Text
- _ _ _-- __-__.
Document Transmittal #: 94668 Date: 5/6/98 T::
NRC (DC DESK)
MAC: N/A Destination:
==
Description:==
Copy Copy Totals Document:
Revision:
Comment:
INFO CNTL MSTR AR0603 20 24 1
0 0
instructions to the Addressee:
Pirase verify the document (s) received agrees with the above information.
Operations department must attach old document (s) or portions of document (s) superseded by the above to this transmittal.
The signature indicates acknowledgment of receipt of the above document (s) and that documents have been updated. Retum signed and dated transmittal to Document Control within 15 working days of transmittal date to mall code:
o)\\
I NA1C Florida Power Corporation l
Cryetal River Energy Complex
\\
(\\h i
l Document Control, NA1C
)
l j
15760 W. Power Line St.
\\
Crystal River, FL 34428-6708 j
Signature of Addressee:
Date:
9905190417 990506 l
PDR ADOCK 05000302 l
P PM l
Ecs. 20 l
Fffective Date _' [ ~ Z N,___ _
l L
l l
~
INFOR VIATION L.
ONLY l
l
[-
ANNUNCIATOR RESPONSE AR-603 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 l
O TGF 0 ANNUNCIATOR RESPONSE' tv i
l l
l l
1 i
l l
l 1
l l '.
(.
APPROVED BY:
Interpretation Contact 1
[
$2tk -.
L l
(S TUR O.
FILE)
DATE:
II
[
O 1"'<er*<'a' o~ <o"'^<':
e<."<,
e, o < 4 -
e Support
l l
IABLE_0E.COSIINIS Sf.Ol0N PACE 1.0l VRP_QiE...........................................
................. 1 L O_ R E r E 8 EM ES............................................................ 1 l
2.1. IMPLEMENTING R[F_ERENCES.............
............................. 1
- 2. 2 ptvELOPMENTAL _.8t EERENCl;S......
.............. 1 L 0lE R$QMN EL_.INP0GTRINAUDN................................................ 1 i
t L.03 NSIRUCU 0fG............................................................ 2 L
LO._E0M 0Wdj P ACUDNS....................................................... 2 ENCLOS_URE 1
Annunciator Response...........
.................................. 3 l
l s
[
AR-603 Rev. 20 Page i
L O..u PUliP,ASE a
i
.k L1
~ Establish a. reference document for each Annunciator Window on the TGF-AX3 Lampbox.-
1.2 Establish operator actions for -valid Annunciator alarms on the TCF-AX3 tampbox.
1.3 Estabh sh a. reference to-other procedures which address operator actions for valid Annunciator alarn.s'on ti.a TCF-AX3 Lan pbox.
>I L.D '
_REELREIKf3
. 2. l'
.IMPlffl[NIMG_REELRENCES 12.1.1 AP-660, Turbine Trip 2.1.2.
OP-607. Condenser vacuum System
~2.1.3 EOP, Emergency Operating Procedure 1
-2.1.4 OP-701, Operation of the Main Electrical Generator Systems 3
2.1.5
- AR-921',. Hydrogen Panel Annunciator Response
.2.1.6:
OP-203, Plant Startup-2.1.7-OP-204, Power Operations 2.1.8-PT-325, Turbine Generator Checks j
2.2.
DEYEL0fEENIALREEEEEECES 2.2.1, INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-049 2. 2. 3_ _
. Westinghouse Vendor Drawing CN6F9177 L2.2.4 LMAR 92-04-01-02, _ tube Oil Purifier. Installation -
h
.L0-PEBS_0NNEL_INQQCIBIfNAT_ ION 3.1 The Annunciator System is powered from VBDP-5 Breaker 28.
j 4
1
(
(f
)
.l c
AR-603 F.ev. 20 Page 1-L
4,0.. _._, _ INS 1ptK,11oNS 41 I'espond to alarms on the 1GF-AX3 Lampbox as indicated on Enclosure
- 1. Annunt1ator Respont,e, 1,0
__ Epij 0W-UP.JCUONS None l
l l
F l
i
)
l I
l
\\
i t
l i
i n
AR-603 Rev. 20 Page 2
l-
[
v l:
[NCIUSDRE.1
'(Page 1 of 103)
'lGF 0 ANNUNCIA10R RLSPON5E TGF-AX3-01-01 0-01-01 1
e._m TURB GEN
~ BRG OIL PUMP TRIP EVENT P0lNT 1614 INDICATED CONDITION:
o TBP-2 BREAKER OPEN WITH. CONTROL HANDLE IN THE NORMAL AFTER START POSITION.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT IS ON WITH A RED FLAG ON CONTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE.TBP-3 STARTS.
DISCUSSION:
}EFERENCES: DRAWING'208-057 TB-03 SENSING ELEMENT: CS/SC, CS/0,(CONTROL STATION CONTACTS) 42B BREAKER CONTACT
' AR-603--
Rev 20 Page 3
ENLt.05URE J
[
(Page 2 of'303) t--------
[
1CF 0 ANNUNCIATOR Rf SPONSE 1CF-AX3-01-01 0-01-01 l.
)
r!N3 -- _. _,__
TURB GEN BRG OIL PUMP TRIP h gg' g Q1g g
A-----=
a EVENT POINT 1G18 INDICATED CONDITION:.
o TBP-3 DC STARTER OPEN WITH CONTROL HANDLE IN NORMAL AFTER START POSITION.
V' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT IS ON WITH A RED FLAG ON CONTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:.
o ENSURE TBP-2 AUTO STARTS o ENSURE TBP-8 AUTO STARTS DISCUSSION:
REFERENCES:
DRAWING 208-057 TB-12 SENSING. ELEMENT: CS/SC, CS/0 CONTROL STATION CONTACTS, 42X STARTER CONTACT 1
.'AR-603 Rev. 20 Page 4 1
t____________..__
.)
EN(10$URE.1 (Page 3 of-1C3) ff N
IGF. O ANNUNCIA10R RESPONSE 1CF-AX3-01-04 0-01-04
, m maa..
mum er--- -
m
-~ ~
C3 l
TURB GEN l
BRG OIL PUMP AUTO START EVENT POINT 1613 INDICATED CONDITION:
o TBP-2 BREAKER CLOSED WITH CONTROL HANDLE IN NORMAL AFTER STOP POSITION.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT IS ON WITH A GREEN FLAG ON CONTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF OIL PUMP AUTO START.
o CHECK MAIN LUBE OIL PRESSURE.
l DISCUSSION:
LUBE OIL PRESSURE <12 PSIG AS~ SENSED BY T8-254-PS AUTO STARTS TPB-2
REFERENCES:
DRAWING ~ 208-057 TB-03
[
SENSING-ELEMENT: CS/ST, CS/0 CONTROL STATION CONTACTS, 42A BREAKER CONTACT y
' AR-603-Rev. 20 Page 5
l, ILNCI OSURE _1 (n)
(Page 4 of 103)
'.u TGF 0 ANNUNCIA10R RESPONSE 1CF-AX3-01-04 0-01-04 f
___~._-.m._,__
N_.
l BRG OlL PUMP TURB GFN AUTO START 1
. ~
1 EVENT POINT.1617 INDICATED CONDITION:
o TBP-3 STARTER CLOSED WITH CON 1ROL HANDLE IN NORMAL AFTER STOP POSITION.
(m i
)
%J REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT IS ON WITH A GREEN FLAG ON CONTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF OIL PUMP AUTO START.
o CHECK MAIN LUBE OIL PRESSURE.
DISCUSSION:
LUBE OIL PRESSURE <10 PSIG AS SENSED BY TB-253-PS AUTO STARTS TPB-3
REFERENCES:
DRAWING 208-057 TB-12
/{)\\
i SENSING ELEMENT: CS/ST, CS/0 CONTROL STATION CONTACTS, 42X STARTER CONTACT AR-603 Rev. 20 Page 6
l.
l
?
(Page 5 of 103)
' Q
. ~..
1GF 0 ANNUNCIA10R RESPONSE TGF-AX3-01-05 0-01-05 l
HP SEAL OIL-E EACKUP PUMP TRIP l
EVENT P0lNT 1616 INDICATED CONDITION:
o TBP-8 BREAKER OPEN WITH CONTROL HANDLE IN NORMAL AFTER START POSITION.
O-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT IS ON WITH A RED FLAG ON CONTROL' STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
)
l o ENSURE EITHER TBP-2 OR TBP-3,- AND TBP-4 ARE RUNNING.
I o ENSURE TBP-5 OR TBP-10 IS RUNNING.
I L o INVESTIGATE CAUSE OF TBP-81 RIP.
1 DISCUSSION::
I
REFERENCES:
DRAWING 208-057 TB-04 f 0%.(j
. SENSING ELEMENT: CS/ST, CS/0 CONTROL STATION CONTACTS, 42B BREAKER CONTACT L
AR-603 Rev. 20 Page 7
l
[NCl 05URE J (Page G of 103)
.'._ F O'ANNUNCIA10R RESPONSE 1GF-AX3-01-06 0-01-06 lG
---.s.._____,,,
l HP SEAL OIL
~ BACKUP PUMP E
AUTO START
- EVENT POINT 1615 i
INDICATED CONDITION:
o TBP-8 BREAKER CLOSED WITH CONTROL HANDLE IN NORMAL AFlER STOP POSITION.
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 o RED LIGHT IS ON WITH A GREEN FLAG ON CONTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
- o INVESTIGATE CAUSE OF TBP-8 AUTO START.
o CHECK OPERATION OF RUNNING TURBINE GENERA 10R OIL. AND SEAL OIL PUMP (S).
o CHECK MAIN LUBE OIL PRESSURE.
1 i
DISCUSSION:
{
DECREASING LUBE OIL PRESSURE <12 PSIG AS SENSED BY TB-254-PS AUTO STARTS HIGH PRESSURE SEAL OIL BACK-UP PUMP, TBP-8 1
REFERENCES:
DRAWING 208-057 TB-04
'l SENSING ELEMENT:- CS/ST, CS/0 CONTROL STATION CONTACTS, 42A BREAKER CONTACT -
.k l
I' 7:
L
' AR-603
Rev. 20 Page 8 L__-_-_______
(
(M LOSRREj 10 (Page 7 of 103)
- r..Q
' 1CF 0 ANNUNCIATOR RESPONSE TCF-AK3-01-07 0-01.
m e-
~
TURB GEN LUBE OIL SYS TROUBLE M Ol-6-
M
.. M WJ EVENT POINT 0310
~
INDICATED COND1 TION:
o LOPU-1B SYSTEM SHUTDOWN REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
);&
o DIRTY STRAINER LAMP ILLUMINATED ON LOPU-1B CONTROL PANEL o LOW OIL LEVEL FOR LOT-2 AS SENSED BY TB-329-LS o LOW FLOW LAMP ILLUMINATED i
o HIGH SYSTEM VACUUM h12"HG
.l OPERATOR ACTIONS FOR A VALID ALARM:
- o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE 0F LOPU-18. SYSTEM -
SHUTDOWN.
j e
l DISCUSSION:
i 1
l.
REFERENCES:
DRAWING 209-038 LO-01 N
SENSING-ELEME'NT: LOPU-1B CONTROL CIRCUIT CR6X j
TAR-603 Rev. 20 Page 9 lwx=_:-_____-_-_-----_
~
ENG 03V8L1
.(Page 8 of 303) t - Q)
TGF 0 ant.UNCIATOR RESPONSE 1GI'-AX3-01-07 0-01-07
~ ~ <. ~
TURB GEN LUBE OIL SYS TROUBLE EVENT POINT 0311 INDICATED CONDITION:
o LOPU-3A DIRTY FILTER ALARM.
O-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AMBER IND LIGHT ON LOCAL PANEL FOR FILTER #1 AS SENSED BY LO-51-DPIS o AMBER IND LIGHT ON LOCAL PANEL FOR FILTER #2 AS SENSED BY LO-52/53-DPIS o AMBER IND LIGHT ON LOCAL PANEL FOR FILTER #3 AS SENSED BY LO-54-DPIS OPERATOR ACTIONS'FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF DIRTY FILTER ALARM.
DISCUSSION:
DIRTY FILTER ~ ALARM INDICATES E 25 PSID ON ONE OR ALL OF THE FILTERS ASSOCIAIED WITH LOPU-1A.
FILTER CilANGE OUT WILL BE REQUIRED.
s s*
REFERENC(:S: DRAWING 209-038-LO-01 SENSING ELEMENT: LOPU-IB CONTROL CIRCUIT CR7X AR-603 Rev. 20 Page 10 a
LSG 050RE _1 A
(Page 9 of 101) 1GF 0 ANNUNCIATOR RESPON5E IGF-AX3-01-07 0-01-07
--.n_.__,..
.[
TURB GEN LUBE OIL SYS TROUBLE EVENT POINT 0312 INDICATED CONDITION:
o LOP-2 STOP ALARM.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:-
o LO-76-SV AND LO-78-SV CLOSED OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF PUMP TRIP.
DISCUSSION:
I LOP-2 IS THE "A & B" FEED PUMP LUBE OIL PURIFIER CIRCULATING PUMP.
EITHER "A" FW TURBINE CONSOLE (AS SENSED BY 3FW-207-LS) OR "B" FW TURBINE CONSOLE (AS SENSED BY. 3FW-208-LS) INCREASING OIL LEVEL WILL TRIP LOP-2.
{
A HIGH CONSOLE OIL LEVEL MAY BE CAUSED BY A MISMATCH BETWEEN LOP-2 i
DISCHARGE FLOW AND THE RETURN DRAIN FLOW.
l h
REFERENCES:
DRAWING 208-038 LO-07 SENSING ELEMENT: 3FW-207-LS/3FW-208-LS I_
l:
AR-603:
Rev. 20 Page 11 l
--_-__-_________---_a
f f.fi OEV8LJ
.I (Page 10 of 303)
.n
, ~ -.
- 1GF 0 ANNUNCIATOR RESPO'bE TCF-AX3-03 -07 0-01-07
. TURB GEN LUBE Oil SYS TROUBLE EVENT POINT 0316 INDICATED CONDITION:
o LOPU-1A SYSTEM SHUTDOWN.
O REDUNDANT: INDICATION WHICH WILL VERIFY ALARM:
o DIRT ( STRAINER LAMP ILLUMINATED ON LOPU-1A CONTROL PANEL o LOW OIL LEVEL FOR LOT-2 AS SENSED BY TB-329-LS o LOW FLOW LAMP ILLUMINATED l
o HIGH SYSTEM VACUUM 112"HG j
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF LOPU-1A SYSTEM SHUTDOWN.
J DISCUSSION:
i
/~T
REFERENCES:
- DRAWING 209-038-LO-01 l.
SENSING ELEMENT: LOPU-1A CONTROL CIRCUIT CR6X i-
'AR-603 Rev.' 20 Page 12
L NCLOS QRE...I (Page 11 of 103) l :(T
~
l\\J 1CF 0 ANNUNCIA10R RESPONSE 1GF-AX3-01-07 0-01-07 TURB GEN LUBE OIL SYS TROUBLE 1'
EVENT POINT 0317 INDICATED CONDITION:
o LOPU-IB DIRTY FILTER ALARM.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AMBER IND LIGHT ON LOCAL PANEL FOR FILTER #1. AS SENSED BY LO-63-DPIS o AMBER IND LIGHT ON LOCAL PANEL FOR FILTER #2 AS SENSED BY LO-64/65-DPIS o AMBER'IND LIGHT ON LOCAL PANEL FOR FILTER #3 AS SENSED BY LO-66-DPIS OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE-CAUSE OF DIRTY FILTER ALARM.
