOMMENDED). ENSURE MVAR LOADING LESS THAN 100 MVAR DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS l

EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUCE SYSTEM DUE TO HIGH FAN I

EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS I

OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL RESTART.

REFERENCES:

DRAWING 208-040 S'iEET MT-90 l

SENSING ELEMENT: 30/6 Ov AR-703 Rev. 14 Page 22

____________-._______A

ENCLOSURE 1 (Page 22 of 63) dSF-A3 ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 0737 INDICATED CONDITION:

l o STEP-UP TRANSFORMER PHASE "A" WINDING TEMPERATURE IS >105* C.

REDUNDAM INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON "A" STEP UP XFMR (3-3) ALARM PANEL o COMPUTER POINT A-310 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "A" STEP UP TRANSFORMER OIL PUMPS AND FANS OPERATING o FOR VALID ALARM REDUCE ELECTRICAL LOAD UNTIL ALARM CLEARS (100 MW LOAD REDUCTION INCREMENTS PER HALF HOUR RECOMMENDED). ENSURE MVAR LOADING LESS 1

THAN 100 MVAR DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL RESTART.

1

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/7 O

AR-703 Rev. 14 Page 23

l i.

l ENCLOSURE 1 (Page 23 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A-03-02 R-03-02 1

STEPUP XFMR MAJOR ALARM i

EVENT POINT 0738 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" PRESSURE RELIEF DEVICE ACTUATED >IO PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

)

i o RED LIGHT IS ON, LOCATED ON THE "A" STEP UP XFMR (3-3) ALARM PANEL 1

i OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER I

j o VERIFY ALL "A" STEP UP XFMR OIL PUMPS AND FANS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL l

o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. FURTHER DEGRADATION OF THIS INSULATION COULD CAUSE A FIRE / EXPLOSION IN THE TRANSFORMER,

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/8 AR-703 Rev. 14 Page 24

f'~N ENCLOSURE 1 g

(_,)

(Page 24 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFAAR MAJOR ALARM EVENT POINT 0739 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" COMBUSTIBLE GAS MONITOR ACTUATED > 200 CC GAS VOLUME REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE "A" STEP UP XFMR (3-3) ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "A" STEP UP XFMR OIL PUMPS AND FANS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE l

TRANSFORMER. AS THE INSULATION DEGRADES COMBUSTIBLE CAS EVOLVES. THE CAS COLLECTS IN A CHAMBER ON THE TOP OF THE TRANSFORMER. THE AMOUNT OF THIS CAS IS READ ON A GAUGE ON THE TRANSFORMER.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/9 O

l AR-703 Rev. 14 Page 25 i

l

l ENCLOSURE 1 (Page 25 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 4

STEPUP XFMR MAJOR ALARM EVENT POINT 1159 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" TOP OIL TEMPERATURE >90* C REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE "B" STEP UP XFMR (3-2) ALARM PANEL o COMPUTER POINT A-312 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "B" STEP UP XFMR OIL PUMPS AND FANS OPERATING o FOR VALID ALARM REDUCE ELECTRICAL LOAD UNTIL ALARM CLEARS (100 MW LOAD REDUCTION INCREMENTS PER HALF HOUR RECOMMENDED). ENSURE MVAR LOADING LESS THAN 100 MVAR DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL RESTART.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/6 O

AR-703 Rev. 14 Page 26 s

ENCLOSURE 1 (Page 26 of 63)

SSF ANNUNCIATOR RESPONSE SS F-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 1160 INDICATED CONDITION:

l o STEP-UP TRANSFORMER PHASE "B" WINDING TEMPERATURE >105a C REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

, s) o RED LIGHT IS ON, LOCATED ON THE "B" STEP UP XFMR (3-2) ALARM PANEL o COMPUTER POINT A-309 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "B" STEP UP XFMR OIL PUMPS AND FANS OPERATING l

o FOR VALID ALARM REDUCE ELECTRICAL LOAD UNTIL ALARM CLEARS (100 MW LOAD REDUCTION INCREMENTS PER HALF HOUR RECOMMENDED). ENSURE MVAR LOADING LESS THAN 100 MVAR DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN j

EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS l

OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL l

RESTART.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/7 O

l AR-703 Rev. 14 Page 27 i

ENCLOSURE 1

^

(Page 27 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 1161 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" PRESSURE RELIEF DEVICE ACTUATED > 10 PSIG n

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE "B" STEP UP XFMR (3-2) ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "B" STEP UP XFMR OIL PUMFS AND FANS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. FURTHER DEGRADATION OF THIS INSULATION COULD CAUSE A FIRE / EXPLOSION IN THE TRANSFORMER.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/8 AR-703 Rev. 14 Page 28

\\

1

ENCLOSURE 1 iO (Page 28 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 1162 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" COMBUSTIBLE GAS MONITOR ACTUATED > 200 CC GAS VOLUME REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE "B" STEP UP XFMR (3-2) ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

I o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "B" STEP UP XFMR OIL PUMPS AND FANS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD l

DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. AS THE INSULATION DEGRADES COMBUSTIBLE GAS EVOLVES. THE GAS l

COLLECTS IN A CHAMBER ON THE TOP OF THE TRANSFORMER. THE AMOUNT OF THIS GAS IS READ ON A GAUGE ON THE TRANSFORMER.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/9 AR-703 Rev. 14 Page 29

ENCLOSURE 1 (Page 29 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 1169 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "C" TOP OIL TEMPERATURE > 90* C REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

C o RED LIGHT IS ON, LOCATED ON THE "C" STEP UP XFMR (3-1) ALARM PANEL o COMPUTER POINT A-311 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "C" STEP UP XFMR OIL PUMPS AND FANS OPERATING o FOR VALID ALARM ELECTRICAL LOAD UNTIL ALARM CLEARS (100 MW LOAD REDUCTION INCREMENTS PER HALF HOUR RECOMMENDED). ENSURE MVAR LOADING LESS THAN 100 MVAR 4

l DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUFPS WILL j

I RESTART.

REFERENCES:

DRAWING 208-040 SHEET MT-90 l

l SENSING ELEMENT: 30/6 O

l AR-703 Rev. 14 Page 30

O ENCLOSURE 1 (Page 30 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 1170 s

INDICATED CONDITION:

l o STEP-UP TRANSFORMER PHASE "C" WINDING TEMPERATURE > 105* C l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

[C o RED LIGHT IS ON, LOCATED ON THE "C" STEP UP XFMR (3-1) ALARM PANEL l

o COMPUTER POINT A-308 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "C" STEP UP XFMR OIL PUMPS AND FANS OPERATING o FOR VALID ALARM REDUCE ELECTRICAL LOAD UNTIL ALARM CLEARS (100 MW LOAD REDUCTION INCREMENTS PER HALF HOUR RECOMMENDED). ENSURE MVAR LOADING LESS THAN 100 MVAR DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL RESTART.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/7 O

I AR-703 Rev. 14 Page 31

(

ENCLOSURE 1 i,

(Page 31 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 i

l l

l l

STEPUP XFMR MAJOR ALARM l

l EVENT POINT 1171 l

INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "C" PRESSURE RELIEF DEVICE ACTUATED > 10 PSIG

'\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE "C" STEP UP XFMR (3-1) ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

l o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "C" STEP UP XFMR OIL PUMPS AND FANS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD l

DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. FURTHER DEGRADATION OF THIS INSULATION COULD CAUSE A FIRE / EXPLOSION IN THE TRANSFORMER.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/8 AR-703 Rev. 14 Page 32 i

(

ENCLOSURE 1 (Page 32 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-02 R-03-02 STEPUP XFMR MAJOR ALARM EVENT POINT 1172 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "C" COMBUSTIBLE GAS MONITOR ACTUATED > 200 CC GAS VOLUME REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i

)

o RED LIGHT IS ON, LOC,irEO ON TH.F. "C" STEP UP XFMR (3-1) ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL "C" STEP UP XFMR OIL PUMPS AND FANS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL l

o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. AS THE INSULATION DEGRADES COMBUSTIBLE CAS EVOLVES. THE CAS COLLECTS IN A CHAMBER ON THE TOP OF THE TRANSFORMER. THE AMOUNT OF THIS GAS IS READ ON A GAUGE ON THE TRANSFORMER.

