Text
_ _ _ _ _ _ _ _ _ _.
REY. ISSUE /DATE NUMBER TmJ!
FR.Z.2 RESPONSE TO CONTAINMENT FLOODING Rev. 1 3.
A.
PURPOSE nis procedure provides actions to respond to containment flooding.
B.
SYMPTOMS OR ENTRY CONDITIONS m.
i This procedure is entered from F-0.5. COSTAINMENT Cridcal Safety Function Status Tre on an ORANGE condition, 4
i f'
l l
l l
I I
l l
[
[
i i
(
4 Page 1 of 2 8810250331 001007 PDR ADOCK 05000213 P
PDR t
NUMBER TTC.E REV. ISSUE /DATE FR.Z.2 RESPONSE TO CONTAINMENT FLOODING Rev,1 I
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED 1
TRY TOIDE?mFY UNEXPECI1!D SOURCE OF WATER INPlJrTO SUMP:
- a. Check CARFAN service water
- a. Isolate service water to CARFAN(s) 8!
flows NORMAL with abnormal service water flow,
- b. Check CCW surge tank level-
- b. Attempt to idenify and isolate source STABG ofleakage.
- c. Check primary water to containment,
- c. Close PW V 141.
PW V 141 CLOSED
- d. Attempt to identify and isolate source flowindications NORMAL ofleakage.
2 CHECK CONTAINMENT SUMP ACITVITY EVEL:
- a. Draw local grab sample t
IE containment entry is possible i
3 NOTIFY PLANT ENGINEERING STAFF OF SUMP LEVEL AND ACITVITY LEVELTO OBTAIN RECOMMENDED ACITON 4
RETURN IQ PROCEDURE AND STEP IN EFFECT END l
t r
Page 2 of 2 e. _. _ - - _ _ _. _ - _,
_-