ML20196G337

From kanterella
Jump to navigation Jump to search
Reissued Rev 15 to AR-702, Ssf Q Annunciator Response
ML20196G337
Person / Time
Site: Crystal River 
Issue date: 11/25/1998
From: Winship M
FLORIDA POWER CORP.
To:
References
AR-702-01, AR-702-1, NUDOCS 9812070311
Download: ML20196G337 (138)


Text

_ _ _ _

i

[

Document Transmittal #: 108173 Date: 11/25/98 j

1 Tc:

NRC (DC DESK)

MAC: N/A Holder #: 1242 Destination:

==

Description:==

Copy Totals Document:

Revision:

Comment:

INFO CNTL MSTR AR0702 15 IMMEDIATE ISSUE 1

0 0

i

!nstructions to tne Addressee: Please verify the document (s) received agrees with the above information.

0

/

Engineering managers are required by NEP-121 to determine if new, revised, or temporary changes to procedures affect job functions of their personnel. Managers will communicate change information appropriately and provide documentation of any training conducted to the Engineering Training Coordinator.

Operations department must attach old document (s) or portions of document (s) superseded by the above

/ ['

t3 this transmittal.

/

l The signature indicates acknowledgment of receipt of the above document (s) and that documents have been updated. Retum signed and dated transmittal to Document Control within 15 working days of transmittal date to mail code:

NA1C Florida Power Corporation h h (~)

Documerd Control, NA1C Crystel River Energy Complex 15760 W. Power une St.

Crystal River, FL 34428-6708 Signature of Addressee:

Date:

9812070311 981125 - [er hDR ADOCK 05000302 i

PDR L L..

J

Rev. 15 Effective Date l$ ~ E$' 07

~

CONTROLLED COPY l

NUCLEAR OPERATIONS m,ao l

ANNUNCIATOR RESPONSE AR-702 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 SSF Q ANNUNCIATOR RESPONSE l

APPROVED BY: Interpretation Contact hA& JL N h /UA f (SIGNATURE ON' FILE) '

//!'7 6 7

DATE:

/

/

INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support

O "IMMEDIATE ISSUE" NOTIFICATIO I

l Procedure Number:

AR0702 Current Revision:

15 Effective Date:

//-85-((

PRR #:

16101 O

~

O e.e1-1

. ~..... ~. -. ~... -

-.. -., - - -, ~..... ~....... _ - _, -

..... ~. - - -... -. - -. ~.. --.-.

i l

t I

-Authors MICHAEL A. WINSHIP SR. at cr Date 11/25/98 1:38 PM

,'7riority: Normal l

i.'

Receipt Requested TO: TERESA LORISS at er

)

Subject:

Immediate Issue of AR-702


Message Contents ------------------------------------

Terri, Please do an Immed! ate Issue of AR-702 as MAR 97-08-01-01, FCN 2 has been completed on EDG

'A'

'B' BKRs and the changes to AR-702 are required for MAR turnover.

Thanks M Winship Ext: 3316 t

l l

r l

l u

_____ __. _._.__ _ _ -. ___._.~_ _._. _ -....._.-._ _ _ _.

g (Page 8 of 111)

O SSF ANNUNCIATOR RESPONSE SF-A2-02-02 Q-02-02 i

c DIESEL GEN A BREAKER TRIP f

EVENT POINT 0315 INDICATED CONDITION:

o DIESEL GENERATOR 'A' BKR 3209 LOCKOUT ACTUATEDl-Generator-%'-OKR-3209 toekotit-Atttratedr I

O l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED FLAG WITH A GREEN LIGHT IS ON, LOCATED ON BREAKER 3209 CONTROL l

STATION.

o VERIFY 86B EDG BREAKER LOCKOUT RELAY OPEN.

OPERATOR ACTIONS FOR A VALID ALARM:

l l

o REFER TO AP-770.

DISCUSSION: THE 86B EDG BREAKER LOCKOUT RELAY WILL TRIP AND PREVENT RECLOSURE OF THE EDG OUTPUT BREAKER FOR:

o OVERCURRENT DEVICE (51V) o NEGATIVE SEQUENCE (DEVICE 46) o GENERATOR GROUND (DEVICE 64) o ES BUS FEEDER BREAKER OVERCURRENT (DEVICE SIB, 51BN) l THE' ACTUATION OF THE NEW 86B LOCKOUT WILL RESULT IN THE ENGINE REMAINING l

RUNNING WITH THE OUTPUT BREAKER OPEN. THIS WILL REQUIRE THE ENGINE SHUTDOWN WITHIN 2 HOURS.

REFERENCES:

DRAWING 208-040 MT-13 SENSING ELEMENT: CS/SC.CS/0,CS CONTACTS,52H/A,525/8 & 86B/3209 CONTACTS I

I lAR-702 Rev.

,p9 Page

l i

(Page 72 of 111) s

\\

SSF ANNUNCIATOR RESPONSE SF-A2-05-02 Q-05-02 i

DIESEL GEN B BREAKER TRIP EVENT POINT 0336 l

INDICATED CONDITION:

o DIESEL GENERATOR 'B' BKR 3210 LOCKOUT ACTUATED l O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o - GREEN LIGHT IS ON WITH A RED FLAG ON THE BREAKER 3210 CONTROL STATION.

o VERIFY 86B EDG BREAKER LOCKOUT RELAY OPEN

)

l l

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION: THE 86B EDG BREAKER LOCK 0UT RELAY WILL TRIP AND PREVENT RECLOSURE OF THE EDG OUTPUT BREAKER FOR:

o OVERCURRENT (DEVICE 51V) o NEGATIVE SEQUENCE (DEVICE 46) o GENERATOR GROUND (DEVICE 64) o ES BUS FEEDER BREAKER OVERCURRENT (DEVICE 51B, 51 BN)

THE ACTUATION OF THE NEW 86B LOCKOUT WILL RESULT IN THE ENGINE REMAINING RUNNING WITH THE OUTPUT BREAKER OPEN. THIS WILL REQUIRE THE ENGINE SHUTDOWN WITHIN 2 HOURS

REFERENCES:

DRAWING 208-040 MT-14 O'

SENSING ELEMENT: CS/SC,CS/0 CS CONTACTS, 52H/A, 525/B & 868/3210 CONTACTS AR-702 Rev.

(

I Page J[

~)

PR'OCEDORE DEVELOPMENT AND REVISION RECORD PART 1 - PROCEDURE WRITER l (NOCS 00929,62467,05742,00943). ~

~

Procedure #:

AR0702' New Rev #:

16 PRR#:

16101 Procedure SSF-Q ANNUNCIATOR RESPONSE

Title:

PROCEDURE PROCESS STATISTICS -

T Check the processes and/or activities that provide input to this new procedure, cancellation, or revision.

C l MAR:

l97-08-01-01 l

C lFCN:

p l

0 FAP:

l l

0 jNUPOsT:

l l

C l NOTES:

l l

O psicuistion:

I I

D iFsAR:

l l

0 lits Amendment:

I I

OITs Bases:

l l

0 lNRC Violation Response: l l

0 Nendor Manuai:

I I

O lOther:

I I

' MINOR CHANGES t ' ~

~

If Minor Changes are included, check the applicable box (es) and provide a list of affected steps.,

_[ ^

[

The following corrections are incorpotated throughout:

O sentence structure O Redundant words or phrases Punctuation O Abbreviations O Capitaiizstion O Obviousiv incorrect units of measure O speiiino 0 inadvertentiv omitted symbois (n. E etc.)

C Organizational Changes: position titles.

O Obvious step numbering discrepancies department names, or telephone numbers p

The following corrections are incorporated in the step (s) indicated: "Throughout" is used in lieu of step # if a specific change effects a large number of steps.

SupaN Correcting equipment nomenclature that does not agree with field labels or balance of procedure Changing information that is obviously incorrect and referenced

(

correctly elsewhere AIO400C Rev. 25 Page 1

1 1

t PROCEDURE DEVELOPMENT AND REVISION RECORD PART 1 - PROCEDURE WRITER

(NdCS 00929, 62467, 05742, 00943)',

.x s

\\

Procedure #:

AR0702 New Rev #: 16 PRR#:

16101

)

Procedure SSF-Q ANNUNCIATOR RESPONefe

Title:

l l

MINOR CHANGES:

c c

l

.j-Misplaced decimals that are neither setpoint values nor tolerances 1

l Reference to a procedure when. c; approved procedure has taken the I

place of another procedure Fixing branching points when it is clear the branching steps were onginally intended but were overlooked or incorrectly stated due to step number changes i

Adding clanfying information such as NOTES and CAUTIONS Adding words to clarify steps, NOTES, or CAUTIONS which clearly do not change the methodology or intent of the steps NON lNTENT ' CHANGES

^

~

i a

.. a 3..,

u

?'

4 Changes are incorporated for the reasons provided. 'Throughout" is used in lieu of Step # if a specific change affects a large number of steps.

i 1

Step #(s)

Reason, including reference to the initiating process or activity. (CAP, MAR etc.)

Window Q 02-02, Event New event Point 0315 added by MAR 97-08-02-02, FCN 2 Point 0315 Window O-05-02, Event New Event point 0336 added by mar 97-08-01-01, FCN 2 Point 0336 l

l CHANGE OF INTENT, CANCELLATION, OR NEW PROCEDURE -

t:

,.t..

d _ L, 4

Changes are incorporated for the reasons provided. "Throughout" is used in lieu of Step # if a specific change affects a large number of steps. For new or cancelled procedures the reason is provided.

l Step #(s)

Reason, including reference to the initiating process or activity. (CAP MAR, etc.)

l l

s AIO400C Rev. 25 Page 2 i

-. ~. -

O PROCEDURE DEVELOPMENT [AND REVISION RECO'RD:

f

~

0-

~

PART 1 - PROCEDURE WRITER:,

(NOCS OU929,62467,05742,00943)'-

-i

/'

Procedure #: 'AR0702

'New Rev #: 16 PRR#:

16'101

~

Procedure SSF-Q ANNUNCIATOR RESPONSE

Title:

CHANGES OF INTENT, C NCELLATI'ON, OR NEW PROCEDUREd

~

+

~

~~

~ ~

s.

.s,

,w.

Independent Approval by CP-213 qual 6ed person required if Non-intent Changes are included.

htf$~

(( W 9 $

% Wel

.. n CP-213 Qual 6eu Person Nafb (Pnnt)

Sdnatud Date i

O AIO400C Rev. 25 Page 3

l 1

PROCs6URE DEVELOPMENT AN6' REVISION RECORD '

~

~

l PARTf2 - PROCEDURE WRITER i,

(NOCS 00943):

^

t a.nw u.

.. r,,:.

n..

a,

. ~.,

.c Procedure #:

AR0702 New Rev #: 16 PRR*:

16101 Procedure SSF-Q ANNUNCIATOR RESPONSE l

Title:

l EROCEDU' E5 IMP 'CTED'B'YLTHIS REVISIONL R

~~

v t

e es.____

  1. .w.,,

_,_.4 s

Procedure #

Procedure Title Procedure Owner

~

EXCEPTIONS TO Al-402B

s. An

,._. b.:..z Step #

Reason PRO'C5 DURE WRITER'S"CH'E'CKLISTi '

~

~

J.

' ~

.... nc,....

. ~.n Yes N/A g

Part 1 of Enclosure 1 is complete.

Q Exceptions to Al-402B are explained.

~

O owners of impacted procedures were noti'ied and impacts caused by this ae* or revi$ed procedure are 4

resolved.

l f

7, Procedure Reviewer Form: Qualified Review is complete and reviewer comments are j

resolved.

i g, Procedure Reviewer Fonn: Technical Review is complete and reviewer comments are

{

resolved, i

g, Procedure Reviewer Form: Validation Review is complete and reviewer comments are resolved.

f 1

g, CMIS Database Update Request Form is complete.

i

/

g Q

Categorization of changes as non-intent is approved by CP-213 quahtied individuat.

l The procedure is exempted from CP 213 and the exemption Safety Assessment conclusions remain valid.

g CP-213, Preparation of a Safety Assecsment and Unreviewed Safety Question, is complete.

Final draft of the procedure is correct and suitable for use, b lCIIM N.

tAHhl}

N s

Procedure Writer Name (Pnnt) [

\\

' Signature Date i

!O AIO400C Rev. 25 Page 4

-. = - -

PROCEDURE DEVELOPMENT'AND REVISIDN RECORD l

~

e x

PART 3.- PROC $ DURE OWNER x.

(NOCS 00943)1 X'

c - - -,

t

.cs-

.A.

.4 i

Procedure #: AR0702 New fiev#:

16 PRR#:

a j

16101 Procedure SSF-Q ANNUNCIATOR RESPONSE Thie:

~PROCE60RE" OWNER'S REVIEW I

~

+,1 7 Y '.' _i

'ia s

,.a

/-

ca..

C IWCC Being Made Permanent w

s Yes N/A Part 1 and 2 of Enclosure 1 are complete.

All necessarv reviews are complete and reviewer comments are resolved. (Refer to Enclosure 3, instructions for Determining Review Requirements.)

Impacts on the intent or content of other procedures have been resolved.

Catagorization of changes as non-intent is approved by CP-213 qualified individual.

CP 213, Preparation of a Safety Assessment and Unreviewed Safety Question Determination, is complete.

Change imput is appropriately incorporated and the content is correct and suitable for use.

O CMIS Database Update Request Form was forwarded to Nuclear Configuration uanagement.

Implementing references are changing and the CRP has been forwarded to Nuclear Regulatory Compliance.

Commitment Change Requests are approved.

PRC review was performed if required or desired.

Final version of the procedure was proofread.

NUPOST comments are updated.

If training is needed, arrangements are underway to train appropriate individuals prior to the effective date of the procedure.

The NSM was notified and administrative controls are in place if the position of component, valves, switches, breakers, etc. are changed when the procedure becomes effective.

18 the procedure being cancelled?

ML / b.GuMn (Nlw l sdm? //l2h Procedure Owner Name (Print) [

(

' Signature Date t

O I

AIO400C Rev. 25 Page 5 (Last Page)

E!iCLOSURE 4 (Page 1 of 2)

O PROCEDURE REVIEWER FORM:

QUALIFIED REVIEW Q

[NOCS 62493, 62459' 40444, 07376]

TO: diu r$r //u m A,-t c, MAIL CODE: AJR 2 6 l PRR:16101 DEPARTMENT: O gg S..ofor*T PROCEDURE:AR0702 The attached proce6ure requiefel QUALIFIED REVIEW, as indicated below, by your department.

[ } REVIEW THE ENTIRE PROCEDURE.

[ ] REVIEW ONLY SECTIONS CONTAINING CHANGES.

When your review is conplete, please return the procedure review package, all pertinent comments, and this form / s i str cted below.

6 DOE DATE: f/

f9 l RETURN TO: N.

8MSb-M l MAIL CODE:h ENSURE THE FOtLOWING, AS APPLICABLE 1-8 GENERAL

[ VYES

[ ] NO

[] N/A The procedure is written according to guidance listed in AI-400A, AI-4028, and AI-400G.

[ ] YES

[ ] NO

{T N/A The job titles agree with the current orQanization chart.

(W YES

[]NO

[] N/A Tables, figures, and enclosures are presented consecutively based on the order in which they are used within the procedure.

[W N/A The CRP and applicable Commitment Change Requests are attached

[ } YES

[ ] NO and accurately reflect implementing references.

[4'YES i ] NO

[] N/A The title identifies the obiect of the action of the procedure.

[d YES

[ ] NO

[ ] N/A All required information is included on the procedure cover sheet.

l WYES

[]NO

[ ] N/A The purpose is stated clearly.

l

[ ] YES

[ ] NO

[W N/A Forms, etc., which are not Quality Assurance documents, are identified as " Optional Records Non-Quality."

[d YES

[]NO

[ ] N/A All tables, figures, and enclosures are listed in the Table of Contents.

T) YE5

[}NO

[gN/A The documents used to develop the procedure are listed as O

Developmental References.

[4 YES

[]NO

[ } N/A Titles and numbers of all references are identified correctly.

[Q'rES

[ ] NO

[] N/A When other procedures are referenced, the proper section is l

referenced and the procedures adequately address the activity.

[ } YES

[]NO

[vfN/A Non-common words and/or terms are defined.

[] YES

[ ] NO

[W N/A If using terms defined in another procedure, the definitions are consistent.

i

[ ] YES

[]NO prN/A Definitions are presented in alphabetical order.

HUMAN FACTORING / ERROR REDUCTION / PERSONNEL SAFETY i

I l 44E5

[]NO

[ ] N/A Ninety percent or more of the instructions are written in short, concise, identifiable steps.

[ *f YES'

[ ] NO

[ ] N/A Most action steps contain no more than one action.

[ WYES

[]NO

[ ] N/A Adequate prerequisites exist to streamline performing the activity.

[ W YES

[ } NO

[] N/A Cautions and notes are placed immediately ahead of the step (s) i

/

to which they apply.

[t(YES

[ } NO

[ ] N/A Cautions and notes do not contain action statements.

l

[5 RYES

[ } NO

[ ] N/A Step numbering is correct.

l

[}YES

[]NO

[rfN/A Limits and Precautions apply to the procedure and are complete.

[ dMES

[ ] NO

[] N/A The procedure wording can be " literally applied" in the field

/ without causing an interpretation issue.

[ ] YES

[}NO

[q'N/A Equipment needed to perform the procedure is listed (size, how

/

many, part number, calibration rea., etc.).

[L(YES

[ ] NO

[ } N/A Ir.structions are suitable for individuals to perform the activity without direct supervision (limit referring personnel to other procedures where possible).