1 DISCUSSION:
DIRTY FILTER ALARM INDICATES't 25 PSID ON ONE OR ALL OF THE FILTERS ASSOCIATED WITH LOPU-IB.
FILTER CHANGE 0VT WILL BE' REQUIRED,
REFERENCES:
DRAWING 209-038.LO-01 SENSING ELEMENT: LOPU-IB CONTROL CIRCUIT CR7X AR-603 Rev. 20 Page 13
iM.I OSURE...I l
(Page 32 of 303)
V(',D i
1GF 0 ANNUNCIATOR RESPONSE 1C,F-AX3-01-07 0-01-07 TURB GEN LUBE OIL SYS g
TROUBLE EVENT POINT 0318 INDICATED CONDITION:
. o FEEDWATER TURBINE LUBE OIL PURIFIER OVERFLOW CHAMBER LEVEL LOW AS SENSED BY TB-329-LS..
d.M -
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A.VALIO ALARM:
~
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF LOW OIL LEVEL.
DISCUSSION:
LOP-2 IS TRIPPED BY THIS LEVEL SWITCH.
REFERENCES:
DRAWING 208-038 LO-07~
SENSING ELEMENT: TB-329-LS AR-603 Rev. 20 Page 14
l 'd i OkUR E 1 (Page 13 of E U O
H,F 0 ANNUNCIA10R hlSPONSE TGF-AX3-01-09 0-01 09 I
-4=6 e mpi h
engul GLAND STEAN f
DRN TNK LEVEL LOW D_ b._ _ _.. _ m._
EVENT POINT 1701 INDICATED CONDITION:
o GLAND STEAM CONDENSER DRAIN TANK LEVEL <9" AS SENSED BY TD-3-LS.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO ENSURE TDV-40 CLOSED.
DISCUSSION:
A MAR HAS BEEN INSTALLED WHICH ADDED AN ADDITIONAL SOLEN 0ID TO CLOSE 1DV-40 WHEN THE LOW LEVEL ALARM IS RECEIVED. THE LEVEL SETPOINT IS MEASURED FROM PLANT DATUM WITH Tile TURBINE BUILDING FLOOR AT THE 95' ELEVATION. IF TDV-40 IS STUCK OPEN, A POTENTIAL LOSS OF VACUUM CAN OCCUR.
REFERENCES:
DRAWING 208-073 SENSING ELEMENT: TD-3-LS AR-603 Rev. 20 Page 15
l L
i
-LNH OSykE J l:
(Page 14 of 103) g t
1GF O' ANNUNCIA10R RESPONSE TGF-AX3-01-10 0-01-10 c--~r---__,,--
GLAND STEAM SYSTEM
'~
TROUBLE l
EVENT POINT 0252 INDICATED CONDITION:
l-o GLAND STEAM EXHAUST PRESSURE >10" H,0 AS SENSED BY GS-1-PS.
l I \\p) i.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l-OPERATOR ACTIONS FOR A VALID ALARM:
i o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF HIGH PRESSURE.
o ENSURE ONE CLAND' EXHAUST FAN IN OPERATION.
o ENSURE-THE FOLLOWING:
CONDENSATE FLOW TO GLAND STEAM EXHAUST CONDENSER l
FAN IS NOT FULL OF WATER
(.
GLAND STEAM SUPPLY IS NOT EXCESSIVE i.
l L
DISCUSSION:
i
REFERENCES:
DRAWING 208-033 GS-01 g
SENSING ELEMENT: GS-1-PS i
l AR-603 Rev. 20 Page 16
t fNClQSV8E.1 (Page 35 of 103) l Q:
1GF 0 ANNUNCIA10R RISPONSE 1GF-AX3-01-10 0
___._ 10._
j l
l l
)
GLAND STEAM SYSTEM TROUBLE
,_a.n..----....._
i EVENT POINT 0253 H
INDICATED CONDITION:
o GSF-1A TRIPPED.
.i I
REDUNDANT INDICATION WHICH WILL VERIFY M ARM:
.o GREEN LIGHT IS ON WITH A RED FLAG ON COMTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF FAN TRIP.
.o' PLACE ALTERNATE GLAND EXHAUST FAN IN OPERATION.
i..
f DISCUSSION:
L i
I
REFERENCES:
' DRAWING 208-033 GS-01
. SENSING ELEMENT: CS/SC, CS/0 CONTROL STATION CONTACTS, 42/B BREAKER CONTACT l
l-AR-603 Rev. 20 Page 17 i
.____u______
I hcl USUl?E.1 ~
(Page 36 r;f 103)-
l l,,)
A#
.lGF 0 WNUNCIA10R. RESPONSE ICF-AX3-01-10 0-01-10 i
']
GLAND STEAM -
SYSTEM.
TROUBLE -
ikeN EVENT POINT 0254 INDICATED CONDITION:
o GSF-IB TRIPPED.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT IS ON WITH A RED FLAG ON CONTROL STATION.
I OPERATOR ACTIONS FOR A VALID ALARM:
I o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF FAN TRIP.
o PLACE ALTERNATE GLAND EXHAUST FAN IN OPERATION.
DISCUSSION:
t
REFERENCES:
DRAWING 208-033 GS-02 SENSING ELEMENT: CS/SC, CS/0 CONTROL STATION CONTACTS, 42/B BREAKER CONTACT AR-603 Rev. 20 Page 18
l-I t h.Ct 05QR f..1 L
(Page 17 of 103)-
TGF 0 ANNUNCIATOR R SPONSE 1GF-AX3-01-10 0-01-10 u.
l
-..~._:-
GLAND STEAM SYSTEM TROUBLE IN_5 EVENT POINT 0255 INDICATED CONDITION:
o GLAND STEAM PRESSURE IS ONE OF THE FOLLOWING:
HP TURBINE SUPPLY
>6.1 PSIG AS SENSED BY GS-6-PS.
OR ANY LP TURBINE <.5 PSIG AS SENSED BY GS-28, 29,. 32, OR 34-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o COMPUTER POINTS T001 THROUGH T005 MONITOR GLAND STEAM PRESSURES FOR THE LOW PRESSURE AND HIGH PRESSURE TURBINE GLANDS.
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE GLAND STEAM PRESSURES.
DISCUSSION:
GS-28-PS MONITORS THE GENERATOR END OF LP TURBINE 3A.
GS-29-PS MONITORS THE GOVERNOR END OF LP TURBINE 3A.
GS-32-PS MONITORS THE GENERATOR END OF LP TURBINE 3B.
l CS-34-PS MONITORS THE GOVERNOR END OF LP. TURBINE 3B.
REFERENCES:
DRAWING ~208-033 GS-07
)
SENSING ELEMENT: GS-6-PS, GS-28-PS, GS-29-PS, GS-32-PS, GS-34-PS i
.AR-603; Rev. 20 Page 19 u___.________________
_a
.lM L QSM E _1 (Pace JS of 103)
TGF 0 ANNUNCIATOR RESPONSE lcr AX3-02-01 0-02-01 wae =-
- = = =
l.
l TURB GEN
. LIFT Olt PUMP TRIP i
l-(
I EVENT POINT 1621 l
INDICATED CONDITION:
t:
o TBP-6 BREAKER OPEN WITH CONTROL HANDLE IN NORMAL AFTER START.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
f o GREEN LIGHT IS ON WITH A RED FLAG ON CONTROL STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o IF TURBINE' RPM IS-<600 RESTART TBP-6.
l o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE LUBE OIL SYSTEM.
l l
DISCUSSION:
BEARING OIL PRESSURE <3 PSIG AS SENSED BY 18-256-PS ALSO TRIPS 1BP-6 I
7-
REFERENCES:
DRAWING 208-057 TB-05
[ SENSING ELEMENT: CS/SC, CS/0,(CONTROL STATION CONTACTS) 42B BREAKER CONTACT
.q l
\\
L
.AR-603 Rev. 20 Page 20 bo a
I NCl%URL 1 (Puge 39 of 103)
(
)
A_/
1CF 0 A',NUNEIATOR RESPON5E l 1CF-AK3-02-02 0-02-02
)
, ~,- m,
~
l l
TURB GEN LIFT OIL PRESS LOW EVENT POINT 1620 INDICATED CONDITION:
o TURBINE CENERATOR BEARING LII'T OIL PRESSURE <850 PSIG AS SENSED BY TB-331-PS.
/
i i
LJ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE TBM-1 IS SHUTDOWN.
o DO NOT ROLL TURBINE UNTIL ALARM CONDITION IS CLEAR.
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE LUBE oil SYSTEM.
DISCUSSION:
THIS CONDITION SHOULD BE CORRECTED EXPEDITIOUSLY SO AS NOT TO CAUSE THE TURBINE TO BE IDLE FOR AN EXTENDED PERIOD WITH GLAND STEAM APPLIED TO THE SHAFT WHERE A SHAl-T BOW COULD DEVELOP.
s
REFERENCES:
DRAWING 208-057 TB-05
()
SENSING ELEMENT: TB-331-PS AR-603 Rev. 20 Page 21 L_____-.------
QCt05URL 1 (Page 20 of 103)
O 1GF 0 AY; UNCI AlOR RI SPO',$E 1GF-AX3-02-03 0-02-03
- m. _.,e.
_m.- _ _ _.m. -
---?E D
~
TURB GEN
(('.[
OIL PRESS PRETRIP wsCW1 Nr9
.cirJ a.ttm As..&
- SEm:
EVENT POINT 1631 INDICATED CONDITION:
o TURBINE GENERATOR BEARING OIL PRESSURE <6 PSIG AS SENSED BY TB-267-PS.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIP OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-660.
o CHECK MAIN LUBE OIL PRESSURE.
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE LURE OIL SYSTEM.
DISCUSSION:
TURBINE TRIP ON LOW MAIN TURBINE BEARING OIL PRESSURE IS >5 PSIG AND <7 PSIC
REFERENCES:
DRAWING 208-057 TB-15 SENSING ELEMENT: TB-267-PS AR-603 Rev. 20 Page 22
f Kl.05VR[J (Page ?I of 103)
IT U
iGF 0 ANNUNCIA10R'RLSPONSE 10F-AX3-02-04 0-02-04 y - -, _ ~ ~ _
i I
[7Q) l
- TURB GEN 3
EMERG BRG PP i
OVERLOAD EVENT POINT 1619 INDICATED CONDITION:
o TBP-3 MOTOR OVERLOAD.
REDUNDANT INDICATION WHICH WILL VERIFY AIARM:
o WHITE INDICATING LIGHT IS OUT (LUBE OIL PRESSURE <25 PSIG)
OPERATOR ACTIONS FOR A VALID ALARM:
o IF TURBINE ROLLING THEN START TBP-2.
o CHECK MAIN LUBE OIL PRESSURE.
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE THERMAL OVERLOAD ON BREAKER DISCUSSION:
THIS ALARM TELLS YOU THE THERMAL OVERLOAD HAS TRIPPED. YOU PAY STILL HAVE
- THE RED INDICATING LIGHT ON THE CONTROL STATION. IF THE PUMP IS NOT IN OPERATION THEN THE WHITE INDICATING LIGHT (AUTO START TEST PB) SHOULD BE OFF INDICATING PUMP DISCHARGE PRESSURE IS LOW (<25 PSIG).
b)
REFERENCES:
DRAWING 208-057 TB-12
%/
. SENSING ELEMENT:.49(OL)
AR-603 Rev. 20 Page 23 d
!Mt 05VRL1 (Page 22 of 303)
/,_ }
.lGF 0 ANNUNCIA10R RESPONSE TGF-AX3-02-05 0-02-05 i
===vr4 w.-m emiaremr -
a -
~
TG LUBE OIL E1M RESVR LEVEL filGil/ LOW EVENT POINT 1636 INDICATED CONDITION:
o TURBINE LUBE OIL TANK LEVEL >6.9' AS SENSED BY 18-248-LS.
i p l
\\,
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l OPERATOR ACT11 3 FOR A MLID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE HIGH OIL LEVEL.
l 1
DISCUSSION:
1 i
REFERENCES:
DRAWING 208-057.TB-15 1/
SENSING ELEMENT: TB-248-LS r
AR-603 Rev. 20 Page 24
11K!O5URL 1 (Page 23 of 101)
O[O TGF 0 ANNUNCIA10R RESPONSE 1GF-AX3-02-05 0-02 05 L
Vd3[_[
~
TG LUBE OIL RESVR LEVEL HIGH/ LOW 6
EVENT POINT 1637 l
INDICATED CONDITION:
o TURBINE LUBE OIL TANK LEVEL <5.9' AS SENSED BY TB-248-LS.
l l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
l o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE LOW OIL LEVEL.
i l
DISCUSSION:
y l-l.
t l
l r
REFERENCES:
DRAWING 208-057 TB-15
' (
Q..
SENSING ELEMENT: TB-248-LS AR-603 Rev. 20 Page 25
h j>
ESCl.0SURE_1 (Page 24 of 303) if l'V IGF 0 ANNUNCIA10R RESPONSE
- TGF-AX3-02-06 0-02-06
,,,.___m._,.
TURB GEN BRG Oll' PUMP.
big OUT OF SERVICE EVENT-POINT 1678 INDICATED CONDITION:
o TBP-2 IN PULL TO LOCK POSITION.
O
.- Qj REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A. VALID ALARM:
DISCUSSION:
THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.
REFERENCES:
DRAWING 208-057 TB-03 A/
SENSING ELEMENT: CS/PTL CONTROL STATION CONTACT AR-603' Rev. 20 Page 26
l i
J.NCLOSVRL.1 (Page 25 of 303)
TGF 0 PAUNCIA10R RE5bNSE 1GF-AX3-02-06 0-02-06 l
l TURB GEN BRG Oil PUMP EOM OUT OF SERVICE EVENT POINT 1679-1 INDICATED CONDITION:
I o T8P-3 IN PULL TO LOCK POSITION.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
i DISCUSSION:
i
- THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS,
REFERENCES:
DRAWING 208-057 TB-12 SENSING ELEMENT:-CS/PTL CONTROL STATION CONTACT L
AR-60 3..
Rev. 20 Page 27
t Vfj 05URL1 (Page 26 of 103) i TG LUBE OIL VAPOR EXTRCT 1
W5 1 ROUBLE EVENT POINT 1622 INDICA 1ED CONDITION:
o TURBINE GENERATOR LUBE OIL RESERVOIR PRESSURE <1.3" H,0 VACUUM AS SENSED BY TB-285-PS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
COMPUTER POINT T021 l
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE TURBINE OIL RESERVOIR VAPOR EXTRACTOR' FAN (LOF-4) FOR PROPER OPERATION.
l DISCUSSION:
A MISADJUSTED FAN DAMPER AND/OR EXCESSIVE AIR INLEAKAGE COULD CAUSE THIS ALARM.
THE RESERVOIR VAPOR EXTRACTOR FAN KEEPS A SMALL NEGATIVE PRESSURE ON THE TURBINE CENERATOR LUBE OIL RESERVOIR. THE FAN HAS A DISCHARGE DN4PER USED TO AD]UST FLOW TO MAINTAIN THIS SMALL VACUUM.
