Category:REPORTABLE OCCURRENCE REPORT (SEE ALSO AO
MONTHYEARML20043H9921990-06-22022 June 1990 Special Rept 1-90-04:on 900523,valid Diesel Generator 1B Tripped.Caused by Replaced Jacket Water Temp Switches.Onsite Calibr Procedure Revised to Provide Technique Consistent W/ Actual Operating Conditions ML20043B6001990-05-24024 May 1990 Special Rept:On 900415,loose Part Detection Sys Inoperable for More than 30 Days.Caused by Either Sensors IXE-0750 & IXE-0751 Attached to Reactor Head or pre-amplifier Located 6 Ft Away.Sensors Will Be Inspected After Next Mode 5 Entry ML20042F3781990-05-0404 May 1990 Special Rept 1-90-03: on 900415,steam Line Radiation Monitor Removed from Svc When Personnel Unable to Enter Parameters on Digital Process Module.New Circuit Board Installed on 900430 & Monitor Returned to Svc by 900501 ML20012C3371990-03-12012 March 1990 Special Rept 2-90-02-01:on 900124 & 25,Diesel Generators 2A & 2B Failed,Respectively.Caused by Air Leak from Right Bank Air Start Blocking Valve Solenoids.Air Start Distributor Filters Replaced ML20011F5621990-02-19019 February 1990 Special Rept 2-90-02:on 900124 & 25,when Start Button Depressed,Diesel Generator 2A Rolled Slowly for Approx Two Turns But Did Not Start.On 900201,when Diesel Paralleled to Grid,Low Excitation Alarm Received.Bridge Circuit Repaired ML20006B9891990-01-29029 January 1990 Special Rept 1-90-01:on 900103,when Diesel Generator 1B Started for Monthly Surveillance,Low Turbocharger Oil Pressure Annunicator Alarmed.Caused by Small Leak on Low Oil Pressure Switch.Switch Replaced & Surveillance Completed ML20006B9141990-01-29029 January 1990 Special Rept 2-90-01:on 891206-900110,containment Radiation Level high-range Monitors Inoperable.Caused by Bad Preamplifier Circuit Board Which Caused Spurious Alarms. Preamplifier Circuit Board Replaced ML19332D9051989-11-29029 November 1989 Special Rept 50-424/1989-003:on 891030,31 & 1107,tendon Grease Deficiencies Noted During Combined Tendon Surveillances.No Corrosion or Cracks Found.Tensile Test Results for Strand Samples Expected by End of Dec 1989 ML19325E2611989-10-26026 October 1989 Special Rept.On 891016,channel Calibr for Loose Part Detection Sys Not Performed as Specified in Fsar.Caused by Belief That Calibr Not Required.Channel Calibr Entered Into Tech Spec Surveillance Tracking Program 1990-06-22
[Table view] Category:LER)
MONTHYEARML20043H9921990-06-22022 June 1990 Special Rept 1-90-04:on 900523,valid Diesel Generator 1B Tripped.Caused by Replaced Jacket Water Temp Switches.Onsite Calibr Procedure Revised to Provide Technique Consistent W/ Actual Operating Conditions ML20043B6001990-05-24024 May 1990 Special Rept:On 900415,loose Part Detection Sys Inoperable for More than 30 Days.Caused by Either Sensors IXE-0750 & IXE-0751 Attached to Reactor Head or pre-amplifier Located 6 Ft Away.Sensors Will Be Inspected After Next Mode 5 Entry ML20042F3781990-05-0404 May 1990 Special Rept 1-90-03: on 900415,steam Line Radiation Monitor Removed from Svc When Personnel Unable to Enter Parameters on Digital Process Module.New Circuit Board Installed on 900430 & Monitor Returned to Svc by 900501 ML20012C3371990-03-12012 March 1990 Special Rept 2-90-02-01:on 900124 & 25,Diesel Generators 2A & 2B Failed,Respectively.Caused by Air Leak from Right Bank Air Start Blocking Valve Solenoids.Air Start Distributor Filters Replaced ML20011F5621990-02-19019 February 1990 Special Rept 2-90-02:on 900124 & 25,when Start Button Depressed,Diesel Generator 2A Rolled Slowly for Approx Two Turns But Did Not Start.On 900201,when Diesel Paralleled to Grid,Low Excitation Alarm Received.Bridge Circuit Repaired ML20006B9891990-01-29029 January 1990 Special Rept 1-90-01:on 900103,when Diesel Generator 1B Started for Monthly Surveillance,Low Turbocharger Oil Pressure Annunicator Alarmed.Caused by Small Leak on Low Oil Pressure Switch.Switch Replaced & Surveillance Completed ML20006B9141990-01-29029 January 1990 Special Rept 2-90-01:on 891206-900110,containment Radiation Level high-range Monitors Inoperable.Caused by Bad Preamplifier Circuit Board Which Caused Spurious Alarms. Preamplifier Circuit Board Replaced ML19332D9051989-11-29029 November 1989 Special Rept 50-424/1989-003:on 891030,31 & 1107,tendon Grease Deficiencies Noted During Combined Tendon Surveillances.No Corrosion or Cracks Found.Tensile Test Results for Strand Samples Expected by End of Dec 1989 ML19325E2611989-10-26026 October 1989 Special Rept.On 891016,channel Calibr for Loose Part Detection Sys Not Performed as Specified in Fsar.Caused by Belief That Calibr Not Required.Channel Calibr Entered Into Tech Spec Surveillance Tracking Program 1990-06-22
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217K4591999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20217K8041999-09-30030 September 1999 Rev 1 to Vegp,Unit 2 Cycle 7 Colr ML20217K7741999-09-30030 September 1999 Rev 1 to Vegp,Unit 1 Cycle 9 Colr ML20216E5061999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Vegp,Units 1 & 2. with ML20210P9841999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20209H1211999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20196F9711999-05-31031 May 1999 Owner Rept for ISI for Vogtle Electric Generating Plant, Unit 1 Eighth Maint/Refueling Outage ML20195G1731999-05-31031 May 1999 Monthly Operating Repts for May 1999 for VEGP Units 1 & 2. with ML20206N2141999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20206A6561999-04-21021 April 1999 Safety Evaluation Authorizing Licensee Re Rev 9 to First 10-year ISI Interval Program Plan & Associated Requests for Relief (RR) 65 from ASME Boiler & Pressure Vessel Code ML18016A9011999-04-12012 April 1999 Part 21 Rept Re Defect in Component of DSRV-16-4,Enterprise DG Sys.Caused by Potential Problem with Connecting Rod Assemblies Built Since 1986,that Have Been Converted to Use Prestressed Fasteners.Affected Rods Should Be Inspected ML20206C2291999-03-31031 March 1999 Revised Monthly Operating Repts for Mar 1999 for Vogtle Electric Generating Plant,Units 1 & 2 ML20205Q8081999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Vegp,Units 1 & 2. with ML20205A9581999-03-31031 March 1999 Rev 0 to VEGP Unit 1 Cycle 9 Colr ML20207K6051999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20209H3951999-02-15015 February 1999 Rev 2 to ISI Program Second 10-Year Interval Vogtle Electric Generating Plant Units 1 & 2 ML20209H4091999-02-15015 February 1999 Rev 1 to ISI Program Second 10-Year Interval Vogtle Electric Generating Plant Units 1 & 2 ML20202H9851999-01-29029 January 1999 Safety Evaluation Accepting Rev 8 to First 10-year Interval Inservice Insp Program & Associated Requests for Relief for Vogtle Electric Generating Plant,Unit 1 ML20199F8041999-01-13013 January 1999 Corrected Pages to VEGP-2 ISI Summary Rept for Spring 1998 Maint/Refueling Outage ML20199E7561998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20198S1781998-12-31031 December 1998 SER Re Second 10-year Interval Inservice Insp Program Plan & Associated Requests for Relief for Southern Nuclear Operating Co,Inc Units 1 & 2 ML20196E5221998-12-0101 December 1998 Rev 8 to ISI-P-014, ISI Program for VEGP-2 ML20198B8571998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Vogtle Electric Generating Plant,Units 1 & 2.With ML20195H2131998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Vogtle Electric Generating Station,Units 