USNRC 10CFR Part 21 Notification
ML081990210
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 07/15/2008
From: Barry R
Flowserve Corp
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML081990210 (2)


Text

I© §ýLýFlow Control Division Anchor/Darling Valves BW/IP Valves Edward Valves Worcester Valves Valtek Control Products July 15, 2008 NRC Document Control Desk US Nuclear Regulatory Commission Washington, DC 20555-0001

Subject:

USNRC 10CFR Part 21 Notification This is to notify the US Nuclear Regulatory Commission, in accordance with the provisions of 10CFR -Part 21 of a deviation identified by Flowserve Corporation.

On May 13, 2008, Flowserve Inc. Raleigh N.C. was notified by SCE&G -VC Summer Nuclear that a pair of ASME Section III Class 3, NPS 16" Classl50 Butterfly Valves with Fail Open Air Actuators, installed in the site service water system (SW) in May 2008 during RF -17, failed to open during post installation testing against design differential pressure.

The plant was in a safe shutdown condition at the time of the testing.The valves are used for isolation and are normally closed but fail open during loss of power.The valves must also open upon start of the SW booster pump to provide SW cooling to the RBCU to maintain Reactor Building temperature.

A number of issues were discovered during installation and subsequent evaluation of these valves and were corrected by SCE&G under direction of Flowserve Field Service Technicians and Flowserve Engineering support. The as installed configuration of the valves and actuators included site modifications and parts supplied by Flowserve to decrease the valve operating torque and increase the actuator opening output torque. After the modifications, the valves were tested and opened at full design differential pressure and closed as required.The root cause of the failure has yet to be determined.

This failure is under investigation by Flowserve Engineering.

An examination of the valve hardware will be necessary to complete the investigation and failure analysis.

The investigation will proceed after replacement of the valves/parts and the release of the original valves/parts by SCE&G to Flowserve.

Flowserve U S Inc Flow Control Division Raleigh Operations PO Box 1961 1900 South Saunders Street Raleigh, NC 27603 Toll Free: 1-800-225-6989 Phone: 1-919-832-0525 Facsimile:

1-919-831-3369 www.flowserve.com Visit our on-line catalog through Thomas Register at http://thomasreoistae.com/Flowserve As a result of this incident, Flowserve, Raleigh has reviewed the history of Butterfly Valves supplied to the nuclear industry and has determined that none were supplied with fail open air actuators of the same design as supplied for the SCE&G application.

The SCE&G specifications required equipment unique to the application.

Therefore, this incident does not affect Flowserve, Raleigh equipment provided to other nuclear facilities.

Flowserve Corporation Flow Control Division Robert D. Barry ýf-Quality Assurance Manager Flowserve U S Inc Flow Control Division Raleigh Operations PC Box 1961 1900 South Saunders Street Raleigh, NC 27603 Toll Free: 1-800-225-6989 Phone: 1-919-832-0525 Facsimile: