ML20203C746
| ML20203C746 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 02/03/1999 |
| From: | Winship M FLORIDA POWER CORP. |
| To: | |
| References | |
| AR-801, NUDOCS 9902120212 | |
| Download: ML20203C746 (92) | |
Text
-. ~ -. -.. ~.. _ ~
..- _ - - +.,_-._-.._-. -
'~
Document Transmittal #: 111270 Date: 2/5/99 i
(
To:
NRC (DC DESK)
MAC: N/A.
Holder #: 1242 i
Destination:
==
Description:==
I l
Copy Totals
(
Document:
Revision:
- _C# Comment:
INF CTL MST i
11 I AR0801 12 1
0 0
l l
l t
J l
s l
I C \\
i' l
l l
Instructions to the Addressee: Please verify the document (s) received agrees with the above
-)
information. Notify Document Controlif changes are required to addressee information, or mark th) transmittal and return as indicated below.-
Engineering managers are required by NEP 121 to determine if new revised or temporary changes to 9
procedures affect job functions of their personnel Managers will communicate change information g
tppropriately and provide documentation of any training conducted to the Engineenng Training Coordinator Opsrations department must attach old document (s) or portions of document (s) superseded by the above l
to this transmittal.
The signature indicates acknowledgment of receipt of the above document (s) and that documents have been updated. Return signed and dated transmittat to Document Contro! within 15 working days of transmittal date to mait code' SA2A Florida Power Corpcration Docuanent Control, CA2A Crystal River Energy Coeuplex 15700 W. Power Line St.
Crystal River, FL 34428 C708 1"00gg
. Signature of Addressee:
Date:
9902120212 990203:
I PDR -ADOCK 05000302 t
l F
POR S
_ _.. - - _.-.. ~..-. - - -..-.
.~. ~. -. -
i O
Rev. 12 EffectiveDateM'I~'ff i
ANNUNCIATOR RESPONSE i
AR-801 I
FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 f
FSA ANNUNCIATOR RESPONSE i
i l
I I
PPROVED BY:
Procedure owner,-
l
- k. A WL SItNATURE 'ON FI[E) j 2 !3 DATE:
O i
PROCEDURE WRITER:
Michael A. Winship t
RESPONSIBLE DEPARTMENT:
Nuclear Plant Operations Support j
l
~.-
TABLE OF CONTENTS SECTION PAGE 1.0 PURPOSE.........................................................,,,.,,,,,1 9
f
2.0 REFERENCES
1 2.1 DEVELOPMENTAL REFERENCES............................................
1 i
i 3.0 PERSONNEL I!JDOCTRINATI.QN................................................
1 l
4.0 INSTRUCTIONS.............................................................
1 f
5.0 FOLLOW-UP ACTIONS.........................
............................ 1 ENCLOSURE i
I 1
Annunciator Response................................................
2 l
E b
l a
i 2
i
!~
AR-801 Rev. 12 Page i f
4 e-
1.0 PURPOSE g
%- I 1.1 Establish a reference document for each Annunciator Window on the FSA Lampbox.
1.2 Establish operator actions for valid Annunciator alarms on the FSA Lampbox.
1.3 Establish a reference to other procedures which address operatcr actions for valid Annunciator alarms on the FSA Lampbox.
2.0 REFERENCES
2.1 DEE LOPMENTAL REFERENCES t
l2.1.1' INPO 90-021, Good Practice OP-217, Alarm Response Procedures l2.1.2 Annunciator Window Engraving Drawing E-224-050 l2.1.3 Calculation I-95-0007 R-0, EFW Source Volumes 3.0 PERSONNEL _INDQCIJIINA_IIQN l
3.1 The Fire Service Annunciator System is powered from ACDP-40 Breaker 19.
l 4.0 INSTRUCTIONS l
4.1 Respond to alarms on the FSA Lampbox as indicated on Enclosure 1, i
Annunciator Response.
5.0 FOLLOW-UP ACTIONS None j
i i
i l
l i
AR-801 Rev. 12 Page 1
l i
/}
kJ~
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-01 FS-01-01 1
i FIRE WTR TANK 3A LEVEL LOW i
INDICATED CONDITION: TANK LEVEL s;35'7" i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-47-LS O
AR-801 Rev. 12 Page 2 L
.. _. ~. _ _. _ _ _ _ _ _ _.. _ _. _.
(..