1 & 2.With ML20154L5681998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Vegp,Units 1 & 2 ML20151W3681998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Vogtle Electric Generating Plant Units 1 & 2.With ML20154L5721998-08-31031 August 1998 Corrected Page from MOR for Aug 1998 for Vegp,Unit 2 ML20237D2051998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Vogtle Electric Generating Plant Units 1 & 2 ML20236V3121998-07-29029 July 1998 Final Part 21 Rept Re Enterprise DSR-4 & DSRV-4 Edgs.Short Term Instability Was Found During post-installation Testing & Setup as Part of Design mod/post-work Testing Process. Different Methods Were Developed to Correct Problem ML20236P6991998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Vogtle Electric Generating Plant,Units 1 & 2 ML20236Q3051998-06-30030 June 1998 Owner'S Rept for ISI for Sixth Maint/Refueling Outage of Vogtle Electric Generating Plant,Unit 2 ML20249A3911998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Vogtle Electric Generating Plant ML20248A1671998-05-22022 May 1998 Interim Part 21 Re Enterprise DSR-4 & DSRV-4 Emergency diesel.Post-installation Testing Revealed,High Em/Rfi Levels Affected New Controllers,Whereas Original Controllers Were unaffected.Follow-up Will Be Provided No Later than 980731 ML20249A3931998-04-30030 April 1998 Revised MOR for Apr 1998 for Vogtle Electric Generating Plant Unit 1 ML20247F3841998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Vogtle Electric Generating Plant,Units 1 & 2 ML20154Q9721998-04-20020 April 1998 10CFR50.59(B) Rept of Facility Changes,Tests & Experiments for Vogtle Electric Generating Plant,Units 1 & 2 ML20217H7181998-04-0101 April 1998 Corrected Page 5 to 980324 SER Re Relief Requests Associated W/Second 10-year Interval Insp program.RR-21 in Error in That Component,Suction Damper Inadvertently Omitted. Corrected Page 7 of Technical Ltr Rept Also Encl ML20216D6141998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Vogtle Electric Generating Plant,Units 1 & 2 ML20217Q1301998-03-31031 March 1998 Rev 0 to Vepc Unit 2 Cycle 7,COLR ML20217B8831998-03-24024 March 1998 SER Accepting Relief Request RR-5,RR-19,RR-20,RR-21,RR-23 & RR-24 for Second 10-yr Interval ISI Program Plan ML20216E2421998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Vogtle Electric Generating Plant,Units 1 & 2 ML20203H9551998-02-23023 February 1998 SER Denying Quality Assurance Program Description Change for Vogtle Electric Generating Plant,Units 1 & 2 ML20203E4831998-02-11011 February 1998 Rev 1 to Vogtle Electric Generating Plant,Units 1 & 2 Second Ten-Yr Interval Pump Inservice Test Program ML20198T1211998-01-31031 January 1998 Owners Rept for Inservice Inspection for Seventh Maintenance/Refueling Outage ML20202G5441998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Vogtle Electric Generating Plant,Units 1 & 2 ML20199E5431998-01-31031 January 1998 Rev 3 to WCAP-14720, Vogtle Units 1 & 2 Spent Fuel Rack Criticality Analysis W/Credit for Soluble Boron ML20198L6471997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Vogtle Electric Generating Plant,Units 1 & 2 ML20203C2811997-12-0909 December 1997 Safety Evaluation Authorizing Request for Relief of Second 10 Yr Interval Inservice Insp Program ML20202B7881997-12-0101 December 1997 Rev 8 to ISI-P-006, ISI Program for Gpc Vogtle Electric Generating Plant Unit 1 ML20203H0601997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Vegp,Units 1 & 2 1999-09-30
[Table view] |
Text
. - . . - . . - - . ..
Georg:a Power Company . 1
. , 333 Piedmont Awnuo ! . 'r
<* ' . - Attanta, Geof0 a 30308 1 +
' Telephone 404 520-3195l- t
. Mading Addressi.
40 invctness Center Parkway Post Offce Box 1295 .
