MONTHYEARPY-CEI-NRR-2438, Informs That DBNPS & Pnpp Staffs Have Modified or Withdrawn Several of Positions Proposed within Re Request for Approval of Qap.Revised Positions Encl1999-10-14014 October 1999 Informs That DBNPS & Pnpp Staffs Have Modified or Withdrawn Several of Positions Proposed within Re Request for Approval of Qap.Revised Positions Encl ML20217F3901999-10-14014 October 1999 Discusses Request That Proprietary Document NEDE-32907P,DRF A22-0084-53, Safety Analysis Rept for Perry NPP 5% Power Uprate, Class III Dtd Sept 1999 Be Withheld.Determined Document Proprietary & Will Be Withheld ML20217G9201999-10-14014 October 1999 Discusses Utils Request for Approval of Quality Assurance Program Changes PY-CEI-NRR-2435, Responds to NRC Re Violations Noted in Insp Rept 50-440/99-13.Corrective Actions:Ts SRs with Incorrect Descriptions Were Annotated to Ensure That CR Operators Are Aware That ACs Are Effect1999-10-13013 October 1999 Responds to NRC Re Violations Noted in Insp Rept 50-440/99-13.Corrective Actions:Ts SRs with Incorrect Descriptions Were Annotated to Ensure That CR Operators Are Aware That ACs Are Effect ML20212K9271999-09-30030 September 1999 Refers to 990927 Meeting Conducted at Perry Nuclear Power Plant to Discuss Initiatives in Risk Area & to Establish Dialog Between SRAs & PSA Staff ML20212J1451999-09-30030 September 1999 Forwards Order,In Response to 990505 Application PY-CEI/NRR- 2394L.Order Approves Conforming License Amend Which Will Be Issued & Made Effective When Transfer Completed ML20217E7111999-09-30030 September 1999 Documents Telcon Conducted on 990929 Between M Underwood of Oh EPA & D Tizzan of Pnpp,Re Request to Operate Pnpp Sws,As Is,Until Resolution Can Be Obtained ML20212G4161999-09-24024 September 1999 Informs of Completion of Licensing Action for Generic Ltr 98-01, Y2K Readiness of Computer Systems at Nuclear Power Plants, for Perry Nuclear Power Plant ML20212G5811999-09-23023 September 1999 Informs That Licenses for Ta Lentz,License SOP-31449,PJ Arthur,License SOP-30921-1 & Dp Mott,License SOP-31500 Are Considered to Have Expired,Iaw 10CFR50.74(a),10CFR55.5 & 10CFR55.55 PY-CEI-NRR-2432, Forwards NRC Form 536, Operator Licensing Exam Data, in Response to Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams1999-09-21021 September 1999 Forwards NRC Form 536, Operator Licensing Exam Data, in Response to Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams PY-CEI-NRR-2428, Submits Resolution to Seventh Question Proposed within NRC 980615 RAI Relating to Cooling Water Sys That Serve Containment Air Coolers & Assessment,Post Accident,Of Potential Water Hammer & two-phase Flow Conditions1999-09-16016 September 1999 Submits Resolution to Seventh Question Proposed within NRC 980615 RAI Relating to Cooling Water Sys That Serve Containment Air Coolers & Assessment,Post Accident,Of Potential Water Hammer & two-phase Flow Conditions ML20212D0151999-09-14014 September 1999 Requests Cancellation of NPDES Permit 3II00036.Permit Has Been Incorporated in Permit 3IB00016*ED.Discharge Point Sources & Associated Fees Currently Covered Under Permit 3IB00016*ED ML20212A8371999-09-13013 September 1999 Forwards Insp Rept 50-440/99-13 on 990712-30 & Notice of Violation.Insp Included Evaluation of Engineering Support, Design Change & Modification Activities,Internal Assessment Activities & Corrective Actions ML20217A8971999-09-0909 September 1999 Forwards Insp Rept 50-440/99-09 on 990709-0825.One Violation of NRC Requirements Occurred & Being Treated as NCV, Consistent with App C of Enforcement Policy PY-CEI-NRR-2431, Forwards Revised Emergency Plan for Perry NPP, IAW 10CFR50.54(q).Changes Constitute Revs,Temporary Changes or Reissued Pages1999-09-0909 September 1999 Forwards Revised Emergency Plan for Perry NPP, IAW 10CFR50.54(q).Changes Constitute Revs,Temporary Changes or Reissued Pages ML20211Q6911999-09-0606 September 1999 Informs That NRC Tentatively Scheduled Initial Licensing Exam for Perry Operator License Applicants During Wks of 010108 & 15.Validation of Exam Will Occur at Station During Wk of 001218 IR 05000440/19990011999-08-31031 August 1999 Requests That Page Number 4, P2 Status of EP Facilities, Equipment & Resources, of Insp Rept 50-440/99-01 Be Replaced with Encl Rev PY-CEI-NRR-2425, Forwards Copy of Oh EPA Approval for Use of Nalco 7348 & Nalco 7468 at Pnpp,Iaw License NPF-58,App B,Epp,Section 3.21999-08-26026 August 1999 Forwards Copy of Oh EPA Approval for Use of Nalco 7348 & Nalco 7468 at Pnpp,Iaw License NPF-58,App B,Epp,Section 3.2 PY-CEI-NRR-2411, Informs That Firstenergy Nuclear Operating Co Has Developed Corporate QA Program Manual for Davis-Besse Nuclear Power Station & Perry Nuclear Power Plant,As Discussed on 990318 Between Util & Nrc.Revised USAR Pages,Encl1999-08-19019 August 1999 Informs That Firstenergy Nuclear Operating Co Has Developed Corporate QA Program Manual for Davis-Besse Nuclear Power Station & Perry Nuclear Power Plant,As Discussed on 990318 Between Util & Nrc.Revised USAR Pages,Encl ML20210Q8421999-08-13013 August 1999 First Final Response to FOIA Request for Documents.Records Listed in App a Being Released in Entirety & Records Listed