,. C/
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-02 FS-01-02 i
l i
i FIRE WTR TANK 38 LEVEL LOW
[
l r
b l
INDICATED CONDITION: TANK LEVEL s35'7" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACTION FOR A VALID ALARM: REFILL TANK i
DISCUSSION:
l 1
REFERENCES:
OWG 208-031 FS-21 SENSING ELEMENT: FS-48-LS 1
i' I
i t
1 l
1 i
AR-801 Rev. 12 Page 3 1
l
=
~
. - -. _ - ~ _
l FIRE SYSTEM ANNUNCIATOR RESPONSE
'FS-01-04 FS-01-04 P
l CO2 TANK PRESS Hl/LO r
i
\\
l l
l INDICATED CONDITION: CARD 0X TANK PRESSURE RELAY RAR ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-1-2 ALARM O
- LOCAL PRESSURE INDICATOR CO-1-PI
)
l (V i
1 OPERATOR ACTION FOR A VALID ALARM
- l
- WALK DOWN C0 SYSTEM AND ENSURE NO LEAKS l
- ENSURE PROPER OPERATION OF CARD 0X UNIT DISCUSSION: CARD 0X TANK RELAY RAR IS ACTUATED WHEN CARD 0X TANK PRESSURE AS SEEN BY CO-1-PS1 IS 2325 PSIG OR s:275 PSIG.
l
REFERENCES:
DWG 208-031 FS-21, DWG FL-16996 4 i
SENSING ELEMENT: CARD 0X TANK RELAY RAR i
l t
AR-801 Rev. 12 Page 4 1
r-i r
(
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-05 FS-01-05 PUMP TEST RET WATER TO TANK i
I INDICATED CONDITION: FLOW IN FIRE SERVICE RECIRC LINE 2540 CPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-12-FS O
AR-801 Rev. 12 Page 5 a
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-07 FS-01-07 C'
FREON SYSTEM ACTIVATED INDICATED CONDITION: FREON SYSTEM ACTIVATED IN CABLE SPREADING ROOM f
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: NOTIFY FIRE BRIGADE TO INSPECT CABLE SPREADING ROOM. REFER TO AP-880 (FP)
I DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: KIB FREON SYSTEM INTERFACE FIRING UNIT O
-AR-801 Rev. 12 Page 6
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-08 FS-01-08 l
l I
t FDWTR PP & TURB DR 3A (HAZ 1) i I
i INDICATED CONDITION: CARD 0X HAZARD ZONE 1 RELAY PE ACTUATED (FWP-2A)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-1-1 ALARM i
p
- LOCAL WARNING BELL d
J OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2A
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP).
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-3-TS1 THROUGH CO-3-TS7.
REFERENCES:
DWG 208-031 FS-21,'DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 1 RELAY PE l
i O
AR-801 Rev. 12 Page 7
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-09 FS-01-09 1
I FDWTR PP & TUR8 DR 3B l
(HAZ-2) t INDICATED CONDITION: CARDOX HAZARD ZONE 2 RELAY PE ACTUATED (FWP-28)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARDOX PANEL WINDOW CO-2-1 ALARM O
- LOCAL WARNING BELL O
OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2B l
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP).
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-4-TS1 THROUGH CO-4-TS7
REFERENCES:
DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 2 RELAY PE I
i N
!O l
^
AR-801 Rev. 12 Page 8
I]
l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-10 FS-01-10 l
l l
l TURB GEN BitGS i
1-5 (HAZARD-3) i i
INDICATED CONDITION: CARD 0X HAZARD ZONE 3 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-3-1 ALARM
- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON TURBINE GENERATOR BEARINGS 1 THROUGH 5
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP).
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE i
COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-5-TS1 THROUGH CO-5-T54 i
REFERENCES:
DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 3 RELAY PE D(d AR-801 Rev. 12 Page 9
I i
D (V
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-11 FS-01-11 i
TURB GEN BRGS
)
6-9 (HAZARD-4)-
INDICATED CONDITION: CARD 0X HAZARD ZONE 4 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-4-1 ALARM
- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON TURBINE GENERATOR BEARINGS 6 i
THROUGH 9
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP)
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE DETECTORS CO-6-TS1 THROUGH CO-6-TS4
REFERENCES:
DWG 208-031 FS-21, DWC FL-16995 4 SENSING ELEMENT: HAZARD ZONE 4 RELAY PE l
O AR-801 Rev. 12 Page 10 l
l
l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-13 FS-01-13 I
FSP 1 RUNNING l
INDICATED CONDITION: POWER IS APPLIED TO FSP-1 MOTOR AND FSP-1 PUMP SHOULD i
BE RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:
FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER 01-13.
REFERENCES:
DWC 208-031 FS-14, FS-03 SENSING ELEMENT: MA1-1 l
b AR-801 Rev. 12 Page 11
l t
t i
1
.Q FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-14 FS-01-14 i
l FSP-1 CONTR PWR OFF i
s I
i INDICATED CONDITION: CONTROL POWER TO FSP-1 IS OFF OR RELAY FAILURE (ACDP 7 BREAKER #9) 1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION:
REFERENCES:
DWG 208-031 FS 14, FS-04 SENSING ELEMENT: mal-1 1
i i
1 I
O i
AR-801 Rev. 12 Page 12
. - ~.
..- - -,-.. ~ -.
-. ~..
I i
h s
. FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-15 FS-01-15 i
i I
1' I
CABLE SPR ROOM AUTO FANS OFF.
l t
i t
i
?
t l
I INDICATED CONDITION: SELECTOR SWITCH PLACED IN THE "0FF" F SITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: VERIFY SELECTOR SWITCH IS IN THE AUTO POSITION. INSTALL-TEMPb*'ARY FANS IF NECESSARY.
l DISCUSSION:
REFERENCES:
SENSING ELEMENT: FSE-592 E
^
!,O AR-801 Rev. 12 Page 13 j
l l
i l
i
- v FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-16 FS-01-16 1
F.S. TANK INSTR HEAT TRACE FAIL 1
I INDICATED CONDITION: OUTSIDE AIR TEMP s34 DEG F; HEAT TRACE FAIL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: DETERMINE IF TEMP REQUIRES A CHANGE IN THE FIRE SERVICE SYSTEM LINEUP. CHECK HEAT TRACE LINES.
DISCUSSION: CHECK METEOROLOGICAL STATION INDICATION
REFERENCES:
DWG 208-031.FS-21 SENSING ELEMENT: FS-49-TS AR-801 Rev. 12 Page 14 l
l
.)
FIRE. SYSTEM ANNUNCIATOR RESPONSE FS-02-01 FS-02-01 l
-i FSP-2A OVERSPEED INDICATED CONDITION: FSP-2A OVERSPEED :t2100 RPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH O
AR-801 Rev. 12 Page 15
l
(
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-02 FS-02-02 j
i i
L FSP-2A l
HI WATER TEMP l
l l
INDICATED CONDITION: HI WTR TEMP ON COOLING WTR 2190 DEG F REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O y
OPERATOR ACTION FOR A VALID ALARM: CHECK WATER LEVEL IN DIESEL COOLING l
SYSTEM.
P DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM i
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: FS-15-TS O
AR-801 Rev. 12 Page 16
i r
i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-03 FS-02-03 l
I I
t i
i i
i INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
)
OPERATOR ACTION FOR A VALID ALARM: REFILL WITH OIL IF NECESSARY.
DISCUSSION:
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: FS-40-PS i
l i
i O
AR-801 Rev. 12 Page 17
.m.
.__~.__.__,_.___..-._....m.____._.__
1 V
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-04 FS-02-04 t.
{
1 i
I i
I FSP-2A 3
NOT IN AUTO 1
INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: RETURN SWITCH TO AUTO DISCUSSION:
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: CS i
l
!O AR-801 Rev. 12-Page 18
3
' (d FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-05~
FS-02-05 FSP-2A l
Fall TO START INDICATED CONDITION: PUMP NOT RUNNING UP TO SPEED 90 SECONDS AFTER DIESEL RECEIVES AN AUTO START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO RESET ALARM
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: RELAY 7R l
- O l
AR-801 Rev. 12 Page 19 I
l
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-06 FS-02-06 FSP-2A, RUNNING l
l 1
t l
l INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED l
l l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
, ()
OPERATOR ACTION FOR A VALID ALARM: NONE l
DISCUSSION:
FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER 01-13.
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: RELAY 15R i
i 1
i
' O) i.
s L
AR-801 Rev. 12 Page 20 4
FIRE SYSTEM ANNUNCIATOR. RESPONSE FS-02-07 FS-02-07 FSP-2A FUEL LEVEL LOW INDICATED CONDITION: FUEL TANK LEVEL s66.5% FULL REDUNDANT INDICATION WHZCH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-13-LS AR-801 Rev. 12 Page 21
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-09 FS-02-09 FSP-2B OVERSPEED INDICATED CONDITION: FSP-28 OVERSPEED 22100 RPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
,)
OPERATOR ACTION FOR A VALID ALAF01.
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH YsY AR-801 Rev. 12 Page 22
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-10 FS-02-10 I
FSP-28 HI WATER TEMP INDICATED CONDITION: HI WATER TEMP LN COOLING WTR 2190 DEG F
(~~}
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
V OPERATOR ACTION FOR A VALID ALARM: CHECK WATER LEVEL IN DIESEL COOLING SYSTEM.
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: FS-16-TS O
AR-801 Rev. 12 Page 23
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-11 FS-02-11 FSP-2B LO LUBE OIL PRESS INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ?LARM:
OPERATOR ACTION FOR A VALID ALARM: REFILL WITH OIL IF NECESSARY DISCUSSION:
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: FS-41-PS
\\
AR-801 Rev. 12 Page 24 u
-. =.
.-.. -. ~
. _. =.
L FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-12 FS-02-12 i
i l
f l
l FSP-2B NOT IN AUTO 4
l INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
Ov OPERATOR ACTION FOR A VALID ALARM: RETURN TO AUTO DISCUSSION:
REFERENCES:
DWG 208-031 FS-8-13, FS-02 i
SENSING ELEMENT: CS l
i O
AR-801 Rev. 12 Page 25
y FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-13 FS-02-13 FSP-28 Fall TO START INDICATED CONDITION: DIESEL NOT UP TO SPEED AND RUNNING 90 SECONDS AFTER RECEIVING AN AUTO START SIGNAL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: RELAY 7R O
AR-801 Rev. 12 Page 26
~..
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-14 FS-02-14 i
e i
FSP-28 RUNNING INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A' VALID ALARM: NONE DISCUSSION:
l FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER 01-13
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: RELAY 15R l
1 i
U'l AR-801 Rev. 12 Page 27
rr:-
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-15 FS-02-15 s
FSP-28 FUEL LEVEL LOW INDICATED CONDITION: FUEL T/NK LEVEL s50% FULL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-14-LS-O AR-801 Rev. 12 Page 28
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-01 FS-03-01 MN TRANSF 3-1 FIRE SYS TRBL INDICATED CONDITION: MAIN TRANSFORMER #3-1 DELUGE VALVE (FSV-69) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-68), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-5, FD-302-231 SHT 01 0F 05 i
SENSING ELEMENT: K-2, K-5 i
l I
O AR-801 Rev. 12 Page 29
T
(,)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-02 FS-03-02 MN TRANSF 3 2 I
FIRE SYS TRBL l
j I
l INDICATED CONDITION: MAIN TRANSFORMER #3-2 DELUGE VALVE (FSV-66) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-65), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-6, FD-302-231 SHT 010F 05 SENSING ELEMENT: K-2, K-5 l
i i
i i
i i
f%
O AR-801 Rev. 12 Page 30
V)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-03 FS-03-03 i
MN TRANSF 3-3 l
FIRE SYS TRBL I
1 INDICATED CONDITION: MAIN TRANSFORMER #3-3 DELUGE VALVE (FSV-64) LOSS OF j
POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-63), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
.O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
l I
l
REFERENCES:
DWG 208-031 FS-07, FD-302-231 SHT 010F 05
)
i SENSING ELEMENT: K-2, K-5 l
l t
1 i
1 l
i AR-801 Rev. 12 Page 31
.m.._-_
i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-04 FS-03-04
'l J
UNIT TRANSF 3 FIRE SYS TRBL 1
l INDICATED CONDITION: UNIT AUX TRANSFORMER DELUGE VALVE (FSV-72), LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-71), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-08, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 i
I O
AR-801 Rev. 12 Page 32 I
i
hd FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-05 FS-03-05 l
STRT-UP TRAN 3 FIRE SYS TR8L i
INDICATED CONDITION: START UP TRANSFORMER DELUGE VALVE (FSV-61) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-60), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-09, FD-302-231 SHT 01 0F 05 l
f SENSING ELEMENT: K-2, K-5 l
[
t 5-
- O AR-801 Rev. 12 Page 33
O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-06 FS-03 WATER CURTAIN TROUBLE i
l INDICATED CONDITION: TURBINE BUILDING WATER CURTAIN DELUGE VALVE (FSV-239)
LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-238), OR CIRCUIT l
TROUBLE i
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-22, FD-302-231.iHT 01 0F 05 j
SENSING ELEMENT: K-2, K-5 l-i.
- o i
AR-801 Rev. 12 Page 34
j-FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-07 FS-03-07 TURB LUBE OIL FIRE SYS TRBL l
I t
INDICATED CONDITION: TURBINE LUBE OIL DELUGE VALVE (FSV-10) LOSS OF POWER TO I
CIRCUIT. ISOLATION VALVE NOT OPEN (FSV-108), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-10. FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 l
i 1
AR-801 Rev. 12 Page 35
.. =.. ~
. ~ - _. _
C)
FIRE SYSTEM ANNUNCIATOR RESPONSE F: 08 FS-03-08 i
FEEDWTR PUMP l'
FIRE SYS TRBL INDICATED CONDITION: FEEDWATER PUMP CONSOLES DELUGE VALVE (FSV-67) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-62), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i l
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING j
DISCU.t'. ION:
REFERENCES:
DWG 208-031 FS-10, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 l
l l
l AR-801 Rev. 12 Page 36 l-
. ~. -. _.. -
i
!k'J FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-09 FS-03-09 l
l l
H2 SEAL OIL -
FIRE SYS TRBL j
l INDICATED CONDITION: HYDROCEN SEAL OIL DELUGE VALVE (FSV-82) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE'NOT OPEN (FSV-83), OR CIRCUIT TROUBLE REDUNDANT INDICATION.WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-12, FD-302-231 SHT 010F 05 SENSING ELEMENT: K-2, K-5 i
1 i
j
'O AR-801 Rev. 12 Page 37
6 t
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-10 FS-03-10
[
l l
l B/U ES XFMR TRBL i
l l
INDICATED CONDITION: BACKUP ES TRANSFORMER DELUGE VALVE (FSV-832) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-831), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-22, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: FSCP-4 1
D
~(G AR-801 Rev. 12 Page 38
. _... ~... _
t p
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-11 FS-03-11'
[
FIRE PUMP HSE SPRINKLER ACT I
l l
INDICATED CONDITION: FIRE PUMP HOUSE SPRINKLER SYSTEM ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE l
DISCUSSION:
i
REFERENCES:
DWG 208-031 FS-21 l
SENSING ELEMENT: FS-17-PS I
AR-801 Rev. 12 Page 39
_____m_
i
-FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-12 FS-03-12 I
[
l i
i RB MAINT BLD j
SPRINKLER ACT I
L INDICATED CONDITION: FIRE SPRINKLER SYSTEM HAS ACTUATED IN THE RB MAINTENANCE SUPPORT BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:. SPRINKLER SYSTEM PRESSURIZED T
TO >30 PSIG l
~.)