i

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/9

(

AR-703 Rev. 14 Page 33

r ENCLOSURE 1 t

(Page 33 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

STEPUP XFMR MINOR ALARM EVENT POINT 0731 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" AUXILIARY POWER NORMAL SOURCE FAILURE ALARM p

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 5) o VERIFY ALTERNATE POWER AVAILABLE (ACDP-2 BREAKER 5)

DISCUSSION:

i

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/1 STEPUP XFMR 4A CONTROL PANEL Ot v

AR-703 Rev. 14 Page 34

O ENCLOSURE 1 (Page 34 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 7,

STEPUP XFMR MINOR ALARM EVENT POINT 0732 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" AUX POWER ALTERNATE SOURCE FAILURE ALARM

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALTERNATE POWER AVAILABLE (ACDP-2 BREAKER 5) l o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 5)

DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/2 STEPUP XFMR 4A CONTROL PANEL v

AR-703 Rev. 14 Page 35 l__--__------___---_-_--__-------------------------_--------

(s ENCLOSUR O t

(Page 35 of 63) 1 SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 0733 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" CONTROL CIRCUIT POWER FAILURE ALARM O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET 000R OPERATOR ACTIONS FOR A VA' TD ALARM:

o NOTIFY SYSTEM DISPATCHER o CHECK CONTROL PANEL INTERNAL BREAKERS i

DISCUSSION:

THIS ALARM INDICATES THAT POWER HAS BEEN INTERRUPTED TO ONE OR MORE MAIN CONTROL CIRCUITS. ADDITIONAL ALARMS ON OIL PUMP FLOW MAY BE COINCIDENT.

1

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/3 STEPUP XFMR 4A CONTROL PANEL AR-703 Rev. 14 Page 36

i I

,w ENCLOSURE 1 t

(Page 36 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 0734 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" OIL FLOW LOW f

\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

w o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR o TRANSFORMER LOCAL OIL FLOW INDICATOR (FIVE INDICATORS PER TRANSFORMER)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY PUMP BREAKER (5) CLOSED (INSIDE CABINET)

DISCUSSION:

)

1 l

REFERENCES:

DRAWING 208-040 SHEET MT-90 O

SENSING ELEMENT: 30/4 STEPUP XFMR 4A CONTROL PANEL

%)

l AR-703 Rev. 14 Page 37

e ENCLOSURE 1 (Page 37 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 0735 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" OIL LEVEL LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR o TRANSFORMER LOCAL OIL LEVEL INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o OBSERVE LOCAL OIL LEVEL (NORMAL INDICATION >25%)

o CHECK TRANSFORMER FOR OIL LEAKAGE DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/5 STEPUP XFMR 4A CONTROL PANEL AR-703 Rev. 14 Page 38

1 ENCLOSURE 1

,[]

\\kJ (Page 38 of 63) l SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

i STEPUP XFMR MINOR ALARM l

EVENT POINT 0740 l

INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "A" ALARM SYSTEM LOSS OF DC POWER

, (/

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY DC POWER AVAILABLE (DPDP-3A BREAKER 1) 1 DISCUSSION:

THIS ALARM INDICATES NO OTHER LOCAL ALARMS ON THE TRANSFORMER ARE l

AVAILABLE.

INCREASED MONITORING FREQUENCY FOR THIS TRANSFORMER SHOULD BE CONSIDERED.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 27/6 STEPUP XFMR 4A CONTROL PANEL

%)

l AR-703 Rev. 14 Page 39

l p

ENCLOSURE 1 1

(Page 39 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 1154 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" AUXILIARY POWER NORMAL SOURCE FAILURE ALARM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

v o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

' o NOTIFY SYSTEM DISPATCHER o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 4) o VERIFY ALTERNATE POWER AVAILABLE (ACDP-2 BREAKER 4)

DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/1 STEPUP XFMR 48 CONTROL PANEL AR-703 Rev. 14 Page 40

-__-____-_______________A

ENCLOSURE 1 (Page 40 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

l l

STEPUP XFMR MINOR ALARM l

EVENT POINT 1155 l

INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" AUX POWER ALTERNATE SOURCE FAILURE ALARM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALTERNATE POWER AVAILABLE (ACDP-2 BREAKER 4) o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 4)

