ML20207P045

From kanterella
Jump to navigation Jump to search
Part 21 Rept 146 Re Defect in Left Intercooler Inlet Adapter on Standby Diesel Engine Generator.Recommends Utils Inspect Left Intake Manifold Drain as Part of Operating Plan.Addl Info Expected by 881015
ML20207P045
Person / Time
Site: Perry, Catawba, Harris, Grand Gulf, Vogtle, Comanche Peak, Bellefonte, 05000000, Washington Public Power Supply System
Issue date: 10/05/1988
From: Guntrum B
IMO DELAVAL, INC.
To:
Office of Nuclear Reactor Regulation
References
REF-PT21-88, REF-PT21-88-119-000 146, PT21-88-119, PT21-88-119-000, NUDOCS 8810200039
Download: ML20207P045 (3)


Text

FM f

Imo Lulasalinc o

Enterprise I:ngine Dhlaion DP.(i Enterprtw W ay and V t h Au nue IM 2161 (idlana UA 91w.

u,, ::tm October 5, 1988 Director, Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Report #146

Dear Sir,

On September 30, 1988, System Energy Resources. Inc. notified the Commission of a potential safety hazard at the Grand Gulf Nuc.'. ear Station, Unit 1, according to the requiremente of 10CFR21.

The nature of the defect concerns the left intercooler inlet adapter on their standby diesel engine generator.

The subject adapter is nanufactured by IMO Delaval Inc. and provided as a part of the dieeel engine.

This letter is wr.i' ten as a follow-t.p to the System Energy Resources letter to inform the Commission of other sites where similar equipment is installed and of IMO Delaval's recormended corrective action.

Affected site locatione include the fol]owing:

UTILITY SITE SERIAL NO.

MODEL System Energy Resources Grand Gulf 74033/36 DSRV-16-4 Carolina Power & Light Shearon Harrie 74046/49 DSRV-16-4 Duke Power Catauba 75017/20 DSRV-16-4 Cleveland Electric Perry 75051/54 DSRV-16-4 TVA Bellefonte 75080/83 DSRV-16-4 Washington Pub. Power WNP-1 75084/85 DSRV-16-4 Texas Utilities Electric Commanche Peak 76001/04 DSRV-16-4 Georgia Power Vogtle 76021/24 DSRV-16-4 IMO Delaval is currently reviewing thic failure for recommended corrective action.

It is anticipated that specific information will be available no later than October 15, 1988.

In the interim, we recommend that site personnel include a periodic irspection of the left intake manifold drain as a part of their operating plan.

As the Jacket water system le pressurized at all times, any leaking tubes will be evidenced by a flow of water out of the intake manifold drain.

This periodic inspection should also verify that the subject drain is clear and free from obstruction.

N 9S 10 2 0u 0 3')

VelooS

/,

{pN Apoc( o'iogoJ7 '[

o:

Page 2 October 5, 1988 US Nuclear Regulatory Commission A copy of this letter will be sent to all of the affected sites as indicated by the carbon copy list.

Sincerely

=

Bruce

untrum Manager, Quality Assurance BCG/dfa ec

System Energy Resources, Inc.

P.O. Box 23070 Jackson, Micoleeippi 39225-3070 Attn:

Mr. Ted. H. Cloninger V.P. Nuclear Engineering & Support R.H. Hutchinson Plant Manager

?.0. Box 469 Port Gibson, Missieelppi 39150 Fred H. Titus Director, Nuclear Plant Engineering l

P.O. Box 429 Port Gibson, Hiesiselppi 39150 Carolina Power & Light Company Shearon Harris Nuclear Plante P.O. Box 165 New Hill, N.C.

27662 Attn:

Mr. R.A. Watson. Vice President Mr. L.I. Loflin, Manager Harris Plant Engineerina Mr. George Furchand Director, QA/QC

- c..

Page 3 October 5, 1988 US Nuclear Regulatory Commiceion ec:

Cor.t.

Duke Power - Clitawba Mill Power Supply Company P.O. Box 32307 Charlotte, NC 28232 Attn:

H.T. Robertson, President Cleveland Electric Illuminating Company C/O Perry Nuclear Power Plant P.O. Box 97 Perry, Ohio 44081 Attn:

Mr. C.M. Shuster

'anager Nuclear Quality. oarance Mr. E.

Riley, Dire? tor Nuclear Quality Accurance Tennessee Valley Authority - Bellefonte W70126, 400 West Summit Hill Drive Knoxville, TN 37902 Attn:

Mr.

I.L. Beltz Washington Public Power Supply System P.O. Fox 460 Richland, WA 99352 Attn:

Mr. G.K. Dyekman Acting Acet. Program Director Texas Utilities Electric Skyway Tower 400 North Oliver Street L.B.

81 Dallas, Texas 75201 Attn:

Mr. W.G. Counell, Jr.

Executive Vice Freeldent Georgia Power Company Plant Vogtle P.O. Box 1600 l

Waynesboro, Georgia 30830 i

Attn:

Mr. George Bockhold Jr.

l Plant Manager 1

l

, - - _ _ - -