OPERATOR ACTION FOR A VALID ALARM: CHECK RBMSB FOR FIRE l
DISCUSSION:
l
REFERENCES:
SS 211-031 FS-02 l
l SENSING ELEMENT: FS-508-PS2 l
i l
\\
l AR-801 Rev. 12 Page 40
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-13 FS-03-13 TURB BLDG BEL 119' SPR ACT i
INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATION i
ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
u OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-24-PS i
l i O AR-801 Rev. 12 Page 41
I O-FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-14 FS-03-14 i
TURB BLDG BEL 119' SPR ACT I
t i
INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATION ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i
/'~h O
i OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-25-PS J
.f)
L)
AR-801 Rev. 12 Page 42 j
A
h
.,w-_
.-a sa s
.s-sx -. =
a s.u.-.u.a...~.--.a.+s
=nna
-.a FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-15 FS-03-15 i
v i
OUTAGE SUPP BLDG FIRE i
f 4
f I
INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN OUTAGE SUPPORT BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i I
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP)
DISCUSSION:
l
REFERENCES:
DWG 211-031 FS-076 i
SENSING ELEMENT: FS-472-FS j
k i
l I
AR-801 Rev. 12 Page 43
l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-01 FS-04-01 i
MAIN TRANSF j
3-1 FIRE 1
l INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA REFER TO AP-880 (FP) l DISCUSSION:
l l
REFERENCES:
DWG 208-031 FS-05 l
SENSING ELEMENT: K-4 l-l
,10V AR-801 Rev. 12 Page 44
i
?
f FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-02 FS-04-02 l
MAIN TRANSF 3-2 FIRE j
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
fq OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO
()
AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-06 SENSING ELEMENT: K-4 l
l
.O
\\
l i
AR-801-Rev. 12 Page 45 l
.. ~...
i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-03 FS-04-03 MAIN TRANSF 3-3 FIRE
)
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION.
REFERENCES:
DWG 208-031 FS-07 SENSING ELEMENT: K-4 1
i l
3(a i
AR-801 Rev. 12 Page 46
L l
1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-04 FS-04-04 UNIT TRANSF 3 FIRE i
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
1
REFERENCES:
DWG 208-031 FS-08 SENSING ELEMENT: K-4 4
l p AR-801 Rev. 12 Page 47
[.
1 J
i i
FIRE SYSTEM ANNUNCIATOR' RESPONSE FS-04-05 FS-04-05 I
l STARTUP TRANSF 3 FIRE i
i l
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(3
-v/
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-09 SENSING ELEMENT: K-4 1
C\\
l V l
AR-801 Rev. 12 Page 48 n
n (M
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-06 FS-04-06 WATER CURTAIN FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-22 SENSING ELEMENT: K-4 i
i O
l l
l AR-801 Rev. 12 Page 49
[
\\
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-07 FS-04-07 TURB LUBE OIL SYSTEM FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-10 SENSING ELEMENT: K-4 I
I
/'g b
AR-801 Rev. 12 Page 50
FIRE SYSTEM ANNUNCIATOR RESPONSE
'FS-04-08 FS-04-08 FEEDWTR PUMP CONSOLE FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DTM.USSION:
REFERENCES:
DWG 208-031 FS-11 i
SENSING ELEMENT: K-4 O
AR-801 Rev. 12 Page 51
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-09 FS-04-09 H2 SEAL OIL UNIT FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-12 SENSING ELEMENT: K-4 OV
-AR-801 Rev. 12 Page 52 s
- u
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-10 FS-04-10 l
B/U ES XFMR i
FIRE l
l l
i l
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY i
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i i
l i
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
l
REFERENCES:
DWG 208-040 MT-140 i
SENSING ELEMENT: FSCP-4 i
i l
l l
l
'O AR-801 Rev. 12 Page 53 l
l
t i
L
("
I FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-11 FS-04-11 l
t l
TURB BLDG BEL 145' SPR ACT l
INDICATED CONDITION: TURB BLOG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l O OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO f
AP-880 (FP) l
)
l DISCUSSION:
l
REFERENCES:
D4 208-031 FS-21 i
l i
SENSING ELEMENT: FS-26-FS l
I e
AR-801 Rev. 12 Page 54 l
l l
l l
I
! A'b FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-12 FS-04-12 l
1 i
l 1
l-1 TUR8 BLDG BEL 145' SPR ACT
]
INDICATED CONDITION: TUR8 BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION ;t10 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-27-F5 l
i i
O AR-801 Rev. 12 Page 55
-~
f3' C/
' FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-13 FS-04-13 i
l CONT COMP BEL 108' SPR ACT t
I c.