in App B Being Withheld in Part (Ref FOIA Exempt 5) ML20210R7861999-08-12012 August 1999 Forwards Insp Rept 50-440/99-12 on 990712-16.No Violations Noted.New Emergency Preparedness Program Staff & Mgt Personnel Were Professional & Proactive ML20210S3961999-08-11011 August 1999 Requests That Ten Listed Individuals Be Registered to Take 991006 BWR Gfes of Written Operating Licensing Exam.Two Listed Personnel Will Have Access to Exams Before Exams Are Administered PY-CEI-NRR-2423, Provides Final Response to NRC GL 98-01, Y2K Readiness of Computer Sys at Npps. Remediation of Meteorological Monitoring Sys Has Been Completed & Ppnp Facility Is Now Y2K Ready1999-08-10010 August 1999 Provides Final Response to NRC GL 98-01, Y2K Readiness of Computer Sys at Npps. Remediation of Meteorological Monitoring Sys Has Been Completed & Ppnp Facility Is Now Y2K Ready PY-CEI-NRR-2421, Forwards Semiannual fitness-for-duty Rept,Iaw 10CFR26.71(d) for Pnpp Covering Period of 990101-9906301999-08-10010 August 1999 Forwards Semiannual fitness-for-duty Rept,Iaw 10CFR26.71(d) for Pnpp Covering Period of 990101-990630 ML20210Q7981999-08-10010 August 1999 Informs That Intention to Utilize Sulfuric Acid in Pnpp Circulating Water Sys to Lower Ph Is Anticipated to Be Completed in Nov ML20210Q5831999-08-10010 August 1999 Requests Permission to Chemically Treat CWS for Algae Due to Cooling Water Basin Becoming Infected with Algae of Various Types PY-CEI-NRR-2422, Forwards Addl Info Re ASME Section IX Relief Request (IR-023) for Inservice Examination Program at Pnpp,Submitted on 9808261999-08-10010 August 1999 Forwards Addl Info Re ASME Section IX Relief Request (IR-023) for Inservice Examination Program at Pnpp,Submitted on 980826 ML20210K6331999-08-0404 August 1999 Submits Response to Requests for Addl Info to GL 92-01,Rev 1, Reactor Vessel Structural Integrity, for Perry Nuclear Plant,Unit 1 PY-CEI-NRR-2417, Forwards NP0059-007, Pnpp - Unit 1 ISI Summary Rept Results for Outage 7 (1999) First Period,Second Interval, IAW ASME Boiler & Pressure Vessel Code,Section XI,1989 Edition,Article IWA-60001999-08-0202 August 1999 Forwards NP0059-007, Pnpp - Unit 1 ISI Summary Rept Results for Outage 7 (1999) First Period,Second Interval, IAW ASME Boiler & Pressure Vessel Code,Section XI,1989 Edition,Article IWA-6000 ML20210G8411999-07-28028 July 1999 Informs That Based on Determination That Rev 14 Changes to Various Portions of Perry Nuclear Power Plant Emergency Plan Does Not Decrease Effectiveness of Licensee Emergency Plan & Meets Standard of 10CFR50.47(b),no NRC Approval Required ML20210E0661999-07-22022 July 1999 Forwards Insp Rept 50-440/99-08 on 990518-0708.No Violations Noted.Overall Conduct of Activities at Perry Facility, Conservative & Professional with Continuing Focus on Safety PY-CEI-NRR-2419, Forwards Four Copies of Rev 27 to Pnpp Security Plan,Per 10CFR50.54(p)(2).Changes Have Been Determined Not to Decrease Effectiveness of Security Plan.Rev Withheld1999-07-21021 July 1999 Forwards Four Copies of Rev 27 to Pnpp Security Plan,Per 10CFR50.54(p)(2).Changes Have Been Determined Not to Decrease Effectiveness of Security Plan.Rev Withheld PY-CEI-NRR-2415, Submits Estimate of Number of Licensing Submittal for FY00 & 01,for Pnpp,Per Administrative Ltr 99-02, Operating Reactor Licensing Action Estimates1999-07-19019 July 1999 Submits Estimate of Number of Licensing Submittal for FY00 & 01,for Pnpp,Per Administrative Ltr 99-02, Operating Reactor Licensing Action Estimates ML20210A6441999-07-15015 July 1999 Advises That Listed Operator Licenses for Company Personnel Have Expired,As of 990715,per 10CFR50.74(a) & 10CFR55.5. Individuals Listed Have Assumed Responsibilities at Pnpp That Do Not Require Operator Licenses ML20209E5951999-07-0909 July 1999 Ltr Contract:Task Order 46, Perry Engineering & Technical Support (E&Ts) Insp, Under Contract NRC-03-98-021 ML20209D5931999-07-0101 July 1999 Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Investigation Rept 3-98-005 Issued on 990510.Corrective Actions Will Be Examined During Future Inspections ML20211A3881999-06-30030 June 1999 Supplements Re NRC Incomprehensible Enforcement Inactions.Understands That NRC Claiming Hands Tied in Matter Re Discrimination Violation at Perry Npp.Requests That NRC Take Listed Two Actions PY-CEI-NRR-2410, Submits Response to NRC Request for Info Re GL 98-01, Y2K Readiness of Computer Sys at Npps. Attachment 1 Provides Y2K Readiness Disclosure for Plant1999-06-29029 June 1999 Submits Response to NRC Request for Info Re GL 98-01, Y2K Readiness of Computer Sys at Npps. Attachment 1 Provides Y2K Readiness Disclosure for Plant PY-CEI-NRR-2413, Advises That Jk Wood Will Replace Lw Myers as Pnpp,Vice President - Nuclear,Effective 9907061999-06-29029 June 1999 Advises That Jk Wood Will Replace Lw Myers as Pnpp,Vice President - Nuclear,Effective 990706 PY-CEI-NRR-2403, Submits Response to RAI Re GL 96-05 Program at Plant1999-06-29029 June 1999 Submits Response to RAI Re GL 96-05 Program at Plant ML20196H9641999-06-29029 June 1999 Confirms 990615 Telcon Request with J Lieberman for Addl Time to Respond to Enforcement Action 99-012.FirstEnergy Has 60 Days to Respond to EA PY-CEI-NRR-2412, Forwards Perry Nuclear Plant Simulator Four Yr Test Rept & NRC Form 474, Simulation Facility Certification, Which Describes Tests Conducted from June 1995-19991999-06-28028 June 1999 Forwards Perry Nuclear Plant Simulator Four Yr Test Rept & NRC Form 474, Simulation Facility Certification, Which Describes Tests Conducted from June 1995-1999 ML20211A3991999-06-28028 June 1999 Submits Concerns Re Proposed Changes to Enforcement Policy. Believes That NRC Existing Regulations & Policies Provide Adequate Controls & That NRC Not Administering Consistent Enforcement Policies in Response to Discriminatory Actions ML20196A6601999-06-16016 June 1999 Forwards Master Decommissioning Trust Agreements Revised After 1990 for Ohio Edison Co,Cleveland Electric Illuminating Co,Toledo Edison Co & Pennsylvania Power Co Re Bvnps,Units 1 & 2,DBNPS,Unit 1 & Perry Unit 1 PY-CEI-NRR-2405, Informs NRC That Pnpp Staff Has Implemented Formal Industry Position on Severe Accident Mgt1999-06-14014 June 1999 Informs NRC That Pnpp Staff Has Implemented Formal Industry Position on Severe Accident Mgt ML20195H9051999-06-10010 June 1999 Forwards Two License Renewal Applications Consisting of NRC Form 398 & NRC Form 396 for Bk Carrier,License OP-30997 & Jt Steward,License OP-30564-1 ML20212H5841999-06-10010 June 1999 Responds to NRC Notice of Level III Violation Received by K Wierman.Corrective Actions:K Wierman Has Been Dismissed from Position at Perry NPP PY-CEI-NRR-2408, Forwards Rev 4 to Pump & Valve Inservice Testing Program Plan, Incorporating Changes to Program to Implement Second Ten Yr Insp Interval1999-06-10010 June 1999 Forwards Rev 4 to Pump & Valve Inservice Testing Program Plan, Incorporating Changes to Program to Implement Second Ten Yr Insp Interval ML20195G6741999-06-10010 June 1999 Forwards Insp Rept 50-440/99-03 on 990407-0517.Two Violations of NRC Requirements Occurred & Being Treated as non-cited Violations,Consistent with App C of Enforcement Policy PY-CEI-NRR-2407, Responds to NRC Re Violations Noted in Investigations Rept 3-98-005.Corrective Actions:Initiated Internal Investigation Into Matter to Discover Party Responsible for Falsification of Training Records1999-06-0909 June 1999 Responds to NRC Re Violations Noted in Investigations Rept 3-98-005.Corrective Actions:Initiated Internal Investigation Into Matter to Discover Party Responsible for Falsification of Training Records 1999-09-09
[Table view] Category:INCOMING CORRESPONDENCE
MONTHYEARPY-CEI-NRR-2438, Informs That DBNPS & Pnpp Staffs Have Modified or Withdrawn Several of Positions Proposed within Re Request for Approval of Qap.Revised Positions Encl1999-10-14014 October 1999 Informs That DBNPS & Pnpp Staffs Have Modified or Withdrawn Several of Positions Proposed within Re Request for Approval of Qap.Revised Positions Encl PY-CEI-NRR-2435, Responds to NRC Re Violations Noted in Insp Rept 50-440/99-13.Corrective Actions:Ts SRs with Incorrect Descriptions Were Annotated to Ensure That CR Operators Are Aware That ACs Are Effect1999-10-13013 October 1999 Responds to NRC Re Violations Noted in Insp Rept 50-440/99-13.Corrective Actions:Ts SRs with Incorrect Descriptions Were Annotated to Ensure That CR Operators Are Aware That ACs Are Effect ML20212G5811999-09-23023 September 1999 Informs That Licenses for Ta Lentz,License SOP-31449,PJ Arthur,License SOP-30921-1 & Dp Mott,License SOP-31500 Are Considered to Have Expired,Iaw 10CFR50.74(a),10CFR55.5 & 10CFR55.55 PY-CEI-NRR-2432, Forwards NRC Form 536, Operator Licensing Exam Data, in Response to Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams1999-09-21021 September 1999 Forwards NRC Form 536, Operator Licensing Exam Data, in Response to Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams PY-CEI-NRR-2428, Submits Resolution to Seventh Question Proposed within NRC 980615 RAI Relating to Cooling Water Sys That Serve Containment Air Coolers & Assessment,Post Accident,Of Potential Water Hammer & two-phase Flow Conditions1999-09-16016 September 1999 Submits Resolution to Seventh Question Proposed within NRC 980615 RAI Relating to Cooling Water Sys That Serve Containment Air Coolers & Assessment,Post Accident,Of Potential Water Hammer & two-phase Flow Conditions ML20212D0151999-09-14014 September 1999 Requests Cancellation of NPDES Permit 3II00036.Permit Has Been Incorporated in Permit 3IB00016*ED.Discharge Point Sources & Associated Fees Currently Covered Under Permit 3IB00016*ED PY-CEI-NRR-2431, Forwards Revised Emergency Plan for Perry NPP, IAW 10CFR50.54(q).Changes Constitute Revs,Temporary Changes or Reissued Pages1999-09-0909 September 1999 Forwards Revised Emergency Plan for Perry NPP, IAW 10CFR50.54(q).Changes Constitute Revs,Temporary Changes or Reissued Pages PY-CEI-NRR-2425, Forwards Copy of Oh EPA Approval for Use of Nalco 7348 & Nalco 7468 at Pnpp,Iaw License NPF-58,App B,Epp,Section 3.21999-08-26026 August 1999 Forwards Copy of Oh EPA Approval for Use of Nalco 7348 & Nalco 7468 at Pnpp,Iaw License NPF-58,App B,Epp,Section 3.2 PY-CEI-NRR-2411, Informs That Firstenergy Nuclear Operating Co Has Developed Corporate QA Program Manual for Davis-Besse Nuclear Power Station & Perry Nuclear Power Plant,As Discussed on 990318 Between Util & Nrc.Revised USAR Pages,Encl1999-08-19019 August 1999 Informs That Firstenergy Nuclear Operating Co Has Developed Corporate QA Program Manual for Davis-Besse Nuclear Power Station & Perry Nuclear Power Plant,As Discussed on 990318 Between Util & Nrc.Revised USAR Pages,Encl ML20210S3961999-08-11011 August 1999 Requests That Ten Listed Individuals Be Registered to Take 991006 BWR Gfes of Written Operating Licensing Exam.Two Listed Personnel Will Have Access to Exams Before Exams Are Administered PY-CEI-NRR-2421, Forwards Semiannual fitness-for-duty Rept,Iaw 10CFR26.71(d) for Pnpp Covering Period of 990101-9906301999-08-10010 August 1999 Forwards Semiannual fitness-for-duty Rept,Iaw 10CFR26.71(d) for Pnpp Covering Period of 990101-990630 PY-CEI-NRR-2423, Provides Final Response to NRC GL 98-01, Y2K Readiness of Computer Sys at Npps. Remediation of Meteorological Monitoring Sys Has Been Completed & Ppnp Facility Is Now Y2K Ready1999-08-10010 August 1999 Provides Final Response to NRC GL 98-01, Y2K Readiness of Computer Sys at Npps. Remediation of Meteorological Monitoring Sys Has Been Completed & Ppnp Facility Is Now Y2K Ready PY-CEI-NRR-2422, Forwards Addl Info Re ASME Section IX Relief Request (IR-023) for Inservice Examination Program at Pnpp,Submitted on 9808261999-08-10010 August 1999 Forwards Addl Info Re ASME Section IX Relief Request (IR-023) for Inservice Examination Program at Pnpp,Submitted on 980826 PY-CEI-NRR-2417, Forwards NP0059-007, Pnpp - Unit 1 ISI Summary Rept Results for Outage 7 (1999) First Period,Second Interval, IAW ASME Boiler & Pressure Vessel Code,Section XI,1989 Edition,Article IWA-60001999-08-0202 August 1999 Forwards NP0059-007, Pnpp - Unit 1 ISI Summary Rept Results for Outage 7 (1999) First Period,Second Interval, IAW ASME Boiler & Pressure Vessel Code,Section XI,1989 Edition,Article IWA-6000 PY-CEI-NRR-2419, Forwards Four Copies of Rev 27 to Pnpp Security Plan,Per 10CFR50.54(p)(2).Changes Have Been Determined Not to Decrease Effectiveness of Security Plan.Rev Withheld1999-07-21021 July 1999 Forwards Four Copies of Rev 27 to Pnpp Security Plan,Per 10CFR50.54(p)(2).Changes Have Been Determined Not to Decrease Effectiveness of Security Plan.Rev Withheld PY-CEI-NRR-2415, Submits Estimate of Number of Licensing Submittal for FY00 & 01,for Pnpp,Per Administrative Ltr 99-02, Operating Reactor Licensing Action Estimates1999-07-19019 July 1999 Submits Estimate of Number of Licensing Submittal for FY00 & 01,for Pnpp,Per Administrative Ltr 99-02, Operating Reactor Licensing Action Estimates ML20210A6441999-07-15015 July 1999 Advises That Listed Operator Licenses for Company Personnel Have Expired,As of 990715,per 10CFR50.74(a) & 10CFR55.5. Individuals Listed Have Assumed Responsibilities at Pnpp That Do Not Require Operator Licenses ML20211A3881999-06-30030 June 1999 Supplements Re NRC Incomprehensible Enforcement Inactions.Understands That NRC Claiming Hands Tied in Matter Re Discrimination Violation at Perry Npp.Requests That NRC Take Listed Two Actions PY-CEI-NRR-2403, Submits Response to RAI Re GL 96-05 Program at Plant1999-06-29029 June 1999 Submits Response to RAI Re GL 96-05 Program at Plant PY-CEI-NRR-2413, Advises That Jk Wood Will Replace Lw Myers as Pnpp,Vice President - Nuclear,Effective 9907061999-06-29029 June 1999 Advises That Jk Wood Will Replace Lw Myers as Pnpp,Vice President - Nuclear,Effective 990706 PY-CEI-NRR-2410, Submits Response to NRC Request for Info Re GL 98-01, Y2K Readiness of Computer Sys at Npps. Attachment 1 Provides Y2K Readiness Disclosure for Plant1999-06-29029 June 1999 Submits Response to NRC Request for Info Re GL 98-01, Y2K Readiness of Computer Sys at Npps. Attachment 1 Provides Y2K Readiness Disclosure for Plant ML20211A3991999-06-28028 June 1999 Submits Concerns Re Proposed Changes to Enforcement Policy. Believes That NRC Existing Regulations & Policies Provide Adequate Controls & That NRC Not Administering Consistent Enforcement Policies in Response to Discriminatory Actions PY-CEI-NRR-2412, Forwards Perry Nuclear Plant Simulator Four Yr Test Rept & NRC Form 474, Simulation Facility Certification, Which Describes Tests Conducted from June 1995-19991999-06-28028 June 1999 Forwards Perry Nuclear Plant Simulator Four Yr Test Rept & NRC Form 474, Simulation Facility Certification, Which Describes Tests Conducted from June 1995-1999 ML20196A6601999-06-16016 June 1999 Forwards Master Decommissioning Trust Agreements Revised After 1990 for Ohio Edison Co,Cleveland Electric Illuminating Co,Toledo Edison Co & Pennsylvania Power Co Re Bvnps,Units 1 & 2,DBNPS,Unit 1 & Perry Unit 1 PY-CEI-NRR-2405, Informs NRC That Pnpp Staff Has Implemented Formal Industry Position on Severe Accident Mgt1999-06-14014 June 1999 Informs NRC That Pnpp Staff Has Implemented Formal Industry Position on Severe Accident Mgt ML20212H5841999-06-10010 June 1999 Responds to NRC Notice of Level III Violation Received by K Wierman.Corrective Actions:K Wierman Has Been Dismissed from Position at Perry NPP ML20195H9051999-06-10010 June 1999 Forwards Two License Renewal Applications Consisting of NRC Form 398 & NRC