DISCUSSION:

l

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/2 STEPUP XFMR 48 CONTROL PANEL AR-703 Rev. 14 Page 41

ENCLOSURE 1 (Page 41 of 63) l SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

l l

STEPUP XFMR MINOR ALARM EVENT POINT 1156 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" CONTROL CIRCUIT POWER FAILURE ALARM 1

\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o CHECK CONTROL PANEL INTERNAL BREAKERS DISCUSSION:

THIS ALARM INDICATES THAT POWER HAS BEEN INTERRUPTED TO ONE OR MORE MAIN CONTROL CIRCUITS. ADDITIONAL ALARMS ON OIL PUMP FLOW MAY BE COINCIDENT.

REFERENCES:

DRAWING 208-040 SHEET MT-90 O)

SENSING ELEMENT: 30/3 STEPUP XFMR 4B CONTROL PANEL l

AR-703 Rev. 14 Page 42

fp ENCLOSURE 1 g

(Page 42 of 63) 1 SSF ANNUNCIATOR RESPONSE 55F-A3-03-03 R-03-03 l

STEPUP XFMR MINOR ALARM EVENT POINT 1157 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" OIL FLOW LOW 0-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR o TRANSFORMER LOCAL OIL FLOW INDICATOR (FIVE INDICATORS PER TRANSFORMER)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY PUMP BREAKER (S) CLOSED (INSIDE CABINET)

DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/4 STEPUP XFMR 4B CONTROL PANEL AR-703 Rev. 14 Page 43

l ENCLOSURE 1 hs V

(Page 43 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

l l

STEPUP XFMR MINOR ALARM l

l EVENT POINT 1158 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" OIL LEVEL LOW O\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR o TRANSFORMER LOCAL OIL LEVEL INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o OBSERVE LOCAL OIL LEVEL (NORMAL INDICATION >25%)

o CHECK TRANSFORMER FOR OIL LEAKAGE DISCUSSION:

i

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/5 STEPUP XFMR 4B CONTROL PANEL l

AR-703 Rev. 14 Page 44

_-__________________________-.____.----U

h ENCLOSURE 1

%J (Page 44 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 1163 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "B" ALARM SYSTEM LOSS OF DC POWER OV REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY DC POWER AVAILABLE (DPDP-3A BREAKER 1)

DISCUSSION:

THIS ALARM INDICATES NO OTHER LOCAL ALARMS ON THE TRANSFORMER ARE AVAILABLE. INCREASED MONITORING FREQUENCY FOR THIS TRANSFORMER SHOULD BE CONSIDERED.

I

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 27/6 STEPUP XFMR 4B CONTROL PANEL AR-703 Rev. 14 Page 45 o

p ENCLOSURE 1 Q

(Page 45 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 1164 INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "C" AUX POWER NORMAL SOURCE FAILURE ALARM O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 1) o VERIFY ALTERNATE POWER AVAILABLE (ACDP-2 BREAKER 3)

I DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/1 STEPUP XFMR 4C CONTROL PANEL l

AR-703 Rev. 14 Page 46

l t

t EN_(LOSURE 1 (Page 46 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 1165 l

INDICATED CONDITION:

o STEP-UP TRANSFORMER PHASE "C" AUX POWER ALTERNATE SOURCE FAILURE ALARM l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALTERNATE POWER AVAILABLE (ACDP-2 BREAKER 3) o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 1)

DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 30/2 STEPUP XFMR 4C CONTROL PANEL AR-703 Rev. 14 Page 47

L i

ENCLOSURE 1

,y (Page 47 of 63)

{

l SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

STEPUP XFMR MINOR ALARM EVENT POINT 1166 INDICATED CONDITION.

o STEP-UP TRANSFORMER PHASE "C" CONTROL CIRCUIT POWER FAILURE ALARM 4

O REDUNDANT INDICATION Wl'ICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o CHECK CONTROL PANEL INTERNAL BREAKERS DISCUSSION:

THIS ALARM INDICATES THAT POWER HAS BEEN INTERRUPTED TO ONE OR MORE MAIN CONTROL CIRCUITS. ADDITIONAL ALARMS ON OIL PUMP FLOW MAY BE COINCIDENT.