REFERENCES:
DRAWING 208-057 18-08 n) g SENSING ELEMENT: TB-285-PS v
AR-603
.Rev. 20 Page 28
i.
!,NCLCSURL 1 j
(Page 27 of K3)
.j TGF'0' ANNUNCIATOR.RLSPONSE
-1GF-AX3-02 07 0-02-07 t^
l TG LUBE OIL l:
VAPOR EXTRCT TROUBLE P
EVENT POINT 1643 INDICATED CONDITION:
i o TURBINE GENERATOR SEAL OIL LOOP SEAL OIL TANK. PRESSURE <0.5" H,0 VACUUM '
AS SENSED BY TB-304-PS.
REDUNDANT INDICATION WHICH WILL-VERIFY ALARM:
o COMPUTER POINT G001 AS SENSED BY TB-304-PS.
.o MAGNAHELLIC CAGE AT'TBP-9.
1 OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT. OPERATOR TO INVESTIGATE GENERATOR BEARING OIL
. DRAIN TANK VAPOR EXTRACTOR FAN (TBP-9) FOR PROPER OPERATION.-
i i
i DISCUSSION:-
THE SEAL OIL VAPOR EXTRACTOR FAN KEEPS A SMALL NEGATIVE PRESSURE ON THE'
. TURBINE' GENERATOR SEAL DIL LOOP SEAL. THE FAN HAS A DISCHARGE DAMPER USED-P TO ADJUST FLOW TO MAINTAIN THIS'SMALL VACUUM, i
{., $}.
REFERENCES:
DRAWING 208-057 TB-08 LSENSING ELEMENT: TB-304-PS.
~AR-603:
Rev. 20-Page 29
L NCI 05 URE._.)
(Page 28 of F.,5)
O 1GF 0 ANNUNCIATOR RI SPO%E TGF-AX3-03-01 0-03-01
___. _._.-~~
MAIN Tuna p
EVENT POINT 1624 INDICATED CONDITION:
o TURBINE AUTO STOP OIL PRESSURE <45 PSIG AS SENSED BY T8-324-PS.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC CONTROL PANEL.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-660 OR E0P.
DISCUSSION:
MAIN TURBINE TRIPS ARE AS FOLLOWS:
-LOW CONDENSER VACUUM >7" HgA AND <IO" IlgA
(>20" ligV AND <23"HgV)
-LOW BEARING OIL PRESSURE <7 PSIG AND >5 PSIG
-EXCESSIVE AXIAL THRUST
-REACTOR TRIP
-MANUAL (LOCAL OR REMOTE)
-ELECTRICAL FAULTS (SEVERAL AND VARIOUS)
REIERENCES: DRAWING 208-057 TB-15 O
SENSING ELEMENT: 18-324-PS AR-603 Rev. 20 Page 30
L IMl OSURE.] -
(Page 29 of 103)
.~.__&
~
TGF 0 ANNUNCIATOR RLSPONSE
,1CF-AX3-03-02 0-03-02 r
?
V8 i
'TURB
~
VACUUM PRETRIP EVENT POINT 1630 INDICATED CONDITION:
o MAIN CONDENSER VACUUM > 5" HgA (< 25".HgV) AS SENSED BY TB-265-PS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o CONDENSER VACUUM INDICATION CD-7-PIR.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-607.
o ENSURE BACKUP AIR REMOVAL PUMP IS OPERATING.
o UNIT LOADS < 30%-(= 260 MWe) CONDENSER VACUUM MUST.BE MAINTAINED < 3.5"
' HgA (> 26.5" HgV) ANQ UNIT _ LOADS >30% CONDENSER VACUUM MUST '
i BE MAINTAINED <. 5.5" HgA ' (> 24.5 HgV). IF VACUUM CANNOT BE MAINTAINED l
WITHIN THESE-LIMITS,-IllEN IMMEDIATELY REDUCE REACTOR POWER BELOW THE
- ANTICIPATORY TRIP SETPOINT-AND TRIP THE MAIN TURBINE WITHIN 5 MINUTES OF' L
EXCEEDING CONDENSER VACUUM LIMITS.
j l
~
DISCUSSION':
-THIS; ALARM IS A TRUE PRETRIP ALARM. THE SETPOINT FOR A TURBINE TRIP IS FROM
>7" HgA E.TO
<10"; HgA,
(>20". HgV _ LTO
<23" HgV).
SUBSTANTIAL TURBINE DAMAGE WILL-OCCUR'IF OPERATION CONTINUES FOR MORE THAN.
j 5 MINUTES WHILE VACUUM IS BELOW THE ABOVE STATED LIMITS.
REFERENCES:
. DRAWING'208-057 TB-15 l
SENSING ELEMENT:. TB-265-PS
' AR-603-Rev. 20
- Page 31 L;
1 fliCLO5tffL_1 L (-
(Page 30.of 103)
C 0 k U CIA 10R RESPONSE-TGF-AX3-0503 0-03-03 l
L i.
PREl RIP l
l EVENT POINT 1629 INDICATED CONDITION:
l.'
o THRUST BEARING OIL PRESSURE >35 PSIG AS SENSED BY TB-266-PS.
i.! ; jDg
'O l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l' OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE TURBINE' LOAD.
o REFER TO AP-660.
l:
l-DISCUSSION:
THIS ALARM IS' A TRUE PRETRIP ALARM. THE SETPOINT 'FOR A TURBINE TRIP IS l-L
>65 PSIG TO <80 PSIC.
l j
REFERENCES:
DRAWING 208-057 TB-15 SENSING ELEMENT: TB-266-PS AR-603-Rev. 20 Page 32 o
l l
l I'
LNCIOSURE_1 (Page 31 of 103) i i
1GF 0 ANNUNCIA10R RLSPONSE 1CF-AX3-03 0-03-04 Rf;E TURB THROTTLE PRESSURE HIGH/ LOW EVENT POINT 0947 INDICATED CONDITION:
o TURBINE THROTTLE PRESSURE >939 PSIG AS SENSED BY SP-10-PS.
,O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o THROTTLE PRESSURE INDICATION SP-010A-PIR1.
OPERATOR ACTIONS FOR A VALID ALARM:
j o ENSURE CORRECT MAIN STEAM HEADER PRESSURE SETPOINT IS SET ON IC-10-MS.
o INVESTIGATE CAUSE OF HIGH THROTTLE PRESSURE.
o IF TURBINE IS NOT CONTROLLING, TAKE MANUAL CONTROL OF TURBINE.
l..
DISCUSSION:
i.yN,
REFERENCES:
DRAWING 208-057 MS-14 t'
L
' SENSING ELEMENT: SP-10A-PY2-1,PYI-3, SP-10B-PY2-1,PY1-1 (NNI CONTACTS) i AR 603 Rev. 20 Page 33 L_:_
l 1
i LSO 05!)F.E J l
(Page 32 of 103) j N
(
1CF 0 ANNUNCIA10R RESPONSE 1GF-AX3-03-04 0-03 04
)
=~-----.m Rd TURB THROTTLE PRESSURE HIGH/ LOW i
EVENT P0lNT 0948 1
INDICATED CONDITION:
o TURBINE THROTTLE PRESSURE <835 PSIG AS SENSED BY SP-10-PS.
j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o THROTTLE PRESSURE INDICATION SP-010A-PIR1.
OPERATOR _ ACTIONS FOR A VALID ~ ALARM:
o ENSURE' CORRECT MAIN STEAM HEADER PRESSURE SETPOINT IS SET ON IC-10-MS.
o INVESTIGATE CAUSE OF LOW THROTTLE PRESSURE.
o IF TURBINE IS NOT CONTROLLING, TAKE MANUAL CONTROL OF TURBINE.
ll l
DISCUSSION:
/
REFERENCES:
DRAWING 208-057.MS-14 SENSING ELEMENT: SP-10A-PY2-1 PYI-3, SP-10B-PY2-1,PY1-1 (NNI CONTACTS)
AR-603 Rev._20 Page 34 i
f_NCLOSURE_1 L
(Page 33 of J03)
-[
j' TGF 0 ANNUNCI A10R RESPONSE T GF-AX3- 03-09 0-03-09 i
' n.- -a LOCKOUT RELAY DC POWER LOSS l
l m
EVENT POINT 0713 INDICATED CONDITION:
o GENERATOR NEUTRAL GROUND LOCKOUT RELAY LOSS OF DC POWER.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SECTION, l
REAR OF MCB, AND IS LABELED " GEN #3 NEUTRAL GROUND LOCKOUTS."
l OPERATOR ACTIONS' FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF 'DC POWER.
DISCUSSION:
p i(
DC CONTROL POWER IS SUPPLIED FROM DPDP-4B FUSE #14. TWO-SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
- q. -..
f()
REFERENCES:
DRAWING 208-040 MT-71 i
SENSING ELEMENT:-27C/86GG i
AR-603.
Rev. 20
'Page 35 L1 _____ _ _ _ _
_________..____________.___________________o
INCIOSUM. 1 (Page 34 of 303) 3
_a-g_
.A i
TGF 0 ANNUNCIA10R f4SPONSE 1GF-AX3-03-09 0-03-09 L
LOCKOUT RELAY DC POWER
. LOSS I
EVENT POINT 0714-INDICATED CONDITION:
o SlEP-UP TRANSFORMER / GENERATOR DIFFERENTIAL LOCK 0UT RELAY LOSS OF DC POWER.
- p) -
L REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCK 0UT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON SSR SECTION, REAR OF MCB, AND IS LABELED " STEPUP XFRMR 3 CEN 3 A LOCK 0UTS."
OPERATOR ACTIONS' FOR A VALID ALARM:
o -INVESTIGATE CAUSE OF LOSS OF DC' POWER.
DISCUSSION:
DC CONTROL-POWER IS SUPPLIED FROM DPDP-4A FUSE #8. WO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
REFERENCES:
DRAWING 208-040 MT-72 SENSING ELEMENT: 27C/186T l
-AR-603-Rev. 20 Page 36 J
t..
s
[NC LO5DEC.)
l
'(Pace 35 of.103) 1GF 0 ANNUNCIA10R RE SPONSE TCF-AX3-03-09 0-03-09 LOCKOUT RELAY i
DC POWI.R LOSS F)E EVENT POINT 0715 INDICATED CONDITION:
o GENERATOR DIFFERENTIAL LOCKOUT RELAYS LOSS OF DC POWER.
.h,F'\\
REDUNDANTJINDICATION WHICH WILL VERIFY ALARM:
o LOCK 0UT RELAY AMBER INDICATING-LIGHT IS OFF, LOCATED ON TGR SECTION, REAR OF MCB, AND IS LABELED " GEN #3 A LOCK 0UTS."
OPERATOR' ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED FROM DPDP-4A FUSE #8. TWO SMALL FUSES ARE LOCATED.INSIDE THE MCB FOR THIS CIRCUIT.
I l.s h U
REFERENCES:
DRAWING 208-040 MT-73 SENSING ELEMENT
- 27C/86G AR-603:
Rev. 20-Page 37
I-f l-O i.0 050RE_1 (Page 36 of 303)
]
- (/
.. 1GF 0 ANNUNCIA10R RLSPONSE TGr-AX3-03-09 0-03-09 l
LOCKOUT RELAY I
DC POWER LOSS WJSN
\\
1 o
EVENT POINT 0716 INDICATED CONDITION:
o GENERATOR BACKUP AND NEGATIVE SEQUENCE LOCKOUT RELAY LOSS OF DC POWER.
rh r
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:-
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON TGR - REAR OF MCB, AND IS LABELED " GEN #3 BACKUP & NEG SEQUENCE LOCK 0UTS."
OPERATOR ACTIONS FOR A VALID ALARM:
i o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED TROM DPDP-48 FUSE #14. ALSO 2 SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
REFERENCES:
DRAWING 208-040 MT-74
!g
[SENSINGELEMENT: 27C/86 BUB 2 AR-603.
Rev. 20 Page 38
EN_ CLOSURE 1 E
C (Page 37 of 103) l'k.)\\
1GF 0 ANNUf,CIATOR RFSPONSE TCF-AK3-03-09 0-03-09 i
~
LOCKOUT RELAY DC POWER LOSS E
EVENT POINT 0717 INDICATED CONDITION:
o GENERATOR FIELD FAILURE LOCKOUT RELAY LOSS OF DC POWER.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o LOCK 0UT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SECTION -~ REAR MCB, AND IS LABELED " GEN #3 FIELD FAILURE LOCKOUTS."
l OPERATOR ACTIONS FOR A VALID ALARM:
1 o INVESTIGATE CAUSE OF LOSS OF DC POWER'.
I DISCUSSION:
DC CONTROL. POWER IS SUPPLIED FROM DPDP-4A FUSE #8. TWO SMALL FUSES ARE
' LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
j'
REFERENCES:
DRAWING 208-040 MT-75
.,m.
SENSING ELEMENT: 27C/86FF L
AR-603 Rev. 20 Page 39 i
L BGOSURE J j
(Page 38 of 103) fm; D.
iGF 0 ANNUNCIA10R RESPONSE TGF-AX3-03-09 0-03-09
, - ~ ~
l' LOCKOUT RELAY DC POWER LOSS
~EPf21 EVENT POINT 0718 INDICATED CONDITION:
o 480V ES BUS 3A UNDERVOLTAGE LOCKOUT RELAY LOSS OF DC POWER.
,, \\.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF LOCATED ON THE SSR SECTION OF THE REAR MCB, AND IS -LABELED "480V ES BUS A UV LK/0T 8627/ESA."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED FROM DPDP-5A FUSE #6. TWO SMALL FUSES ARE LOCATED INSIDE THE CONTROL BOARD FOR THIS CIRCUIT.
['
REFERENCES:
DRAWING 208-040 MT-77 I[)
SENSING ELEMENT: 27C/ESA AR-603 Rev. 20 Page 40
'i__________...______
MCl!)SURE _1 (Page 39 of 103)
'f}
=.
V 1GF 0 ANNUNCIA10R RLSPONSE TGF-AX3 03-09 0-03-09 p-...____.___
j._-
i g__
LOCKOUT RELAY i
DC POWER LOSS WlG EVENT POINT 0721 INDICATED CONDITION:
o EXCITER OVERCURRENT AND GENERATOR VOLTAGE / FREQUENCY LOCKOUT RELAY LOSS OF DC POWER.
,,y l
t.
n/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LMKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SECTION OF THE REAR MCB, AND IS LABELED " GEN #3 VOLTS / HERTZ LOCK 0UTS."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED FROM DPDP-4A FUSE #8. TWO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
REFERENCES:
DRAWING 208-040 MT-78
[)').
SENSING ELEMENT: 27C/86EXC l
\\
j AR-603-Rev. 20 Page 41 F
.]
ENCLOSURE 1 (Page 40 of 303) i 1GF 0 ANNUNCIATOR RESPONSE TGF-AX3-03-09 0-03-09
)
t i
LOCKOUT RELAY DC POWER LOSS i
l W
EVENT POINT 0723 INDICATED CONDITION:
o 480V ES BUS 3B UNDERVOLTAGE LOCK 0UT RELAY LOSS OF DC POWER.
f A
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
I o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE SSR SECTION OF THE REAR MCB, AND IS LABELED "480V ES BUS B UV LK/0T 8627/ESB."
l t
OPERATOR ACTIDI:S FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
i DISCUSSION:
DC CONTROL POWER-IS SUPPLIED FROM DPDP-5B FUSE #6. TWO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
i l.