Form 396 for Bk Carrier,License OP-30997 & Jt Steward,License OP-30564-1 PY-CEI-NRR-2408, Forwards Rev 4 to Pump & Valve Inservice Testing Program Plan, Incorporating Changes to Program to Implement Second Ten Yr Insp Interval1999-06-10010 June 1999 Forwards Rev 4 to Pump & Valve Inservice Testing Program Plan, Incorporating Changes to Program to Implement Second Ten Yr Insp Interval PY-CEI-NRR-2407, Responds to NRC Re Violations Noted in Investigations Rept 3-98-005.Corrective Actions:Initiated Internal Investigation Into Matter to Discover Party Responsible for Falsification of Training Records1999-06-0909 June 1999 Responds to NRC Re Violations Noted in Investigations Rept 3-98-005.Corrective Actions:Initiated Internal Investigation Into Matter to Discover Party Responsible for Falsification of Training Records PY-CEI-NRR-2404, Submits Rept of Reduction in PCT Greater than 50 F Due to Implementation of Ge,Safr/Gestr LOCA Methodology for Fuel Cycle 8.Methodology Replaces Original LOCA Methodology1999-06-0707 June 1999 Submits Rept of Reduction in PCT Greater than 50 F Due to Implementation of Ge,Safr/Gestr LOCA Methodology for Fuel Cycle 8.Methodology Replaces Original LOCA Methodology ML20195E4561999-05-25025 May 1999 Submits Petition Per Other Actions Provision of 10CFR2.206,requesting That Radiation Protection Manager at Perry NPP Be Banned by NRC from Participation in Licensed Activities at & for Any NPP for at Least Five Yrs PY-CEI-NRR-2401, Forwards Changes to ERDS Data Point Library & Communication Survey for Perry Nuclear Power Plant.Changes Are Identified by Margin Rev Bars1999-05-20020 May 1999 Forwards Changes to ERDS Data Point Library & Communication Survey for Perry Nuclear Power Plant.Changes Are Identified by Margin Rev Bars PY-CEI-NRR-2402, Notifies of Completion of Plant Core Shroud Insp in Accordance with GL 94-03, Intergranular Stress Corrosion Cracking of Core Shrouds in Bwrs,1999-05-18018 May 1999 Notifies of Completion of Plant Core Shroud Insp in Accordance with GL 94-03, Intergranular Stress Corrosion Cracking of Core Shrouds in Bwrs, PY-CEI-NRR-2394, Forwards Application for Order & Conforming License Amend for Transfer of Interest in OL NPF-58 for Pnpp.Authorization of Ceic to Possess Dl 13.74% Undivided Ownership in Pnpp, Requested1999-05-0505 May 1999 Forwards Application for Order & Conforming License Amend for Transfer of Interest in OL NPF-58 for Pnpp.Authorization of Ceic to Possess Dl 13.74% Undivided Ownership in Pnpp, Requested PY-CEI-NRR-2397, Forwards Revised COLR Cycle 8, & Rev 1 to J11-03371SRLR, Supplemental Reload Licensing Rept for Pnpp,Unit 1 Reload 7,Cycle 8, IAW TS Section 5.6.51999-04-30030 April 1999 Forwards Revised COLR Cycle 8, & Rev 1 to J11-03371SRLR, Supplemental Reload Licensing Rept for Pnpp,Unit 1 Reload 7,Cycle 8, IAW TS Section 5.6.5 PY-CEI-NRR-2396, Provides post-examination Results of Weld Overlay Repair for FW Nozzle to safe-end Weld at Pnpp.Info Supplements Licensee 990325 & 0401 Ltrs Submitted to NRC That Requested Approval of Repair Plan for 1B13-N1C-KB FW Nozzle to safe-en1999-04-28028 April 1999 Provides post-examination Results of Weld Overlay Repair for FW Nozzle to safe-end Weld at Pnpp.Info Supplements Licensee 990325 & 0401 Ltrs Submitted to NRC That Requested Approval of Repair Plan for 1B13-N1C-KB FW Nozzle to safe-end Weld 05000440/LER-1999-002, Forwards LER 99-002-00, LCO 3.0.3 Entered Due to TS Bases Statement Interpretation. Action Occurred After RHR Pump Failed to Start.Plant at No Time Was in Condition Where Required Decay Heat Removal System Were Not Available1999-04-26026 April 1999 Forwards LER 99-002-00, LCO 3.0.3 Entered Due to TS Bases Statement Interpretation. Action Occurred After RHR Pump Failed to Start.Plant at No Time Was in Condition Where Required Decay Heat Removal System Were Not Available PY-CEI-NRR-2388, Forwards Annual Environ & Effluent Release Rept for Pnnp Unit 1 for 1998. Pnpp Had No Liquid Effluent Discharges in 1998 & All Other Release Points Were Well Below Applicable Limits1999-04-22022 April 1999 Forwards Annual Environ & Effluent Release Rept for Pnnp Unit 1 for 1998. Pnpp Had No Liquid Effluent Discharges in 1998 & All Other Release Points Were Well Below Applicable Limits PY-CEI-NRR-2371, Provides Suppl Response to Violations Noted in Insp Rept 50-440/98-18.Corrective Actions:Two Condition Rept Investigations Were Performed to Evaluate Issues Re Fire Protection Program & Addl Training Was Conducted1999-04-21021 April 1999 Provides Suppl Response to Violations Noted in Insp Rept 50-440/98-18.Corrective Actions:Two Condition Rept Investigations Were Performed to Evaluate Issues Re Fire Protection Program & Addl Training Was Conducted PY-CEI-NRR-2382, Forwards 1998 Annual Rept for Firstenergy Corp, for Perry Nuclear Power Plant & Davis-Besse Nuclear Power Station.Form 10-K Annual Rept to Us Securities & Exchange Commission for FY98 Also Encl1999-04-21021 April 1999 Forwards 1998 Annual Rept for Firstenergy Corp, for Perry Nuclear Power Plant & Davis-Besse Nuclear Power Station.Form 10-K Annual Rept to Us Securities & Exchange Commission for FY98 Also Encl PY-CEI-NRR-2392, Forwards Diskette