O f

AI-400C Rev. 25 l

ENCLOSURE 4 (Page 2 of 2) i PROCEDURE REVIEWER FORM:

QUALIFIED REVIEW

[NOCS 62493, 62459, 40444, 07376)

PROCEDURE:AR0702 l PRR:16101 ENSLSE THE FOLLOWING, AS APPLICABLEs:_

,u f(}4E5 [ ] NO

[]

The procedure is written to one " primary" user; i.e., one person is

/

N/A responsible for coordinatinQ the activity ll}4E5 []NO II Procedure steps are written to limit radiation exposure while N/A,

performinQ activities. [NOCS 07375]

[ } YES []NO l'f The procedure steps are written to limit generation of radioactive N/A waste / hazardous material.

[] YES [ ] NO (W

The procedure, data sheets, and worksheets provide for independent N/A _

verification and sign-off of calculations.

[ ] YES []NO IW Worksheets facilitate calculations. Spaces are provided for N/A recording and processing data (performing additions, multiplication, i

failure analysis, etc.).

[TYES [}NO

[]

NUPOST comments have been evaluated and resolved.

N/A TECHNICAL

( MLS I ] NO

[]

Plant components and equipment are properly identified (tag number, N/A name, etc.).

I ] YES []NO

[cP Limits and precautions are specific and clear.

N/A /

I ] YES I ] NO IF Adequate instructions are provided to ensure appropriate foreign N/A material exclusion (FME) practices.

[ ] YES []NO IT Calculations required by the procedure are based on technically N/A accurate, and up-to-date formulas.

ic}'YES []NO

[]

Setpoints reflect normal indicated values for the activity being N/A / performed.

I 1 YES []NO IF Acceptance criteria are adequately stated.

N/A

[ ] YES []N0 (W

If inspection planning is required per CP-113C, inspection planning N/A methods are incorporated.

[ ] YES []NO (F

Reasonable contingency instructions are provided for when N/A acceptance crittria are not satisfied.

,/ Steps requiring the use of calibrated tools or equipment are 1 ) YES []NO (W

preceded by an instruction to verify and document the calibration N/A due date.

I ) YES I ] NO

(( Any statement of "or equivalent" includes the name or position of the person who is authorized to determine equivalency.

N/A Instructions are provided to ensure adherence to match marks,

[] YES [ ] NO 10 '

protection of seats, and proper re-assembly during component N/A / disassembly and re-assembly.

i ] YES []NO IT Instructions for performing alignment of items are written such N/A that each item requiring alignment is individually specified and l

identified with a unique number or nomenclature, the position in which the item is to be placed is specified, and a sign-off space

/ is provided for position verification.

[ ] YES []NO

[F Instruction Steps, restoration steps, and valve lineups governed by N/A tags do not conflict and do provide proper test boundaries. [NOCS 07374]

[ ('YES []N0

()

The content is technically correct as written.

N/A,

[ } YES [ ] NO l(

System restoration instructions are clear and adequate.

h/A COMPLETION OF PROCEDURE REVIEW: The required review indicated above is complete and comments are attached.

Ark kJ M

,A W

N y

s y

Reviewer's Name (print)

Reviewer's Signature Date l

AI-400C Rev. 25

l l

ENCLOSURE S PROCEDURE REVIEWER FORM:

TECHNICAL REVIEW l

[NOCS 62493, 62644, 62571, 062459, 05396, 03234, 62464, 62629]-

O TO: 2). % slew MAIL CODE: NR.Q R l PRR:16101 DEPARTMENT:od G w T PROCEDURE:AR0702 lI l

Th ttached procedure requires TECHNICAL REVIEW, as indicated below, by your department.

[ ] REVIEW ONLY SECTIONS CONTAINING CHANGES.

[ ] REVIEW THE ENTIRE PROCEDURE.

When your review is complete, please return the procedure review package, all pertinent comments, and this form as instructed below.

DUE DATE: /h2 sh Y l RETURN TO:

  1. W I s l MAIL CODE: d/k K

[ ] YES []NO

[d If this procedure impacts other procedures controlled by the reviewing department, then other disciplines / sections have reviewed the procedure and comments are included.

l

[Q4ES j ] NO

[]

Plant components ar.d equipment are properly identified (tag number, name, i

N/A _

etc.).

[ ] YES []NO

[7 Limits and precautions are specific and clear.

N/A It.]MES []NO

[]

Adequate instructions are provided to ensure appropriate foreign material N/A exclusion (FME) practices.

[ ] YES [ ] NO

[y' Calculations required by the procedure are based on technically accurate.

N/A and up-to-date formulas.

[ ] YES []NO 1,4 Setpoints reflect normal indicated values for the activity being performed.

N/A

[ ] YES []NO

[.V Acceptance criteria are adequately stated.

1 O

N/A J

[ ] YES []NO

[ *1' If inspection planning is required per CP-113C, inspection planning methods N/A are incorporated.

[ ] YES [ ] NO

[ }-

Reasonable contingency instructions are provided for when acceptance N/A criteria are not satisfied.

Steps requiring the use of calibrated tools or equipment are preceded by an

[ ] YES []NO

((-

instruction to verify and document the calibration due date.

N/A l

Any statement of "or equivalent" includes the name or position of the person l

[] YES [ ] NO

[&

who is authorized to determine equivalency.

)

N/A Instructions are provided to ensure adherence to match marks, protection of

[ ] YES [ ] NO

[V seats, and proper re-assembly during component disassembly and re-assembly.

N/A

[ ] YES [ ] NO

[V Instructions for performing alignment of items are written such that each N/A item requiring alignment is individually specified and identified with a unique number or nomenclature, the position in which the item is to be placed is specified, and a sign-off space is provided for position

/ verification.

l

[] Y45 []NO hi Instruction steps, restoration steps, and valve lineups governed by tags do

/

N/A not conflict and do provide proper test boundaries. [NGCS 07374]

([YES [ ] NO

[]

The content is technically correct as written.

N/A.

l

[ ] YES []NO

[

System restoration instructions are clear and adequate.

[ ] YES [ ] NO

[#

Engineering Technical Reviewers: Technical conformance of the change to the N/A design basis has been confirmed. [NOCS 62460]

[ ] YES l ] NO

[y Engineering Technical Reviewers: The change is compatible with existing N/A engineering calculations / analyses assumptions and results. [NOCS 62460]

[ ] YES []NO l y/A Nuclear Regulatory Compliance Reviewers: Proposed cnanges to commitment N

implementing references have been evaluated and are acceotable.

. )

COMPLETION OF PROCEDURE REVIEW: The r uired rev is cramplete, and comments are attached.

$ id. &.tl6 V 11l_AWW

,w.

r

(

AI-400C Rev. 25 0

.=... -.

Rev. 16 O

l. (,/

Effective Date l

ANNUNCIATOR RESPONSE AR-702 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 SSF Q ANNUNCIATOR RESPONSE C'1 i

l APPROVED BY: Procedure Owner i

(SIGNATURE ON FILE)

DATE:

l PROCEDURE WRITER: Michael A Winship l

RESPONSIBLE DEPARTMENT: Operations Support-l

6%M

" 8 '" '

Florida FCN DESCRIPTION /

TABLE OF CONTENTS FCN NO.

2 FCN&TDCRIM

(

PAGE 1

OF 2

PCN DESCRIPTION:

The purpose of this FCN is to provide the permanent events recorder alarm for the new 86B EDG breaker lockout relay. A temporary events recorder point was used in the MAR because there were no spare cables available. This FCN installs new cable for the permanent alarm and also installs new terminal blocks in the 4160V ES switchgear 3A12 and 3B3. This is discussed in the MAR Design Activity Description.

An Events Recorder / Annunciator Window will be provided for each new device 86B EDG breaker lockout relay. The temporary alarms were provided by a contact from each new EDG breaker lockout relay in parallel with existing events recorder alarm point 568 Diesel Generator A Breaker 3209 Auto Trip"and point 571 Diesel Generator B Breaker 3210 Auto Trip". This parallel contact will be removed from these event recorder points andRp~

ieventsVs6oid5ds%ihls'315 and 336ar~eji&O These event recorder alarm points go to the WiiUi5Eiator windows W-AD242 desefGen A Breaker Trip"andgNSRA-05.EB Diesel Gen B Breaker Trip" respectively. The permanent alarms are provided by new events recorder alarm point 315 Diesel Generator A Breaker 3209 Lockout Actuated"and point 336 Diesel Generator B Breaker 3210 Lockout actuated" These event recorder alarm points will be tied to Annunciator windows SSF-A2-02-02 Diesel Gen A Breaker Trip" p

and SSF-A2-05-02 Diesel Gen B Breaker Trip" respectively. Note that event recorder U

points 568 and 571 will remain tied to the same Annunciator windows. Events recorder points 568 and 571 descriptor will be changed back to Diesel Generator A Breaker 3209 Auto Trip"and Diesel Generator B Breaker 3210 Auto Trip" respectively. The annunciator windows descriptor remains the same.

Annunciator response procedure AR-702 revision 15 is affected by this change and

, requires revision. Refer to the revised DIR items 15 and 16 for additional information.

TABLE OF CONTENTS SECTION A FCN INCLUSIONS 1.

MAR (FCN # 2) Open items ( 1 sheet) 2.

FCN Installation Instructions (5 sheets) 3.

Bill of Material (1 sheet) 4.

Design input Record (2 sheet) 5.

Verification Report (2 sheets) 6.

Annunciator Events Recorder Event Point list (3 sheets) 7.

Cable Pulling and Term. Data Sheet for MTK308 and MTK309 (4 sheets) 8.

Cable routing report CKSR2410BI (1 sheet) l Rev. 3/96 RET: Ufe of Ptern RESP: NwckerEn0 6

)

f' S'\\

FCN#2 MAR NumbIr 97-08-01-01 i

l

\\

Page 1 of 1

(

MAR ( FCN # 2) OPEN ITEMS

(

Crystal River Unit 3 uAna.rnu l

MAR ( FCN # 2) OPEN ITEMS (if NA, do not include in package)

1. Structural Calculation S-97-0288 revision 1 to include the structural qualification of the terminal blocks added per FCN # 2. This is to address the qualification, mounting, and impact to the qualification of the 4160V ES switchgear of the added terminal blocks. Required to be completed prior to return to service.
2. Operations to review and revise as appropriate AR-702 for the annunciator / events recorder points.
3. Fr rto Ew.. Wa a r Pac _K tv'.E.

- ?aTort To tIGLb ufor K tmU l

r\\

.n

.n l

ArenovED MAPuA R E On DESIG ElDA

~

Fo,t 6.A. 6ntrutse 2 lt7 /qA m

Av s

i "

i g

m. =

m u,..,m m..

,o-

~. =

MAR 97-08-01-01 norida Power DESIGN INPUT RECORD

~*"

Crystal River Unit 3 onum l

Sheet 33 of 10 3.

The EDG breaker protective relaying tripping circuit voltage is from the 125 VDC Class 1E DC distribution system.

.p eg 4.

Seismic Qualification of the added components, which are theLierminal blocMlockout relays, indicating light, fuses, and fuse blocks to be located in the 4160 VAC Train A and Train B switchgear breakers 3209 and 3210, is in accordance with IEEE-344-1975.

The lens cap of the GE ET-16 Indicating lamp is replaced with a white lens cap that was purchased as non-safety related. The lens cap is screwed on the indicating lamp the same way as the lens cap that comes with the safety related lamp. The function of the lens cap is to give color to the lamp, therefore it is acceptable to replace the lens lamp to provide a different color.

See Structural DIR.

5.

The essential equipment being modified by this MAR is the tripping parameters of the EDG and the EDG output breaker. A new EDG breaker lockout relay will be added at the EDG breakers 3209 and 3210. The following 600 series drawings are included as interim drawings to this MAR; 600-062 sheets 12,13, and 15. CIDP 97091607 will be generated to update CMIS. 10CFR50.49 is not applicable to this MAR as the zones where the equipment is located are classified as MILD. Refer to item 6 below. The effect of this modification on essential equipment is that the only protective relays that will trip the EDG engine are the generator differential relays. The generator differential relays and p

the other protective relays that previously tripped the EDG engine will now trip the EDG output t

I breaker only. Justification for this is included in the SA-USOD, and items 2 and 15 of this DIR.

G 6.

Environmental conditions are per Environmental and Seismic Qualification Program Manual rev. 8.

Environmental Data Zone # 43 rev. interim 97-05, which is a Mild Environment Zone, is for the 4160 VAC ES Switchgear rooms in elevation 108 of the Control Complex. Environmental Data Zone # 27 rev. 8, which is a Mild Environment Zone, is for the EDG Control room area of the EDG building.

Equipment added meets the environmental conditions of these zones.

7.

This MAR interfaces with the MAR 97-03-02-01 which is adding sdditinnni firea.: tn th, pre h=Mers 3209 and 3210 for Appendix R req Jirements. The additional fusos added by this MAR do not impa::t the fuse selections of this MAR.

MAR #

M M-0I- 0 I 8.

See item 27.

E FCN*

9.

See Structural DIR.

2, I

O_

SI-:EET r

10.

See Structural DIR.

DWG,

_ gg The following equipment is being added to each of the 4160V ES $witchgear cubicles 3A12 and 3B3J 1 lockout relay GE HEA61A weight =4.96 pounds mounted on the top front cubicle door at l

l lower left comer.

i 1 indicating light GE ET-16 w/2K ohm resistor weight =0.12 pounds mounted on the top front cubicle door to the right of the lockout relay, 1 fuse blocks Bussman type 2604 2-pole weight =0.66 pounds mounted on free space inside c

- the top compartment of the cubicle, to the left of existing fuse blocks AX and AY.

. (v)

M 2 fuses Gould Shawmut A2Y weicht =0 04 pounds these fuses are mounted in the fuse block.

E I

1 four point States terminal block mounted mounted on tree space inside the top compartment of the cubicle.

j The following equipment is being added to each of the 4160V ES Switchgear cubicles 3A14 and 381 n. um m: u..m use==i., o, e

m m

MAR 97-08-01-01 I u power DESIGN INPUT RECORD 5 7

'W OI-0 I Crystal River Unit 3 e

wm Sheet 44 of 10l FCNc 2-t 1 fuse biccks Bussman type 2604 2 pole weight =0.66 pounds mounted on free space inside SHEET OF*lthe top cc mpartment of the cubicle, to the right of existing fuse block LV.

l ztusescould Shawmut A2Y weight =0.04 pounds these fuses are mounted in the fuse block.

Ah~ WR OWG :

I me oppsmete weights shown above were taken by Steve Bums and Pablo Rubio using the electronic scale kJcated in the stores warehouse.

The Seismic report of the 4160V ES Switchmar is in calculation E69-0001. Additionally, calculation E86-0005 also contains equipment addition @E HEA61 A lockout relay and GE ET-16 indicating light) in approximately the same location of the cubicle door for the 4160V ES A and B switchgear due to MAR 80-09-13-01.

FcM 2

Busmann fuse blocks 2607 3 poles,2604 2 poles, and 2601 1 pole are installed in the 4160V ES Switchgear, Remote Shutdown Panel, and Remote Shutdown Auxiliary Relay Racks. These cabinets are on the same Control Complex elevation as the 4160V ES Switchgear. Reference Patel Engineers Technical report PEl-TR-82-8-8, PEl-TR-82-8-16, and PEl-TR-82-8-17.

'p-J The terminal blocks that are being installed are of the same type, States type ZWM, as are presently installed in the 4160V ES Switchgear by original design. The Seismic report of the 4160V ES Switchgear is in calculation E69-0001. Terminal blocks States type ZWM are also installed in the remote shutdown Panel auxiliary racks located in the 4160V Switchgear rooms. These terminal blocks were qualified per Patel Engineers Technical reports PEl-TR-82-8-7, PEl-TR-82-8-16, and PEl-TR-82-8-17. These Patel reports also reference the Acton States terminal blocks report no. 15809-82.

V)

The mounting hardware is per the Bill of Materials items 2,3, and 4. The seismic installation of the

(

terminal blocks is addressed by calculation S-97-0288 revision 1.

.1 13.

Modification 80-09-13-01 added protective relaying trips to the EDG and EDG output breaker. MAR 97-08-01-01 changes the design philosophy of the protective relays that trip the EDG engine. MAR 97-08-01-01 will trip the EDG engine lockout relay on generator differential current only and install a new device 86B to trip and prevents subsequent closure of the EDG output breaker. This modification will install a new EDG breaker device-86 lock-out relay on the 4160V ES switchgear EDG breaker 3209 and 3210 cubicle. Device-51V AC time overcurrent relaying with voltage restraint, device-B6B/B1 lock-out relaying from each of the three bus offsite power source breakers, and the device-64DG generator ground relay from the EDG engine device-86 lock-out relay will be moved to the new EDG breaker device-86B lock-out relay.

In addition, the device-46DG negative sequence relay will be moved from the EDG breaker trip circuit to the new EDG breaker device-86 lock-out relay. The device-46DG negative sequence relay is being connected to the new EDG breaker device-86 lock-out relay to prevent EDG breaker cycling due to an unsymmetrical og erating condition. EDG breaker cycling could occur since the device-46DG negative sequence relay will reset after the EDG breaker trips. Next, the device-27 bus undervoltage relaying would re-close the EDG breaker (assuming the EDG had been the sole power source for the 4160V ES bus). If the unsymmetrical operating condition still existed (example: open conductor on a large auto-connected load motor), the cycle would repeat.

