FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302 / LICENSE NUMBER DPR-72 ATTACHMENT B LICENSE AMENDMENT REQUEST #251, REVISION 0 EDITORIAL CORRECTION TO ADMINISTRATIVE CONTROLS SECTION Proposed ITS Change Pages Strikeout / Shadow Format Strikeout Text indicates deleted text Shadowed text indicates added text I)0"Eco$! Eo$$002 P

PDR I

High Radiation Area 5.8 5.0 ADMINISTRATIVE CONTROLS 5.8 High Radiation Area 1

5.8.1 Pursuant to 10 CFR 20, paragraph 20.1601 (2) erid (3) '(c),

ilternithe Laethods h are _ssedito iccintro1Mccess[tothightradiation areas.76 Eeach high radiation area, as defined in 10 CFR 20, in 1

which the intensity of radiation (measured at 30 cm) is

> 100 mrem /hr but < 1000 mrem /hr, shall be barricaded and conspicuously posted as a high radiation area and entrance thereto shall be controlled by requiring issuance of a Radiation Work Permit (RWP).

Any individual or group of individuals permitted to enter such areas shall be provided with or accompanied by one or more of the following:

a.

A radiation monitoring device that continuously indicates the radiation dose rate in the area.

b.

A radiation monitoring device that continuously integrates the radiation dose in the area and alarms when a preset integrated dose is received.

Entry into such areas with this monitoring device may be made after the dose rate levels in the area have been established and personnel are aware of them.

c.

An individual qualified in radiation protection procedures with a radiation dose rate monitoring device, who is responsible for providing positive control over the activities within the area and shall perform periodic radiation surveillance.

i 5.8.2 In addition to the requirements of Specification 5.8.1, areas with radiation levels 21000 mrem /hr at 30 cm shall be provided with locked or continuously guarded doors to prevent unauthorized entry and the keys shall be. maintained under the administrative control g

of the Shift Supervisor on duty or health physics supervision.

Doors shall remain locked except during periods of access by personnel.

Direct or remote (such as closed circuit TV cameras) continuous surveillance may be made by personnel qualified in radiation protection procedures to provide positive exposure control over the activities being performed within the area.

(continued)

Crystal River Unit 3 5.0-30 Amendment No. 149 t

FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302 / LICENSE NUMBER DPR-72 ATTACHMENT C LICENSE AMENDMENT REQUEST #251, REVISION 0 EDITORIAL CORRECTION TO ADMINISTRATIVE CONTROLS SECTION Proposed ITS Change Pages Revision Bar Format

'. I '

High Radiation Area 5.8 5.0 ADMINISTRATIVE CONTROLS 5.8 High. Radiation Area 5.8.1 Pursuant to 10 CFR 20, paragraph 20.1601(c), alternative methods are used to control access to high radiation areas.

Each high radiation area, as defined in 10 CFR 20, in which the intensity of radiation (measured at 30 cm) is > 100 mrem /hr but < 1000 mrem /hr, shall be barricaded and conspicuously posted as a high radiation area and entrance thereto shall be controlled by requiring issuance of a Radiation Work Permit (RWP).

Any individual or group of individuals permitted to enter such areas shall be provided with or accompanied by one or more of the following:

a.

A radiation monitoring device that continuously indicates the radiation dose rate in the area.

b.

A radiation monitoring device that continuously integrates

'the radiation dose,in the area and alarms when a preset integrated dose is received.

Entry into such areas with this monitoring device may be made after the dose rate levels in the area have been established and personnel are aware of them.

c.

An individual qualified in radiation protection procedures with a radiation dose rate monitoring device, who is responsible for providing positive control over the activities within the area and shall perform periodic radiation surveillance.

5.8.2 In addition to the requirements of Specification 5.8.1, areas with radiation levels 21000 mrem /hr at 30 cm shall be provided with locked or continuously guarded doors to prevent unauthorized entry and the keys shall be maintained under the administrative' control of the Shift Supervisor on duty or health physics supervision.

Doors shall remain locked except during periods of access by personnel.

Direct or remote (such as closed circuit TV cameras) continuous surveillance may be made by personnel qualified in radiation protection procedures to provide positive exposure control over the activities being performed within the area.

(continued)

Crystal River Unit 3 5.0-30 Amendment No.