ML20154G952

From kanterella
Revision as of 04:46, 23 October 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Notice of Deviation from Insp on 880404-08.Deviation Noted: Utilization of Designated Combustible Storage Area W/Partial Height Separation Walls of Room Not Approved Fire Rated
ML20154G952
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 05/13/1988
From: Herdt A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20154G946 List:
References
50-348-88-13, NUDOCS 8805250172
Download: ML20154G952 (1)


Text

__ _ . _ _ _ . _ __ __ .. _ _ _ . _ _ _ _ . _ _ _ . . . _ .

^-. '. ,

l j

i  ;

l ENCLOSURE j i

l NOTICE OF DEVIATION _  ;

i Alabama Power Corporation Docket No. 50-348  !

l Farely Unit 1 License No. NPF-2 j l The following deviation was identified during a Nuclear Regulatory Comission  !

l (NRC)inspectionconductedonApril 4-8, 1988. j i Farley FSAR Section 98.2.2.2 states that storage of combustible materials  !'

is authorized only in areas separated from safe shutdown related areas by approved fire walls, doors and ceilings (i.e., proper storage areas).  :

i

Contrary to the above, at the time of the inspection, Unit 1, Room 444, was  ;

being utilized as a designated combustible storage area; however, the j j partial height separation walls of the room were not approved rated fire j walls.  ;

4 4 Please provide to the U.S. Nuclear Regulatory Comission, ATTN: Document 4 Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, <

i Region II, and a copy to the NRC Resident Inspector, in writing within 30 days 2

of the date of this Notice, the reasons for the deviation, the corrective steps '

which have been taken and the results achieved, the corrective steps which will l be taken to avoid further deviations, and the date when your corrective action j i will be cumpleted. Where good cause is shown, consideration will be given to  !

extending the response time.  ;

! Security or safeguards information should be submitted as an enclosure to ,

facilitate withholding it from public disclosure as required by 10 CFR 2.790(d) i or 10 CFR 73.21.  !

FOR THE NUCt. EAR REGULATORY COMMISSION  :

fA0, /S/ ( O A l

OfIst W i I

Alan R. Herdt, Chief I Engineering Branch 1 Division of Reactor Safety i i

Atlanta, Georgia j Dated agday of May 1988 this f l  !

1 l

\

? l i

l 1

8805250172 880513 PDR ADOCK 05000348 .

! Q DCD l i -.- - - - - - . - -- - - a