The two device-86B1 lock-out relays that were installed for Remote Shutdown Panel operation will I

also be connected to the new EDG breaker device-86B lock-out relay. As before, the two device-86B1 lock-out relays are only functional after controlis transferred to the Remote Shutdown Panel. If a Main

/

Control Room fire / Cable Spreading Room fire occurred shorting out conductors to the device-86B V

lock-out relaying located on the Main Control Board and tripping the EDG breaker device-86B lock-out relay, an operator action to reset the EDG breaker device-868 lock-out relay is required. This is considered acceptable since the new EDG breaker device-868 lock-out relay is located in the 4160V ES Switchgear Room with the associated Remote Shutdown Panel transfer switches. The need to n.um am ue..m-= aswu, o, an n,=, soo Pos

dh Florida MAR VERIFICATION REPORT s Power Crystal River Unit 3 a """"

MVM.FRM Page 1 of 2 y MAR NUMBEM l 97-08-01-01 FCN # 2 PROJECT:

EDG PROTECTIVE RELAYING - LOCKOUT RELAY EVENTS RECORDER POINTS VERWICATioN METHOD:

@ Design Review (use checklist below)

Alternate Calculations (attach analysis calcule+ ion sheet)

O Qualification Testing tuse attachments as necessary)

YES No N/A

1. I Were the inputs correctly selected and incorporated into design?

2.

O F

Are assumptions necessary to perform the design activity adequately described and reasonable? Where necessary, are the assumptions identified for subsequent i

reverification when the detailed design activities are completed?

3. 6O O

Are the appropriate quality and quality assurance requirements specified?

4. 7 Are the applicable codes, standards and regulatory requirements including issue and addenda properly identified and are their requirements for design met?

j I

O Have applicable construction and operating experience been considered?

5.

6. [

Have the design interface requirements been satisfied?

7.

Q" Was an appropriate design method used?

8.

Is the output reasonable compared to inputs?

9. IO O

Are the specified parts, equipment, and processes suitable for the required application?

10. [

Are the specified materials compatible with each other and the design environmental conditions to which the material will be exposed?

11.

O O

[ Have adequate maintenance features and requirements been specified?

12. [C C

Are accessibility and other design provisions adequate for performance of needed maintenance and repair?

13.

O O

Has adequate accessibility been provided to perform the in-service inspection expected to be required during the plant life?

14.

O

[ Has the design properly considered radiation exposure to the public and plant per

15. W D

Are the acceptance criteria incorporated in the design documents sufficient to allow verification that design requirements have been satisfactorily accomplished?

16. Y O

Have adequate pre-operational and subsequent periodic test requirements been ppropriately specified?

17.

Are adequate handling, storage, cleaning ano shipping requirements specified?

18.

Are adequate identification requirements specified?

(

19.

Are requirements for record preparation review, approval, retention, etc. adequately specified?

,C40.

O Has seismic adequacy been considered and have appropriate design requirements been established?

21.

O I Have fire protection considerations been adequately addressed?

SFWda MAR VERIFICATION REPORT Power Crystal River Unit 3 a""-

Page 2 of 2 MAR NUMBEM 97-08-01-01 FCN # 2 PROJECT:

EDG PROTECTIVE RELAYING - LOCKOUT RELAY EVENTS RECORDER POINTS YES NO N/A 22.

O Have High Energy Line Break (HELB) considerations been adequately addressed?

23.

O O

Have Environmental Qualification requirements been identified and adequately addressed?

24.

O O

Have Electrical System Calculation requirements been adequately addressed?

25. 70 O

Have SBO considerations been adequately addressed?

26.

O O

7 Have ES System Hydraulic Calculation requirements been adequately addressed?

27.

O O

VHave Emergency Diesel Generator Loading requirements been adequately addressed?

28.

WD 0

Has technical design information provided via REA, IOC, letter or telecon by other isciplines or programs been verified by that discipline or program?

29.

O O

Has technical design information provided via letter or taken from an external engineering rganization or vendor been confirmed and accepted by FPC7 30.

O O

Lg if the MAR incorporates a standardized design approved by a recognized authority, have any known problems been considered and their affects on other design features been ddressed?

DJ1.

O O

If the MAR incorporates a standardized design with known problems, have the original design and verification measures been adequately documented and referenced in the.

MAR for this application of the standardized design?

E'7O O

If a standardized or previously proven design is used in the MAR, have all pertinent 32.

design inputs, including environmental conditions, been verified for each application in

[this MAR?

33.

O O

Has the design adequately addressed the need for FSAR, improved Technical Specification, and improved Technical Specification Bases impacts and changes? If "Yes," have such changes been initiated or identified as "Open items"?

34.

O O

Has the design identified the need for plant design document changes and/or other changes to other configuration management documents? If "Yes," have change ocuments been issued or have the affected documents been identified as "Open items"?

35.

O O

Have actions been appropriately indicated or identified for items on the Design Data Sheet and MAR Program Impact Assessment as required by the procedures for items which are not specifically addressed above?

)

Id l

wmy 1

l

CEPO6TI CW' Outs J

ANNUNCIAF~ N EVENTS CECORDER FLORIDA r ?fR CORPORATION SORTED G$

INT POINT C*YSTAI DCI UNIT 3 Og ANNUNCi d / EVENTS RECORDE3-k Lt.ST CEVId - "%/06/97 08/06/37 PACE Q ' 35 ES(C) = ES(AB)*

+ = LOWER CASE.

EVENT RECORDER DESCRIPTOR ELEM. DWG DEVICE WINDOW NUMBER INPUT-LAMP POINT STATUS PRIORITY LOCATION CBLE NO DUTPUT TERM WINDOW LEGEND OPEN/ CLOSED TO ALARM SINGLE / COMBINED 0332

  • SC PUMP B 208-052 SC-02 52H/A 525/B CS/SC & CS/0 PSA-Y' 01 0314191817 33-H-TRIP 2

SWGR.MN CONT BD SCK-OO9 210R P 04LP 07 SC PUMPpTRIP CLOSED COMBINED PAIRED W/ 0329 C333

  • SC SURGE TANK 208-052. SC-05 SC-68-LS PSA-Y 03 0318242223 33-AA LEVEL HIGH 2

SURGE TANK SCK-Ott 2tOCCBB12LP 23 SC SYSTEMcTROUBLE CLOSED COMBINED PAIRED W/ 0334 0334

  • SC SURGE TANK 208-052 SC-05 SC-68-LS PSA-Y 03 0318212223
s;.

LEVEL LOW "2

SURGE TANK SCK-Ot2 2tOCCBBt2LP 23 SC SYSTEMeTROUBLE CLOSED COMBINED PAIRED W/ 0333 N

C335

  • SC SURGE TANK 208-052 SC-05 SC-89-PS PSA-Y 03 0318101211 33-AA PRESSURE LOW 2

NR PUMP 8

SCK-Ot3 210CCBB12LP 23 SC SYSTEMeTROUBLE CLOSED COMBINED 3

0336 I *SP*fE biffd!t. GEANEfATM $ (3M4 Jaec Jtop.os/o N f.sW 868 32TO 05-01 1104342829 Mf2 SSF-M K*9 964X W OSNC SL )

Acwmo

//

q. t etswT*

nr EvMI.Osca emge lnsel. c,eAs 6 6 nacuts e nr>

0337

  • SPENT FUEL COOLANT PUKP A 208-053. SF-Of 42B CS/SC & CS/0 PSA-Y 04 0320272526 J3-LL TRIP 2

MCC.MN CONT BO SFK-OO2 3 TOT 5 16NC 32

- SPENT FUEL 9 PUMP 9 TRIP CLOSED COMBINED C338

  • SPENT FUEL COOLANT PUMP B 208-053 SF-02 428 CS/SC & CS/O PSA-Y 04 0320242423 33-LL TRIP SPENT FUELOPUMPeTRIP.

2 MCC.MN CONT BD SFK-OO4 3 TOT S 16NC 32 CLOSED COMOINED PAIRED W/ 0339 0339

  • BORATED WATER RECIRC PUMP SFP-2 208-053 SF-03 42B CS/SC & CS/0 PSA-Y 04 0320212223 33-LL AUTO TRIP 2

MCC.MN CONT BD SFK-021

'3 TOT S 16NC 32 SPENT FUEL *PUMPeTRIP CLOSED COMBINED PAIRED W/ 0338 0340

  • SPENT FUEL POOL A 208-053 SF-04 SF-t-LSt PSA-Y O't 0316242223 33-5 LEVEL HIGH 2

NNI CAB SFK-OO6 2tOJ+H+08LP 15 SPENT FUElePOOL LEVEL *HIGH/ LOW CLOSED COMBINED PAIRED W/ 0341 0341

  • SPENT FUEL POOL A 208-053 SF-04 SF-t-LSt PSA-Y 01 0316212223 33-5 LEVEL LOW 2

NNI CAB SFK-OO7 210d*H+08LP 15 l

M Ar< 97-oP-d-f

'O e

EVENTS CECDRDEC FLOR POWE3 CORPORATION SotTE3 I lvENT POINT CRY IVE3 UNIT 3 LAST C'twD - 08/06/97 08/06 97 PAG C3 A

TOR / EVENTS CECORDE3 ES(C) = ES(AB)

+ = LOWER CASE EVENT RECORDER DESCRIPTOR ELEM. DWG DEVICE WINDOW NUMBER INPUT LAMP POINT STATUS PRIORITY LOCATION CBLE NO OUTPUT TERM WINDOW ' LEGEND OPEN/ CLOSED TO ALARM SINGLE / COMBINED.

AUTO TRIP 4

MN CONT BD.SWGR MTK-045 CLOSED 0566

  • UNIT AUX XFMR 3 BREAKER 3208 208-040 MT-12 27C SSF-A2 04 0812161817 48-43 LOSS OF DC POWER 3

SWGR MTK-046 22td H O2NC 04 ES BKR90C POWERpLOSS CLOSED COMBINED PAIRED W/ 0569 0567

  • ES BUS B BREAKER 3208 OVERCURRENT 208-040. MT-12 86B/3208 0918131514 TRIP 4

MN CONT BD MTM-043 CLOSED 6

0568

  • OIESEL GENERAT'1D A BKR 3209 208-040. MT-13 CS/SC & CS/0 52H/A 525/

SSF-A2

-02'02 0811272526 48-04 AUTO TRIlP f - f ^ ^ ~

g 1

MN CONT BD.SWGR MTK-048 209J H O2NC 90 DIESEL GEC AeBREAKERpTRIP CLOSED MNGt& Qg,qp 0569

  • DIESEL GENERATOR A BREAKER 3209 208-040. MT-13 27C SSF-A2 04 0812191817 48-43 LOSS OF DC POWER 3

SWGR MTK-050 22td H O2NC 04 ES BKRpDC POWER

  • LOSS CLOSED COMBINED PAIRED W/ 0566 0570
  • SPARE 0815242223 PAIRED W/ 0573

[

0571

  • DIESEL.GENFDATOR R ND "

208-040, MT-14 CS/SC & CS/0 52H/A 525/

SSF-A2 02 081113t514.

48-12 AUTO TRI C,Z^^^

J [

1 MN CONT BD.SWGR MTK-052 209X W 05NC 9L DIESEL GEN BeBREAKER9TTIP

. CLOSED ffHet+ CbM8m3

~

0572

  • DIESEL GENERATOR B BREAKER 3210 208-040. NT-14 27C SSF-AR 04 -0813342829 48-43 LOSS OF DC POWER 3

SWGR MTK-054 22tJ H O2NC 04 ES BKRpDC POWEReLOSS CLOSED COMBINED 0573

  • DUMMY BREAKER UNIT 3 208-040. MT-90 52H/B SSF-A2 05 0815212223 49-H WITHDRAWN-3 SWGR MTK-254 221J+H+08LP 15 ES* BREAKER
  • WITHDRAWN CLOSED COMBINED PAIRED W/ 0570 0574
  • UNIT 1 BREAKER 3211 208-040. MT-15 CS/SC & CS/0 52H/A 525/8 0918161817 AUTO TRIP 4

MN CONT BD.SWGR MTK-056 CLOSED PAIRED W/ 0576

~

4 g_

9 7 og - or - 01. "

Fc^J 4 z 1

L a

CEPORT C33OO6 ANNUNCIA*" N EVENTS RECORDE3 FLORIDP'"TE3 CORPORATION -

x SORTE] C;

[NT POINT CRYSTA'l lEQ UNIT 3

\\

LAST CEvi,,/ - 08/06/97 ANNUNChJ / EVENTS CECORDER 08/06/97 PAGE 33 ES(C).= ES(AB). -

+ = LOWER CASE.

EVENT RECORDER DESCRIPTOR ELEM. DWG DEVICE WINDOW NUMBER INPUT LAMP POINT STATUS PRIORITY LOCATION CBLE NO OUTPUT TERM

~ WINDOW LEGEND OPEN/ CLOSED TO ALARM SINGLE / COMBINED TURB GEN 9LU*1E DIL SYS97 ROUBLE CLOSED COMBINED PAIRED W/ 0313 0313

  • SPARE 0710191817 4

PAIRED W/ 0312 C314

  • T0XIC GAS DETECTORS 208-005 AH-84 AH-648.649.652.653-CE PSA-X 01 0216161817 31-C TROUBLE 2

LOCAL AHK-392 ~206F E O2LP 03 T0XIC GA59 MONITOR 9TR000LE CLOSED COMBINED PAIRED W/ 0432 0315 l Cee+ee-btE5Et. Gguct4TeR A BK.R 3 to9 2 C'E* 0% MT-r3 966-3209 SsF-At 02 071127252s O~04 LocKccT AcinATEo s/

s*WG A MTX-NE 203.T H OtNd 9D CL SED coMawso D_IESEL darAt A g pgraggg g g,p L

0316

  • LOPU-1A SYSTEM SHUTDOWN WD950096 CR6X.

[

TGF-AX3 07 0711242223 45-A 3

CONDITIONER E

LOX-014 318M'K+2ONC 40 TURO GENeLUBE OIL SYS9 TROUBLE CLOSED COMBINED PAIRED W/ 0317 0317

  • LOPU-1B DIRTY FILTER WD950096 CR7X TGF-AX3 07- 0711212223 45-A 3

CONDITIONER LOK-016 318M+K+20NC 40 TURB GENeLUBE OIL SYS9 TROUBLE CLOSED.

COMBINED PAIRED W/ 0316 0318

  • FW TURB LO PURIFIER OVERFLOW 208-038 LO-07 3TB-329-LS TGF-AX3 07 0711101211 45-A LFvEL LOW 3

CONT STA LO-1 LOK-OO3 318M+K+2ONC 40 TURB GEN 9 LUBE DIL SYS9 TROUBLE CLOSED COMBINED 0319

  • SPARE 1103191817 4

PAIRED W/ O264 0320

LOCAL MOK-OOt CLOSED EXTRACTION TO HEATER 6 DRAIN POT 208-068 MD-03 MD-5.6.9.10-LS 0909161817 0321

  • LEVEL HIGH 4

LOCAL MOK-OOG CLOSED PAIRED W/ 0322 k*

- 0$~O N O I

. ~ ;.

.,s. g

?

2 s u a

1 l

! (d Rev. 15

-s

)

Effective Date /l ES 97 i

i l

l ANNUNCIATOR RESPONSE AR-702 i

FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 1

l r"'s SSF Q ANNUNCIATOR RESPONSE

(

)

v I

i l

t l

l l

r l

l l

APPROVED BY: Interpretation Contact h auJL N h /UA f (SIGNATURE ON' FILE) '

DATE:

///16 7

/

/

INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support

j i

TABLE OF CONTENTS i

p\\

i SECTION PAGE I

i i

1.0 PURP0SE.................................................................

1 i

2.0 REFERENCES

1 2.1 IMPLEMENTING REFERENCES.............................................

1 2.2 PEVELOPMENTAL REFERENCES............................................

1 3.0 PERSONNEL INDOCTRINATION................................................

1 i

4.0 INSTRUCTIONS............................................................

1 5.0 FOLLOW-UP-ACTIONS.......................................................

1 ENCLOSURES 1

Ann u nci ato r Re s pon s e........................................... 2

(

s t

I l

1 r

i l

l I

i AR-702 Rev. 15 Page i

(

. -...-..=. -

=. -. - -. - - - - - -. -.........

1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the SSF-A2 Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the SSF-A2 Lampbox.

1. 3 -

Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the SSF-A2 Lampbox.

I

2.0 REFERENCES

2.1 IMPLEMENTING REFERENCES 2.1.1

.t.P-770, Emergency Diesel Generator Actuation 2.1.2 OP-703, Plant Distribution System 2.2 DEVELOPMENTAL REFERENCES s

2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-049^

3.0 PERSONNEL INDOCTRINATION 3.1 The Annunciator System is powered from VBDP-5 Breaker 28.

4.0 INSTRUCTIONS 4.1 Respond to alarms on the SSF-A2 Lampbox as indicated on Enclosure 1, Annunciator Response.

1 5.0 FOLLOW-UP-ACTIONS None l O l

l AR-702 Rev. 15 Page 1 1

ENCLOSURE 1 I

(Page 1 of-111)

SSF ANNUNCIATOR RESPONSE S F-A2-01-10 Q-01-10 i

BUS PARALLELED I

EVENT POINT 0540 INDICATED CONDITION:

o "A" 6900V RX AUX BUS BREAKERS 3101 AND 3103 CLOSED.

' O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o BREAKER POSITION INDICATION FOR BREAKERS 3101 AND 3103.