Containing Pnpp Thermoluminescent Dosimeter Doses in Format Requested by Reg Guide 8.7.Without Diskette1999-04-19019 April 1999 Forwards Diskette Containing Pnpp Thermoluminescent Dosimeter Doses in Format Requested by Reg Guide 8.7.Without Diskette PY-CEI-NRR-2387, Documents Telcon Held Between NRC Staff & Members of Perry Nuclear Power Plant Staff on 990406,re Safety Evaluation for License Amend 1051999-04-14014 April 1999 Documents Telcon Held Between NRC Staff & Members of Perry Nuclear Power Plant Staff on 990406,re Safety Evaluation for License Amend 105 PY-CEI-NRR-2386, Forwards Copy of Application Submitted to FERC Proposing Transfer of Jurisdictional Transmission Facilities of Firstenergy Corp Operating Companies to American Transmission Sys,Inc.With One Oversize Drawing1999-04-0606 April 1999 Forwards Copy of Application Submitted to FERC Proposing Transfer of Jurisdictional Transmission Facilities of Firstenergy Corp Operating Companies to American Transmission Sys,Inc.With One Oversize Drawing ML20206N3361999-04-0505 April 1999 Informs NRR of Continued Events Re Transfer of Generation Assets Between Duquesne Light Co & Firstenergy.No Negotiated Settlement Between Firstenergy & Local 270 Pertaining to Generation Asset Swap Has Been Reached PY-CEI-NRR-2384, Provides Supplemental Info Re 990325 Request for Approval of Repair Plan for Feedwater Nozzle to safe-end Weld. Clarification Provided on Listed Three Items,Per 990329 Telcon with NRC1999-04-0101 April 1999 Provides Supplemental Info Re 990325 Request for Approval of Repair Plan for Feedwater Nozzle to safe-end Weld. Clarification Provided on Listed Three Items,Per 990329 Telcon with NRC PY-CEI-NRR-2383, Withdraws Inservice Exam Relief Requests IR-036 & IR-041, Submitted in Licensee to Nrc.Relief Request IR-041 Is Being Clarified with Respect to Alternative Proposed1999-04-0101 April 1999 Withdraws Inservice Exam Relief Requests IR-036 & IR-041, Submitted in Licensee to Nrc.Relief Request IR-041 Is Being Clarified with Respect to Alternative Proposed L-99-052, Forwards Info Concerning Dls Decommissioning Planning for Bvps,Units 1 & 2 & Pnpp Unit 1.DL Is Continuing to Utilize External Sinking Funds to Provide Financial Assurance for Nuclear Decommissioning Funding1999-03-30030 March 1999 Forwards Info Concerning Dls Decommissioning Planning for Bvps,Units 1 & 2 & Pnpp Unit 1.DL Is Continuing to Utilize External Sinking Funds to Provide Financial Assurance for Nuclear Decommissioning Funding ML20205H6171999-03-29029 March 1999 Forwards Util Consolidated Financial Statements for Twelve Month Period Ending 981231 & Internal Cash Flow Projection, Including Actual 1998 Data & Projections for 1999 PY-CEI-NRR-2377, Submits Decommissioning Repts for Bvps,Units 1 & 2,Davis- Besse Nuclear Power Station,Unit 1 & Perry Nuclear Power Plant,Unit 1,per 10CFR50.75(f)(1)1999-03-29029 March 1999 Submits Decommissioning Repts for Bvps,Units 1 & 2,Davis- Besse Nuclear Power Station,Unit 1 & Perry Nuclear Power Plant,Unit 1,per 10CFR50.75(f)(1) PY-CEI-NRR-2380, Requests Approval of Attached Repair Plan for Feedwater Nozzle to safe-end Weld N4C-KB.Proposed Weld Overlay Design & Installation Plan Details Included in Attachment 1. Attachment 2 Provides Applicable Preliminary Weld Procedure1999-03-25025 March 1999 Requests Approval of Attached Repair Plan for Feedwater Nozzle to safe-end Weld N4C-KB.Proposed Weld Overlay Design & Installation Plan Details Included in Attachment 1. Attachment 2 Provides Applicable Preliminary Weld Procedure 1999-09-09
[Table view] Category:UTILITY TO NRC
MONTHYEARPY-CEI-NRR-1226, Forwards LERs 90-018-00 & 90-019-00 for Plant1990-09-14014 September 1990 Forwards LERs 90-018-00 & 90-019-00 for Plant PY-CEI-NRR-1218, Responds to Generic Ltr 90-07 Re Proposed OL Exam Schedule, Operator Requalification Schedule & Generic Fundamental Exam Schedule for Plant.Licensee Will Continue to Train & Requalify Operators on Annual Basis1990-09-10010 September 1990 Responds to Generic Ltr 90-07 Re Proposed OL Exam Schedule, Operator Requalification Schedule & Generic Fundamental Exam Schedule for Plant.Licensee Will Continue to Train & Requalify Operators on Annual Basis ML20059E8741990-09-0505 September 1990 Forwards Fourteenth Quarterly Rept Cleveland Electric Illuminating Co Seismic Monitoring Network Jan-June 1990. Five Microevents Originating within Network & Three Other Events Originating Outside of Network Recorded PY-CEI-NRR-1216, Forwards Perry Nuclear Power Plant Unit 1 Semiannual Radioactive Effluent Release Rept,1990 Quarters 1 & 2. Response to Recommendations from NRC Re Range of Dilution Flows Will Be Submitted W/Next Effluent Rept1990-08-29029 August 1990 Forwards Perry Nuclear Power Plant Unit 1 Semiannual Radioactive Effluent Release Rept,1990 Quarters 1 & 2. Response to Recommendations from NRC Re Range of Dilution Flows Will Be Submitted W/Next Effluent Rept PY-CEI-NRR-1201, Forwards First Semiannual fitness-for-duty Rept for Plant for 900103-0630,per 10CFR26.71(d) Requirements1990-08-28028 August 1990 Forwards First Semiannual fitness-for-duty Rept for Plant for 900103-0630,per 10CFR26.71(d) Requirements PY-CEI-NRR-1211, Responds