REFERENCES:

DRAWING 208-040 SHEET MT-90

'~%

SENSING ELEMENT: 30/3 STEPUP XFMR 4C CONTROL PANEL (J

AR-703 Rev. 14 Page 48

)

O ENCLOSURE 1 b

(Page 48 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 l

STEPUP XFMR MINOR ALARM EVENT POINT 1167 INDICATED CONDITION:

o STEP-UP XFMR PHASE "C" OIL FLOW LOW

/D U

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR o TRANSFORMER LOCAL OIL FLOW INDICATOR (FIVE INDICATORS PER TRANSFORMER)

OPERATOR ACTIONS FOR A VALID ALARM:

l o NOTIFY SYSTEM DISFATCHER o VERIFY PUMP BREAKER (S) CLOSED (INSIDE CABINET)

DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-90 p

SENSING ELEMENT: 30/4 STEPUP XFMR 4C CONTROL PANEL V

I AR-703 Rev. 14 Page 49

ENCLOSURE 1 (Page 49 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 STEPUP XFMR MINOR ALARM EVENT POINT 1168 INDICATED CONDITION:

o STEP-UP XFMR PHASE "C" OIL LEVEL LOW O-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR o TRANSFORMER LOCAL OIL LEVEL INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o OBSERVE LOCAL OIL LEVEL (NORMAL INDICATION >25%)

o CHECK TRANSFORMER FOR OIL LEAKAGE DISCUSSION:

1

REFERENCES:

DRAWING 208-040 SHEET MT-90

(

SENSING ELEMENT: 30/5 STEPUP XFMR 4C CONTROL PANEL l

l i

AR-703 Rev. 14 Page 50

ENCLOSURE 1 (Page 50 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-03-03 R-03-03 i

STEPUP XFMR MINOR ALARM EVENT POINT 1173 INDICATED CONDITION:

o STEP-UP XFMR PHASE "C" ALARM SYSTEM LOSS OF DC POWER j

1 OV REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT ON CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY DC POWER AVAILABLE (DPDP-3A BREAKER 1) i DISCUSSION:

THIS ALARM INDICATES NO OTHER LOCAL ALARMS ON THE TRANSFORMER ARE AVAILABLE. INCREASED MONITORING FREQUENCY FOR THIS TRANSFORMER SHOULD BE CONSIDERED.

REFERENCES:

DRAWING 208-040 SHEET MT-90 p

SENSING ELEMENT: 27/6 STEPUP XFMR 4C CONTROL PANEL AR-703 Rev. 14 Page 51

ENCLOSURE 1 (Page 51 of 63) i SSF ANNUNCIATOR RESPONSE SSF-A3-04-01 R-04-01 l

l l

l l

I I

UNIT AUX XFMR I

FAULT I

l l

EVENT POINT 0691 INDICATED CONDITION:

1 o UNIT AUXILIARY TRANSFORMER NEUTRAL GROUND C'

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TURBINE TRIP <45% RTP; TURBINE AND REACTOR TRIP >45% RTP o THE FOLLOWING BREAKERS TRIP OPEN:

3101, 3102, 3201, 3202, 3207, 3208, 1661, 1662, 1660, EXCITER REGULATOR BREAKER.

o THE FOLLOWING BREAKERS WILL CLOSE (IF AUT0/ MANUAL SEL SW IS IN AUT0):

3103, 3104, 3203, 3204.

o 86TNUA-2 LOCKOUT HAS TRIPPED ON SSR SECTION OF REAR MCB OPERATOR ACTIONS FOR A VALID ALARM:

o ENSt,lRE ELECTRICAL POWER AUTOMATICALLY TRANSFERS TO THE AFFECTED BUSSES o IF A UNIT 4160 VAC BUS IS DE-ENERGIZED RUN THE PLANT BACK PEh AP-545 o IF A 6900 VAC BUS IS DE-ENERGIZED, ENSURE THE REACTOR IS TRIPPED, REFER TO E0P DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BFEAKDOWN INSIDE THE TRANSFORMER. FURTHER DEGRADATION OF THIS INSULATION COULD CAUSE A FIRE / EXPLOSION IN THE TRANSFORMER.