OPERATOR ACTIONS FOR A VALID ALARM:

i DISCUSSION:

THIS IS A NORMAL ALARM WHILE TRANSFERRING BUSSES TO ALTERNATE SUPPLIES WHEN MORE THAN ONE SUPPLY BREAKER IS CLOSED.

b

REFERENCES:

DRAWING 208-040 MT-03 1

l SENSING ELEMENT: 3101/52A CONTACT AND 3103/52A CONTACT (6900V BREAKERS) g i

AR-702 Rev. 15 Page 2 i

N ENCLOSURE 1

)

(Page 2 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-01-10 Q-01-10 BUS PAPALLELED EVENT POINT 0543 INDICATED CONDITION:

"B" 6900V RX AUX BUS BREAKEPS 3102 AND 3104 CLOSED.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

BREAKER POS'ITION INDICATION FOR BREAKERS 3102 AND 3104.

o OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS IS A NORMAL ALARM WHILE TRANSFERRING BUSSES TO ALTERNATE SUPPLIES WHEN MORE THAN ONE SUPPLY BREAKER IS CLOSED,

REFERENCES:

DRAWING 208-040 MT-04 SENSING ELEMENT: 3102/52A CONTACT AND 3104/52A CONTACT (6900V BREAKERS)

AR-702 Rev. 15 Page 3 r

ENCLOSURE 1 U]

(

(Page 3 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-01-10 Q-01-10 BUS PARALLELED EVENT POINT 0546 INDICATED CONDITION:

"A" 4160V UNIT BUS BREAKERS 3201 AND 3203 CLOSED.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o BREAKER POSITION INDICATION FOR BREAKERS 3201 AND 3203.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS IS A NORMAL ALARM WHILE TRANSFERRING BUSSES TO ALTERNATE SUPPLIES WHEN MORE THAN ONE SUPPLY BREAKER IS CLOSED.

REFERENCES:

DRAWING 208-040 MT-05 SENSING ELEMENT: 3201/52A CONTACT AND 3203/52A CONTACT (4160V BREAKERS)

AR-702 Rev. 15 Page 4

ENCLOSURE 1 (Page 4 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-01-10 Q-01-10 I

I I

I l

Bus l

PARALLELED 1

1 I

ZZZZZZZ EVENT POINT 0549 INDICATED CONDITION:

o "B" 4160V UNIT BUS BREAKERS 3202 AND 3204 CLOSED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o BREAKER POSITION 7NDICATION FOR BREAKERS 3202 AND 3204.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS IS A NORMAL ALARM WHILE TRANSFERRING BUSSES TO ALTERNATE SUPPLIES WHEN MORE THAN ONE SUPPLY BREAKER IS CLOSED.

i

/~~}

REFERENCES:

DRAWING 208-040 MT-06 SENSING ELEMENT: 3202/52A CONTACT AND 3204/52A CONTACT (4160V BREAKERS)

AR-702 Rev. 15 Page 5

1 I

ENCLOSURE 1 l O.

(Page 5 of 111)

V SSF ANNUNCIATOR RESPONSE SF-A2-01-10 Q-01-10 BUS PARALLELED 1

1 EVENT POINT 0556 INDICATED CONDITION:

o ANY COMBINATION OF "A" ES 4160V BUS BREAKERS 3205, 3207, 3209, 3211 CLOSED.

l O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o BREAKER POSITION INDICATION FOR BREAKERS 3205,3207,3209,3211.

OPERATOR ACTIONS FOR A VALID ALARM:

i DISCUSSION:

THIS IS A NORMAL ALARM WHILE TRANSFERRING BUSSES TO ALTERNATE SUPPLIES WHEN MORE THAN ONE SUPPLY BREAKER IS CLOSED.

1

REFERENCES:

DRAWING 208-040 MT-09 SENSING ELEMENT: 3205/52A, 3207/52A, 3209/52A, 3211/52A CONTACTS

)

AR-702 Rev. 15 Page 6

ENCLOSURE 1 (Page 6 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-01-10 Q-01-10 l

I I

I I

i I

i l

l BUS i

l l

PARALLELED 1

1 i

I i

l EVENT POINT 0560 I

INDICATED CONDITION:

o ANY COMBINATION OF "B" ES 4160V BUS BREAKERS 3206, 3208, 3210, 3212 l

CLOSED.

f lO

{

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

{

l o BREAKER POSITION INDICATION FOR BREAKERS 3206, 3208, 3210, 3212.

t OPERATOR ACTIONS FOR A VALID ALARM:

i l

l i

I DISCUSSION:

THIS IS A NORMAL ALARM WHILE TRANSFERRING BUSSES TO ALTERNATE SUPPLIES WHEN MORE THAN ONE SUPPLY BREAKER IS CLOSED.

l

REFERENCES:

DRAWING 208-040 MT-10 SENSING ELEMENT: 3206/52A, 3208/52A, 3210/52A, 3212/52A CONTACTS l

AR-702 Rev. 15 Page 7

ENCLOSURE 1 i.

(Page 7 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-01 Q-02-01 w

rrrrr I

I l

l l

l l

l 4 KV l

l ES BUS A l

l DEAD I

I l-l l

l 1

EVENT POINT 0649 INDICATED CONDITION:

o "A" ES 4160V BUS UNDERVOLTAGE O

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 l

o "A" ES 4160V VOLTAGE INDICATION.

I OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION:

THIS ALARM IS THE RESULT OF A 2 OUT OF 3 UNDERVOLTAGE (FLUR) RELAY LOGIC.

THE FLUR RELAYS ARE INTENDED TO PROVIDE ES 4160VAC UNDERVOLTAGE RESPONSE WHEN VOLTAGE DROPS INSTANTLY TO ZERO. THE SLUR RELAY WILL PROVIDE UNDERVOLTAGE RESPONSE WHEN THE VOLTAGE DROPS GRADUALLY BELOW THE SLUR SETPOINT.

l

REFERENCES:

DRAWING 208-040 MT-65 SENSING ELEMENT: 27Y-3/32EA RELAY AR-702 Rev. 15 Page 8

i t

ENCLOSURE 1 l ('s (Page 8 of 111)

U SSF ANNUNCIATOR RESPONSE SF-A2-02-02 Q-02-02 DIESEL GEN A BREAKER TRIP l

OSIS EVENT POINT 0568-1 1

INDICATED CONDITION:

i o W4ERGENCY DIESEL CENERATOR 00TFUT BREAKER TRIFFED.-

Ic.5sl 3cpirL% r~

k ' f$k'f2 3d Lo do s b Y

<~h, I

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED FLAG WITH A GREEN LIGHT IS ON, LOCATED ON BREAKER 3209 CONTROL STATION.

o VERIFY 86B EDG BREAKER LOCKOUT RELAY OPEN.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION: THE 86B EDG BREAKER LOCKOUT RELAY WILL TRIP AND PREVENT RECLOSURE OF THE EDG OUTPUT BREAKER FOR:

}

o OVERCURRENT DEVICE (51V) o NEGATIVE SEQUENCE (DEVICE 46) o GENERATOR GROUND t' DEVICE 64) o ES BUS FEEDER BREAKER OVERCURRENT (DEVICE 518. 51BN)

THE ACTUATION OF THE NEW 868 LOCKOUT WILL RESULT IN THE ENGINE REMAINING RUNNING WITH THE OUTPUT BREAKER OPEN. THIS WILL REQUIRE THE ENGINE SHUTDOWN WIItLIN 2 HOURS.

,_s

REFERENCES:

DRAWING 208-040 MT-13 SENSING ELEMENT: CS/SC,CS/0 1,0NT N WTTCu-CONTACTS, 52H/A, 525/B/ CONTACTS G5

/j AR-702 Rev. 15 G d46/M 7Page 9

ENCLOSURE 1 (Page 9 of 111) i SSF ANNUNCIATOR RESPONSE SF-A'2-02-03 Q-02-03 l

i DIESEL GEN A BREAKER CLOSED EVENT POINT 1182 l

l INDICATED CONDITION:

"A" EMERGENCY DIESEL GENERATOR OUTPUT BREAKER CLOSED, WITH ES ACTUATION o

SIGNAL OR UNDERVOLTAGE SIGNAL PRESENT.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l RED LIGHT IS ON WITH A GREEN FLAG ON BREAKER 3209 CONTROL STATION.

o 1

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

i DISCUSSION:

l

REFERENCES:

DRAWING 208-040 MT-129 SENSING ELEMENT: 86B/ESA AR-702 Rev. 15 Page 10 i

. ~ -

1 ENCLOSURE 1 (Page 10 of 111) i SSF ANNUNCIATOR RESPONSE SF-A2-02-04 Q-02-04 4KV ES A CROSS-TIE BLOCKED s

EVENT POINT 1183 l

INDICATED CONDITION:

f o BREAKERS 3209 AND 3210 CLOSED WITH EITHER 3206, 3208, OR 3212 CLOSED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIESEL GEN "A" CROSS-TIE LIGHT EXTINGUISHED.

o IF 3206 CLOSED, THEN BLOCK CLOSING ACTUATED 3205 LIGHT IS ON.

o IF 3208 CLOSED, THEN BLOCK CLOSING ACTUATED 3207 LIGHT IS ON.

o IF 3212 CLOSED, THEN BLOCK CLOSING ACTUATED 3211 LIGHT IS ON.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

REFERENCES:

DRAWING 208-040 MT-129 SENSING ELEMENT: 3-52-1, 3-525 CONTACTS AR-702 Rev. 15 Page 11

ENCLOSURE 1 (Page 11 of 111 SSF ANNUNCIATOR RESPONSE SF-A2-02-05 Q-02-05 DIESEL GEN A VOLTAGE ADJ IN CONTROL RM l

EVENT POINT 1177 INDICATED CONDITION:

DIESEL GENERATOR "A" VOLTAGE ADJUST SELECTED TO THE CONTROL ROOM.

l o

l O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIESEL GENERATOR A "EXC VOLT ADJ SELECT" SWITCH SELECTED TO " CONT RM" POSITION.

l OPERATOR ACTIONS FOR A VALID ALARM:

l l'

DISCUSSION:

THIS SWITCH IS NORMALLY SELECTED TO THE "DG RM" POSITION.

j e

REFERENCES:

DRAWING 208-027 EG-17 SENSING ELEMENT: SS/0,CB/SSF CONTACT AR-702 Rev. 15 Page 12 l.

ENCLOSURE 1 (Page 12 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-07 Q-02-07 I

i l

l 480V ES BUS A i

r l

DEAD I

l EVENT POINT 0653 INDICATED CONDITION:

o "A" ES 480V BUS UNDERVOLTAGE.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o 480V ES BUS "A" VOLTAGE INDICATES LESS THAN NORMAL.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770 i

DISCUSSION:

l l

REFERENCES:

DRAWING 208-040 MT-66 SENSING ELEMENT: 27Y-1/33EA I

AR-702 Rev. 15 Page 13

t

\\

ENCLOSURE 1 (Page 13 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-08 Q-02-08

+

480V ES BUS A UV LOCKOUT ACT i

EVENT POINT 0719 1

INDICATED CONDITION:

o "A" ES 480V BUS UNDERVOLTAGE LOCK OUT RELAY ACTUATED.

D REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o 4160V ES BUS "A" VOLTAGE INDICATES LESS THAN NORMAL.

o 480V ES BUS "A" VOLTAGE INDICATES LESS THAN NORMAL.

o BREAKER 3209 INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770 l

DISCUSSION:

THE 480V ES UNDERVOLTAGE LOCK OUT RELAY IS ACTUATED WHEN, EITHER THE "A" l

NIESEL OUTPUT BREAKER IS CLOSED, OR 4160V ES BUS A UNDERVOLTAGE OCCURS

'nITH AN ES ACTUATION.

[

REFEREilCES: DRAWING 208-040 MT-77 SENSING ELEMENT: 86/27ESA AR-702 Rev. 15 Page 14 l

ENCLOSURE 1

(~

(Page 14 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10

)

POTENTIAL TRANSFORMER TROUBLE l

\\

EVENT POINT 0642 i

i INDICATED CONDITION:

o "A" 6900V REACTOR AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

j i

1 OPERATOR ACTIONS FOR A VALID ALARM-o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES i

DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

'F MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVE; THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMtR ALARM IS DISABLED.

l

REFERENCES:

DRAWING 208-040 MT-63 SENSING ELEMENT: 27Y-1/31RA 27Z/31RA RELAYS AR-702 Rev. 15 Page 15

l l

l l

l i

ENCLOSURE 1 (Page 15 of 111) l SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 8

l i

l l

POTENTIAL TRANSFORMER TROUBLE I

EVENT POINT 0644 l

INDICATED CONDITION:

i "B" 6900V REACTOR AUX BUS UNDERVOLTAGE ON "I OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

lO i

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l i

{

OPERATOR ACTIONS FOR A VALID ALARM:

l o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

-THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS l

UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES': DRAWING 208-040 MT-63

'~

SENSING ELEMENT: 27Y-1/31RB 27Z/31RB RELAYS 1

AR-702-Rev. 15 Page 16

i ENCLOSURE 1

!O D

(Page 16 of 111) t SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-IO i

i I

t, POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0646 INDI'CATED CONDITION:

o "A" 4160V UNIT BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

lO i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i i

OPERATOR ACTIONS FOR A VALID ALARM:

l o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

(G

REFERENCES:

DRAWING 208-040 MT-64 SENSING ELEMENT: 27Y-1/320A 27Z/320A RELAYS AR-702 Rev. 15 Page 17

ENCLOSURE 1 l r~

(Page 17 of 111)

L}J SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 i

POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0648 i

l INDICATED CONDITION:

"B" 4160V UNIT BUS 3B UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

j b

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-64 SENSING ELEMENT: 27Y-1/32VB 27Z/32VB RELAYS AR-702 Rev. 15 Page 18

l l

ENCLOSURE _1

[

(Page 18 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 l

t i

l i

l I

POTENTIAL TRANSFORMER TROUBLE l

EVENT POINT 0650 l

l INDICATED CONDITION:

o "A" ES 4160V BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

i

/%

b

]

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES i

DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTEfffIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

i

REFERENCES:

DRAWING 208-040 MT-65 SENSING ELEMENT: 27Y-1/32EA 27Z/32EA RELAYS i

AR-702 Rev. 15 Page 19 f.

l 1

i l

l l

ENCLOSURE 1 i

[

(Page 19 of 111) l SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 l

r i

l

\\

POTENTIAL l

TRANSFORMER l

TROUBLE i

1 EVENT POINT 0652 I

INDICATED CONDITION:

o "B" ES 4160V BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

c l'

l

. (-

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

)

l I

i OPERATOR ACTIONS FOR A VALID ALARM:

l o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

)

i i

REFERENCES:

DRAWING 208-040 MT-65 SENSING ELEMENT: 27Y-1/32EB 27Z/32EB RELAYS AR-702 Rev. 15 Page 20 f

ENCLOSURE 1 I

l (Page 20 of 111) t SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0654 INDICATED CONDITION:

4 "A" ES 480V BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL o

TRANSFORMER CIRCUIT HAS FAILED.

t O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS'UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

i i

(~

REFERENCES:

DRAWING 208-040 MT-66 SENSING ELEMENT: 27Y-1/33EA 27Z/33EA RELAYS AR-702 Rev. 15 Page 21

ENCLOSURE 1 O

(Page 21 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0656 INDICATED CONDITION:

"B" ES 480V BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL o

TRANSFORMER CIRCUIT HAS FAILED.

Ob]

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

I

REFERENCES:

DRAWING 208-040 MT-66 SENSING ELEMENT: 27Y-1/33EB 27Z/33EB RELAYS AR-702 Rev. 15 Page 22

i l

ENCLOSURE 1 (Page 22 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 i

l POTENTIAL TRANSFORMER TROUBLE l

l EVENT POINT 0658 INDICATED CONDITION:

"A" 480V REACTOR AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

(}

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES l

DISCUSSION:

l THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPCRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-67 SENSING ELEMENT: 27Y-1/33RA 27Z/33RA RELAYS AR-702 Rev. 15 Page 23 l

l

ENCLOSURE 1 (Page 23 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 POTENTIAL TRANSFORMER TROUBLE E

EVENT POINT 0660 INDICATED CONDITION:

"B" 480V REACTOR AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE nilRTNG A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN I UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND

.l THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

)

REFERENCES:

DRAWING 208-040 MT-67 SENSING ELEMENT: 27Y-1/33RB 27Z/33RB RELAYS AR-702 Rev. 15 Page 24

ENCLOSURE 1 (Page 24 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 i

i POTENTIAL TRANSFORMER l

TROUBLE i

EVENT POINT 0662 i

l INDICATED CONDITION:

"A" 480V TURBINE AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES l

DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

I

REFERENCES:

DRAWING 208-040 MT-68 SENSING ELEMENT: 27Y-1/33TA 27Z/33TA RELAYS AR-702 Rev. 15 Page 25

ENCLOSURE 1 (Page 25 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0664 INDICATED CONDITION:

"B" 480V TURBINE AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-68 SENSING ELEMENT: 27Y-1/33TB 27Z/33TB RELAYS AR-702 Rev. 15 Page 26

ENCLOSURE 1 b

(Page 26 of 111) v SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0666 INDICATED CONDITION:

"A" 480V INTAKE AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

AV REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES

~

DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

(

REFERENCES:

DRAWING 208-040 MT-69 SENSING ELEMENT: 27Y-1/33IA 27Z/33IA RELAYS AR-702 Rev. 15 Page 27

f.NCLOSURE 1 (Page 27 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 1

I POTENTIAL TRANSFORMER TROUBLE


I EVENT POINT 0668 j

l i

INDICATED CONDITION:

l "B" 480V INTAKE AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND l

THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-69

~'

SENSING ELEMENT: 27Y-1/33IB 27Z/33IB RELAYS AR-702 Rev. 15 Page 28 l

l

1 i

1 ENCLOSURE 1 (Page 28 of 111)

(

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 1

POTENTIAL TRANSFORMER TROUBLE EVENT POINT 0670 INDICATED CONDITION:

480V PLANT AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

q

(

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

)

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFOP.MER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC.

IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPCRADES TO. BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-70 SENSING ELEMENT: 27Y-1/33P 27Z/33P RELAYS AR-702 Rev. 15 Page 29

ENCLOSURE 1 iO (Page 29 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 i

POTENTIAL TRANSFORMER TROUBLE

^

EVENT POINT 0672 INDICATED CONDITION:

)

480V HEATING AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE o

POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES l

i DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION.

POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-70 SENSING ELEMENT: 27Y-1/33H 27Z/33H RELAYS AR-702 Rev. 15 Page 30 i

i ENCLOSURE 1 (Page 30 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-02-10 Q-02-10 I

I I

l POTENTIAL l

TRANSFORMER I

TROUBLE I

I I

EVENT POINT 1991 INDICATED CONDITION:

o 4160V REALTOR AUX BUS UNDERVOLTAGE ON "1 OUT OF 3" LOGIC OR A SINGLE POTENTIAL TRANSFORMER CIRCUIT HAS FAILED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o OBSERVE BUS VOLTAGE WITHIN NORMAL VALUES DISCUSSION:

THIS ALARM MAY BE ONE OF THE FIRST ALARMS TO ACTUATE DURING A BUS UNDERVOLTAGE CONDITION. POTENTIAL TRANSFORMER TROUBLE USES A "1 OUT OF 3" UNDERVOLTAGE LOGIC. IF MORE THAN 1 UNDERVOLTAGE RELAY OR POTENTIAL TRANSFORMER IS INVOLVED THEN THE ALARM UPGRADES TO BUS UNDERVOLTAGE AND THE POTENTIAL TRANSFORMER ALARM IS DISABLED.

REFERENCES:

DRAWING 208-040 MT-136 SENSING ELEMENT: 32RA AR-702 Rev. 15 Page 31 L

ENCLOSURE 1 I

(Page 31 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-03-01 Q-03-01 r w xrrr I

I l

I l

DIESEL GEN A l

l IN THE 30 MIN LIMIT I

I I

I I

I l

l EVENT POINT 1590 INDICATED CONDITION:

o DIESEL GENERATOR "A" OVER 3250 KW.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIESEL GENERATOR "A" KW INDICATION.

DIESEL GENERATOR "A" "EDG-3A El.APSED TIME IN 30 MIN RATING." TIMER IS o

OPERATING.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

REDUCE LOAD IF SURVEILLANCE TESTING.

o DISCUSSION:

THIS ALARM IS INSTANTANEOUS WHEN DIESEL LOAD EXCEEDS 3250 KW

REFERENCES:

DRAWING 208-027 EG-22 SENSING ELEMENT: 62BX AR-702 Rev. 15 Page 32

ENCLOSURE 1

(

(Page 32 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-03-04 Q-03-04 4KV ES A UNDERVOLTAGE TRIP BLOCKED EVENT POINT 0823 INDICATED CONDITION:

o "A" ES 4160V BUS UNDERVOLTAGE PROTECTION DISABLED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

TRIP BLOCK SWITCHES, TBS 1 AND TBS 2, LOCATED IN MTCP-1A IN THE 4160V ES "A" SWITCHGEAR ROOM ARE IN OPEN POSITION.

OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR "A" ES BUS VOLTAGES DURING UNDERVOLTAGE RELAY TESTING.

DISCUSSION:

THIS ALARM WILL OCCUR WHEN TESTING THE BUS UNDERVOLTAGE RELAYS. NO UNDERVOLTAGE PROTECTION IS AVAILABLE DURING TESTING.

REFERENCES:

DRAWING 208-040 MT-65B SENSING ELEMENT: TBS 1, TBS 2 l

AR-702 Rev. 15 Page 33

t ENCLOSURE 1 (Page 33 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-02 Q-04-02 t

k 4KV ES BUS DEGRADED VOLT TRIP EVENT POINT 1747 INDICATED CONDITION:

"A" ES 4160V BUS VOLTAGE <3952 VOLTS FOR >5 SECONDS.

o REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o "A" ES 4160V BUS VOLTAGE METER INDICATING < 3952 VAC l

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION:

I THIS ALARM WILL OCCUR WHEN ANY OF THREE VOLTAGE SENSE RELAYS DETECT LTSS THAN 3952 VOLTS FOR GREATER THAN 5 SECONDS. A DIESEL GENERATOR START SIGNAL IS INITIATED IF ALL THREE VOLTAGE RELAYS SENSE THIS CONDITION.

f

REFERENCES:

DRAWING 208-040 MT-131 SENSING ELEMENT: 27B-A/32EA, 27B-B/32EA, 27B-C/32EA AR-702 Rev. 15 Page 34

.. ~.

I ENCLOSURE 1 (Page 34 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-02 Q-04-02 f

4KV ES BUS DEGRADED VOLT l

TRIP i

EVENT POINT 1818 L

l INDICATED CONDITION:

l o

"B" ES 4160V BUS VOLTAGE <3952 VOLTS FOR >5 SECONDS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o "B" ES 4160V BUS VOLTAGE METER INDICATING < 3952 VAC OPERATOR ACTIONS FOR A VALID ALARM:

i o REFER TO AP-770.

l l

DISCUSSION:

l' THIS ALARM WILL OCCUR WHEN ANY OF THREE VOLTAGE SENSE RELAYS DETECT LESS THAN 3952 VOLTS FOR GREATER THAN 5 SECONDS. A DIESEL GENERATOR START l

SIGNAL IS INITIATED IF ALL THREE VOLTAGE RELAYS SENSE THIS CONDITION.

,h

REFERENCES:

DRAWING 208-040 MT-132

^m SENSING ELEMENT: 27B-A/32EB, 27B-B/32EB, 27B-C/32EB AR-702 Rev. 15 Page 35

l ENCLOSURE 1 (Page 35 of 111) i SSF ANNUNCIATOR RESPONSE SF-A2-04-03 Q-04-03 1

i t-CROSS-TIE BLOCKED LOSS OF DC l

EVENT POINT 1184 INDICATED CONDITION:

"A" ES 4160V BUS CROSS TIE LOCKOUT RELAY LOSS OF DC CONTROL POWER.

o REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #6.

FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.

REFERENCES:

DRAWING 208-040 MT-129, MT-127 SENSING ELEMENT: 27C-1A AR-702 Rei. 15 Page 36

.~.

.~ _

i ENCLOSURE 1 (Page 36 of 111) i f

SSF ANNUNCIATOR RESPONSE SF-A2-04-03 Q-04-03 l

i CROSS-TIE BLOCKED l

LOSS OF DC I

EVENT POINT 1185 i

INDICATED CONDITION:

i o

"A" ES 4160V BUS CROSS TIE CIRCUIT LOSS OF DC CONTROL POWER.

O l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC C0t. TROL POWER IS SUPPLIED FROM DPDP-5A FUSE #6. ADDITIONAL FUSES BEHIND THE CONTROL BOARD ARE ALSO INVOLVED.

I t

REFERENCES:

DRAWING 208-040 MT-129, MT-127 l

SENSING ELEMENT: 27C-2A AR-702 Rev. 15 Page 37

1 ENCLOSURE 1

/]

(Page 37 of 111)

V SSF ANNUNCIATOR RESPONSE SF-A2-04-03 Q-04-03 CROSS-TIE BLOCKED LOSS OF DC EVENT POINT 1188 INDICATED CONDITION:

"B" ES 4160V BUS CROSS TIE LOCKOUT RELAY LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #6.

FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.

REFERENCES:

DRAWING 208-040 MT-129, MT-128 SENSING ELEMENT: 27C-1B AR-702 Rev. 15 Page 38

f ENCLOSURE 1 (Page 38 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-03 Q-04-03 P

P CROSS-TIE BLOCKED LOSS OF DC EVENT POINT 1189 I

l t

INDICATED CONDITION:

"B" ES 4160V BUS CROSS TIE CIRCUIT LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

L OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #6.

ADDITIONAL FUSES BEHIND THE CONTROL BOARD ARE ALSO INVOLVED.

1

REFERENCES:

DRAWING 208-040 MT-129, MT-128 SENSING ELEMENT: 27C-2B AR-702 Rev. 15 Page 39

ENCLOSURE 1 (Page 39 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR

~

DC POWER LOSS I

EVENT POINT 0555 INDICATED CONDITION:

o "A" ES 4160V BUS SUPPLY BREAKER 3205 LOSS OF DC CONTROL POWER.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o-NO^ INDICATI NG ~ tIGilTS" ARE' ONTt0CATE D ' ON' TH E ' BRE' KER ' 3'205" CONTROL" A

STATION.

)

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

i DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #10.

l

REFERENCES:

DRAWING 208-040 MT-9 SENSING ELEMENT: 27C/3205 AR-702 Rev. 15 Page 40 l

ENCLOSURE 1 io

'Page 40 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 i

i ES BKR

{

DC POWER LOSS EVENT POINT 0559 l

INDICATED CONDITION:

"B" ES 4160V BUS SUPPLY BREAKER 3206 LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3206 CONTROL o

STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

DISCUSSION:

I DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #10.

l

REFERENCES:

DRAWING 208-040 MT-10 SENSING ELEMENT: 27C/3206 l

AR-702 Rev. 15 Page 41 i.

lh ENCLOSURE 1 (Page 41 of 111)

,v S5F ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 t

i 6

l ES BKR DC POWER LOSS l

l EVENT POINT 0563 INDICATED CONDITION:

"A" ES 4160V BUS SUPPLY BREAKER 3207 LOSS OF DC CONTROL POWER.

o REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3207 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

i o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

I j.

DISCUSSION:

i

(

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #10.

l l

i a

REFERENCES:

DRAWING 208-040 MT-11 L

SENSING ELEMENT: 27C/3207 i

AR-702 Rev. 15 Page 42

P s

ENCLOSURE 1 (Page 42 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR DC POWER LOSS i

EVENT POINT 0566 I

INDICATED CONDITION:

"B" ES 4160V BUS SUPPLY BREAKER 3208 LOSS OF DC CONTROL POWER.

o REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3208 CONTROL o

STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #10.

f

REFERENCES:

DRAWING 208-040 MT-12 V

SENSING ELEMENT: 27C/3208 AR-702 Rev. 15 Page 43

I ENCLOSURE 1 (Page 43 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04 Q-04-04 ES BKR DC POWER LOSS EVENT POINT 0569 INDICATED CONDITION:

o "A" ES 4160V BUS SUPPLY BREAKER 3209 LOSS OF DC CONTROL POWER.

i m REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LCCATED ON THE BREAKER 3209 CONTROL STATION.

l l

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

DISCUSSION:

I

[

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #10.

REFERENCES:

DRAWING 208-040 MT-13 SENSING ELEMENT: 27C/3209 AR-702 Rev. 15 Page 44

l i

ENCLOSURE 1

[

(Page 44 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 I

i ES BKR i

~

DC POWER LOSS t

EVENT POINT 0572 INDICATED CONDITION:

"B" ES 4160V BUS SUPPLY BREAKER 3210 LOSS OF DC CONTROL POWER.

o

)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3210 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #10.

l

REFERENCES:

DRAWING 208-040 MT-14 SENSING ELEMENT: 27C/3210 I'

AR-702 Rev. 15 Page 45 l

O)

ENCLOSURE 1

(/

(Page 45 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 l

t ES BKR DC POWER LOSS I

EVENT POINT 0575 '

l INDICATED CONDITION:

o "A" ES 4160V BUS SUPPLY BREAKER 3211 LOSS OF DC CONTROL POWER.

Ob) t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

t o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3211 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

DISCUSSION:

l DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #10.

i

)

REFERENCES:

DRAWING 208-040 MT-15 SENSING ELEMENT: 27C/3211 AR-702 Rev. 15 Page 46

ENCLOSURE 1 (Page 46 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 i

l

)

ES BKR DC POWER LOSS

(

j i

EVENT POINT 0578 1

INDICATED CONDITION:

l "B"'ES 4160V BUS SUPPLY BREAKER 3212 LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3212 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

o REFER TO OP-703.

DISCUSSION:

i DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #10.

l'

REFERENCES:

DRAWING 208-040 MT-16 SENSING ELEMENT: 27C/3212 i

4 AR-702 Rev. 15 Page 47

i ENCLOSURE 1 (Page 47 of 111 i

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR I

DC POWER LOSS EVENT POINT 0588 INDICATED CONDITION:

"B" ES 480V BUS TRANSFORMER SUPPLY BREAKER 3220 LOSS OF DC CONTROL o

POWER.

(N REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3220 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #10.

i l

REFERENCES:

DRAWING 208-040 MT-24 k

SENSING ELEMENT: 27C/3220 AR-702 Rev. 15 Page 48 a

l

ENCLOSURE 1 (Page 48 of 111) u SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 1

l ES BKR DC POWER LOSS i

l EVENT POINT 0590 I

i INDICATED CONDITION:

o "A" ES 480V BUS TRANSF0i'MER SUPPLY BREAKER 3221 LOSS OF DC CONTROL l

POWER.

f%,

t i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3221 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #10.

1 i

REFERENCES:

DRAWING 208-040 MT-25 SENSING ELEMENT: 27C/3221 AR-702 Rev. 15 Page 49

ENCLOSURE 1 O

(Page 49 of 111)

L' SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR DC POWER LOSS EVENT POINT 0592 INDICATED CONDITION:

o 480V PLANT AUX BUS TRANSFORMER SUPPLY BREAKER 3222 LOSS OF DC CONTROL POWER.

O 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3222 CONTROL o

STATION.

i OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

l 1

DISCUSSION:

)

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #10.

l l

l A

REFERENCES:

DRAWING 208-040 MT-26

)

l SENSING ELEMENT: 27C/3222 AR-702 Rev. 15 Page 50

I l

)

ENCLOSURE 1 (Page 50 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-04-04 Q-04-04 i

i I

l l

ES BKR DC POWER i

1.

LOSS 8

EVENT POINT 0609 i

INDICATED CONDITION:

1 "B" ES 480V BUS SUPPLY BREAKER 3310 LOSS OF DC CONTROL POWER.

o REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3310 CONTROL STATION.

l OPrRATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #9, l

l C

REFERENCES:

DRAWING 208-040 MT-34 SENSING ELEMENT: 27C/3310 AR-702 Rev. 15 Page 51 I

_ _.. =.. _ _ -.

I ENCLOSURE 1 (Page 51 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-04-04 Q-04-04 i

ES BKR DC POWER LOSS l

EVENT POINT 0612 INDICATED CONDITION:

o "A" ES 480V BUS SUPPLY BREAKER 3311 LOSS OF DC CONTROL POWER.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3311 CONTROL STATION.

{

OPERATOR ACTIONS FOR A VALID ALARM:

i o INVESTICATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #9.

l i

REFERENCES:

DRAWING 208-040 MT-35 SENSING ELEMENT: 27C/3311 AR-702 Rev. 15 Page 52

ENCLOSURE 1 (Page 52 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR DC POWER LOSS EVENT POINT 0616 INDICATED CONDITION:

"B" ES 480V BUS CROSS-TIE BREAKER 3390 LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3390 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #9.

REFERENCES:

DRAWING 208-040 MT-37 SENSING ELEMENT: 27C/3390 AR-702 Rev. 15 Page 53

.. =

ENCLOSURE 1 O)

C/

(Page 53 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR i

DC POWER LOSS i

EVENT POINT 0618 INDICATED CONDITION:

"A" ES 480V BUS CROSS-TIE BREAKER 3391 LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ARE ON, LOCATED ON THE BREAKER 3391 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWLR.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #9.

REFERENCES:

DRAWING 208-040 MT-38 SENSING ELEMENT: 27C/3391 AR-702 Rev. 15 Page 54

ENCLOSURE 1 (Page 54 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR DC POWER LOSS EVENT POINT 0673 INDICATED CONDITION:

480V ES MCC 381 SUPPLY BREAKER 3340 LOSS OF DC CONTROL POWER.

o REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #9.

~

REFERENCES:

DRAWING 208-040 MT-47 I

SENSING ELEMENT: 27C/3340 AR-702-Rev. 15 Page 55

_.______.._.m____

p ENCLOSURE 1 (Page 55 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 i

l ES BKR DC POWER LOSS EVENT POINT 0674 INDICATED CONDITION:

o 480V ES MCC 3Al SUPPLY BREAKER 3341 LOSS OF DC CONTROL POWEF.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

i

)

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #9,

REFERENCES:

DRAWING 208-040 MT-54 SENSING ELEMENT: 27C/3341 AR-702 Rev. 15 Page 56 r

!e ENCLOSURE 1 i

(

(Page 56 of 111) i j

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04

)

l ES BKR 1

DC POWER LOSS l

l-l EVENT POINT 0677 INDICATED C?8DITION:

l o 480V ES MCC 3AB CROSS-TIE BREAKER 3361 LOSS OF DC CONTROL POWER.

lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #9.

l

REFERENCES:

DRAWING 208-040 MT-89 i

SENSING ELEMENT: 27C/3361 AR-702 Rev. 15 Page 57

i ENCLOSURE 1 (Page 57 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 l

i ES BKR l

DC POWER l

LOSS l

EVENT POINT 0679 l

l i

INDICATED CONDITION:

480V ES MCC 3AB CROSS-TIE BREAKER 3360 LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

(

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

l' DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-58 FUSE #9.