REFERENCES:
DRAWING 208-040 MT-79 SENSING ELEMENT: 27C/ESB 1
AR-603 Rev. 20 Page 42
[NO DSURE_l (Page 41 of 103) 1CF- 0 ANNUNCIA10R RESPONSE 1CF-AX3-03-09 0-03-09 a
LOCKOUT RELAY DC POWER LOSS EVENT POINT 0724 INDICATED CONDITION:
o STEP-UP TRANSFORMER SUDDEN PRESSURE LOCKOUT RELAY LOSS' 0F DC POWER.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON-THE SSR SECTION-
.0F THE REAR MCB, AND IS LABELED " STEPUP, XFMR 3 SUDDEN PRESS LOCKOUTS." '
OPERATOR ACTIONS FOR A. VALID ALARM:
o' INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:-
DC CONTROL = POWER IS SUPPLIED FROM DPDP-48 FUSE #14. TWD SMALL FUSES ARE LOCATED INSIDE.THE MCB FOR THIS CIRCUIT.
1 i=
REFERENCES:
DRAWING 208-040 MT-80 SENSING ELEMENT: 27C/86SPSU.
AR-603.
Rev. 20 Page 43
_ = _ - _ _ _ _ _ _ _ - _ _ _ -.
p.
f NO OSUF.E._1 iO_
(Page 42 of 203)-
i TGF 0 ANNUNCIA10R RESPONSE 1GF-AX3-03-09 0-Ohk 88p smarr or m-usu l
LOCKOUT RELAY l
DC POWER LOSS E
. EVENT POINT 0725 l
INDICATED CONDITION:
o UNIT AUX TRANSFORMER LOCKOUT RELAY LOSS OF DC POWER.
l
\\'
Q.
,s REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FOR THE UNIT AUX TRANSFORMER ONE OR MORE OF THE FOLLOWING:
PHASE DIFFERENTIAL NEUTRAL GROUND SUDDEN PRESSURE LOCKOUT RELAY AMBER INDICATING LIGHTS ARE OFF, LOCATED ON THE SSR SEGION OF THE REAR MCB, AND ARE LABELED " UNIT AUX XFMR 3."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
I DC CONTROL POWER IS SUPPLIED FROM THE FOLLOWING: NEUTRAL GND DPDP-4A FUSE l-
- 11/ PHASE DIFFERENTIAL DPDP-4B FUSE #15 / SUDDEN PRESSURE DPDP-4A FUSE I
- 11.
TWO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR EACH CIRCUIT.
' gj;
REFERENCES:
DRAWING 208-940, MT-81, 82, 83 SENSING ELEMENT: 27C/86TNUA/26TUA/86SPSUA l-i AR-603-Rev. 20 Page 44 l
u____________________z________1____..
EhCtp50RE J i'
(Page 43 of 103)
\\[
TGF 0 ANNUNCI A10R RESPONSF TGF-AX3-03-09 0-03-09 LOCKOUT RELAY DC POWER LOSS g
EVENT POINT 0726 INDICATED CONDITION:
o BACKUP TRANSFORMER LOCKOUT RELAY LOSS OF DC POWER.
(;w/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FOR THE BACKUP ES TRANSFORMER ONE OR MORE OF THE FOLLOWING:
PHASE DIFFERENTIAL NEUTRAL GROUND SUDDEN PRESSURE LOCK 0UT RELAY AMBER INDICATING LIGHTS ARE OFF, LOCATED ON THE SSAA-1 SECTION OF THE-REAR MCB AND ARE LABELED " BACKUP ES XFMR LK/0T RLY."-
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DISPATCHER APPROVAL IS REQUIRED PRIOR TO RESETTING ANY LOCKOUTS WHICH
-HAVE YELLOW CONTROL HANDLES.
DC CONTROL POWER IS SUPPLIED FROM:
FOR SUDDEN PRESSURE AND NEUTRAL GROUND-THEY ARE-DPDP-4A FUSE #11/. PHASE DIFFERENTIAL IS DPDP-4B FUSE #15 TWO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
REFERENCES:
DRAWING 208-040 MT-137, 138, 139 SENSING ELEMENT: 27C/86TNGDBEST, 86PBEST, 86TBEST l
AR-603 Rev. 20 Page 4 5 w __ -_--____ ____
Etal 05URE j i
(Page 44 of I'.3)
('N;
'\\d 1GF 0 ANNUNCIA10R Ri! P(55E TGI-Ax3-03-09 0-03-09 s
~m
~~
[_ _[
LOCKOUT RFLAY DC POWER LOSS I
}
pra A
~-
EVENT POINT 0729 INDICATED CONDITION:
o BACKUP TRANSFORMER LOCKOUT RELAY LOSS OF DC PO4ER.
,a i
i G
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FOR THE BACKUP ES TRANSFORMER ONE OR MORE OF THE FOLLOWING:
PHASE DIFFERENTIAL NEUTRAL GROUND SUDDEN PRESSURE LOCKOUT RELAY AMBER INDICATING LIGHTS ARE OFF, LOCATED ON THE SSR SECTION OF THE REAR MCB AND ARE LABELED "STARTUP XFMR 3 LOCKOUTS."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DISPATC11ER APPROVAL IS REQUIRED PRIOR TO RESETTING ANY LOCKOUTS WHICH HAVE YELLOW CON 1ROL HANDLLS.
DC CONTROL POWER IS SUPPLIED FROM:
FOR SUDDEN PRESSURE AND NEUTRAL GROUND THEY ARE DPDP-4A FUSE #11/ PilASE DIFFERENTIAL IS DPDP-4B FUSE #15 TWO SMALL FUSES ARE LOCATED INSIDE TiiE MCB FOR THIS CIRCUIT.
( N, j
REFERENCES:
DRAWING 208-040 MT-84, 85, 86
,v SENSING ELEMENT: 27C/86SPSTU, 86TNSTU, 86TSTU i
AR-603 Rev. 20 Page 46 u_____
p l.
i
[h(LO1URE J l
(Page 45 of 303)
.(
... Q.
l IGF 0 ANNUNCIATOR RESPONSE TGF-AX3-03-09 0-03-09
~i.
~~
LOCKOUT RELAY DC POWER LOSS l-m 1
-_w--,-__
L EVENT POINT 0730 INDICATED CONDITION:
j o BACKUP ES TRANSFORMER MASTER TRIP LOCK 0UT RELAY LOSS OF DC POWER.
' (3 U
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FOR THE BACKUP ES TRANSFORMER LOCKOUT RELAY AMBER INDICATING LIGHTS ARE OFF, LOCATED ON THE SSR SEGION OF THE MCB AND IS LABELED " BACKUP ES XFMR MASTER LK/0T RLY 'A'.AND
'B'."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
l-l 1
DISCUSSION:
i (j -
REFERENCES:
DRAWING 208-040 MT-141, 142 SENSING ELEMENT: 27C/86BESTMTA, 86BESTMTB AR-603 Rev. 20 Page 47
f N(l.OSURE.J (Page 46 of 103)
- +'-u TGF 0 ANNUNCIA10R RESPONSE 1CF-AX3-03-09 0-03-09 i
l' l.
j.
~ ~. -,..,
LOCKOUT RELAY DC POWER LOSS j
l c__
EVENT POINT 0850 INDICATED CONDITION:
o CUTOUT SWITCHES ARE OPEN, (LOSS OF DC POWER) FOR ONE OR MORE OF THE FOLLO4ING:
i UNIT TRIP PRIMARY OR ALTERNATE LOCKOUT RELAY (86UTPX,PY; 86UTAX,AY) l i
i i
[
REDUNDA W INDICATION WHICH WILL VERIFY ALARM:
l o LOCK 0UT RELAY INDICATING LIGHT IS OFF, LOCATED ON THE GENERATOR FEED AUX ASMBLY SECTION OF THE REAR MCB.
i OPERATOR ACTIONS FOR A VALID ALARM:
l o INVESTIGATE CAUSE OF LOSS OF DC POWER.
I i-DISCUSSION:
l DC CONTROL POWER IS SUPPLIED FROM DPDP-7A FUSE #7 FOR UNIT TRIP PRIMARY l
AND ALTERNATE TRIP RELAYS. TWO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR l
THIS CIRCUIT.
I OPENING THESE CUTOUT SWITCHES DISABLES THE SUBSTATION TRIPS FROM OPENING PLANT BREAKERS AUTOMATICALLY.
J
REFERENCES:
DRAWING 208-079 58-03, 58-04, SB-16, SB-17 I
SENSING ELEMENT: LOA 6,'LOAS, LOA 2, LOA 3 RELAYS
.AR-603 Rev. 20 Page 48
fyCLOSVRE.1 f-(Page 47 of Ei)
{y
'~}
1GF 0 ANNUNCIA10R RLSPONSE 1CF-AX3-03-09 0-03-09 _
LOCKOUT RELAY DC POWER LOSS MZ EVENT POINT 1131 INDICATED CONDITION:
OFFSITE POWER SOURCE TRANSFORMER, MTTR-9; TRANSFORMER LOCKOUT RELAYS LOSS OF POWER' l
(w/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPEPATOR ACTIONS FOR A VALID ALARM:
o NOTIFY RELAY DEPT.
o INVESTIGATE CAUSE OF LOSS OF DC POWER l
DISCUSSION:
WILL REMOVE TRIPPING POWER FROM LOCKOUT RELAYS FOR PHASE DIFFERENTIAL, SUDDEN PRESSURE, AND TRANSFORMER GROUND / NEUTRAL DIFFERENTIAL LOCK 0UT RELAYS LOCATED ON RELAY RACK IN 500 Kv SWITCHYARD CONTROL HOUSE.
REFERENCES:
DRAWING 208-079 5B-18, i
SENSING ELEMENT: BF-4900 / BF-4902 L
AR-603 Rev. 20 Page 49 L.__________._______.____
)
l
(.
i l-FM LD5 PRE 1 i
(Page 48.of 103)
'f)
V TGF 0 ANNUNCIA10R RESPONSE -
1CF-AX3-03-09 0-03-09 l
l l
1
._,___n j
LOCKOUT RELAY l
DC POWER j
LOSS i
l 1
=
a i
EVENT POINT 1175 l
i INDICATED CONDITION:
o REACTOR TRIPPED LOCKOUT RELAY LOSS OF DC P06'ER.
f)\\ -
REDUNDANT INDICATION MICH WILL VERIFY ALARM:
(
o LOCK 0UT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE SSR SECTION OF THE REAR MCB, AND IS LABELED " REACTOR TRIPPED LOCKOUT 86/ REC."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED FROM DPDP-4B FUSE #15. AO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
LOSS OF DC POWER TO LOCKOUT RELAY "86/ REC" WILL DISABLE AUTO TRIP OF MAIN TURBINE ON A REACTOR TRIP.
REFERENCES:
DRAWING 2Cil-040MT-98 3
SENSING ELEMENT: 27C/REA l
l
\\
l AR-603 Rev. 20 Page 50 l
I M I QbV8E._)
]
(Page 49 of 103) lGF 0 ANNUNCIA10R RESPONSE TGF-AX3-03-09 0-03-09 LOCKOUT PELAY DC POWER LOSS E
EVENT POINT 1180 INDICATED CONDITION:
o GENERATOR UNDERFREQUENCY LOCKOUT RELAY LOSS OF DC POWER.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SECTION OF THE REAR MCB, AND IS LABELED "UNDERFREQUENCY LOCK 0UTS."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE.CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED FROM DPDP-4B FUSE #14. D O SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
j:
REFERENCES:
DRAWING 208-040 MT-102 k
/~y SENSING ELEMENT: 27C/81G i N.]
I' AR-603 Rev. 20 Page 51
{5 g
IMLOVRLJ t.
(Page 50.of 303) g%
%j
.TGF' 0 ANNUNCIATOR RESPONSE-
-1GF-AX3-03-09
0-03-09
- LOCKOUT RELAY l
DC POWER LOSS EVENT POINT '1639l INDICATED CONDITION:
- o EH LOW FLUID LEVEL LOCK 0UT RELAY LOSS OF DC POWER.
i.
f-l
{
REDUNDANT INDICATION WHICH VILL VERIFY. ALARM:
l-
. o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SECTION OF THE REAR MCB,-' AND IS LABELED "LO E 1 FLUID LOCKOUT 86/LFT."
l i
OPERATOR ACTIONS'FOR A VALID ALARM:
o INVESTIGATE CAUSE- 0F LOSS OF DC POWER.
i DISCUSSION:
i l
DC CONTROL' POWER IS SUPPLIED FROM DPDP-3A FUSE'#20. TWO SMALL FUSES ARE i
LOCATr') INSIDE' THE MCB FOR THIS CIRCUIT.
LOSS'.0F DC POWER WILL DEFEAT ABILITY OF "86/LFT" LOCK 0UT. TO TRIP EHC' PUMP ON... LOW LEVEL
REFERENCES:
-DRAWING 208-057 TB-16 SENSING FLEMENT: 27C/86LFT I
AR-603L Rev. 20 Page 52 w______--______-_-__
!NCl05VRE_1 (Page 51 of 303) 1GF 0 ANNUNCIA10R RI.SPO% E
'I GF-AX3-03-09 0-03-09
,.~.,-:_-.-_..
._ __ [
LOCKOUT RELAY DC POWER LOSS IE3 EVENT POINT 1674 INDICATED CONDITION:
o TURBINE TRIP LOCK 0UT RELAY LOSS OF DC POWER.
REDUNDAMT INDICATION WHICH WILL VERIFY ALARM:
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SECTION OF THE REAR MCB, AND IS LABELED, "TURB 3 STOP VLVS LOCK 0UTS."
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF DC POWER.
DISCUSSION:
DC CONTROL POWER IS SUPPLIED FROM DPDP-4B FUSE #20. TWO SMALL FUSES ARE LOCATED INSIDE THE MCB FOR THIS CIRCUIT.
REFERENCES:
DRAWING 208-057 TB-22 SENSING ELEMENT: 27C/86TURB AR-603 Rev. 20 Page 53
')
U M OSUR L)
(Page 52 of 103)
ICF 0 ANNUNCIATOR RESPONSE TGF-AX3-04-01 0-04-01 s
?
' HIGH -
EVENT POINT 1632 INDICATED CONDITION:
o LP TURBINE #1. EXHAUST TEMPERATURE >175T AS SENSED BY TB-279-TS.
Em/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 OPERATOR ACTIONS FOR A VALID ALARM:
.o START HOOD SPRAYS.
DISCUSSION:
l l'
MAXIMUM AT BEWEEN CONDENSERS USING LP TURBINE EXHAUST TEMPERATURE IS 50' F.
REFERENCES:
ORAWING 208-057 TB-15 SENSING ELEMENT: 18-279-TS
. AR-603' F.ev. 20 Page 54.
E __ _ ___ _ _-
f M I OSURE_1 l
(Page 53 of 103) p.
l TGF 0 ANNUNCIA10R RESPONSE TGF-AX3 01 0-04-01 l
TURB EXH STM TEMP HIGH EVENT POINT 1633 INDICATED CONDITION:
o LP TURBINE #2 EXHAUST TEMPERATURE >175T AS SENSED BY TB-280-TS.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o START HOOD SPRAYS.
