Oakland. CA 01621 Enn rproc Way and M5th Asenue l'. O Ikix :2161 April 29, 1988 Director, Office of Inspection and Enforcement US Nuclear Regulatory Commission Washington, D.C.
20553 Report #145
Dear Sir,
In accordance with the requirements of Title 10, Chapter 10, Code of Federal Regulations, Part 21, IMO Delaval Inc. hereby notifies the Commission of a potential defect in a component of a DSR or DSRV Standby Diesel Generator.
There exists a potential problem with certain engine control devices in the air start, lube oil, Jacket water systems and crankcase systems.
IMO Delaval has supplied DSR and DSRV engines with this potential defect to the following sitest UTILITY SITE SERIAL NO.
MODEL LILCD Shoreham" 74010/12 DSR-48 V
System Energy Resources Grand Gulf 74033/36 DSRV-16-4 Gulf States River Bend" 74039/40 DSR-48 Carolina Power & Light Shearon Harris
- 74046/49 DSRV-16-4 Duke Power Catawba./
75017/20 DSRV-16-4 So. Cal. Edison San Onof re /
75041/42 DSRV-20-4 Cleveland Electric PerryN' 75051/54 DSRV-16-4 TVA Bellefonte V 75080/83 DSRV-16-4 Washington Pub. Fower WNP-1 75084/85 DSRV-16-4 Texas Utilities Electric Commanche Peak '76001/04 DSRV-16-4 Georgia Power Vogtle d[
76021/24 DSRV-16-4 N
Consumer Power Midland /
77001/04 DSRV-12-4 TVA Harteville 77024/25 DSRV-16-4 SMUD Rancho Seco x/
81015/16 DSR-48 The subject components are manufactured by California Controls (Calcon) and are specifically identified as follows:
IMO Part Number Description KR-OO1-OOO Air Start Valve KP.-OO4-OO1 Air Start Valve KR-OO4-OO2 Air Start Valve F-573-156 Low Pressure Lube Oil Trip F-573-330 High Temperature Jacket Water Trip l
F-573-359 High Pressure Crankcase Trip I
l In response to a number of field reported failures, IMO Delaval l
performed an audit of Calcon's manufacturing facility on April 1
21, 1988.
We identified a failure in the implementation of their i
8805060041 880429
!f PDR ADOCK 05000206 S
b Page 2 h
April 29, 1988 y
US Nuclear Regulatory Commission Quality Assurance program with regard to product testing there is no objective evidence of product testing having been per-formed.
This, coupled with the recent reported field failures places the reliability of the above noted components in question.
Failure of these devices in a safety related system may render the diesel engine-generator inoperable.
IMO Delaval recommends that all of the above referenced compo-nents in on-site warehouse storage be returned to IMO Delaval for inspection and test.
Devices already installed and operating in their respective systems have demonstrated their reliability.
While we do not recommend removal and return of these installed components, we do suggest a surveillance plan be developed and implemented within the individual site operating / maintenance pro-grams.
IMO Delaval will perform source inspection on all safety related components prior to shipment until such time that a reaudit con-firms full Quality Assurance program implementation.
We are also working with Calcon to investigate and determine the cause of the recorded field component failures.
It is important to note that new management was in place at Cal-con approximately two (2) weeks prior to our audit.
It was noted at the time of the audit that measures were being taken to return product quality and reliability to its previous high level.
The above referenced inspection / test program has the full support of Calcon.
A copy of this letter will be sent to all of the sites referenced in paragraph 2 of this letter as indicated by the carbon copy list.
Our evaluation of this matter was concluded on April 27, 1988.
Sincerely, f
nw=
Brura Guntrum Manager, Quality Assurance BCG/dfa