I i

i

REFERENCES:

DRAWING 208-040 MT-88 l SENSING ELEMENT: 27C/3360 AR-702 Rev. 15 Page 58

ENCLOSURE 1 (Page 58 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2 04-04 Q-04-04 ES BKR DC POWER LOSS EVENT POINT 0681 INDICATED CONDITION:

o 480V ES MCC 3A2 SUPPLY BREAKER 3351 LOSS OF DC CONTROL POWER.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

(

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-SA FUSE #9.

REFERENCES:

DRAWING 208-040 MT-46 SENSING ELEMENT: 27C/3351 AR-702 Rev. 15 Page 59

ENCLOSURE 1 (Page 59 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-04 Q-04-04 ES BKR DC POWER LOSS EVENT POINT 0765 INDICATED CONDITION:

480V ES MCC 383 SUPPLY BREAKER 3330 LOSS OF DC CONTROL POWER.

o O

REDUNDANT INDICATION WHICH WILL VE'RIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL-POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #9.

8

REFERENCES:

DRAWING 208-040 MT-116 SENSING ELEMENT: 27C/3330 AR-702 Rev. 15 Page 60

.m.__..___.m ENCLOSURE 1 (Page 60 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-04-04 Q-04-04 l

ES BKR DC POWER LOSS EVENT POINT 0766 INDICATED CONDITION:

o 480V ES MCC 3A3 SUPPLY BREAKER 3331 LOSS OF DC CONTROL POWER.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP SA FUSE #9.

b)

REFERENCES:

DRAWING 208-040 MT-113

\\/

SENSING ELEMENT: 27C/3331 l

AR-702 Rev. 15 Page 61

ENCLOSURE 1 h

(Page 61 of 111)

%s SSF ANNUNCIATOR RESPONSE S F-A2-04-04 Q-04-04 l

i ES BKR DC POWER LOSS EVENT POINT 1152 INDICATED CONDITION:

o 480V ES MCC 382 SUPPLY BREAKER 3350 LOSS OF DC CONTROL POWER.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOSS OF DC CONTROL POWER.

DISCUSSION:

DC CONTROL POWER IS SUPPLIED FROM DPDP-5B FUSE #9.

l I

[

REFERENCES:

DRAWING 208-040 MT-119 SENSING ELEMENT: 27C/3350 AR-702' Rev. 15 Page 62 l

f_NCLOSURE 1 (Page 62 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-05 Q-04-05 0

ES BREAKER

{

WITHDRAWN EVENT POINT 0573 1

4 INDICATED CONDITION:

o UNIT #3 DUMMY BREAKER WITHDRAWN.

('

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT.

DISCUSSION:

1 l-THIS BREAKER IS LOCATED IN THE "B" ES 4160V BUS SWITCHGEAR. THIS IS AN l

EXPECTED ALARM WHEN THE BREAKER IS IN THE TEST POSITION. TO RACK THIS BREAKER IN/0UT THE BACKUP ES TRANSFORMER AND ES 4160VAC BUSSES MUST BE DEENERGIZED.

THE DUMMY BREAKER HAS NO AUTOMATIC TRIP FUNCTIONS, IT ACTS TO CONNECT THE BACKUP ES TRANSFORMER FEED TO BREAKERS 3205 AND 3206 FOR THE ES 4160VAC BUSSES.

[3

REFERENCES:

DRAWING 208-040 KE-90 206-011 q)

SENSING ELEMENT: 52H/B CONTACT FOR DUMMY BREAKER.

AR-702 Rev. 15 Page 63

. ~ _

i i fq ENCLOSURE 1 j Q (Page 63 of 111)

)

l SSF ANNUNCIATOR RESPONSE SF-A2-04-05 Q-04-05 l

l

)

ES BREAKER WITHDRAWN f

EVENT POINT 0698 INDICATED CONDITION:

o "B" ES 480V BUS TRANSFORMER SUPPLY BREAKER 3220 NOT RACKED IN.

f" i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NEITHER RED NOR GREEN LIGHTS ARE ON, LOCATED ON BREAKER 3220 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT.

i DISCUSSION:

THIS IS AN EXPECTED ALARM WHEN THE BREAKER IS IN THE TEST POSITION.

l t

REFERENCES:

DRAWING 208-040 MT-24 SENSING ELEMENT: 52H/B CONTACT FOR BREAKER 3220.

AR-702 Rev. 15 Page 64

- ~ _ -

t t

l i

ENCLOSURE 1 I

(Page 64 of 111)

+

SSF ANNUNCIATOR RESPONSE SF-A2-04-05 Q-04-05 r

f l

l ES

}

BREAKER l

WITHDRAWN l

l EVENT POINT 0699 i

l INDICATED CONDITION:

l o

"A" ES 480V BUS TRANSFORMER SUPPLY BREAKER 3221 NOT RACKED IN.

I

(

k C

l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NEITHER RED NOR GREEN LIGHTS ARE ON, LOCATED ON BREAKER 3221 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT.

i DISCUSSION:

THIS IS AN EXPECTED ALARM WHEN THE BREAKER IS IN THE TEST POSITION.

i l

REFERENCES:

DRAWING 208-040 MT-25 SENSING ELEMENT: 52H/B CONTACT FOR BREAKER 3221.

AR-702 Rev. 15 Page 65

. _. _. = _ _.

I i

i l

ENCLOSURE 1 (Page 65 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-05 Q-04-05 l

ES BREAKER I

WITHDRAWN t

l EVENT POINT 0707 INDICATED CONDITION:

o "B" ES 480V BUS SUPPLY BREAKER 3310 NOT RACKED IN.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NEITHER RED NOR GREEN LIGHTS ARE ON, LOCATED ON BREAKER 3310 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

l 0 INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT.

I l

DISCUSSION:

l THIS IS AN EXPECTED ALARM WHEN THE BREAKER IS IN THE TEST POSITION.

l

REFERENCES:

DRAWING 208-040 MT-34 SENSING ELEMENT: 52H/B CONTACT FOR BREAKER 3310.

AR-702 Rev. 15 Page 66

J ENCLOSURE 1 (Page 66 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-05 Q-04-05 ES BREAKER WITHDRAWN EVENT POINT 0709 INDICATED CONDITION:

o "A" ES 480V BUS SUPPLY BREAKER 3311 NOT RACKED IN.

REDUNDANT INDICATION WHICH WILL VERIFY Al. ARM:

NEITHER RED NOR GREEN LIGHTS ARE ON, LOCATED ON BREAKER 3311 CONTROL o

STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT.

DISCUSSION:

THIS IS AN EXPECTED ALARM WHEN THE BREAKER IS IN THE TEST POSITION.

REFERENCES:

DRAWING 208-040 MT-35 SENSING ELEMENT: 52H/B CONTACT FOR BREAKER 3311.

AR-702 Rev. 15 Page 67

. ~..

1 ENCLOSURE 1 (Page 67 of 111) s.

l SSF ANNUNCIATOR RESPONSE SF-A2-04-05 Q-04-05 ES BREAKER WITHDRAWN EVENT POINT 0712 INDICATED CONDITION:

o 480V ES MCC 3AB CROSS-TIE BREAKERS 3360 AND 3361 NOT RACKED IN.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE THE CAUSE FOR BOTH BREAKERS BEING RACKED OUT.

DISCUSSION:

l l

REFERENCES:

DRAWING 208-040 MT-88, MT-89 SENSING ELEMENT: 52H/B CONTACIS FOR BREAKERS 3360 AND 3361.

1 l

AR-702 Rev. 15 Page 68

_. _ _ _ _...=._,.. _.

I ENCLOSURE 1 (Page 68 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-07 Q-04-07 1

ES MCC 3AB DEAD EVENT POINT 0697 l

INDICATED CONDITION:

i o 480V ES MCC 3AB LOSS OF VOLTAGE AS SENSED BY THE AR RELAY.

l O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l I

OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO OP-700B

[

o INVESTIGATE CAUSE FOR MCC 3AB LOSS OF VOLTAGE.

o DEPRESS PUSH-BUTTON LABELED " TRANSFER TO 480V AC ES SWGR 3A/3B" TO RESTORE POUER TO MCC.

DISCUSSION:

WHEN TRANSFER OF POWER IS COMPLETE. THE INDICATOR LIGHT _ON MCB LABELED

" LOAD TO MCC 3AB" WILL ILLUMINATE.

l

REFERENCES:

DRAWING 208-040 MT-125 SENSING ELEMENT: AR RELAY.

AR-702 Rev. 15 Page 69

i i

ENCLOSURE 1 s

I (Page 69 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-04-08 Q-04-08 l

1 l

ES MCC 3AB BREAKER OPEN EVENT POINT 0678 i

INDICATED CONDITION:

o 480V ES MCC 3AB CROSS-TIE BREAKER 3361 OPEN.

i

/^\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE FOR MCC 3AB BREAKER 3361 OPEN.

DISCUSSION:

i

REFERENCES:

, DRAWING 208-040 MT-89 SENSING ELEMENT: R/B SWITCHGEAR CONTACT FOR BREAKER 3361 AR-702 Rev. 15 Page 70

- ~ -. - -. -

ENCLOSURE 1

(

(Page 70 of 111) l l

l SSF ANNUNCIATOR RESPONSE SF-A2-04-08 Q-04-08 l

ES MCC 3AB BREAKER OPEN EVENT POINT 0680 l

INDICATED CONDITION:

o 480V ES MCC 3AB CROSS-TIE BREAKER 3360 OPEN.

(%'

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE FOR MCC 3AB BREAKER 3360 OPEN.

DISCUSSION:

REFERENCES:

DRAWING 208-040 MT-88 SENSING ELEMENT: R/B SWITCHGEAR CONTACT FOR BREAKER 3360 AR-702 Rev. 15 Page 71 i

ENCLOSURE 1 i

(Page 71 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-05-01 Q-05-01 1

I l

4KV l

l ES BUS B l

l DEAD I

l l

l l

I EVENT POINT 0651 INDICATED CONDITION:

o "B" ES 4160V BUS UNDERVOLTAGE O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o 4160V ES BUS 3B VOLTAGE INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION:

THIS ALARM IS THE RESULT OF A 2 OUT OF 3 UNDERVOLTAGE (FLUR) RELAY LOGIC.

THE FLUR RELAYS ARE INTENDED TO PROVIDE ES 4160VAC UNDERVOLTAGE RESPONSE WHEN VOLTAGE DROPS INSTANTLY TO ZERO. THE SLUR RELAY WILL PROVIDE UNDERVOLTAGE RESPONSE WHEN THE VOLTAGE DROPS GRADUALLY BELOW THE SLUR SETPOINT.

REFERENCES:

DRAWING 208-040 MT-65 SENSING ELEMENT: 27Y-3/32EA RELAY AR-702 Rev. 15 Page 72

ENCLOSURE 1 (Page 72 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-05-02 Q-05-02 l

l l

DIESEL GEN B BREAKER l

TRIP l

l 033b EVENT POINT 4574 INDICATED CONDITION:

"'/' ES 4160V BUS DIESEL GUTPUT BREAKER 3210--TMPPE&--

o b?ese\\

enera4- 0r

'Ib' Skt Salo Locko& Ackled 3

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT IS ON WITH A RED FLAG ON THE BREAKER 3210 CONTROL STATION.

l o VERIFY 86B EDG BREAKER LOCKOUT RELAY OPEN OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION: THE 86B EDG BREAKER LOCKOUT RELAY WILL TRIP AND PREVENT RECLOSURE OF THE EDG OUTPUT BREAKER FOR:

o OVERCURRENT (DEVICE 51V) o NEGATIVE SE00ENCE (DEVICE 46) o GENERATOR GROUND (DEVICE 64) o ES BUS FEEDER BREAKER OVERCURRENT (DEVICE 51B. 51 BN)

THE ACTUATION OF THE NEW 868 LOCKOUT WIL' RESULT IN THE ENGINE REMAINING RUNNING WITH THE OUTPUT BREAEER OPEN. THIS WILL REOUIRE THE ENGINE SHUTDOWN WLT_H_IN 2 HOUR.S

REFERENCES:

DRAWING 208-040 MT-14 SENSING ELEMENT: CS/SC,CS/0 EONTROL S M CONTACTS, 52H/A, 525/B[ CONTACTS es a rigsw AR-702 Rev. 15 Page 73

l i

ENCLOSURE 1

(

(Page 73 of 111) l SSF ANNUNCIATOR RESPONSE SF-A2-05-03 Q-05-03 DIESEL GEN B BREAKER CLOSED i

EVENT POINT 1186

)

INDICATED CONDITION:

)

"B" ES 4160V BUS DIESEL OUTPUT BREAKER 32I0 IS CLOSED, WITH EITHER AN ES o

i ACTUATION SIGNAL OR BUS UNDERVOLTAGE SIGNAL PRESENT i

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

RED LIGHT IS ON WITH A GREEN FLAG ON BREAKER 3210 CONTROL STATION.

o OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

DISCUSSION:

I l

l

REFERENCES:

DRAWING 208-040 MT-128, MT-129 SENSING ELEMENT: 86B/ESB AR-702 Rev. 15 Page 74 l

l

M ENCLOSURE 1 O

(Page 74 of 111)

SSF' ANNUNCIATOR RESPONSE SF-A2-05-04 Q-05-04 4KV ES B CROSS-TIE BLOCKED EVENT POINT 1187 l

INDICATED CONDITION:

o BREAKERS 3209 AND 3210 CLOSED WITH EITHER 3205, 3207, OR 3211 CLOSED.

i O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIESEL GEN "A" CROSS-TIE LIGHT EXTINGUISHED.

l o IF 3205 CLOSED THEN, BLOCK CLOSING ACTUATED 3206 LIGHT IS' ON.

l o IF 3207 CLOSED THEN, BLOCK CLOSING ACTUATED 3208 LIGHT IS ON.

j o IF 3211 CLOSED THEN, BLOCK CLOSING ACTUATED 3212 LIGHT IS ON.

j l

OPERATOR ACTIONS FOR A VALID ALARM:

I DISCUSSION:

1 i

REFERENCES:

DRAWING 208-040 MT-127, MT-129 SENSING ELEMENT: 3-52-2, 3-525 CONTACTS l

AR-702 Rev. 15 Page 75

_ _. _ _ _ _ _ _ _. _. _ - _. ~.

l l

l l

ENCLOSURE 1 l.g (Page 75 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-05-05 Q-05-05 DIESEL GEN B VOLTAGE ADJ IN CONTROL RM i

EVENT POINT 1178 INDICATED CONDITION:

o DIESEL GENERATOR "B" VOLTAGE ADJUST SELECTED TO THE CONTROL ROOM.

J i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIESEL GENERATOR B "EXC VOLT ADJ SELECT" SWITCH SELECTED TO " CONT RM" POSITION.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS SWITCH IS NORMALLY SELECTED TO THE "DG RM" POSITION.

REFERENCES:

DRAWING 208-027 EG-18 SENSING ELEMENT:.SS/0,CB/SSF CONTACT AR-702 Rev. 15 Page 76

e ENCLOSURE 1 i

(Page 76 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-05-07 Q-05-07 480V ES BUS B DEAD EVENT POINT 0655 INDICATED CONDITION:

o "B" 480V BUS UNDERVOLTAGE.

(~.

(/

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o 480V ES BUS "B" VOLTAGE INDICATES LESS THAN NORMAL.

l OPERATOR ACTIONS FOR A VALID ALARM:

i o REFER TO AP-770 DISCUSSION:

REFERENCES:

DRAWING 208-040 MT-66 SENSING ELEMENT: 27Y-1/33EB AR-702 Rev. 15 Page 77

ENCLOSURE 1 (Page 77 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-05-08 Q-05-08 480V i

ES BUS B i

UV LOCKOUT ACT EVENT POINT 0722 1

INDICATED CONDITION:

"B" ES 480V BUS UNDERVOLTAGE LOCK OUT RELAY ACTUATED.

o j

f) l U

t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o 4160V ES BUS B VOLTAGE INDICATES LESS THAN NORMAL.

o 480V ES BUS B VOLTAGE INDICATES LESS THAN NORMAL.

o BREAKER 3210 INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770 DISCUSSION:

THE 480V ES UNDERVOLTAGE LOCK OUT RELAY IS ACTUATED WHEN, EITHER THE 'B' DIESEL OUTPUT BREAKER IS CLOSED, OR 4160V ES BUS B UNDERVOLTAGE OCCURS l

WITH AN ES ACTUATION.

REFERENCES:

DRAWING 208-040 MT-79 SENSING ELEMENT: 86/27ESB AR-702 Rev. 35 Page 78

4 W

ENll.05URE 1

(

(Page 78 of 111)

SSF ANNUNCIATOR RESPONSE

.SF-A2-06-01 Q-06-01 rrrr y

r I

I I

I l

l DIESEL GEN B l

l lN TIE 30 MIN LIMIT I

I I

I I

I I

I EVENT POINT 1996 INDICATED CONDITION:

i o DIESEL GENERATOR "B" OVER 3250 KW.

I O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIESEL GENERATOR "B" KW INDICATION.

o DIESEL GENERATOR "B" "EDG-3B ELAPSED TIME IN 30 MIN RATING." TIMER OPERATING.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770.

o REDUCE LOAD IF SURVEILLANCE TESTING.