DISCUSSION:
-MAXIMUM AT BETWEEN CONDENSERS USING LP TURBINE EXHAUST TEMPERATURE IS 50' F.-
l(
'C-
REFERENCES:
DRAWING 208-057 TB-15 SENSING ELEMENT: TB-280-TS
~ R-603 Rev.-20 Page 55 A
'l
)
.E NCLOS URE.1 (Page 54 of 103) 1GF 0. ANNUNCIATOR RESPONSE 1GF-AX3-04-01 0-04-01 i
EVENT POINT 1634 INDICATED CONDITION:
l o LP TURBINE #1 EXHAUST TEMPERATURE >250*F AS SENSED BY TB-279-TS.
-O U
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o INCREASE CONDENSER VACUUM, REFER TO OP-607 o INCREASE TURBINE LOAD.
o IF TURBINE LOAD CANNOT BE INCREASED THEN CONSIDERATION SHOULD BE GIVEN TO TAKE THE TURBINE OFF LINE.
DISCUSSION:
HIGH TURBINE EXHAUST TEMPERATURES WITH NORMAL CONDENSER VACUUM ARE CAUSED BY INSUFFICIENT ENERGY BEING REMOVED FROM THE STEAM BY THE LOW PRESSURE TURBINES. BY INCREASING TURBINE LOAD THESE TEMPERATURES WILL DECREASE.
MAXIMUM AT BETWEEN CONDENSERS USING LP TURBINE EXHAUST TEMPERATURE IS 50' F.
t' l
l-,q
REFERENCES:
DRAWING 208-057 TB-15 SENSING ELEMENT: TB-279-TS AR-603 Rev. 20 Page 56
i-t' JNCIO50RfJ (Page 55 of 103)
,jQ
'V 1GF 0 AN'NUNCIATOR RESPONSE TCF-AX3-04-01 0-04-01 TURB EXH STM TEMP HIGH EVENT POINT 1635 INDICATED CONDITION:
o LP TURBINE #2 EXHAUST TEMPERATURE >250T AS SENSED BY TB-280-TS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o INCREASE CONDENSER VACUUM, REFER TO OP-607 o INCREASE' TURBINE LOAD.
o IF TURBINE LOAD CANNOT BE INCREASED THEN CONSIDERATION SHOULD BE GIVEN TO TAKE THE TURBINE OFF LINE.
DISCUSSION:
HIGH TURBINE EXHAUST TEMPERATURES WITH NORMAL CONDENSER' VACUUM ARE CAUSED BY INSUFFICIENT ENERGY BEING REMOVED FROM THE STEAM BY THE LOW PRESSURE TURBINES. BY INCREASING TURBINE-LOAD ~THESE TEMPERATURES WILL DECREASE.
MAXIMUM AT BETWEEN' CONDENSERS USING LP TURBINE EXHAUST TEMPERATURE IS 50* F.
L l7
REFERENCES:
DRAWING 208-057 TB-15 i
\\
(f SENSING ELEMENT: TB-280-TS AR-603 Rev. 20-Page 57
[NCI050RE 1 (Page 56 of %3) lLF 0 ANNUNCIA10R RESPO%I IGF-AX3-04-02 0-04-02
\\
0131 TURBINE STEAM FLOW LOW
\\
EVENT POINT 1638 INDICATED CONDITION:
o AP BEWLEN HIGH PRESSURE TURBINE INLET AND OUTLET <21 PSID AS SENSED BY.
MS-87-PS, WITH EITHER 1661 AND/OR 1662 OUTPUT BREAKERS CLOSED.
REDUNDANT INDICATION WilICH WILL VERIFY ALARM:
o CENERATOR MEGAWATT INDICATION LOW WITH AT LEAST ONE OUTPUT BREAKER CLOSED OPERATOR ACTIONS FOR A VALID ALARM:
o INCREASE TURBINE LOAD.
o IF TURBINE LOAD CANNOT BE INCREASED THEN CONSIDERATION SHOULD BE GIVEN TO TAKE THE TURBINE OFF LINE BY OPENING ANY CLOSED OUTPUT BREAKER (S).
DISCUSSION:
THIS EVENT POINT SIGNALS THE START OF A 60 SECOND TIME DELAY THAT IF Tile CONDITION DOES NOT CLEAR IN THAT TIME THE TURBINE WILL BE TRIPPED.
WHEN THE FIRST OUTPUT BREAKER IS CLOSED A TIMER IS ACTIVATED WITH A 60 SECOND TIME DELAY. IF TURBINE LOAD IS NOT INCREASED DURING THIS TIME THEN A TRIP SIGNAL IS SENT TO THE TURBINE.
O
REFERENCES:
DRAWING 208-057 TB-20 SENSING ELEMENs: MS-87-PS, 2MS-87-PS(TDE 60 SEC)
AR-603 Rev. 20 Page 58
LMLQMJRL.1 (Page 57 of 103) lCF 0 ANh'UNCIATOR RESPONSE TGF-AX3-04-03 0-04-03
_ m._____ _ _ _ _ _ -,
ma d TURBINE LIMITED l
BY VALVE POS EVENT POINT 1660 INDICATED CONDITION:
~
o GOVERNOR VALVE POSITION IS EQUAL TO SELECTED VALVE POSITION LIMIT.
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INDICATED VALVE POSITION LIMIT ON EHC PANEL.
o INDICATED VALVE POSITION ON EHC PANEL.
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE TURBINE LOAD.
o IF UNIT NOT AT FULL POWER INCREASE VALVE POSITION LIMIT.
DISCUSSION:
1 IF TURBINE IS VALVE' POSITION LIMITED WITH ICS IN FULL AUTO AND THE l
GENERATOR OUTPUT FALLS BELOW THE ULD SETTING, A SIGNIFICANT HEADER l'-
. PRESSURE ERROR WILL DEVELOP AND POSSIBLY RESULT IN ICS SHIFT TO TRACK AT l
50 PSIG HEADER PRESSURE ERROR WITH THE TURBINE SilIFTING TO MANUAL.
REFERENCES:
DRAWING 208-057 TB-27 SENSING. ELEMENT: EHC CONTACT IN VALVE POSITION LIMITING CIRCUIT AR-603 Rev. 20 Page 59
)
C_______________________
i (NCLUSURE.1 l
(Page 58 of 103) j
' ~ '
1CF 0 ANNUNCIATOR RLSPONSE TGF-AX3-04-05 0-04-05 i
TURB GEN fld ROTOR VlB HIGH EVENT POINT 1670 INDICAlED CONDITION:
o TURBINE ROTOR VIBRATION >7 MILS ON ANY 10F 7 TURBINE BEARINGS OR >8.5 MILS ON BEARING T-5 HORIZONTAL OR T-6 VERTICAL.
q kJ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o BEARING VIBRATION INDICATORS FOR EACH TURBINE BEARING ON TGF PANEL.
o BEARING VIBRATION INDICATORS ON VMC-1 LOCATED IN TEST INSTRUMENT CALIBRATION ROOM, OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE SEAL OIL EFFLUENT TEMPERATURES ARE BETWEEN 105*F AND 115*F.
o REDUCE TURBINE LOAD.
o IF AT CRITICAL SPEED ACCELERATE TURBINE TO LEAVE CRITICAL SPEED AREA.
o IF VIBRATION IS GREATER THAN OR EQUAL TO 7 MILS, GREATER THAN 8.5 MILS ON BEARING T-5 HORIZONTAL OR T-6 VERTICAL, (ALERT SETTING) THEN NOTIFY SYSTEM ENGINEER o IF VIBRATION IS GREATER THAN OR EQUAL TO 14 MILS (DANGER SETTING) THEN TRIP THE TURBINE.
DISCUSSION:
VIBRATION INSTRUMENTS ARE USED TO MEASURE TURBINE ROTOR VIBRATION ABOVE 600 RPM. BELOW 600 RPM ROTOR ANOMALIES ARE MEASURED BY THE ECCENTRICITY INSTRUMENT.
(~';
A MAJOR CONTRIBUTOR TO GENERATOR VIBkATION PROBLEMS IS SEAL OIL
()
TEMPERATURE, l
REFLRENCES: DRAWING 208-057 TB-27 i
SENSING ELEMENT: TB-4 5 5-511. 18-461-SI1/VMC-1 l
AddO3 Rev. 20 Page 60
l i
ff, CLOSURE 1 (Page 59 of 103) 7._
(
)
\\#
TGF 0 ANNUNCIATOR RLSPONSE 1GF-AX3-04-06
_ 06 0
- = - - - - - _
~
TURB GEN ROTOR ECC DE3 HIGH EVENT POINT 1669 INDICATED CONDITION:
o' TURBINE ROTOR ECCENTRICITY >3 MILS.
,e i
1 k/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INDICATED ECCENTRICITY FOR TURBINE ROTOR (TB-346-KI) ON TGF PANEL.
o ECCENTRICITY INDICATOR (TB-469-ZI) ON VMC-1 LOCATED IN TEST INSTRUMENT CALIBRATION ROOM.
i OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE TURBINE LOAD.
o IF TURBINE IS OFF LINE WITH GLAND STEAM APPLIED, NOTIFY SECONDARY PLANT OPERATOR TO PLACE ON TURNING GEAR.
DISCUSSION:
ROTOR ECCENTRICITY IS A MEASURE OF HOW MUCH THE TURBINE SHAFT IS BOWED. IT IS CAUSED BY UNEVEN HEATING OF THE TURBINE SHAFT AND USUALLY ONLY OCCURS DURING TURBINE STARTUP OR SHUTDOWN AND WHEN THE TURBINE IS NOT ROTATING.
Tl:E BOWING OF THE RO10R IS RECORDED CONTINUOUSLY FROM TURNING GEAR SPEED l
TO APPROXIMATELY 600 RPM. ABOVE 600 RPM THE VIBRATION INSTRUMENTS ARE USED TO INDICATE ROTOR ANOMALIES.
REFERENCES:
DRAWING 208-057 TB-27
~.J SENSING ELEMENT: TB-469-ZI/VMC-1 i
AR-603 Rev. 20 Page 61
L
- )
)
I NG 45URL l (Page 60 of 303)
' jQ,
i ()'
TGF 0 ANNUNCIATOR RLSPONSE TGF-AX3-04-07 0-04-07 1
l r
e.w.44me-amvasamenu sawartner usam mus.=secem i
TURB EXPANSION TROUBLE l
Erra l
~
l EVENT POINT 1665 l
INDICATED CONDITION:
i o HP-LP/ DIFFERENTIAL OR CASE EXPANSION / ABNORMAL.
i
! O g-
' NY l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o DIFFERENTIAL EXPANSION (TB-347-KI) INDICATION ON TGF PANEL.
l o DIFFEREhfrIAL EXPANSION (TB-465/466-ZI) OR CASE EXPANSION (TB-468-ZI)
INDICATORS LOCATED IN TEST INSTRUMENT CALIBRATION ROOM.
l I
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE TURBINE HEATUP RATE.
l DISCUSSION:
DIFFERENTIAL EXPANSION REFERS TO THE RELATIVE LENGTHS OF THE TURBINE ROTOR-l COMPARED TO THE TURBINE CASING. EITHER A LONG OR SHORT CONDITION CAN CAUSE TURBINE DAMAGE IF CONTACT OCCURS. THE CONDITION IS CAUSED BY UNEVEN HEATUP OF TURBINE COMPONENTS AND CAN BE CORRECTED BY SLOdING THE HEATUP RATE.
REFERENCES:
DRAWING 208-057 TB-27 SENSING ELEMENT: TB-465-ZI, TB-466-ZI, TB-468-ZI/VMC-1
%)
t j
AR-603 Rev. 20 Page 62 E
l l
FAQL.05 URE_1
- j..
(Page 61 of 103)
L U[ 3 1GF 0 ANNUNCIA10R RESPONSE TGF-AX3-04-08 0-04-08 1
L._
TURB ROTOR POSITION TROUBLE m
l EVENT POINT 1663 INDICATED CONDITION:
o LP ROTOR THRUST POSITION A OR B/ ABNORMAL.
.r x REDUNDANT INDICATION WHICH WILL' VERIFY ALARM:
o ROTOR POSITION RECORDER (TB-119-ZIR) INDICATION ON TGF PANEL.
o DUAL THRUST INDICATOR (TB-467-ZI) ON VMC-1 LOCATED IN TEST INSTRUMENT CALIBRATION ROOM.
1 1
OPEPATOR ACTIONS FOR A VALID ALARM:
o REDUCE TURBINE GENERATOR LOAD AND INVESTIGATE CAUSE OF THRUST BEARING NOT CONTROLLING ROTOR POSITION.
o IF TURBINE IS TRIPPED BY lHE THRUST BEARING TRIP DEVICE THEN INSPECT THRUST BEARING COMPONENTS.
DISCUSSION:
THE ROTOR POSITION INSTRUMENT MEASURES THE RELATIVE POSITION OF THE ROTOR THRUST COLLAR TO THE THRUST-BEARING SUPPORT. SMALL CHANGES IN ROTOR POSITION CAN OCCUR WITH CHANGING ELECTRICAL LOAD. ANY WEAR ON THE THRUST SHOES RESULTS IN A MOVEMENT OF THE ROTOR AND IS RECORDED ON TB-119-ZIR.
(/
REFERENCES:
DRAWING 208-057 TB-27 SENSING ELEMENT: TB-467-ZI/VMC-1
'AR-603 Rev. 20 Page 63 l
E_______._____.__.___
- 1. _
L.
l l
IL4ClOh08EJ (Page 62 of 103)
I 1
t
-TGF 0 ANNUNCIATOR RESPONSE TGF-AX3-04-09 0-04-09 l
i TURB GEN SPEED CHANNEL TROUBLE I
)
EVENT POINT 1661
]
i i
INDICATED CONDITION:
I o SPEED CHANNEL FAILURE.
f REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
I
\\
o SPEED CHANNEL MONITOR IS BACKLIGHTED ON THE EHC CONTROL PANEL.
l o TURBINE IN MANUAL OR TURBINE SPEED INDICATOR FAILED TO ZERO RPM i
i OPERATOR ACTIONS FOR A VALID ALARM:
o STABILIZE THE PLANT IF THE TURBINE HAS SHIFTED OUT OF ICS CONTROL INTO MANUAL DISCUSSION:
IF PAIN SPEED TRANSDUCER FAILED TURBINE WILL TRANSFER TO MANUAL CONTROL, j
.IF AUX SPEED TRANSDUCER FAILED TURBINE SPEED INDICATOR WILL FAIL TO ZERO (0)
A SPEED CHANNEL ERROR WILL ALSO DISABLE THE TURBINE OVERSPEED TRIP ELECTRICAL BACKUP HEADER PRESSURE CONTROL WITH THE. TURBINE IN PANUAL IS VIA OPERATOR ACTION l
USING GV OR TV OPEN OR CLOSE P/B's IN ADDITION THE TBV'S WILL CONTROL HEADER PRESSURE IF HEADER PRESSURE ERROR IS 50 PSIG, REACTOR BAILEY IS ALSO IN PANUAL, OR ICS DEPAND DECREASES TO 15%.
REFERENCES:
DRAWING 208-057. TB-27, WESTINGHOUSE #81-2, VOL III i}
.ly/
SENSING ELEMENT: EHC CONTACT l
l l
l' AR-603 Rev. 20 Page 64 i_____..__________________._____________________
fNCLMURLJ (Page 63 of 303) 1GF 0 ANNUNCIATOR RESPONSE TGF4yX3-04-09 0-04-09
---,un_.,,a_
TURB GEN SPEED CHANNEL TROUBLE i
1 W
L 9
EVENT POINT 1662 INDICATED CONDITION:
I o SPEED REFERENCE CHANNEL FAILURE.