INDICATED CONDITION: CONTROL COMPLEX BELOW 103' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG l
t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-33-FS l
l l
AR-801 Rev. 12 Page 56
i
. h,PN FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-01 FS-05-01 t
j 1
CHARCOAL FLTR AHFL-1 TRBL i
i INDICATED CONDITION: PURGE EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE i
I REDUNDANT INDICATION WHICH WILL VFRIFY ALARM:
[ r i
OPERATOR ACTION FOR A VALID ALARh: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-24, FS-13 t
SENSING ELEMENT: K-2, K-5 i
t O
4 AR-801 Rev. 12 Page 57
~
t i
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-02 FS-05-02 i
I t
l CHARCOAL FLTR l
AHFL-2A TRBL l
l INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM l
LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-25, FS-14 SENSING ELEMENT: K-2, K-5 l
- O d
l.
AR-801 Rev. 12 Page 58 l
l
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-03 FS-05-03 CHARCOAL FLTR AHFL-28 TR8L INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARC0AL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING i
DISCUSSION:
I i
REFERENCES:
DWG 208-031 FS-15 SENSING ELEMENT: K-2, K-5 I
)
,1 i
l i
l AR-801 Rev. 12 Page 59
~\\/
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-04 FS-05-04 i
i
. CHA3 COAL FLTR AHFL-2C TRBL
[
I l
l
'I i
INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
' OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-16 i
SENSING ELEMENT: K-2, K<-5 O
AR-801 Rev. 12 Page 60
i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-05 FS-05-05 l
CHARCOAL FLTR l
AHFL-2D TRBL I
INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE J
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-17 SENSING ELEMENT: K-2, K-5
?
AR-801 Rev. 12 Page 61
(
-s G
FIRE SYSTEM ANNUNCI/JOR RESPONSE FS-05-06 FS-05-06 CHARCOAL FLTR AHFL-4A TRBL t
INDICATED CONDITION: CTRL COMPLEX EMERGENCY CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-18 SENSING ELEMENT: K-2, K-5 l
l AR-801 Rev. 12 Page 62
- ~.
O(g FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-07 FS-05-07 P
CHARCOAL FLTR AHFL-4B TR8!.
INDICATED CONDITION: CTRL COMPLEX EMERGENCY CHARCOAL FILTER DELUCE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-19 SENSING ELEMENT: K-2, K-5 r%
s AR-801 Rev. 12 Page 63
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-08 FS-05-08 i
i CHARCOAL FLTR l
AHFL-15 TRBL i
5 INDICATED CONDITION: NUCLEAR SAMPLE ROOM CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VER'.FY ALARM:
u OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-20 SENSING ELEMENT: K-2, K-5 AR-801 Rev. 12 Page 64
n:
.Okj)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-09 FS-05-09 ADMIN BLDG WAREHOUSE FIRE i
1 INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN WAREHOUSE OR ADMIN BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(O j
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:
1
REFERENCES:
SENSING ELEMENT:
)
i i
AR-801 Rev. 12 Page 65 i
I
1 i
l l
' O
,-.,,y.__
..--m.,;._.,-
(_,/
FIRE SYSTEM ANNUNCid:
' #;7T4SE FS-35-10 FS-05-10
.' m-1 OFFICE BLDG i
TROUBLE / FIRE l
i i
INDICATED CONDITION: RUSTY BUILDING FIRE OR INSTRUMENT FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- 1 OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: ZONE 1-3 ALARM
(-
i I
i.
{
AR-801 Rev. 12 Page 66
~
1
]/'
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-11 FS-05-11'
-s_
i CONTROL BLDG TROUBLE / FIRE
)
i I
INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN CONTROL BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM-i I
I OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: ZONE 4-11 ALARM J
l
/(
)
AR-801 Rev. 12 Page 67
- =...
i I
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-12 FS-05-12 4
i i
i i
SWITCH GEAR RM i
TROUBLE / FIRE i
1 l
1 i
INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN SWITCHGEAR ROOM l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: ZONE 12-13 ALARM i
i 1
AR-801.
Rev. 12 Page 68
. ~ -.
l I
i r
1 (u-FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-13 FS-05-13 i
l i
i FIRE PROT TROUBLE i
I I
i i
INDICATED CONDITION: FIRE PROTECTION TROUBLE PLANT OR OFFICE AREA CAB I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ALARM PANELS LOCATED ON 124' i
l ELEV. CONTROL COMPLEX AND 1st FLOOR OF RUSTY BLDG IN TELEPHONE TERMINATION
(
%d l
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA l
1 I
DISCUSSION: THIS ALARM MAY COME IN WHEN THE HALON PROTECTION SYSTEM IS PLACED IN " TEST" l
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: PLANT AREA CAB, OFFICE AREA CAB i
O AR-801 Rev. 12 Page 69
i i
i b
I i
i l
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-14 FS-05-14 l
?