Bamsngham, Alabama 35201
' Telephone 205 BGB 5581 June 22, 1990. 't mwe" <*ac snte"
' W. G. Hairston.111 tF i Scruor Vce President -
' i, Nuclear Operations ELV-Ol F - C 0447
-Docket:No..: 50-424 U. S. Nuclear Regulatory Commission ATTN: : Document Control Desk
' Washington, D. C. 20555 Gentlemen:' .
V0GTLE ELECTRIC GENERATING PLANT-SPECIAL'REPORTi VALID DIESEL GENERATOR FAILURE i
In accordance with the requirements of the Vogtle' Electric Generating Plant Technical ~ Specifications,- Sections 4;8.~1.-l.3 and 6.8.2, Georgia Power Company hereby submits the enclosed:Special- Report;concerning a valid' diesel ~ generator failure.
Sincerely, W..M u>
W. G. Mairston, III WGH,III/NJS/gm- 1
Enclosure:
Special Report 1-90-04 xc: Georaia Power ComERDX ,
Mr. C. K.-McCoy Mr.-.G. Bockhold, Jr.
Mr.- P. D. Rushton s Mr. R.~M. Odom 4 o NORMS :
U. S. Nuclear Reaulatory Commission Mr. S. D. Ebneter, Regional Administrator Mr. T..A.-Reed, Licensing Project Manager, NRR .;
Mr. B. R. Bonser, 'Seniar Resident Inspector,' Vogtle i
jl j
9006270173 900622 PDR
'F -
S ADOCK 05000424 PDC p-
' & '\
l o.
}.
a
,' if it ..f i
j ENCLOSURE L V0GTLE ELECTRIC GENERATING PLANT.- UNIT 1- 1 TECHNICAL-SPECIFICATION SPECIAL REPORT 1-90-04 VALID DIESEL GENERATOR FAILURE
'A. REQUIREMENT FOR REPORT l I This' report.is~ required in accordance.with the Vogtle Electric. Generating !
Plant Technical Specifications, Section 4.8.1.1.3.' This; section of the Technical Specifications requires that all diesel generator. failures,- t valid or non-valid, be reported to:the Commission in.a Special Report pursuant to Technical Specification 6.8.~2.
~
B.- DESCRIPTION OF VALID FAILURE FOR DIESEL GENERATOR 18 -
On 5-23-90,.at 1226 CDT, Diesel Generator (DG) 1B was started pursuant to a normal routine Technical Specification surveillance requirement. Just arior to this surveillance test, the jacket water temperature switches y 1ad been replaced with recalibrated ' switches as'.part of a DG reliability upgrade and the DG had been declared operable. .At 1228.CDT;, DGlB tripped R i and the following alarms were noted: "Lo Turbo Oil Pressure,":"Hi Jacket l Water Temp.," and "Lo Jacket Water Pressure". Several troubleshooting- i n
~~
starts were made and it was determined that the jacket water temperature switches were the. source of-the trip signal. On 5-24-90, the original .
jacket water temperature switches were reinstalled on CGlB.- Both normal:
and emergency starts were successfully conducted and DG1B was-returned:to L service the same day at 2254 CDT. During this time Diesel-Generator 18-l was unavailable for emergency operation' for a period of- 34 hours3.935185e-4 days <br />0.00944 hours <br />5.621693e-5 weeks <br />1.2937e-5 months <br /> and 26 minutes, s l
The jacket water temperature. switches were tested by anLindependent laboratory and the trip setpointsiwere determined to-be~31-36 degrees F.
i less than:the required.200 degree F,setpoint. The'.onsiteLcalioration i; . procedure has.been revised to provide a technique-that'is consistent with i the actual operating conditions that the switches experience.
C.
SUMMARY
b This event is classified as a -valid failure per Reg. Guide 1.108, Section '
C.2.e. Since this is the second valid' failure in the past 20 valid tests, the test frequency for DGlB-has been changed to- once per 7. days in accordance.with Table 4.8-1.of the Technical Specifications. As of.
. 5-23-90, there have been a total of 71 valid tests of DGlB-and 5 valid
, failures, l q k
- o. .4 a . ~ . .:, -