L r's
')
l%J REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o SPEED REFERENCE MONITOR IS BACKLIGHTED ON THE EHC CONTROL PANEL.
o TURBINE IN MANUAL OPERATOR ACTIONS FOR A VALID ALARM:
o STABILIZE THE PLANT IF THE TURBINE HAS SHIFTED OUT OF ICS CONTROL INTO t
MANUAL DISCUSSION:
.THE EHC CONTROLLER WILL REVERT TO THE MANUAL MODE IF THERE'IS A FAILURE OF.ANY ONE OF THE FOLLOWING CHANNELS: MAIN SPEED, SPELD REFERENCE, LOAD REFERENCE ~.
f-HEADER PRESSURE CONTROL WITH THE TURBINE IN MANUAL IS VIA OPERATOR ACTION I
USING CV OR TV OPEN OR CLOSE P/B's IN ADDITION THE TBV'S WILL CONTROL HEADER PRESSURE IF HEADER PRESSURE ERROR IS 50 PSIG, REACTOR BAILEY IS
'ALSO IN MANUAL, OR ICS DEMAND DECREASES TO 15%.
A
REFERENCES:
DRAWING 208-057 TB-27. WESTINGHOUSE BOOK #81-2, VOL III SENSING ELEMENT: EHC CONTACT lL
'AR-.603 Rev. 20 Page 65 L
L
EKG DS_VRE_l.
(Page 64 of 303)-
' L.
TGF 0 Af4NUNCIA10R RL5PONSE 1GF AX3-04-09 0-04-09 l
L-u- ~ ~. - - -,,m -
TURB GEN,
SPEED CHANNEL TROUBLE M
ms*Jruzes EVENT POINT 1673 INDICATED CONDITION:
i
'o OPC-TRANSDUCER OR SPEED PROTECTION CONTROL CIRCUIT FAILURE.
A iIh REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o OPC FAILURE INDICATION ON EHC CONTROL PANEL.
l l
OPERATOR = ACTIONS FOR A' VALID ALARM:
l-DISCUSSION:
l l-ll
REFERENCES:
DRAWING' 208-057 TB-27
. SENSING ELEMENT: EHC CONTACT
' O
.N j i
i ll l;
Q AR-603.:
Rev. 20 Page 66 i
L_1_
1-
L-ENO QSURE_1 (Page 65 of 103) 1GF 0 ANNUNCIA10R RESPONSE TGF-AX3-04-10 0-04-10
%=-
e TURB AT ZERO SPEED EVENT POINT 1623 INDICATED CONDITION:
o TURBINE GENERATOR SHAFT HAS STOPPED ROLLING.
O k,)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE SHAFT SPEED INDICATION ON EHC CONTROL PANEL.
o COMPUTER POINT T010.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE TURNING GEAR IS ENGAGED AND SHAFT IS TURNING.
o NOTIFY SECONDARY PLANT OPERATOR TO PLACE TURBINE ON TURNING GEAR MANUALLY IF AUTO l-UNCTION DOES NOT OPERATE.
DISCUSSION:
f
REFERENCES:
DRAWING 208-057 TB-06 I
SENSING ELEMENT: 14/ZSX RELAY l
AR-603.
Rev. 20 Page 67 a-_
i J
f NC105VRE_J (Page 66 of.103) l I
')
-1CF 0 ANNUNCIATOR RESPONSE 1CF+AX3-05-01 0
_ 01 1
TURB AMSAC
. CHANT.EL TRIP EVENT POINT 2041 INDICATED CONDITION:
o REACTOR POWER t 45% RTP ANJ FEEDWATER FLOW <17% RATED FLOW ON AMSAC CHANNEL "A".
f~U)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POWER RANCE. NUCLEAR INSTRUMENTS ON MAIN CONTROL BOARD.
o FEEDWATER FLOW (MAIN AND START-UP) INDICATION ON MAIN CONTROL BOARD.
OPERATOR ACTIONS FOR A VALID ALARM:
' o m., uR TO AP-660.
o REFER TO E0P.
DISCUSSION:
AMSAC SENSES REACTOR POWER USING POST ACCIDENT NI'S, AND FEED FLOW USING MAIN AND/OR STARTUP FEED FLOW INSTRUMENTATION.
A
REFERENCES:
DRAWING 205-074 SP-16 SENSING ELEMEMT: ATCP-1, AT-7-FS, AT-8-FS l.
AR-603 Rev. 20 Page 68
[NfLOSURE I
_\\
(Page 67 of 303)
(O TGF 0 ANNUNCIATOR RESPONSE 1GF-AA3-05-01 0-05-01
~~
~
TURBAMSAC CHANNEL TRIP EVENT POINT 2042 INDICATED CONDITION:
o REACTOR POWER t 45% RTP-&NQ FEEDWATER FLOW <17% RATED FLOW ON AMSAC CHANNEL "B".
Q Q,/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POWER RANGE NUCLEAR INSTRUMENTS ON MAIN CONTROL BOARD.
o FEEDWATER FLOW (FAIN AND START-UP) INDICATION ON MAIN CONTROL BOARD.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-660.
o REFER TO E0P.
DISCUSSION:
AMSAC SENSES REACTOR POWER USING POST ACCIDENT NI'S, AND FEED FLOW USING MAIN AND/0R STARTUP FEED FLOW INSTRUMENTATION.
I
REFERENCES:
DRAWING 205-074 SP-17 SENSING ELEMENT: ATCP-1, AT-7 rS, AT-8-FS I: V) l' L
AR-603 Rev. 20 Page 69 l ' _ _ _ u _ _._._
E
E NCI 05tJBE_1 (Page 68 of 103)'
l (
1GF 0 ANNUNCIATOR RESPONSE 1GF-AX3-05-02
'0-05-02
BYPASS l
EVENT POINT 1504 INDICATED CONDITION:
o REACTOR POWER <45% RTP.
f' l
Hb REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POWER RANGE NUCLEAR INSTRUMENTS ON MAIN CONTROL BOARD.
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY LOCAL CABINE1 STATUS IF REACf0R POWER'IS >45% RTP.
~l DISCUSSION:
WITH REACTOR POWER <45% RTP BY POST ACCIDENT NI'S, THEN THE AMSAC CHANNELS ARE BLOCKED FROM TRIPPING.
m(
REFERENCES:
DR WING 205-074
~j' SENSING ELEMENT: ATCP-1, NI-15-NS, NI-14-NS AR-603-Rev. 20 Page 70
1 I t ( l 05URE._1
)
(Page 69 of 103) i I
t
}0-05-03 1GF 0 ANNUNCIATOR RfSPONSE TGF-A).3-05-03 l
I Z__
Gal TURB AMSAC CHANNEL l
IN TEST I
1 i
g.___
EVENT POINT 1239 l
I l
INDICATED CONDITION:
1 o AMSAC CHANNEL "A" IN TEST.
/
)
h_/
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
I I
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY LOCAL CABINET STATUS IF TESTING IS NOT IN PROGRESS.
l l
DISCUSSION:
THE OPPOSITE CHANNEL NOT IN TEST IS BLOCKED FROM TRIPPING.
REFERENCES:
DRAWING 205-074
/
't SENSING ELEMENT: ATCP-1
'R.j l
AR-603 Rev. 20 Page 71 1
1
-(NCLO RRLJ (Page 70 of 103)
O-1GF. 0 ANNUNCI ATOR RE SPONSE 1GF-AX3-05-03 0-05-03
.___m...._._,._,
M
. TURB AMSAC CHANNEL IN TEST i
EVENT POINT 1243 INDICATED CONDITION:
o AMSAC CHANNEL "B" IN TEST.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR~ A VALID ALARM:
- o VERIFY LOCAL. CABINET STATUS IF TESTING IS NOT IN PROGRESS.
DISCUSSION:
THE OPPOSITE CHANNEL NOT IN TEST IS BLOCKED FROM TRIPPING.
1
REFERENCES:
DRAWING 205-074 I
i SENSING ELEMENT: ATCP-1 AR-603 Rev. 20 Page 72
___-__=--___-___=__x___.
INCLOSURE.]
(Page 71 of 103)
O 1GF 0 ANNUNC]ATOR RLSPONSE TGF-AX3-05-05 0-05-05 1
1
. ~ -
., ~., ~, -
j_.__
~
.Fd ~
RADIO FREQ HIGH EVENT POINT 2005 INDICATED CONDITION:
o MAIN GENERATOR RADIO FREQUENCIES ARE HIGH AS SENSED BY RF MONITORING.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RF MONITORING CABINET LOCAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE RF MONITORING CABINET.
o NOTIFY SYSTEM ENGINEER TO C0f9ARE WITH OTHER KNOWN DATA.
o REFER TO OP-701.
DISCUSSION:
THIS ALARM SERVES AS AN EARLY WARNING OF A GENERATOR FAILURE SUCH AS INSULATION BREAKDOWN AND/0R CAS SPACE IMPURITIES THAT MAY HAVE ENTERED THE GAS SPACES.
THE SYSTEM CONSISTS OF FOUR DETECTORS (ONE FOR EACH PHASE AND ONE FOR THE
- 8 BEARING) WHICH ARE MONITORED INDIVIDUALLY. THE SYSTEM CYCLES THROUGH ALL FOUR POINTS, AND IF ONE EXCEEDS THE ALARM VALUE THE ALARM IS SOUNDED.
THE SYSTEM ENGINEER CAN ASSIST IN DETERMINING IF A VALID CONDITION EXISTS IN THE GENERATOR OR IF THE RF MONITORING EQUIPMENT IS FAILED.
REFERENCES:
DRAWING 208-057 TB-033 SENSING ELEMENT: TB-449-SS AR-603 Rev. 20 Page 73
I M LOS M C.)
(Page 72 of 103)
'L' TGF 0 ANNUNCIATOR RESPONSE 1GF-AX3-05-06 0-05-06 i
i I
I
.n.--
l l
t TURB GEN CONDITION MON E
HIGH l
L EVENT POINT 1956 INDICAlED CONDITION l
o HYDROGEN COOLING GAS CONliu4INATED WITH HIGH CONCENTRATION OF PARTICLES l
INSIDE MAIN ELECTRICAL GENERATOR.
l /']
i ~ (s REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
L o HIGH ALARM ON TB-448-AIR TGR SECTION, REAR MCB.
i i
i OPERATOR ACTIONS FOR A VALID ALARM:
l o VERIFY CONDITION ON TB-448-AIR, TGR SECTION, REAR MCB.
o REFER TO OP-701.
l o TAKE A BACKUP SAMPLE PER SECTION 4.14 0F PT-325.
DISCUSSION:
1 THIS ALARM SERVES AS A WARNING OF GENERATOR FAILURE SUCH AS INSULATION BREAKDC)WN AND/OR GAS SPACE IMPURITIES THAT MAY HAVE ENTERED THE GAS i
SPACES.
REFERENCES:
DRAWING 208-057 TB-033 SENSING ELEMENT: TB-448-AT AR-603 Rev. 20 Page 74 i
L__z____________--_--.___-___--._-.-.--_'
l l
. ENCL =05USE.)
(Page 73 of 103)
/" %
-TGF 0 ANNUNCIATOR RESPONSE TGF-AX3 05-08 0-05-08
-)
GEN AIR SIDE DC SEAL PP OUT OF SERVICE
)
f L
EVENT POINT 1676 INDICATED CONDITION:
o TBP-10 LOSS OF DC POWER.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HYDROGEN PANEL ALARM.
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY P! ANT OPERATOR TO INVESTIGATE CAUSE OF LOSS OF POWER.
4 o NOTIFY CHEMISTRY TO MONITOR GENERATOR AREA FOR HYDROGEN CONCENTRATION.
DISCUSSION:
TBP-10 IS POWERED FROM DPDP-3B SWITCH #13. IF THIS CIRCUIT IS DEENERGIZED THEN THIS ALARM IS RECEIVED. THE CONTROL CIRCUIT FOR TBP-10 IS POWERED FROM DPDP-3B SWITCH #17. NO ALARM IS ASSOCIATED WITH A LOSS OF POWER ON THIS POWER SUPPLY.
[
REFERENCES:
DRAWING 208-057 TB-13 SENSING ELEMENT: 3CR RELAY AR-603 Rev. 20 Page 75
ENCLOSURL_J i
(Page 74 of.103)
)
~U TGF 0 ANNUNCIATOR RESPONSE 0 05-09 1GF AX3-_05-09
~
1 HYDROGEN PANEL ALARM ersaus EVENT POINT 1644 i
INDICATED CONDITION:
o AT LEAST 1 0F 13' DROP TARGETS HAS FALLEN ON THE HYDROGEN ALARM PANEL.
i
)
REDUNDANT INDICATION.WHICH WILL VERIFY ALARM:
)
OPERATOR ACTIONS FOR A VALID ALARM:
'o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE HYDROCEN ALARM PANEL.
o REFER TO AR-921.
j DISCUSSION:
THE FOLLOWING CONDITIONS ARE ALARMED AT THE HYDROGEN ALARM PANEL:
H PURITY PRESSURE H SUPPLY H, TEMPERATURE H SIDE HlGH/ LOW H,HIGH/ LOW PkESSLOW HIGH LdVELLOW SEAL OIL WATER DETECTED SEAL OIL TURBINE DEFOAMING TANK PRESS LOW HIGH ALARM B/U PRESS LOW LEVEL HIGH AIR SIDE SEAL H SIDE SEAL AIR SIDE SEAL OIL ALARM PANEL OIL PUMP OFF OilPUMPOFF B/U PUMP RUN DC POWER FAIL
~h
REFERENCES:
DRAWING 208-057 TB-17 NJ f
SENSING ELEMENT: VARIOUS INPUTS TO HYDROGEN ALARM PANEL AR-603' Rev. 20 Page 76 L________..
l..
IMl.0508E_1
-(Page 75 of 103)
O
'IGF 0 ANNUNCIA OR RESPONSE TGF AX3-05-JO 0-05-30 N.t T91L+..S
- gsJgSO23 gw pt,9sJ m'*****
HYD90 GEN SUPPLY l'RESS LOW l
L WhtS _
1 EVENT POINT 1524 INDICATED CONDITION:
o HYDROGEN MANIFOLD SUPPLY PRESSURE <80 PSIG AS' SENSED BY HY-81-PS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID Al. ARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE HYDROGEN TANK PRESSURE.
l DISCUSSION:
REFERENCES:
DRAWING 209-043 (NG-01)
D SENSING El.EMENT: HY-81-PS s
AR-603-Rev, 20~
Page 77
[NG 05_UBE_1 (Page 76 of 303)
!(
1CF 0 ANNUNCIATOR RISPONSE 1CF-Ax3-06-01 0-06-01
\\
ews-arv e..==
sw-ramunumm
- r. er.vens.,
1 I.
-.. ~
GENERATOR TRIP l
l i
i i
EVENT P0lNT 0683 i-INDICATED CONDITION:
o GENERATOR NEUTRAL GROUND LOCKOUT RELAY TRIPPED.
i (h
1 L.)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TCR SECTION OF THE REAR MCB.
1 i
OPERATOR ACTIONS FOR A VALID ALARM:
p o REFER TO E0P.
o REFER TO AP-660.