DISCUSSION:

THIS ALARM IS INSTANTANEOUS WHEN DIESEL LOAD EXCEEDS 3250 K

REFERENCES:

DRAWING 208-027 EG-21 SENSING ELEMENT: 62BX AR-702 Rev. 15 Page 79 l

I

(

ENCLOSURE 1 (Page 79 of 111)

SSF ANNUNCIATOR IIESPONSE SF-A2-06-04 Q-06-04 f

I 4KV ES B UNDERVOLTAGE TRIP BLOCKED L

EVENT POINT 0824 INDICATED CONDITION:

o "B" ES 4160V BUS UNDERVOLTAGE PROTECTION DISABLED.

/

i REDUNDANT INDICATION WHICH WLL VERIFY ALARM:

TRIP BLOCK SWITCHES, TBS 1 Aim TBS 2, LOCATED IN MTCP-1B IN THE 4160V ES "B" l

SWITCHGEAR ROOM ARE IN OPEli POSITION.

l OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR "B" ES BUS VOLTAGS DURING UNDERVOLTAGE RELAY TESTING.

l DISCUSSION:

l l

THIS ALARM WILL OCCUR WHEN TESTING THE BUS UNDERVOLTAGE RELAYS.

NO UNDER-I VOLTAGE PROTECTION IS AVAIUBLE DURING TESTING.

REFERENCES:

DRAWING 208-040 E-65B SENSING ELEMENT: TBS 1, TBS 2 AR-702 Rev. 15 Page 80 l

i ENCLOSURE 1 (Page 80 of 111)

SSF ANNUNCIATOR RESPONSE l

S F-A2-07-01 Q-07-01 l

l

\\

l I

i l

i l

j B/U ES XFMR l

l FAULT l

l l

I I

I I

I I

EVENT POINT 0727 l

INDICATED CONDITION:

o BACKUP ES TRANSFORMER PRIMARY PROTECTION ALARM BACKUP ES TRANSFORMER PHASE DIFFERENTIAL LOCK-0UT RELAY, 86TBEST-1, HAS o

' V( N ACTUATED DUE TO A DIFFERENCE IN CURRENT ON THE INDIVIDUAL PHASES AS SENSED BY RELAYS 87TBEST-4A, 87TBEST-48, OR 87TBEST-4C REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCKOUT BREAKER 3103 BREAKER 3203 BREAKER 3205 BREAKER 1691 BREAKER 3104 BREAKER 3204 BREAKER 3206 BREAKER 1692 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY FOLLOWING BREAKERS OPEN BREAKER 3103 BREAKER 3203 BREAKER 3205 BREAKER 1691 BREAKER 3104 BREAKER 3204 BREAKER 3206 BREAKER 1692 l

DISCUSSION:

THIS IS AN INDICATION OF A PHASE IMBALANCE ON THE BACKUP ES TRANSFORMER.

l THE LOCK-0UT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED i

TRANSFORMER.

REFERENCES:

DRAWING 208-040 MT-139 SENSING ELEMENT: 86TBEST-1, 87TBEST-4A, 87TBEST-48, 87TBEST-4C AR-702 Rev. 15 Page 81 I

l l

l l

l ('

ENCLOSURE 1 l (

(Page 81 of 111) l SSF ANNUNCIATOR RESPONSE SF-A2-07-01 Q-07-01 l

t I

l 1

I l

l B/U ES XFMR l

1 l

FAULT

)

I I

4 l

l l

l l

I I

EVENT POINT 0728 INDICATED CONDITION:

o BACKUP ES TRANSFORMER SUDDEN PRESSURE RELAY, 86SPBEST-1 AND/OR NEUTRAL GROUND & GROUND DIFFERENTIAL RELAY, 86TNGDBEST-1 HAVE ACTUATED

[

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCKOUT BREAKER 3103 BREAKER 3203 BREAKER 3205 BREAKER 1691 BREAKER 3104 BREAKER 3204 BREAKER 3206 BREAKER 1692 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYST:M DISPATCHER o VERIFY FOLLOWING BREAKERS OPEN BREAKER 3103 BREAKER 3203 BREAKER 3205 BREAKER 1691 BREAKER 3104 BREAKER 3204 BREAKER 3206 BREAKER 1692 DISCUSSION:

THIS IS INDICATION OF A FLASH OVER OR AN INTERNAL GROUND ON THE BACKUP ES

-l TRANSFORMER. THE LOCK 0UT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

()s k

REFERENCES:

DRAWING 208-040 MT-137, 138 l

SENSING ELEMENT: 27C/86TNGDBEST-1, 86SPBEST-1, 51TN, 87GN, 63FPX i

AR-702 Rev. 15 Page 82

I ENCLOSURE 1 l

O (Page 82 of 111)

N)

SSF ANNUNCIATOR RESPONSE SF-A2-07-02 Q-07-02

's BREAKER 1691/1692 i

OPEN

)

EVENT POINT 0855 I

INDICATED CONDITION:

I o BREAKER 1692 IS OPEN O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 o GREEN LIGHT IS ON, LOCATED ON THE BREAKER 1692 CONTROL STATION 1

OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT UNITS 1 & 2 o CONTACT SYSTEM DISPATCHER DISCUSSION:

i THIS IS A NORMAL ALARM WHEN THE BREAKER IS NOT CLOSED. ONE OF THE FEEDER g

BREAKERS BEING OPENED ON THE START-UP TRANSFORMERS MAY PRESENT AN OFFSITE p

POWER AVAILABILITY CONCERN REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

,.~

REFERENCES:

DRAWING 229-102 SENSING ELEMENT: AUXILIARY CONTACT 52a 5/5c AR-702 Rev. 15 Page 83

ENCLOSURE 1

/.g

% ))

(Page 83 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-07-02 Q-07-02 i

BREAKER 1691/1692 OPEN I

EVENT POINT 0860 1

INDICATED CONDITION:

o BREAKER 1692 GROUND FAULT LOCK-0VT RELAY 86FDM HAS ACTUATED, DUE TO CURRENT ON THE NEUTRAL / GROUND SENSED BY RELAY SOC /M 3

(O j

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-0UT l

DREAKER 3103 BREAKER 3104 BREAKER 3203 BREAKER 3204 l

BREAKER 3205 BREAKER 3206 BREAKER 1691 BREAKER 1692 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE BREAKER 1691 HAS UPENED o VERIFY THE OPERATION OF THE FOLLOWING LOCK-0UT RELAYS:

86/FDM 86/PL4 86BU/PL4 86/BBB T

o VERIFY ALL FEEDER BREAKERS FROM STARTUP TRANSFORMER ARE OPEN.

BREAKER 3103 BREAKER 3104 BREAKER 3203 BREAKER 3204 BREAKER 3205 BREAKER 3206 DISCUSSION:

THIS IS INDICATION OF A GROUND ON THE NEUTRAL FOR BREAKER 1692. THE LOCK-0UT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE i

TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

REFERENCES:

DRAWING 229-103 SENSING ELEMENT: 50G/M, 86/FDM AR-702 Rev. 15 Page 84 l

l

1 i

ENCLOSURE 1 (Page 84 of 111) i N i

I SSF ANNUNCIATOR RESPONSE SF-A2-07-02 l Q-07-02 i

l BREAKER 1691/1692 OPEN l

EVENT POINT 0861 INDICATED CONDITION:

o BREAKER 1691 IS OPEN REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT IS ON, LOCATED ON THE BREAKER 1691 CONTROL STATION.

l OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT UNITS 1 & 2 o CONTACT SYSTEM DISPATCHER DISCUSSION:

THIS IS A NORMAL ALARM WHEN THE BREAKER IS NOT CLOSED. ONE OF THE FEEDER BREAKERS BEING OPENED ON THE START-UP TRANSFORMERS MAY PRESENT AN OFFSITE POWER AVAILABILITY CONCERN.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 104 SENSING ELEMENT: AUXILIARY CONTACT 52a 5/Sc h

'AR-702 Rev. 15 Page 85 1

ENCLOSURE 1 (Page 85 of 11D SSF ANNUNCIATOR RESPONSE lSF-A2-07-03 Q-07-03 l

l BACKUP ES XFMR MAJOR ALARM l

EVENT POINT 0631 INDICATED CONDITION:

o BACKUP ES TRANSFORMER PRESSURE RELIEF DEVICE HAS ACTUATED DUE TO A PRESSURE >10 PSIG AS SEMSED BY DEVICE 63 PR O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL PRESSURE INDICATOR l

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL BEST TRANSFORMER OIL PUMPS AND FANS ARE OPERATING o VERIFY TRANSFORMER TEMPERATURES ARE NORMAL o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

H THIS ALARM IS INDICATIVE OF A FAULT INTERNAL TO THE TRANSFORMER, THE LOAD ON THE TRANSFORMER SHOULD BE REDUCED AS MUCH AS POSSIBLE

REFERENCES:

DRAWING 208-040 MT-140, MT-138 SENSING ELEMENT: 63PR, 86SPBEST-1 AR-702 Rev. 15 Page 86

ENCLOSURE 1 1

(Page 86 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-07-03 Q-07-03 BACKUP ES XFMR MAJOR ALARM EVENT POINT 0857 INDICATED CONDITION:

o BACKUP ES TRANSFORMER OIL LEVEL LOW O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o CHECK TRANSFORMER FOR OIL ! AKAGE DISCUSSION:

I

REFERENCES:

DRAWING 208-040 MT-140 SENSING ELEMENT: 71Q AR-702 Rev. 15 Page 87

ENCLOSURE 1 (Page 87 of 111)

J SSF ANNUNCIATOR RESPONSE SF-A2-07-03 Q-07-03 BACKUP ES XFMR MAJOR ALARM EVENT POINT 1813 INDICATED CONDITION:

o BACKUP ES TRANSFORMER TEMPERATURE HIGH DUE TO EITHER OIL TEMPERATURE

>90*C AS SENSED BY DEVICE 26Q OR WINDING TEMPERATURE >IO5*C AS SENSED BY DEVICE 49 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

LOCAL INDICATING GAGES FOR OIL TEMPERATURE AND WINDING TEMPERATURE o

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY ALL BACKUP ES TRANSFORMER OIL PUMPS AND FANS OPERATING o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD DISCUSSION:

THIS IS INDICATIVE OF A PROBLEM WITH THE TRANSFORMER COOLING SYSTEM CONSIDERATION SHOULD BE GIVEN TO REDUCING THE LOAD ON'THE TRANSFORMER.

REFERENCES:

DRAWING 208-40 MT-140 SENSING ELEMENT: 2tiQ AR-702 Rev. 15 Page 88

l l

ENCLOSURE 1 (Page 88 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-07-04 Q-07-04 l

BACKUP ES XFMR MINOR ALARM i

i EVENT POINT 1151 l

t INDICATED CONDITION:

BACKUP ES TRANSFORMER LOSS OF COOLING / GAS CONTROL o

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i i

o LOCAL FLOW INDICATION t

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o VERIFY BEST TRANSFORMER OIL PUMP & FANS OPERATING DISCUSSION:

REFERENCES:

DRAWING 208-040 MT-140 SENSING ELEMENT: 74TDOE, 63C, 63RG, 63LG AR-702 Rev. 15 Page 89

l ENCLOSURE 1 (Page 89 of 111)

]

SSF ANNUNCIATOR RESPONSE SF-A2-07-04 Q-07-04 l

i BACKUP ES XFMR MINOR ALARM i

EVENT POINT 1153 INDICATED CONDITION:

o BACKUP ES TRANSFORMER LOSS OF AUXILIARY AC POWER l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l t

t OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER t

DISCUSSION THE TRANSFORMER SHOULD CONTINUE TO BE FUNCTIONAL ON THE NORMAL POWER SUPPLY

REFERENCES:

DRAWING 208-040 MT-140 SENSING ELEMENT: 27-1, 27-2, 27-3 AR-702 Rev. 15 Page 90

~ -. _.

ENCLOSURE 1 I

(Page 90 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-07-05 Q-07-05 i

BREAKER 1692 TROUBLE EVENT POINT 0856 INDICATED CONDITION:

i o BREAKER 1692 LP AIR SYSTEM PRESSURE IS LOW l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

)

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER DISCUSSION:

BREAKER 1692 IS A 230KV AIR OPERATED (ATB) TYPE OF BREAKER.

THIS ALARM INDICATES THE BREAKER 1692 AIR OPERATING SYSTEM LP AIR PRESSURE IS BELOW NORMAL, AND THEREFORE LARGE AIR LEAKS, OR COMPRESSOR / COMPRESSOR CONTROL FAILURES ARE PROBABLE.

OPERATING BREAKER 1692 SEVERAL TIMES IN A BRIEF PERIOD OF TIME CAN USE MORE AIR THAN THE RATE AT WHICH THE COMPRESSOR CAN MAINTAIN.

REFERENCES:

DRAWING 229-102; DRAWING S171 (SUBSTATION)

SENSING ELEMENT: 63AL AR-702 Rev. 15 Page 91

_...... - _ - ~

l ENCLOSURE 1 i

g (Page 91 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-07-0 5 Q-07-05 l

BREAKER 1692 TROUBLE i

l EVENT POINT 0859 l

i l

INDICATED CONDITION:

j o BREAKER 1692 HP AIR SYSTEM PRESSURE IS LOW i

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM.

o NOTIFY SYSTEM DISPATCHER j

DISCUSSION:

BREAKER 1692 IS A 230KV AIR OPERATED (ATB) TYPE OF BREAKER.

l l

THIS ALARM INDICATES THE BREAKER 1692 AIR OPERATING SYSTEM LP AIR PRESSURE i

IS BELOW NORMAL, AND THEREFORE LARGE AIR LEAKS, OR COMPRESSOR / COMPRESSOR CONTROL FAILURES ARE PROBABLE.

i l

i OPERATING BREAKER 1692 SEVERAL TIMES IN A BRIEF PERIOD OF TIME CAN USE MORE AIR THAN THE RATE AT WHICH THE COMPRESSOR CAN MAINTAIN.

)

v

REFERENCES:

DRAWING 229-102; DRAWING S171 (SUBSTATION)

SENSING ELEMENT: 63AH AR-702 Rev. 15 Page 92

t ENCLOSURE 1 b(N (Page 92 of 111) r SSF ANNUNCIATOR RESPONSE SF-A2-07-05 Q-07-05 BREAKER 1692 TROUBLE l

i EVENT POINT 0866 INDICATED CONDITION:

o BREAKER 1692 AIR COMPRESSOR RUN TIME EXCESSIVE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER DISCUSSION:

BREAKER 1692 IS A 230KV AIR OPERATED (ATB) TYPE OF BREAKER.

THIS ALARM INDICATES THE BREAKER 1692 AIR OPERATING SYSTEM AIR COMPRESSOR l

HAS BEEN RUNNING LONGER THAN NORMAL, AND THEREFORE LARGE AIR LEAKS OR l

FAILURES ARE PROBABLE. THE COMPRESSOR IS USED FOR MAINTAINING THE HIGH PRESSURE RESERVOIR ABOVE THE HP AIR MINIMUM PRESSURE SETPOINT.

OPERATING BREAKER 1692 SEVERAL TIMES IN A BRIEF PERIOD OF TIME CAN USE MORE AIR THAN THE RATE AT WHICH THE COMPRESSOR CAN MAINTAIN.

I

(

REFERENCES:

DRAWING 229-102; DRAWING S171 (SUBSTATION) v SENSING ELEMENT: COMPRESSOR CONTROLLER AR-702 Rev. 15 Page 93

i ENCLOSURE 1 e

(Page 93 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-07-06 Q-07-06 f

i PLANT LINE 4 FAULT i

EVENT POINT 0858 i

l INDICATED CONDITION:

PLANT LINE 4 PRIMARY DIFFERENTIAL LOCK-0UT RELAY 86/PL4 HAS ACTUATED, o

DUE TO CURRENT DIFFERENTIAL ON THE PRIMARY SIDE OF THE STARTUP AND BEST TRANSFORMER AS SENSED BY 87PL44A, 87PL448, OR 87PL44C li O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-0UT BREAKER 3103 BREAKER 3104 BREAKER 3203 BREAKER 3204 BREAKER 3205 BREAKER 3206 BREAKER 1691 BREAKER 1692 OPERATOR ACTIONS FOR A VALID ALARM:

VERIFY THE OPERATION OF THE LOCK OUT RELAYS 86/PL4, 86X/PL4 o

o ENSURE THAT ALL FEEDER BREAKERS FROM THE STARTL'P AND 'BEST' TRANSFORMERS ARE OPEN.

l DISCUSSION:

THIS IS INDICATION OF A FAULT ON THE INCOMING 230KV LINE TO THE STARTUP AND BEST TRANSFORMERS. THE LOCK-OUT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE TRANSFORMERS, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

f(

REFERENCES:

DRAWING 207-012, 229-107 SENSING ELEMENT: RELAY 86BU/PL4-1, 86BU/PL4-2, 87 AUX-$A, 87 AUX-4B, 87 AUX-$C AR-702 Rev. 15 Page 94

ENiCLOSURE 1 (Page 94 of 111)

]

SSF ANNUNCIATOR RESPONSE S F-A2-07-06 Q-07-06 t

l l

PLANT LINE 4 FAULT i

EVENT POINT 0862 INDICATED CONDITION:

i o PLANT LINE 4 BACK-UP DIFFERENTIAL LOCK-0UT RELAY 86BU/PL4 HAS ACTUATED, j

DUE TO AN OVER CURRENT ON THE PRIMARY SIDE OF THE STARTUP AND BEST TRANSFORMERS AS SENSED BY 87AUXtA, 87AUXtB, OR 8 AUX 4tC O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-0UT BREAKER 3103 BREAKER 3104 BREAKER 3203 BREAKER 3204 BREAKER 3205 BREAKER 3206 BREAKER 1691 BREAKER 1692 l

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY THE OPERATION OF THE LOCK OUT RELAYS 86BU/PL4, 8680/PL4

{

ENSURE THAT ALL FEEDER BREAKERS FROM THE STARTUP AND 'BEST' TRANSFORMERS 1

o ARE OPEN.