REFERENCES:

DRAWING 208-040 SHEET MT-81 SENSING ELEMENT: 86TNUA-2 AR-703 Rev. 14 Page 52

r_

/

ENCLOSURE 1 (Page 52 of 63)

SSF ANNUNCIATOR RESPONSE SS F-A3-04-01 R-04-01 l

l t

i I

I UNIT AUX XFMR I,

FAULT l

l l

EVENT POINT 0692 i

INDICATED CONDITION:

l

(

o UNIT AUXILIARY TRANSFORMER SUDDEN PRESSURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TURBINE TRIP <45% RTP; TURBINE AND REACTOR TRIP >45% RTP o THE FOLLOWING BREAKERS TRIP OPEN:

3101, 3102, 3201, 3202, 3207, 3208, 1661, 1662, 1660, EXCITER REGULATOR BREAKER.

o THE FOLLOWING BREAKERS TRIP CLOSED (IF AUT0/ MANUAL SEL SW IS IN AUT0):

3103, 3104, 3203, 3204.

o 86SPSUA-2 LOCK 0UT HAS TRIPPED ON SSR SECTION OF REAR MCB OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE ELECTRICAL POWER AUTOMATICALLY TRANSFERS TO THE AFFECTED BUSSES o IF A UNIT 4160 VAC BUS IS DE-ENERGIZED RUN THE PLANT BACK PER AP-545 o IF A 6900 VAC BUS IS DE-ENERGIZED ENSURE THE REACTOR IS TRIPPED, REFER TO EOP DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-82 SENSING ELEMENT: 86SPSUA-2 AR-703 Rev. 14 Page 53

ENCLOSURE 1 (Page 53 of 63)

%J SSF ANNUNCIATOR RESPONSE SSF-A3-04-01 R-04-01 rr w r

I I

I I

I I

UNIT AUX XFMR FAULT I

I I

I I

I EVENT POINT 0693 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER PHASE DIFFERENTIAL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TURBINE TRIP <45% RTP; TURBINE AND REACTOR TRIP >45% RTP o THE FOLLOWING BREAKERS TRIP OPEN:

3101, 3102, 3201, 3202, 3207, 3208, 1661, 1662, 1660, EXCITER REGULATOR BREAKER.

o THE FOLLOWING BREAKERS TRIP CLOSED (IF AUT0/ MANUAL SEL SW IS IN AUT0):

3103, 3104, 3203, 3204, o 86TUA-2 LOCKOUT HAS TRIPPED ON SSR SECTION OF REAR MCB OPERATOR ACTIONS FOR A VALID ALARM:

l o ENSURE ELECTRICAL POWER AUTOMATICALLY TRANSFERS TO THE AFFECTED BUSSES 1

o IF A UNIT 4160 VAC BUS IS DE-ENERGIZED RUN THE PLANT BACK PER AP-545 l

o IF A 6900 VAC BUS IS DE-ENERGIZED ENSURE THE REACTOR IS TRIPPED, REFER TO

]

E0P i

DISCUSSION:

REFERENCES:

DRAWING 208-040 SHEET MT-83 r

SENSING ELEMENT: 86TUA-2 I

AR-703 Rev. 14 Page 54 j

(~

ENCLOSURE 1 (Page 54 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-04-02 R-04-02 UNIT AUX XFMR MAJOR ALARM EVENT POINT 0746 INDICATED CONDITION:

o UNIT AUX TRANSFORMER PRESSURE RELIEF DEVICE > 10 PSIG 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE UNIT AUX TRANSFORMER ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL UNIT AUX TRANSFORMER FANS AND PUMPS OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. FURTHER DEGRADATION OF THIS INSULATION COULD CAUSE A FIRE / EXPLOSION IN THE TRANSFORMER.

l

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 63PRX AR-703 Rev. 14 Page 55