DISCUSSION:
- p..
I'
REFERENCES:
DRAWING 208-040 MT-71 SENSING ELEMENT: 86GG-2 AR-603 Rev. 20 Page 78
ErsLOSURE_1 4
(Page 77 of 103) 1GF 0 ANNUNEI A10R k[SPOf'SE TGF-AX3-06-01 0-06-01 GENERATOR 1 RIP EVENT POINT 0684 INDICATED CONDITION:
o STEP-UP TRANSFORMER / GENERATOR DIFFERENTIAL LOCK 0UT RELAY TRIPPED.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE SSR SECTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO E0P.
o REFER TO AP-660.
DISCUSSION:
REFERENCES:
DRAWING 208-040 MF-72 SENSING ELEMENT: 186T-2X AR-603 Rev. 20 Page 79
i~
ENO 05UM J (Page 78 of 103) h(H 1CF.0 ANNUNCIATOR RESPONSE TGF-AX3-06-01 0-06-01 GENERATOR TRIP a
EVENT POINT 0685 INDICATED CONDITION:
o GENERATOR DIFFERENTIAL LOCK 0UT RELAY TRIPPED.
\\
U REDUNDANT' INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON.THE TGR-SECTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO E0P.'
o REFER TO AP-660.
DISCUSSION:
/M~
h-
REFERENCES:
DRAWING 208-040 MT-73 l -
SENSING ELEMENT: 86G-2
.AR-603 Rev. 20 Page 80 L.
E__.
INCLOSURE J (Page 79 of 103) i I
GENERATOR TRIP EVENT P0lNT 0686 INDICATED CONDITION:
o GENERATOR BACKVP AND NEGATIVE SEQUENCE LOCKOUT RELAY TRIPPED.
(~~)
kJ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TGR SELTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO EOP.
.o REFER TO AP-660.
DISCUSSION:
- /N
REFERENCES:
DRAWING 208-040 MT-74 SENSING ELEMENT:.86B08-2 AR-603 Rev. 20 Page 81 l
l lM lOSUfL_1
[
(Page 80 of 103)
- 1GF 0 ANNUNCIA10R RESPONSE 1GF-AX3-06-01 0-06-01 GENERATOR TRIP
/
EVENT POINT 0687 INDICATED CONDITION:
o GENERATOR FIELD FAILURE LOCK 0UT RELAY TRIPPED.
10 k/
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC' PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE TCR SEC110N OF THE REAR MCB.
j OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO E0P.
o REFER TO AP-660.
DISCUSSION:
/~T
't").
REFERENCES:
DRAWING 208-040 MT-75 SENSING ELEMENT: 86FF ;
AR-603 Rev. 20 Page 82
i l!.Ct.05URE 1 i
(Page 83 cf 103)
-( )'
TGF O'ANNUNCIA10R RESPONSE TGF-AX 3 01 0-06-01 i
GENERATOR TRIP i
EVENT POINT 0690 INDICATED CONDITION:
o STEP-UP TRANSFORMER SUDDEN PRESSURE LOCK 0UT RELAY TRIPPED.
7-~g kyA REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCK 0UT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE SSR SECTION 0F THE REAR MCB.
-l OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO EOP.
i o REFER.TO AP-660.
DISCUSSION:
l
REFERENCES:
DRAWING 208-040 MT-80 SENSING ELEMENT: 86SPSU-2X AR-603 Rev. 20 Page 83
L l
UKLOSUT;E._1 (Page 82 of 103)'
l:f'g:
' 1.Cl 1GF 0 ANNUNCIATOR RLSPONSE 1GF-AK3-06-01 0-06-01
.l GENERATOR TRIP EVENT POINT 0720 L
INDICATED CONDITION:
o EXCITER OVERCURRENT AND GENERATOR VOLTAGE / FREQUENCY LOCKOUT RELAY TRIPPED.
. Q' i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT 15 0FF, LOCATED ON THE TGR SECTION OF THE REAR MCB~.
OPERATOR ACTIONS FOR A VALID ALARM:
i.
' o REFER TO E0P.
- o. REFER TO AP-660.
L DISCUSSION:
'(b V-.
REFERENCES:
DRAWING 208-040 MT-78 SENSING ELEMENT: 86EXC-2 l
AR-603 Rev. 20 Page 84 L_._1____._._____.___
tNC!050RE.J-(Page 83 of 103) l ' (%.
V 1GF 0 ANNUNCIATOR RESPONSE 1Gr-AX3-06-01 0-06-01 i
.y.!/f3, I
I h
GENERATOR TRIP l
t i
EVENT POINT 0825 INDICATED CONDITION:
o 500 KV' SUBSTATION PRIMARY TRIP LOCKOUT RELAY TRIPPED.
\\
.I. m) t:~-
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE GENERATOR FEED AUX ASMBLY.5ECTION OF THE REAR MCB..
OPERATOR ACTIONS FOR A VALID ALARM:
lo REFER TO E0P.
o REFER TO AP-660.
DISCUSSION:
. n
REFERENCES:
DRAWING 208-079.5B.
SENSING ELEMENT: 86/UTPX AR-603L Rev. 20 Page 85
__d
f DiCLOSURE_1 (Page S4 of 103)
D.
L'M i
TGF 0 ANNUNCIA10R RESPONSE TGF-AX3 06-01 0-06-01 l
l l
l
~ GENERATOR TRIP
'i
.. = _
EVENT POINT 0826 i
l INDICATED CONDITION:
o 500 KV SUBSTATION ALTERNATE TRIP LOCK 0UT RELAY TRIPPED.
,0 Lj REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCKOUT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE GENERATOR FEED AUX ASMBLY SECTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALIO ALARM:
o REFER TO E0P.
o REFER TO AP-660.
)
l
\\
DISCUSSION:
n
REFERENCES:
DRAWING 208-079 5B-04 SENSING ELEMENT:.86/UTAX l
AR-603 Rev. 20 Page 86 t.___._.
E N_(l.05 U RE_]
r.
(Page 85 of 103)
Ch ty-L.
1GF 0 ANNUNCIATOR RLSPONSE TGF-AX3-06-01 0-06-01 t.
wram v *m w..e w-=m m WM 4 GENER/4 TOR T' alp l
EVENT POINT 1176 NDICATED CONDITION:
o REACTOR TRIPPED LOCK 0UT RELAY TRIPPED.
/~'N hv'
{
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TURBINE TRIPPED INDICATION ON EHC PANEL.
o LOCK 0UT RELAY AMBER INDICATING LIGHT IS OFF, LOCATED ON THE SSR SECTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO EOP.
o REFER TO AP-660, l
l I
DISCUSSION:
i i
,(
v
REFERENCES:
DRAWING 208-040 MT-98 SENSING ELEMENT: ~86 REC AR-603 Rev.-20 Page 87
i FNCLOSURE_1 (Page 86 of 103)
(').
TCF 0 ANNUNCIA10R RESPONSE TGF-AX3-06-02 0-06-02 l
l
~
~
WA l
~
EXCITER BREAKER:
1 TRIP l
EVENT POINT 1648 1
INDICATED CONDITION
- i o EXCITATION REGULATOR SUPPLY BREAKER TRIPPED.
i
' G('N l-I r
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT IS ON WITH A RED FLAG ON CONTROL STATION.
o EXCITER CURRENT INDICATION ON MAIN CONTROL BOARD.
l OPERATOR ACTIONS FOR A VALID ALARM:
1 l'
l t
DISCUSSION:
r~m
REFERENCES:
DRAWING 208-057 TB-09 f-SENSING ELEMENT:CS/SC CS/0 CONTROL SWITCH CONTACTS,4IAX1/B BREAKER CONTACT AR-603 Rev. 20 Page 88 L_______-_
l B C10Spgl.1
)
(Page 87.of 103)
J I fo TGF 0 ANNUNCIATOR RESPONSE
~1 GF-AX3 03 0-06-03 l
n m e. _. __
GEN VOLT / HERTZ PRETRIP EVENT POINT 1651 INDICATED CONDITION:
o EXCESSIVE VOLTAGE TO HERTZ RATIO.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM; o TURBINE SPEED INDICATION.
o UNIT VOLTAGE INDICATION.
o EXCITER CURRENT INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o RESTORE SPEED TO SYNCHRONOUS SPEED.
o IF SPEED CANNOT BE INCREASED, TRIP THE FIELD BREAKER.
I DISCUSSION:
i THE POTENTIAL FOR DAMAGE OCCURS WHEN MAGNETIC DEVICLS ARE SATURATED BY l
EXCESSIVE EXCITATION IN AN ATTEMPT TO MAINTAIN OUTPUT VOLTAGE WHEN SPEED IS DECREASING. THIS ALARM IS A TRUE PRETRIP CONDITION TO THE VOLTS / HERTZ 86 LOCKOUT RELAY WHICH INITIATES A TURBINE TRIP.
p i_/
REFERENCES:
DRAWING 208-057 TB-18 SENSING ELEMENT: 59/81 CONTACT i
AR-603 Rev. 20 Page 89 L.
EMIOSURL.1 l
(Page 88 of 103) fy.
1GF 0 ANNUNCIA10R RESPONSE 1C[-Akk06-04 0-06-04 1
l 1
0" GENERATOR UNDER FREQUENCY
=
EVENT POINT 1199 INDICATED CONDITION:
o GENERATOR FREQUENCY <58.5 HERTZ AS SENSED BY UNDERFREQUENCY CIRCUIT #F2.
i 1/T d
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GENERATOR FREQUENCY INDICATION ON MAIN CONTROL BOARD.
o UNDERFREQUENCY TIMER F2 OPERATING,. LOCATED ON THE TGR SECTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SYSTEM DISPATCHER.
DISCUSSION:
. UNIT #3'S FREQUENCY CORRECTION CIRCUITS ARE DISABLED. ANY SYSTEM FREQUENCY PROBLEMS SHOULD BE DIRECTED TO THE SYSTEM DISPATCHER FOR CORRECTION. THE GENERATOR LOCKOUT TRIP ON UNDERFREQUENCY IS AT 58 HERTZ DECREASING.
/
\\.
V
REFERENCES:
DRAWING 208-040 MT-102 SENSING ELEMENT: CP/58.5HZ/F2 AR-603.
Rev. 20 Page 90
l-i
'! NCl 050i4 El l
(Page 89 of 103)
.j 3 IGF 0 ANNUNCIATOR RESPONSE TGF-AX3-06-04 0-06 04
_ m _,.-- _ _ _ _
1 N'd GENERATOR UNDER FREQUENCY i
i i
EVENT POINT 1200 4
1 INDICATED CONDITION:
1 o CENERATOR FREQUENCY <59.5 llERTZ AS SENSED BY UNDERFREQUENCY CIRCUIT #F1.-
m (v)-
4 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GENERATOR FREQUENCY INDICATION ON MAIN CONTROL BOARD.
o UNDERFREQUENCY TIMER F1 OPERATING, LOCATED ON THE TGR SECTION OF THE REAR MCB.
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SYSTEM DISPATCHER.
DISCUSSION:
UNIT #3'S FREQUENCY CORRECTION CIRCUITS ARE DISABLED. ANY SYSTEM FREQUENCY l
PROBLEMS-SHOULD BE DIRECTED TO THE SYSTEM DISPATCHER FOR CORRECTION. THE GENERATOR LOCKOUT TRIP ON UNDERFREQUENCY IS AT 58 HERTZ DECREASING.
V
REFERENCES:
DRAWING 208-040 MT-102 SENSING ELEMENT: CQ/$9.5HZ/F1 AR-603-Rev. 20 Page 91
i l
ERCLD5WE_1 l _
(Page 90 of 103)
(0
[.O 1GF 0 ANNUNCIATOR RESPONSE T GF-' AX3 04 0-06-04 m,.---_..-__n N
GENERATOR UNDER FREOUENCY EVENT POINT 1999 INDICATED CONDITION:
o GENERATOR FREQUENCY <58 HERTZ FOR >I2 SECONDS AS SENSED SV UNDERFREQUENCY CIRCUIT #T3.
,,\\
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:-
o TURBINE TRIP OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO E0P.
o REFER TO AP-660.
o NOTIFY SYSTEM DISPATCHER.
DISCUSSION:
THE DESIGN BEHIND THIS CIRCUIT WAS TO ALLOW UNIT #3 AUXILIARY LOADS TO REMAIN POWERED FROM THE AUXILIARY TRANSFORMER AFTER A SYSTEM FREQUENCY L-DISTURBANCE BY OPENING THE UNITS OUTPUT BREAKERS' AND ALLOWING THE UNIT TO
_ RUNBACK TO THE ICS MINIMUM LOAD SETTING. HOWEVER, A 500 KV SUBSTATION h
CONTACT NOW ENERGIZES 86/UTPX WHEN THE 12 SECOND TIMER ELAPSES, AND A TURBINE TRIP RESULTS. (SEE DRAWINGS 208-079 5B-03,58-05) l
, f] -
' ' 'd
REFERENCES:
DRAWING 208-040 MT-102 1
SENSING ELEMENT: CN/58HZ/T3
.AR-603 Rev. 20 Page 92 u_ __ _ _ _ _ _ _ _ _ _ _
I f tCQh0RLI (Page 91 of 103)
(
1 TGF 0 ANNUNCIATOR RESPONSE TGF-AX3-06-05 0-06-05 l
1
~
I l
l EXCITER fig 3 FIRING CKT POWER LOSS EVENT POINT 1653 INDICATED CONDITION:
o LOSS OF POWER SUPPLY TO EXCITER FIRING CIRCUIT DRAWER #1.
b) i
'm/
l l
REDUNDANT INDICATION WilICH WILL VERIFY ALARM:
l L-I OPERATOR ACTIONS FOR' A VALID ALARM:
o INVESTIGATE CAUSE OF LOSS OF POWER.
j o CHECK FIRING CIRCUIT DRAWER #1 POWER SUPPLY FUSE i
' DISCUSSION:
l I
THE FIRING CIRCUIT DRAWERS ARE REDUNDANT AND IN PARALLEL. THEY SUPPLY j
FIRING PULSES TO THE INVERTER TYPE POWER AMPLIFIER. EITHER FIRING CIRCUIT DRAWER WILL PROVIDE SERVICE, BUT THE LOSS OF POWER SHOULD BE INVESTIGATED AND CORRECTED..
.- (~y V
REFERENCES:
DRAWING 208-057 TB-18 SENSING ELEMENT: FIRING CIRCUIT #1
'AR-603 Rev. 20 Page 93
ENfLOSVREj (Page 92 of 303)
,~-
D' 1GF 0 ANNUNCIATOR RESPONSE 1GF-AX3-06-05 0 05-05
_,____,a--.--
POWER LOSS i
EVENT POINT 1654 l
INDICATED CONDITION:
o LOSS OF POWER SUPPLY TO EXCITER FIRING CIRCUIT DRAWER #2.
g( f i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i 1
1 OPERATOR ACTIONS FOR A VALID ALARM:
, o INVESTIGATE CAUSE OF LOSS OF POWER.