DISCUSSION:

THIS IS INDICATION OF A FAULT ON THE INCOMING 230KV LINE TO THE STARTUP AND BEST TP.ANSFORMER..THE LOCK-0UT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE TRANSFORMERS, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

O Q

REFERENCES:

DRAWING 207-012, 229-107 i

SENSING ELEMENT: RELAY 8680/PL4-1, 86BU/PL4-2, 87 AUX-4A, 87 AUX-48, 87 AUX-$C AR-702 Rev. 15 Page 95 1

ENCLOSURE 1 (Page 95 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-07-07 Q-07-07 6

230KV l

GRID DEGRADING EVENT POINT 0827 INDICATED CONDITION:

o 4160V ES BUS 3A VOLTAGE IS < 4019 VAC FOR >2 SECS AS SENSED BY RELAY 275LUA/32EA 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l "A" ES 4160V BUS VOLTAGE METER INDICATING < 4019 VAC I

o OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER TO INCREASE GRID VOLTAGE DISCUSSION:

THIS ALARM IS INTENDED TO ALERT OPERATORS OF AN IMPENDING DEGRADED VOLTAGE (SLUR) CONDITION IN THE 230KV GRID. THIS CONDITION IS A PRECURSOR TO A DEGRADED VOLTAGE TRIP OF THE "A" ES 4160V BUS.

ALARM RESET SHOULD OCCUR BETWEEN 4038 AND 4058 VOLTS AC.

AC

REFERENCES:

DRAWING 208-040 SHEET MT-131 i

SENSING ELEMENT: RELAY 275LUA/32EA AR-702 Rev. 15 Page 96

r I

l ENCLOSURE 1 (Page 96 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-07-07 Q-07-07 I

230KV GRID DEGRADING l

l EVENT POINT 0828 INDICATED CONDITION:

o 4160V ES BUS 3B VOLTAGE IS < 4019 VAC FOR >2 SECS AS SENSED BY RELAY l

275LUB/32EB lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

"B" ES 4160V BUS VOLTAGE METER INDICATING < 4019 VAC o

i OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER TO INCREASE GRID VOLTAGE DISCUSSION THIS ALARM IS INTENDED TO ALERT OPERATORS OF AN IMPENDING DEGRADED VOLTAGE l

(SLUR) CONDITION IN THE 230KV GRID. THIS CONDITION IS A PRECURSOR TO A i

DEGRADED VOLTAGE TRIP OF THE "B" ES 4160V BUS.

ALARM RESET SHOULD OCCUR BETWEEN 4038 AND 4058 VOLTS AC.

(

REFERENCES:

DRAWING 208-040 SHEET MT-132 SENSING ELEMENT: RELAY 275LUB/32EB AR-702 Rev. 15 Page 97

P ENCLOSURE 1 (Page 97 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-01 Q-08-01 I

rrr_rrm l

l l

I l

l OFFSITE PWR l

l SOURCE XFMR I

l FAULT I

I I

I I

I EVENT POINT 0777 INDICATED CONDITION:

0FFSITE POWER TRANSFORMER GROUND FAULT LOCK-0UT RELAYS 71T9TD, 78D9, o

71T9TN HAS ACTUATED, DUE TO CURRENT ON THE NEUTRAL / GROUND SENSED BY RELAY SON, SOAN, OR SOAM.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-0UT BREAKER 4900 BREAKER 4902 BREAKER 3211 BREAKER 3212 OPERATOR ACTIONS FOR A VALID ALARM:

ENSURE THAT FEEDER AND LOAD BREAKERS FROM OFFSITE POWER TRANSFORMER ARE

{

o OPEN.

BREAKER 4900 BREAKER 4902 BREAKER 3211 BREAKER 3212 l

?

DISCUSSION:

j THIS IS INDICATION OF AN INTERNAL GROUND ON THE OFFSITE POWER TRANSFORMER.

l THE LOCK-0UT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

i:

REFERENCES:

DRAWING 208-079 SHEET SB-18 SENSING ELEMENT: RELAYS SON SOAN SOAM AR-702 Rev. 15 Page 98 i

i

l I

ENCLOSURE 1 (Page 98 of 111)

\\ a j

SSF ANNUNCIATOR RESPONSE S F-A2-08-01 Q-08-01 rrrrrrm l

l I

I l

l OFFSITE PWR l

l SOURCE XFMR l

l FAULT I

I L

I I

I I

l EVENT POINT 2043 l

INDICATED CONDITION:

l o 0FFSITE POWER TRANSFORMER LOCK-0UT RELAYS 71T95P, 7BOC9 HAVE ACTUATED, DUE TO DETECTION OF A SUDDEN PRESSURE RISE, OR A PHASE DIFFERENTIAL AS SENSED BY DEVICE SOM, AND SOAD i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-OUT BREAKER 4900 BREAKER 4902 BREAKER 3211 BREAKER 3212 OPERATOR ACTIONS FOR A VALID ALARM:

o Ei450RE THAT FEEDER AND LOAD BREAKERS FROM OFFSITE POWER TRANSFORMER ARE OPJN.

BREAKER 4900 BREAKER 4902 BREAKER 3211 BREAKER 3212 i

DISCUSSION:

L THIS IS INDICATION OF A FLASH OVER ON THE OFFSITE POWER TRANSFORMER. THE LOCK-0UT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE I

TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

REFERENCES:

DRAWING 208-079 SHEET 58-18 l

SENSING ELEMENT: RELAYS SOAD, 50M i

AR-702 Rev. 15 Page 99 l

l l

ENCLOSURE 1

, [J (Page 99 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-08-02 Q-08-02 1

BREAKER 4900/4902 TRIP r

i EVENT POINT 1103 INDICATED CONDITION:

t i

o 0FF SITE POWER TRANSFORMER PROTECTIVE LOCKOUT RELAY 7BDA-PRI, AND/OR 7BDA-BU HAVE ACTUATED lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-0UT BREAKER 4900 BREAKER 4902 BREAKEP, 3211 BREAKER 3212 I

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770 o VERIFY FEEDER AND LOAD BREAKERS FROM OFFSITE POWER TRANSFORMER OPEN o NOTIFY SYSTEM DISPATCHER DISCUSSION:

I-THIS IS INDICATION OF A FAULT ON THE OFFSITE POWER TRANSFORMER. THE LOCK-l OUT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF OF THE l

TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

REFERENCES:

DRAWING 208-079 SHEET SB-18 SENSING ELEMENT: RELAY 49M/7BDA-PRI, 49N/7BDA-BU AR-702 Rev. 15 Page 100

T ENCLOSURE 1 (Page 100 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-02 Q-08-02 BREAKER 4900/4902 TRIP J

EVENT POINT 1104 INDICATED CONDITION:

o 0FF SITE POWER TRANSFORMER PROTECTIVE LOCKOUT RELAY 7BDB-PRI, AND/OR 7BDB-BU HAVE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THE FOLLOWING BREAKERS WILL AUTOMATICALLY TRIP AND LOCK-0UT BREAKER 4900 BREAKER 4902 BREAKER 3211 BREAKER 3212 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770 o VERIFY FEEDER AND LOAD BREAKERS FROM OFFSITE POWER TRANSFORMER OPEN o NOTIFY SYSTEM DISPATCHER DISCUSSION:

l l

THIS IS INDICATION OF A FAULT ON THE OFFSITE POWER TRANSFORMER. THE LOCK-l OUT RELAY ACTUATES TO STRIP THE POWER FEED AND THE LOADS OFF 0F THE TRANSFORMER, AND TO PREVENT CLOSING IN A BREAKER ON A FAULTED TRANSFORMER.

REFERENCES:

DRAWING 208-079 SHEET 58-18 SENSING ELEMENT: RELAY 49AM/7BDB-PRI, 49AN/7BDB-BU AR-702 Rev. 15 Page 101

~

6 ENCLOSURE 1 (Page 101 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-02 Q-08-02 BREAKER

{

4900/4902 TRIP l

t EVENT POINT 1132 9

L INDICATED CONDITION:

o 0FFSITE POWER TRANSFORMER BREAKER 4900 HAS AUTO TRIPPED l'

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o GREEN BREAKER STATUS LIGHT WILL BE ON l

l OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY BREAKER POSITION o REFER TO AP-770 o NOTIFY SYSTEM DISPATCHER l

l DISCUSSION:

l ONE OF THE FEEDER BREAKERS BEING OPEN ON THE OFFSITE POWER TRANSFORMER MAY l

PRESENT AN OFFSITE POWER AVAILABILITY CONCERN; REFER TO TS FOR l

ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

229-109 1

SENSING ELEMENT: 52b/4900, CS/0, CS/SC h

AR-702 Rev. 15 Page 102 l

ENCLMURE 1 (Page 102 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-08-02 Q-08-02 I

BREAKER 4900/4902 TRIP i

EVENT POltiB0 4

1 INDICATED CONDITION:

i l

o 0FFSITE POWER TRANSFORMER BREAKER 4902 HAS AUTO TRIPPED l

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o GREEN BREAKER STATUS LIGHT WILL BE ON l

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY BREAKER POSITION o REFER TO AP-770 j

1 o NOTIFY SYSTEM DISPATCHER l

DISCUSSION:

ONE OF THE FEEDER BREAKERS BEING OPEN ON THE OFFSITE POWER TRANSFORMER MAY PRESENT AN OFFSITE POWER AVAILABILITY CONCERN; REFER TO TS FOR t

ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

229-110 SENSING ELEMENT: 52b/4902, CS/0, CS/SC AR-702 Rev. 15 Page 103

l ENCLOSURE 1 (Page 103 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-03 Q-08-03 l

l OFFSITE PWR SOURCE XFMR i

MAJOR ALARM l

l l

l EVENT POINT 1337 l

INDICATED CONDITION:

l o 0FFSITE POWER TRANSFORMER PRESS RELIEF DEVICE HAS ACTUATED, DUE TO A l

PRESSURE >10 PSIG AS SENSED BY DEVICE 63PR lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL PRESSURE INDICATOR l

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER l

o REFER TO OP-703 t

l DISCUSSION:

THIS ALARM IS I.NDICATIVE OF A FAULT INSIDE THE TRANSFORMER, Tile LOAD ON g

A' THE TRANSFORMER SHOULD BE REDUCED AS MUCH AS POSSIBLE.

REFERENCES:

DRAWING 208-079 SHEET SB-018 l

SENSING ELEMENT: DEVICE 63PR AR-702 Rev. 15 Page 104

l r

ENCLOSURE 1 f)

(Page 104 of 111)

G SSF ANNUNCIATOR RESPONSE S F-A2-08-03 Q-08-03 OFFSITE PWR l

SOURCE XFMR l

MAJOR ALARM i

f EVENT POINT 1423 INDICATED CONDITION:

o 0FFSITE POWER TRANSFORMER TEMPERATURE HIGH DUE TO EITHER OIL TEMPERATURE

>90*C AS SENSED BY DEVICE 26Q OR WINDING TEMPERATURE >110 C AS ECNSED BY DEVICE 49 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL INSTRUMENTS FOR WINDING AND OIL TEMPERATURE I

l OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER l

o_ VERIFY ALL OFFSITE F9WER TRANSFORMER OIL PUMPS AND FANS OPERATING o CONSIDERATION SHOULD BE GIVEN TO REDUCE ELECTRICAL LOAD o REFER TO OP-703 l

DISCUSSION:

j THIS IS INDICATIVE OF A PROBLEM WITH THE TRANSFORMER COOLING SYSTEM CONSIDERATION SHOULD BE GIVEN TO REDUCING THE LOAD ON THE TRANSFORMER.

THE FANS WILL AUTO START AT 70*C, THE FANS AND PUMP AUTO START AT 80*C.

j REFEP.ENCES:

DRAWING 208-079 SHEET SB-018 SENSING ELEMENT: 26Q, 49 AR-702 Rev. 15 Page 105 i

I i

I

r ENCLOSURE 1 (Page 105 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-03 Q-08-03 OFFSITE POWER SOURCE XFMR l

MAJOR ALARM EVENT POINT 1527 INDICATED CONDITION:

o 0FFSITE POWER SOURCE XFMR LOW OIL LEVEL t

L j

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL LEVEL INSTRUMENT OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER o REFER TO OP-703 DISCUSSION:

o SEND OPERATOR TO SWITCHYARD TO CHECK FOR POSSIBLE LEAK & GET READINGS FROM LOCAL INSTRUMENTATION.

?(j

REFERENCES:

208-079 - SB-18 SENSING ELEMENT: T9AL(71Q)

AR-702 Rev. 15 Page 106 i

._=

.~..

. - ~ -.

ENCLOSURE 1 (Page 106 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-08-04 Q-08-04 i

OFFSITE PWR SOURCE XFMR MINOR ALARM EVENT POINT 0496 INDICATED CONDITION:

o 0FFSITE POWER TRANSFORMER HAS EXPERIENCED A LOSS OF 480V AUXILIARY POWER AS SENSED BY T9AL(27) VOLTAGE RELAY g

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY THE SYSTEM DISPATCHER l

DISCUSSION:

THIS CONDITION SHOULD NOT CAUSE ANY CONCERN, AS THERE IS A BACK UP POWER SUPPLY AS WELL AS A NORMAL POWER SUPPLY. THE TRANSFORMER SHOULD CONTINUE j

TO BE FUNCTIONAL.

l

\\

REFEPENCES:

DRAWING 208-079 SHEET SB-018 SENSING ELEMENT: T9AL(27)

AR-702 Rev. 15 Page 107

. -. ~.

l ENCLOSURE 1 (Page 107 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-04 Q-08-04 W

i OFFSITE PWR l

SOURCE XFMR l

MINOR ALARM t

l I

l EVENT POINT 0797 l

INDICATED CONDITION:

l l

o 0FFSITE POWER TRANSFORMER COOLING FANS, OR OIL PUMPS ARE NOT RUNNING AS l

REQUIRED BY THE TEMPERATURE SWITCHES. AS SENSED BY T9AL(74/TDOE)

.lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o LOCAL OBSERVATION OF COOLING FANS AND OIL PUMP I-OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY THE SYSTEM DISPATCHER o REDUCE LOAD ON THE TRANSFORMER o START ALL PUMPS AND FANS IN MANUAL o REFER TO OP-703 l

DISCUSSION:

l l

THIS CONDITION COULD CAUSE AN OVERHEATING PROBLEM WITH THE TRANSFORMER, i

CONSIDEPATIONS SHOULD BE GIVING TO UNLOADING THE TRANSFORMER UNTIL THE PROBLEM IS CORRECTED.

REFERENCES:

DRAWING 208-079 SHEET SB-018 SENSING ELEMENT: T9AL(74/TDOE)

AR-702 Rev. 15 Page 108 F

ENCLOSURE 1 (Page 108 of 111) v SSF ANNUNCIATOR RESPONSE SF-A2-08-05 Q-08-05 1

J t

i BREAKER 4900/4902 TROUBLE

)

EVENT POINT 0146 1

i INDICATED CONDITION:

l o BREAKER 4900 FAILED TO TRIP OPEN J

s REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

j o BREAKER 4900 IS CLOSED OPERATOR ACTIONS FOR A VALID ALARM:

o OPEN BREAKER 4900 o NOTIFY SYSTEM DISPATCHER DISCUSSION:

i l

REFERENCES:

DRAWING 208-079, SB-18 SENSING ELEMENT: BF4900 l

AR-702 Rev. 15 Page 109 l

l

LNCLOSURE 1 (Page 109 of 111)

SSF ANNUNCIATOR RESPONSE S F-A2-08-05 Q-08-05 l

BREAKER 4900/4902 TROUBLE EVENT POINT 0147

{

INDICATED CONDITION:

o BREAKER 4902 FAILED TO TRIP OPEN i

i O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o BREAKER 4902 IS CLOSED OPERATOR ACTIONS FOR A VALID ALARM:

o OPEN BREAKER 4902 o NOTIFY SYSTEM DISPATCHER DISCUSSION:

l

REFERENCES:

DRAWING 209-079, SB-18 SENSING ELEMENT: BF4902 AR-702 Rev. 15 Page 110 l

~,

ENCLOSURE 1 (Page 110 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-05 Q-08-05 l

l l

l BREAKER 4900/4902 TROUBLE l

EVENT POINT 1883 i

INDICATED CONDITION:

l o BREAKER 4900 LOW CAS/ SPRING CHARGE l

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l l

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER l.

l DISCUSSION:

t i

REFERENCES:

DRAWING 229-109 AV SENSING ELEMENT: 48EE, 48FF AR-702 Rev. 15 Page 111 l

ENCLOSURE 1 (Page 111 of 111)

SSF ANNUNCIATOR RESPONSE SF-A2-08-05 Q-08-05 i

BREAKER 4900/4902 TROUBLE j

)

EVENT POINT 1891 INDICATED CONDITION:

o BREAKER 4902 LOW GAS / SPRING CHARGE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SYSTEM DISPATCHER i

DISCUSSION:

l

REFERENCES:

DRAWING 229-110

]

(

SENSING ELEMENT: 48KK, 48LL AR-702 Rev. 15 Page 112 (LAST PAGE)

.