to NRC Re Violations Noted in Insp Rept 50-440/89-26.Corrective Actions Noted:Necessary Engineering Design Mods Which Evaluation Found Necessary Contained in DCP 90-00861990-08-23023 August 1990 Responds to NRC Re Violations Noted in Insp Rept 50-440/89-26.Corrective Actions Noted:Necessary Engineering Design Mods Which Evaluation Found Necessary Contained in DCP 90-0086 PY-CEI-NRR-1210, Proposes Date of 901207 to Provide Updated Status & Schedules,Per 900604 Request for Addl Info on Disposition of Bulletin 88-005 Product Forms Other than Pipe Fittings & Flanges Received at Plant1990-08-17017 August 1990 Proposes Date of 901207 to Provide Updated Status & Schedules,Per 900604 Request for Addl Info on Disposition of Bulletin 88-005 Product Forms Other than Pipe Fittings & Flanges Received at Plant PY-CEI-NRR-1208, Responds to NRC 900613 Request for Addl Info Re Inservice Insp Relief Requests.Util Revised Relief Requests PT-001 & PT-003 to Provide More Detailed Info & Has Withdrawn Relief Request IR-017.Revised Relief Requests & Summary Encl1990-08-10010 August 1990 Responds to NRC 900613 Request for Addl Info Re Inservice Insp Relief Requests.Util Revised Relief Requests PT-001 & PT-003 to Provide More Detailed Info & Has Withdrawn Relief Request IR-017.Revised Relief Requests & Summary Encl PY-CEI-NRR-1203, Provides Estimate Duration Schedule Re Installation of post-LOCA Neutron Monitoring Sys.Util Will Evaluate Effect of Resolution on Schedule & Confirm or Revise Installation Date as Needed,When Appeal & Criteria Questions Resolved1990-07-27027 July 1990 Provides Estimate Duration Schedule Re Installation of post-LOCA Neutron Monitoring Sys.Util Will Evaluate Effect of Resolution on Schedule & Confirm or Revise Installation Date as Needed,When Appeal & Criteria Questions Resolved PY-CEI-NRR-1200, Forwards Decommissioning Repts on Financial Assurance for Plant1990-07-25025 July 1990 Forwards Decommissioning Repts on Financial Assurance for Plant PY-CEI-NRR-1196, Forwards Rev 0 to Inservice Exam Program. Program Serves as 10-yr Rev to Inservice Insp Program Plan1990-07-24024 July 1990 Forwards Rev 0 to Inservice Exam Program. Program Serves as 10-yr Rev to Inservice Insp Program Plan PY-CEI-NRR-1205, Forwards LERs 90-014-00 & 90-015-00 for Plant1990-07-20020 July 1990 Forwards LERs 90-014-00 & 90-015-00 for Plant PY-CEI-NRR-1193, Responds to Generic Ltr 90-04 Re Implementation Status of Generic Safety Issues1990-06-29029 June 1990 Responds to Generic Ltr 90-04 Re Implementation Status of Generic Safety Issues ML20043H7371990-06-19019 June 1990 Forwards Individual Plant Exam Project Milestones.Milestones Subj to Change from Project or External Causes & Will Not Be Docketed Again Unless Significant Impact on Final Rept Contents or Submittal Date Exists ML20043H1711990-06-14014 June 1990 Discusses Util Radiological Safety Board of Ohio 900614 Comments on Notice of Opportunity for Hearing Re Rev to Previously Submitted License Amend Application.Licensees Would Welcome Opportunity to Consult W/State of Oh ML20043E5771990-06-0808 June 1990 Provides Info Re Implementation of Administrative Controls & Training Related to Use of Tech Spec 3.0.4.Util Intends to Implement Amend 30 Changes by 900618.All Licensed Operators Would Receive Training to Generic Ltr 87-09 ML20043B6981990-05-21021 May 1990 Forwards Info Re Activation Energy Values Utilized for Brand-Rex Co Cable at Facility.Encl Includes Rept, Qualification Tests of Electric Cables for Class 1E Svc in Nuclear Power Plants. ML20043A7041990-05-18018 May 1990 Forwards LERs 90-007-00 & 90-008-00 ML20043A4771990-05-16016 May 1990 Provides Justification Re Events Leading to Declaration of Alert on 900403 Due to Loss of Emergency Svc Water When Manway Flange Gasket Leak Developed at Pump a Discharge Strainer,In Response to Ocre 900406 Petition ML20042F4931990-05-0404 May 1990 Forwards Response to Generic Ltr 89-19 Re Reactor Vessel Overfill Protection ML20042F1961990-04-27027 April 1990 Informs of Adoption of Reorganization Plan Re Plants on 900424.Reorganization Will Make No Changes in Technical or Financial Qualifications for Plants.Application for Amends to Licenses Adding Company as Licensee Will Be Submitted ML20042F8051990-04-19019 April 1990 Forwards 1989 Financial Repts for Centerior Energy Corp, Cleveland Electric Illuminating Co & Toledo Edison Co & Supplemental Sec Form 10-K ML20012F3521990-04-0202 April 1990 Suppls Response to NRC 891215 Ltr Re Deviations Noted in Insp Rept 50-440/89-26.Corrective Actions:Profile of Heat Generation from Stored Fuel Vs Time for First Four Fuel Load Discharges Calculated & Design Changes Implemented ML20012E7811990-03-30030 March 1990 Confirms Basis for 890417 Submittal Re Station Blackout ML20012E9431990-03-26026 March 1990 Forwards Correction Pages to Semiannual Radioactive Effluent Release Rept 1989:Quarters 3 & 4. Changes Affect Liquid Effluent Data Only.Corrections Made Due to High Contribution of Sr-89 to Liquid Effluent Dose ML20012B9851990-03-0909 March 1990 Responds to Generic Ltr 90-01 Re Regulatory Impact Survey ML20012B5931990-03-0808 March 1990 Responds to Open Item Noted in Insp Rept 