'o CHECK FIRING CIRCUIT DRAWER #2 POWER SUPPLY FUSE DISCUSSION:
i:-
THE FIRING CIRCUIT DRAWERS ARE REDUNDANT AND IN PARALLEL. THEY SUPPLY FIRING PULSES TO THE INVERTER TYPE POWER AMPLIFIER. EITHER FIRING CIRCUIT
[-
DRAWER WILL PROVIDE SERVICE, BUT THE LOSS OF POWER SHOULD BE INVESTIGATED I
AND CORRECTED.
es
REFERENCES:
DRAWING 208-057 TB-18 SENSING ELEMENT: FIRING CIRCUIT #2 AR-603 Rev. 20 Page 94
l
[NfI 05yRLI i
(Page 93 of 103)
("g V
1GF 0 ANNUNCIATOR RfSPONSE TCF AX3-06-06 0-06-06 EXCITER GROUND g
i EVENT POINT 1656 INDICATED CONDITION:
o EXCITER CIRCUIT CROUND DETECTED f'N N.)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF EXCITER GROUND.
o NOTIFY SYSTEM ENGINEERING.
\\
DISCUSSION:
THE INSTALLED GROUND DETECTOR PERFORMS AN AUTOMATIC GROUND CHECK ONCE EACH 24 -HOURS, USUALLY ON THE MIDNIGHT SHIFT. IT WILL ANNUNCIATE FOR ALL VALUES OF INSULATION RESISTANCE BELOW.13K OHMS,- AND BETWEEN 13K OHMS AND 100K L
OHMS DEPENDING ON GROUND LOCATION. ANY VALUE ABOVE 100K OHMS IS CONSIDERED
(
SATISFACTORY.
L.,n; i
l
REFERENCES:
DRAWING 208-057 T8-18 SENSING ELEMENT: EXCITER SWITCHGEAR.64 CONTACT AR-603 Rev. 20-Page 95 c_. _
ENCLOSQRE.J (Page 94 of 103) 1GF 0 ANNUNCIATOR RESPONSE TGF-AX3-06-07 0-00-07 i+
l EXCITER LIMITED PRETRIP erma EVENT POINT 1650 INDICATED CONDITION:
o EXCITER EXCITATION IS HIGHER.THAN A PRESET VALUE.
b')
%.)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o EXCITER VOLTAGE INDICATION ON MAIN CONTROL BOARD.
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE EXCITER EXCITATION TO NORMAL VALUES BASED ON VOLTAGE INDICATION.
DISCUSSION:
OVEREXCITATION RESULTS IN EXCESSIVE TEMPERATURE OF THE SYNCHRONOUS FIELD WINDINGS. THIS ALARM, CALLED AN " EXCITATION FORCING ALARM" WARNS THAT
-EXCITATION PRESET VALUES HAVE BEEN EXCEEDED.
n
.(
REFERENCES:
ORAWING 208-057 TB-18 SENSING ELEMENT: EXCITER SWITCHGEAR K4 CONTACT i
I
.AR-603
'Rev. 20 Page 96
ENCL 0SURL_I l
(Page 95 of 103)
{
TGb-AX3-06-08 1GF 0 ANNUNCIATOR RESPONSE 0-06-08 EXCITER RAISE
)
INHIBIT EVENT POINT -1522 INDICATED CONDITION:
WITH UNIT OUTPUT BREAKERS OPEN AND THE FOLLOWING:
o GENERATOR EXCITER HAS REACHED AN EXCITATION LIMIT IMPOSED.
- m N'
o GENERATOR EXCITER HAS REACHED A CURRENT LIMIT IMPOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GENERATOR OUTPUT VOLTAGE WILL NOT INCREASE WHEN EITHER THE BASE ADJUST OR VOLTAGE ADJUST KNOBS ARE INCREASED.
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE EXCITER EXCITATION TO NORMAL VALUES BASED ON VOLTAGE INDICATION.
o IF EXCITATION APPEARS NORMAL BUT THE ALARM WILL NOT CLEAR, NOTIFY SYSTEM ENGINEERING TO EVALUATE THE PROBLEM.
DISCUSSION:
OVEREXCITATI21 RESULTS IN EXCESSIVE TEMPERATURE OF THE SYNCHRONOUS FIELD WINDINGS. THIS ALARM MAY ANNUNCIATE TEMPORARILY DURING RELAY OPERATION FOR STARTUP AND OTHER TIMES WITH THE MAIN GENERATOR IN A NO-LOAD CONDITION.
f )!
L
REFERENCES:
DRAWING 208-057 TB-18 SLNSING ELEMENT: EXCITER SWITCHGEAR DX3 CONTACT AR-603 Rev. 20 Page 97 l
l FNO OSUREj (Page 96 of 103) tv TGF 0 ANNUNCIATOR RESPONSE TGF-AX3-06-09 0-06-09
! GEN RELAY POT XFMR FAILURE i
I 4
EVENT POINT 0688 INDICATED CONDITION:
J o GENERATOR POTENTIAL TRANSFORMER FAILED,
. ("'N SIDUNDANT INDICATION WHICH WILL VERIFY ALAM!:
l
\\
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE LOSS OF GENERATOR POTENTIAL TRANSFORMER.
i ClSCUSSION:
j LOSS OF THE GENEPATOR P01ENTIR TRANSFORMER WILL HAVE UNPREDIGABLE EFFECTS ON THE OPERATION 0F Tli_ GENERATOR tiACKUP-RELAY (ie. MAY CAUSE IT l
TO ACTUATE INADVERTENTLY OR FAIL TO OPERATE FOR' A VALID CONDITION).
THE GENERATOR BACKUP RELA ( PROVIDES TRIP FUNCTION FOR THE MAIN GENERATOR I
.O OUTPUT BP.EAKERS FOR CENERATOR OR' BUS ELECTRICAL FAULTS.
REFERENCES:
DRAWING 208-040 MT-76 I
SENSIf p LEMENT: K60/A RELAY CONTACT AR-633-Rev. 20 Page 98
fMLDSV8E.1 (Page 97 of 303) 1GF 0 ANNUNCI ATOR RESPONSE 1GF-AX3-06-09 0-06-09 GEN RELAY l-POT XFMR FAILURE E8!5 EVENT POINT 0689 -
INDICATED CONDITION:
o EXCITER POTENTIAL TRANSFORMER FAILED.
l N. ~
REDUNDANT INDICATION'WHICH WILL' VERIFY ALARM:
I
[
OPERATOR ACTIONS FOR A VALID ALARM:
j l
o-INVESTIGATE LOSS OF EXCITER POTENTIAL TRANSFORMER.
DISCUSSION:
l LOSS OF'THE EXCITER POTENTIAL' TRANSFORMER WILL HAVE UNPREDICTABLE EFFECTS ON THE OPERATION OF THE GENERATOR FIELD FAILURE RELAY (ie. MAY-CAUSE IT:TO ACTUATE INADVERTENTLY OR FAIL TO OPERATE FOR A VALID CONDITION).
i
-THE GENERATOR BACKUP RELAY PROVIDES TRIP FUNCTION FOR THE MAIN GENERATOR OUTPUT BREAKERS'FOR GENERATOR OR BUS ELECTRICAL FAULTS.
j O.
'Q-
REFERENCES:
DRAWING 208-040 MT-76 s
i SENSING ELEMENT: K60/8 RELAY-CONTACT..
APJ603 Rev. 20 Page 99.
~
l L
[KLR$URFJ t.
(Page 98 of 103) 1GF O ANNUNCJA10R RESPONSE 1Gr-AX3-06-10 0-06 -.. _ _
ISOLATED PHASE BUS DUCT-TROUBLE EVENT POINT 1645 INDICATED CONDITION:
- o PHASE BUS DUCT BLOWER FAN 3A NOT RUNNING WITH SWITCH IN AUTO AND GENERATOR FIELD BREAKER CLOSED.
1 O
1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o; ISOLATED PHASE BUS DUCT FLOW LOW EVENT POINT 1647 OR ISOLATED PHASE
' BUS DUCT TEMPERATURE HIGH EVENT POINT 1646.
OPERATOR ACTIONS FOR A VALID ALARM:
oLIMMEDIATELY REDUCE LOAD TO < THE SELF COOLED RATING OF 10,000 AMPS
- AS INDICATED ON THE GENERATOR AMPS DIAL INDICATOR ON THE TGF PANEL.
o MAINTAIN THE DUCT TEMPERATURE < 151' 8Y REDUCTION IN GENERATOR OUTPUT AND TRANSFERRING LOADS FROM THE AUXILIARY TRANSFORMER.
o NOTIFY SECONDARY' PLANT OPERATOR TO MONITOR THE DUCT TEMPERATURE LOCALLY ON TB-338-TS, AND INVESTIGATE PROBLEMS.
DISCUSSION:
o THE RATE.0F LOAD REDUCTION SHOULD BE BASED ON THE RATE OF RISE OF DUCT TEMPERATURE.
REFERENCE'a:' DRAWING 208-057'TB-23 SENSING ELEMENT: 42X/17CR, 42/16M RELAY CONTACTS AR-603~
Rev. 20 Page 100 L
1
l ENCL 05VRL_1 (Page 99 of 103)
D(3' IGF 0 ANNUNC3ATOR RLSPONSE 1GF-AX3-06-30 0-06-10 i
1 ISOLATED PHASE.
BUS DUCT TROUBLE E
EVENT POINT 1646 i
INDICATED CONDITION:
)
o PHASE BUS DUCT RETURN AIR TEMPERATURE >151 *F AS SENSED BY TB-338-TS.
O
?'O REDUNDANT' INDICATION WHICH WILL VERIFY ALARM:
i OPERATOR ACTIONS FOR A VALID ALARM:
o IF FORCED COOLING HAS BEEN LOST, THEN IK4EDIATELY REDUCE LOAD TO < THE
.SELF COOLED RATING OF 10,000 AMPS AS INDICATED ON THE GENERATOR AMPS INDICATOR ON THE TGF PANEL.
1 o NGTIFY SECONDARY PLANT OPERATOR TO MONITOR THE DUCT TEMPERATURE LOCALLY ON TB-338-TS, AND INVESTIGATE PROBLEMS.
o IF TEMPERATURE REACHES 162* F, CONTACT SYSTEM ENGINEER FOR EVALUATION.
)
DISCUSSION:
. p).
t
REFERENCES:
DRAWING 208-057 TB-23 SENSING ELEMENT: TB-338-TS AR-603 Rev. 20 Page 101
i 0
' y::.
n fjKI 050RE J (Page 100 of 103)
.rj'
~
^
1GF. O ANNUNCI ATOR RESPONSE TGF-AX3-06-10 0-06-10 ISOLATED PHASE BUS DUCT TROUBLE EVENT POINT 1647 INDICATED CONDITION:
o PHASE BUS DUCT AIR FLOW AS SENSED BY TB-338-FS.
REDUNDANT INDICATION WHICH WILL VERIFY _ ALARM:
o PHASE BUS DUCT BLOWER FAN %T RUNNING WITH SWITCH IN AUTO AND THE GENERATOR FIELD BREAKER CAiD EVENT POINT 1645 OR 1655.
OPERATOR ACTIONS FOR A VALID ALARM:
o IF-FORCED COOLING HAS BEEN LOST, THEN IMMEDIATELY REDUCE LOAD TO < THE SELF COOLED RATING OF 10,000 AMPS AS INDICATED ON THE GENERATOR AMPS DIAL INDICATOR ON THE TGF PANEL.
l o MAINTAIN THE-DUCT TEMPERATURE < 151* F BY REDUCTION IN GENERATOR OUTPUT.
i AND TRANSFERRING LOADS FROM THE AUXILIARY TRANSFORMER.
o NOTIFY SECONDARY PLANT OPERATOP TO INVESTIGATE ISOLATED PHASE BUS DUCT COOLING SYSTEM.
1 I
DIiCUSSION:
o THE' RATE OF LOAD REDUCTION SHOULD BE BASED ON THE PATE OF RISE OF DUCT TEMPERATURE.
I' L
q
~.
REFERENCES:
DRAWING 208-057 TB-23 l
SENSING ELEMENT: TB-339-FS
..AR-603 -
Rev. 20 Page 202 u__________-.
FNCLQSPRE_1 (Page 101 of 103) 1CF 0 ANNUNCIATOR RESPONSE 1CF-AX3-06-30 0-06-10 m__._
ISOLATED PHASE BUS DUCT TROUBLE EVENT POINT 1652 INDICATED CONDI1 ION:
o PHASE BUS DUCT AIR HUMIDITY >50% AS SENSED BY TB-341-HS.
I REDUNDANT INDICATION WHICH WILL VERIFY. ALARM:
I OPERATOR ACTIONS FOR' A VALID ALARM:
l o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE ISOLATED PHASE BUS DUCT '
COOLING SYSTEM.
DISCUSSION:
L f
(O) n, ' '
REFERENCES:
DRAWING 208-057 TB-23 SENSING ELEMENT: TB-341-HS AR-603 Rev. 20 Page 103
- - - _ - _ _. _ _ _ - _ - _ _ - _ _ - _ _ _ _ - = - _
EM t OSUBLJ (Page 102 of 103)
O M-1GF 0 ANNUNCIATOR RESPONSE TGF-AX3-06-10 0-06-10 ISOLATED PHASE BUS DUCT TROUBLE I
EVENT POINT 1655 INDICATED CONDITION:
o PHASE BUS DUCT BLOWER FAN 38 NOT RUNNING WITH SWITCH IN AUTO AND GENERATOR FIELD BREAKER CLOSED.
O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o ISOLATED PHASE BUS DUCT AIR FLOW LOW EVENT POINT 1647 OR, ISOLATED PHASE BUS DUCT TEMPERATURE HIGH EVENT POINT 1646.
OPERATOR ACTIONS FOR A VALID ALARM:
o IMMEDIATELY REDUCE LOAD TO < THE SELF COOLED RATING OF 10,000 AMPS
- AS INDICATED ON THE GENERATOR AMIS DIAL INDICATOR ON THE TGF PANEL.
l
. o MAINTAIN THE DUCT TEMPERATURE <15e F BY REDUCTION IN GENERATOR OUTPUT AND TRANSFERRING LOADS FROM THE AUXILIARY TRANSFORMER.
o NOTIFY SECONDARY PLANT OPERATOR TO MONITOR THE DUCT TEMPERATURE LOCALLY ON TB-338-TS, AND INVESTIGATE PROBLEMS.
DISCUSSION:
o THE RATE OF LOAD REDUCTION SHOULD BE BASED ON THE RATE OF RISE OF j
j DUCT TEMPERATURE.
]
e
\\
.rw
REFERENCES:
DRAWING 208-057 TB 23 (J)
'~
SENSING ELEMENT: 42X/25CR, 42/19M RELAY CONTACTS 1
1 AR-603 Rev. 20 Page 104 l
l u
,ri-
!NO OSURE_l (Page 103 of 103)
O,.'")
TCI O ANNUNCIA10R= RESPONSE f1CF-AX306-10 0-06-10 ISOLATED PHASE BUS DUCT TROUELE N!
l EVENT POINT 1675
)
INDICATED CONDITION:
o PHASE BUS DUCT AIR FILTER DIFFERENTIAL PRESSURE >1* H,0 AS SENSED BY-TB-340-PS.
f~
(w)g 3
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE ISOLATED PHASE BUS DUCT COOLING SYSTEM AIR FILTER, AND REPLACE AS REQUIRED.
l
'DISCUSSIGN:-
REFERENCES:
' DRAWING 208-057 TB-23
/~'N SENSING ELEMENT:.TB-340-PS
(
t w.-
l-AR-6'03" Rev. 20 Page 105 (LAST PAGE)
Li_=- _ _.-