O ENCLOSURE 1 U

(Page 55 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-04-02 R-04-02 UNIT AUX XFMR MAJOR ALARM EVENT POINT 0747 INDICATED CONDITION:

o UNIT AUX TRANSFORMER TOP OIL TEMPERATURE > 90* C REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE UNIT AUX TRANSFORMER ALARM PANEL o COMPUTER POINT G-228 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL AUX TRANSFORMER OIL PUMPS AND FANS OPERATING o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL RESTART.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 26/QX 1

v AR-703 Rev. 14 Page 56

O ENCLOSURE 1 N.Y (Page 56 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-04-02 R-04-02 UNIT AUX XFMR MAJOR ALARM EVENT POINT 0748 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER WINDING TEMPERATURE > 120* C REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

,f 4

o RED LIGHT IS ON, LOCATED ON THE UNIT AUX TRANSFORMER ALARM PANEL o COMPUTER POINTS A-314 (4160V), A-315 (6900V)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL UNIT AUX TRANSFORMER OIL PUMPS AND FANS OPERATING o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD

{

DISCUSSION:

l IF XFMR FANS HAVE BEEN OFF FOR AN EXTENDED PERIOD OF TIME AND HIGH OIL TEMPS EXIST, RESTART OF FANS MAY ACTUATE FIRE DELUGE SYSTEM DUE TO HIGH FAN EXHAUST AIR TEMPS. THIS WILL TRIP THE FANS AND OIL PUMPS OFF AGAIN. IF THIS OCCURS THE DELUGE VALVES MUST BE RESET BEFORE XFMR FANS AND PUMPS WILL RESTART.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 49/X i

(~T V

I AR-703 Rev. 14 Page 57 e---__--__-__-____

l O

ENCLOSUBL1 D

(Page 57 of 63)

SSF ANNUNCIATOR RESPONSF SSF-A3-04-02 R-04-02 UNIT AUX XFMR MAJOR ALARM EVENT POINT 0750 l

INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER COMBUSTIBLE GAS MONITOR > 200 CC GAS VOLUME O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT IS ON, LOCATED ON THE UNIT AUX TRANSFORMER ALARM PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL UNIT AUX TRANSFORMER FANS AND OIL PUMPS ARE OPERATING o VERIFY TRANSFORMER TEMPERATURES NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS ALARM INDICATES A POSSIBLE INSULATION BREAKDOWN INSIDE THE TRANSFORMER. AS THE INSULATION DEGRADES COMBUSTIBLE GAS EVOLVES. THE CAS COLLECTS IN A CHAMBER ON THE TOP OF THE TRANSFORMER. THE AMOUNT OF THIS GAS IS READ ON A GAUGE ON THE TRANSFORMER.

REFERENCES:

DRAWING 208-040 SHEET MT-90

(')

SENSING ELEMENT: 63GDRX V

AR-703 Rev. 14 Page 58

l ENCLOSURE 1 (Page 58 of 63)

L SSF ANNUNCIATOR RESPONSE SSF-A3-04-03 R-04-03

'k l

UNIT AUX XFMR MINOR ALARM t

i EVENT POINT 0741 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER ALARM SYSTEM LOSS OF DC POWER O

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ALARM INDICATION ON UNIT AUX TRANSFORMER CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY POWER AVAILABLE FROM DPDP-3A SWITCH 16 DISCUSSION:

THIS ALARM INDICATES NO OTHER LOCAL ALARMS ON THE TRANSFORMER ARE AVAILABLE. INCREASED MONITORING FREQUENCY FOR THIS TRANSFORMER SHOULD BE CONSIDERED.

REFERENCES:

208-040-SHEET MT-90 Q

SENSING ELEMENT: 27 DC AUX TRANSFORMER RELAY AR-703 Rev. 14 Page 59


J

ENCLOSURE 1 (Page 59 of 63)

SSF ANNUNCIATOR RESPONSE SS F-A3-04-03 R-04-03 UNIT AUX XFMR MINOR ALARM EVENT POINT 0742 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER PUMP NO FLOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ALARM IS IN, LOCATED ON THE LOCAL ALARM PANEL o NO FLOW INDICATED ON LOCAL FLOW INDICATORS OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o ENSURE POWER AVAILABLE TO OIL PUMPS (CHECK BREAKERS INSIDE CABINET)

DISCUSSION:

l l

REFERENCES:

DRAWING 208-040 SHEET MT-90 O

SENSING ELEMENT: 74X AUX TRANSFORMER RELAY AR-703 Rev. 14 Page 60

q ENCLOSURE 1 Eg (Page 60 of 63)

SSF ANNUNCIATOR RESPONSE SS F-A3-04-03 R-04-03 UNIT AUX XFMR MINOR ALARM EVENT POINT 0743 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER NORMAL AUXILIARY POWER FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o TRANSFORMER LOCAL ALARM LIGHT IS ON, LOCATED ON THE UNIT AUX TRANSFORMER CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

4 o NOTIFY SYSTEM DISPATCHER o VERIFY NORMAL POWER AVAILABLE (ACDP-1 BREAKER 6) o VERIFY PROPER OPERATION OF TRANSFORMER FANS AND OIL PUMPS DISCUSSION:

REFERENCES:

208-040-MT-90 SENSING ELEMENT: 83 X AUXILIARY TRANSFORMER RELAY

}

AR-703 Rev. 14 Page 61

ENCLOSURE 1 (Page 61 of 63)

SSF-A3 ANNUNCIATOR RESPONSE SSF-A3-04-03 R-04-03 UNIT AUX XFMR MINOR ALARM EVENT POINT 0744 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER EMERGENCY POWER FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I o TRANSFORMER LOCAL ALARM LICHT IS ON, LOCATED ON THE UNIT AUX TRANSFORMER CABINET DOOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY EMERGENCY POWER AVAILABLE (ACDP-2 BREAKER 7) o VERIFY PROPER OPERATION OF TRANSFORMER FANS AND OIL PUMPS DISCUSSION:

I l

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 27 EX AUX XFMR RELAY AR-103 Rev. 14 Page 62 u______-.___--__--------------

O ENCLOSURE 1 (Page 62 of 63) i SSF ANNUNCIATOR RESPONSE SSF-A3-04-03 R-04-03 UNIT AUX XFMR MINOR ALARM EVENT POINT 0745 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER AUXILIARY POWER AUTO TRANSFER

~'

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL ALARM PANEL INDICATOR o ALARMS INDICATING NORMAL POWER IS NOT AVAILABLE (ACDP-1 BKR 6)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY PROPER OPERATION OF TRANSFORMER FANS AND PUMPS o VERIFY POWER IS AVAILABLE FROM ACDP-1 BKR 6 DISCUSSION:

THIS ALARM INDICATES AN AUTO BUS TRANSFER DEVICE HAS ACTUATED INSIDE THE AUX TRANSFORMER CONTROL CABINET. THE NORMAL FEED FOR THIS DEVICE IS ACDP-1 THE ALTERNATE FEED IS ACDP-2. THIS ABT IS A NORMAL SEEKING DEVICE AND SHOULD AUTO RETRANSFER WHEN NORMAL POWER IS REGAINED.

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 89 EX AUX TRANSFORMER RELAY AR-703 Rev. 14 Page 63

l ENCLOSURE 1

/

(Page 63 of 63)

SSF ANNUNCIATOR RESPONSE SSF-A3-04-03 R-04-03 i

l l

UNIT AUX XFMR MINOR ALARM l

EVENT POINT 0749 INDICATED CONDITION:

o UNIT AUXILIARY TRANSFORMER LIQUID LEVEL LOW REDUNDANT. INDICATION WHICH WILL VERIFY ALARM:

i o LOCAL ALARM PANEL INDICATION o LOCAL INDICATOR READING LESS THAN 25% LEVEL OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o INSPECT TRANSFORMER FOR ANY OIL LEAKAGE (ATTEMPT TO CONTAIN ANY LEAKAGE) o VERIFY PROPER TRANSFORMER PUMP AND FAN OPERATION i

I l

DISCUSSION:

I IF AN ACTUAL LOW OIL LEVEL EXISTS CONSIDERATION SHOULD BE GIVEN TO REMOVING ALL LOADS FROM THE TRANSFORMER.

l

REFERENCES:

DRAWING 208-040 SHEET MT-90 SENSING ELEMENT: 63 QLX AUX TRANSFORMER RELAY O

AR-703 Rev. 14 Page 64 (LAST PAGE)