ML20125D692

From kanterella
Revision as of 20:38, 12 July 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Final Rept Re Potential Deficiency of NAMCO-supplied Limit Switches.Switches Do Not Meet Safety Requirements of Original Purchase Specs.Condition Not Reportable Per 10CFR50.55(e)
ML20125D692
Person / Time
Site: Grand Gulf  Entergy icon.png
Issue date: 12/18/1979
From:
MISSISSIPPI POWER & LIGHT CO.
To:
Shared Package
ML20125D689 List:
References
NUDOCS 8001150421
Download: ML20125D692 (1)


Text

__ - - - . - _ - -

FINAL REPORT FOR POTE::TIAL REl'Ol' TABLE DEFICI E.NCY :;0. 79/14 AS DEFINED IN 10 CFR 50.55(e)

1. Description of De ficienet on August 30,1979, NAM 20 Controls notified Bechtel Power Corporation i l

of their determination that the EAlSO series limit switches shipped I against Bechtel Purch 4se Order 9645-F36019 (1) EA740-50001 shippcd

  • 7/16/79 may have a ;op gasket which will emit res in vapor, at tempera-tures above 175 /, which could condense on the normally open contacts I

possibly causi.ig a switch malfunction. Yarway supplied one ::AMC0 l

\

i switch located on a manually actuated valve (QlC4 LF008) .  ;

II. Safety Implications The valve in question is used for position indication only and not required for safe shutdown of the plant. If the switch on the valve had failed causing the valve to become inoperable, no effect on the health and safety of the public would have been experienced nor would it adversely affect the safe operations of the plant. Therefore, this condition was determined not reportable per L0 CFR 50.55(e).

90023158 8001150'/1I

__ _ . _. ... _