I i
h EMER DSL GEN ROOM TROUBLE i
INDICATED CONDITION: LOSS OF POWER OR CIRCUIT FAILURE REDUNDANT-INDICATION WHICH WILL VERIFY ALARM:'
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:
REFERENCES:
DWG 208-031 FS-23 SENSING ELEMENT: OR, RSR TSR O
AR-801 Rev. 12 Page 70
i 3
FIRE SYSTEN ANNUNCIATOR RESPONSE FS-05-15 FS-05-15 EMER DSL GEN ROOM FIRE I
l 2
l
\\
i INDICATED CONDITION: ONE OF TWENTY SENSORS HAS ACTUATED. FSV-101 SHOULD BE i
l OPEN.
j i
i i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA j
1 DISCUSSION:
I l
REFERENCES:
DWG 208-031 FS-23 SENSING ELEMENT: OR I
1 i
4 4
AR-801 Rev. 12 Page 71
..... ~ -. - -.. -... -.. _. -. -.,
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-01 FS-06-01
[
CHARCOAL FLTR AHFL 1 FIRE j
P l
t INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY t
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
t OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-24, FS-13 SENSING ELEMENT: K-4 l
O V
AR-801 Rev. 12 Page 72
r i
l t
i p1 ),
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-02 FS-06-02 j
\\
l i
t CHARCOAL FLTR AHFL-2A FIRE s
i r
l INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN,'OR HAS BEEN OPENED LOCALLY I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM.
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880- (FP) 1 DISCUSSION:
i
REFERENCES:
DWG 208-031 FS-25, FS-14 SENSING ELEMENT: K-4 O
AR-801 Rev. 12 Page 73
l
()
(
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-03 FS-06-03
\\
CHARCOAL FLTR AHFL-28 FIRE i
l INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY 1
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-15 SENSING ELEMENT: K-4 J
m AR-801 Rev. 12 Page 74
'0 t
- ( _./
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-04 FS-06-04 1
t CHARCOAL FLTR AHFL 2C FIRE i
i 1
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) i DISCUSSION:
)
REFERENCES:
DWG 208-031 FS-16 1
1 SENSING ELEMENT: K-4
{
1
)
AR-801 Rev. 12 Page 75 i
)
V( y FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-05 FS-06-05 l
l r
l l
l l
CHARCOAL FLTR AHFL-2D FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-17 SENSING ELEMENT: K-4 1
l 1
i l
l i
I AR-801 Rev. 12 Page 76
l i
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-06 FS-06-06 CHARCOAL FLTR AHFL-4A FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA, REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-18 SENSING ELEMENT: K-4 O
AR-801 Rev. 12 Page 77
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-07 FS-06-07 CHARCOAL FLTR AHFL-48 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATiiE ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-19 SENSING ELEMENT: K-4 lc AR-801 Rev. 12 Page 78
(.
~-..=~ -
. =.
+
I
",r3 1.)
FIRE SYSTEM ANNUNC1ATOR RESPONSE FS-06-08 FS-06-08 t
i CHARCOAL FLTR AHFL-15 FIRE i
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM.
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-20 SENSING ELEMENT: K-4 fm i
AR-801 Rev. 12 Page 79
--. ~.
i l
i I
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-09 FS-06-09 TSC TROUBLE INDICATED CONDITION: ALARM AT PYROTRONICS PANEL kt0UNDANT INDICATION WHICH WILL VERIFY ALARM:
O-OPERATOR ACTION FOR A VALID ALARM: INVESTICATETSCFIRESbEM DISCUSSION:
REFERENCES:
DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL AR-801 Rev. 12 Page 80
.... ~..
I i
t r-l V FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-10 FS-06-10 i
l l
4
't i
TSC FIRE i
i t
i INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN TSC REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC AREA DISCUSSION:
REFERENCES:
DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL i
i l
t
!O AR-801 Rev. 12 Page 81
I
/'N,
(/
FIRE SYSTEM ANNI!NCIATOR RESPONSE FS-06-11 FS-06-11 L
i TSC FILTER i
I AHFL-20 TROUBLE I
INDICATED CONDITION: ALARM AT LOCAL PANEL REDUNDANT INDICATION WHICH WILL VI.RIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM DISCUSSION:
REFERENCES:
DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL I
O AR-801 Rev. 12 Page 82
-~..,.
1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-12 FS-06-12 TSC FILTER AHFL-20 FIRE l
INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN AHFL-20 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM DISCUSSION:
REFERENCES:
209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL l
i O
i AR-801 Rev. 12 Page 83
'I
.~.
. -~
/*N d
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-13 FS-06-13 i
RECORD STORE VAULT FIRE l
\\
)
INDICATED CONDITION: WATER FLOW INTO RECORD VAULT SPRINKLER SYSTEM 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 AQ OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA FOR FIRE.
NOTIFY ADMINISTRATIVE SUPERVISOR.
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-70-FI i
i AR-801 Rev. 12 Page 84 i
.. = _. _.. _..... - _ _.. _ -..
___.-._.~ _.._. _ _ _ _. _ _
I~
v FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-14 FS-06-14 i
i CONT COMPLEX i
FIRE l
i I
i I
i i
i INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY i
REDUNDANT INDICATION WHICH WILL VERIFY A). ARM:
OPERATOR ACTION FOR A VALID ALADM: INS'PECT AREA. REFER TO AP-880 (FP) i DISCUSSION:
REFERENCES:
DWG 208-031 FS-24 i
SENSING ELEMENT: K-4 1
l l
l l
l AR-801 Rev. 12 Page 85
. = _. _ _ _
O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-15 FS-06-15 l
l CONT COMPLEX j
FIRE SYS TRBL i
INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING.
INVESTIGATE LOSS OF CONTINUITY IN HALON SYSTEM FIRING CIRCUIT.
DISCUSSION:
REFERENCES:
DWG 208-031 FS-24 SENSING ELEMENT: K-5, K-2 AR-801 Rev. 12 Page 86 (LAST PAGE) i
t i
i i
e-PROCEDURE DEVELOPMENT AND REVISION RECORD I
\\
Procedure: AR0801 New Rev:
12 PRR#:
16366
Title:
FSA ANNUNCIATOR RESPONSE I
MINOR CHANGES i
If Minor Changes are included, check the applicable box (es) and provide a list of affected steps.
The following corrections are incorporated throughcut:
j
_ Sentence Structure
_ Redundant words or phrases
_. Punctuation
_ Abbreviations
_ Capdalization
_ Obviously incorrect units of measure
_ Spelling
_ inadvertentty omstted symbols (#, %, etc.)
_ Organizetenal Changos: position titles,
_ Obvious step numbering descrepancies department names, or telephone numbers
_ Format The following corrections are incorporated in the step (s) indicated: "Throughout" is used in lieu of Step # if a specific change affects a large number of steps.
Correcting O',._.: nomenclature that does not agree with field labels or balance of procedure I
Changing information that is obviously incorrect and referenced correctly elsewhere Misplaced decimals that are neither setpoint values nor j
tolerances Reference to a procedure when an approved procedure has taken the place of another procedure Fixing branching points when it is clear the branching eteps were originally intended but were overlooked or incorrectly stated due to step number changes Adding clarifying information such as NOTES and CAUTIONS Adding words to clarify eteps, NOTES, or CAUTIONS which clearly do not change the methodology or intent of the steps
..-._,___._. - _._ m. _. ~. _ _ _. _ _. - _
I PROCEDURE DEVELOPMENT AND DEVISION RECORD i
Procedure: AR0801 New Rev:
12 PRR#:
- o388
Title:
FSA ANNUNCIATOR RESPONSE MINOR CHANGES-if Minor Changes are included, check the applicable bon (es) and provide a list of affected steps.
The following corrections are incorporated throughout.
l
_ Sentence Structure
_ Redundant words or phrases
_ Punctuohon
_ Abbreviabons
_ Capdenzaban
_ Obviously incorrect units of measure
_ Speding
_ inadvertently omitted symbols (#, %, etc.)
-l
'3 Organizabowl Changes ponden trios,
_ Otwlous step numbenng diacropenoss j
department names, or telephone numbers K Format 1
The following corrections are incorporated in the step (s) indicated: "Throughout" is used in lieu of Step # if a specific change anects a large number of steps.
Correcting om.ipment nomenclature that does not agree with field labels or balance of procedure Changing infonnation that is obviously incorrect and referenced correctly elsewhere Misplaced decimals that are neither eetpoint values nor tolerances Reference to a, --- ' e when an approved procedure has taken the place of another procedure Flaing branching points when it is clear the branching steps were originally intended but were overtooked or incorrectly stated due to step number changes Adding clarwying information such as NOTES and CAUTIONS l
w Adding words to clarify steps, NOTES, or CAUTIONS which clearly do not change the.. ^U ' _ ;y or intent of the st*Ps j
i
F h
/
I C
PROCEDURE DEVELOPMENT AND REVISION RECORD i
Procedure: AR0001 New Rev:
12 PRR#:
16366 t
Title:
FSA ANNUNCIATOR RESPONSE CHANGE OF INTENT, CANCELLATION, OR NEW PROCEDURE Changes are incorporated for the reasons provided. "Throughou'" is used in lieu of Step # if a spectic change affects a large number of steps. For new or cancelled procedures the reason is provided.
Windows FS41 13 & FS-01-14 Changed nomenclature in Annunciator Windows from FIRE PUMP 3B to FSP-1 as ger DCN 98-278 & attached SA/USQD 96-529 i
Windows FS-02-01, FS--C2-02, Changed nomenclature in Annunchtor Windows from FIRE PUMP 3A to FSP-2A as per DCN FS-02-03, FS-02-04,98-278 & ettached SA/USQD 98-529 FS-02-05, FS-02-06, &
FS-02-07 j
I Windows FS4249, FS-02-10, Changed nomenclature in Annunciator Windows from FIRE PUMP 3C to FSP-2B as per DCN i
FS-02-11, FS-02-12,98-278 & attached SA/USQD 98-529 FS-02-13, FS-02-14, &
l FS-0215 j