50-440/89-29. Corrective Actions:Plant Health Physicist & Operations Superintendent Met W/Health Physics & Operations Crews to Discuss Better Methods of Access Control ML20012A1561990-03-0202 March 1990 Forwards Semiannual Radioactive Effluent Release Rept for Jul-Dec 1989 & Addl Info in Response to NRC 890605 Ltr Re Offsite Dose Calculation Manual ML20012B9801990-03-0202 March 1990 Responds to 890810 Request for Addl Info on Util 890306 Tech Spec Change Request Re MSIV Leakage Limits.Change Does Not Request Increase in MSIV Leakage Beyond Currently Assumed in Updated SAR Chapter 15 ML20006E5131990-02-12012 February 1990 Lists Suggestions on Subj Areas to Be Addressed During Proposed 1990 Licensee Info Conference,In Response to 900117 Ltr ML20006E3211990-02-0909 February 1990 Discusses Implementation of Facility Revised Inservice Testing Program,Per Generic Ltr 89-04.Improvements Listed, Including sign-off Matrix Deletion at End of Instruction & Movement of Comments Section ML20006D0971990-02-0202 February 1990 Provides Update to 880721 Ltr Re Performance of Seismic Margin Evaluation.Util Awaiting Issuance of Individual Plant Exams of External Events Generic Ltr Prior to Proceeding W/ Seismic Margins Study ML20011E1841990-02-0202 February 1990 Forwards LERs 90-001 & 90-002 ML20006D5731990-01-30030 January 1990 Forwards Response to NRC 900112 Request for Addl Info Re 891121 Request for Exemption from Filing Requirements of 10CFR55.45(b)(2)(iii).Qualification Plan for Certification of Existing Simulator Approved in Aug 1987 ML20006B5131990-01-26026 January 1990 Responds to NRC Bulletin 89-002 Re Stress Corrosion Cracking of Type 410 Stainless Preloaded Bolting in Swing Check Valves.No Bolts Subj to Bulletin in Use at Facility ML20006B5571990-01-26026 January 1990 Forwards Response to Generic Ltr 89-13, Svc Water Sys Problems Affecting Safety-Related Equipment. Procedures in Place for Underwater Insp of Intake Structures in Lake as Well as on-shore Pump Houses Annually ML20006A0781990-01-16016 January 1990 Responds to NRC 891215 Ltr Re Deviations Noted in Insp Rept 50-440/89-26.Corrective Actions:Profile of Heat Generation from Stored Fuel Vs Time for First Four Fuel Discharges Calculated & Updated SAR Change Request Will Be Submitted ML20005F9331990-01-0909 January 1990 Provides Inadvertently Omitted Inequality Signs from Util 891213 Response to NRC Bulletin 88-004 Re RCIC Pump Min Flow Limitations from Operating Instructions ML20042D5051990-01-0303 January 1990 Informs That Licensee Implemented fitness-for-duty Program at Plant on 900103,per 10CFR26.More Stringent cut-off Levels Imposed by Util than Required by 10CFR26 ML20005E1391989-12-28028 December 1989 Forwards Response to Generic Ltr 89-10 Re safety-related motor-operated Valve Testing & Surveillance.Each motor- Operated Valve Will Be Stroke Tested to Verify Valve Operability at no-pressure & no-flow Conditions ML19332F7941989-12-13013 December 1989 Responds to NRC 890531 Request for Addl Info Re NRC Bulletin 88-004, Safety-Related Pump Loss. Info Covers pump-to-pump Interaction That Could Result in Deadheading & Adequacy of Min Flow Bypass Lines Against Pump Damage ML19332E6921989-12-0707 December 1989 Responds to Violations Noted in Insp Rept 50-440/89-12 on 890627 & 1023.Corrective Actions:Flange Leakage of Relief Valve Repaired During First Refueling Outage & Design Mods to Enhance Testability of Gasketed Flanges Being Developed ML19332F3851989-12-0606 December 1989 Forwards Twelfth Quarterly Rept Cleveland Electric Illuminating Seismic Monitoring Network,Jul-Sept 1989. Rept Describes Area in Vicinity of Two Waste Injection Wells Located 3 Miles South of Plant Site ML19332E7971989-12-0101 December 1989 Responds to Generic Ltr 89-21 Re Implementation Status of USIs ML19332E3611989-11-28028 November 1989 Submits Supplemental Info Re Tech Spec Change Request Proposing Addition of Requirement to Verify Trip Setpoint of Intermediate Range Monitor Control Rod Block Instrumentation During Performance of Weekly Channel Functional Testing ML19332D5771989-11-27027 November 1989 Submits Supplementary Info to 880520 Tech Spec Change Request,Changing Setpoints for Turbine First Stage Pressure to Reflect Values Actually Measured During Startup Test Program at 40% of Rated Reactor Power.Table Encl ML19332C7341989-11-22022 November 1989 Forwards Executed Amend 3 to Indemnity Agreement B-98 ML19332C4041989-11-22022 November 1989 Responds to NRC 891025 Ltr Re Violations Noted in Insp Rept 50-440/89-23.Corrective Actions:Work Stopped on Div III & Restoration Began to Return to Operation & All Actions Required by Tech Spec 3.0.3 Completed ML19332C8321989-11-21021 November 1989 Forwards Inservice Insp Summary Rept NP0059-0001, Results for Outage 1 (1989),First Period,First Interval, Vols I & Ii,Covering Insp Period 871118-890805 ML19332C4531989-11-21021 November 1989 Requests Exemption from Requirements of 10CFR45.(b)(2)(iii), to Allow for Submittal of NRC Form 474, Simulation Facility Certification, After 910326 Deadline 1990-09-05
[Table view] |
Text
.
$)2//vf(
THE CLEVELAND ELECTRIC ILLUMIN ATING COMP ANY P o. Box 5000 - CLEVELAND. oHlo 44101 - TELEPHONE (216) 622-9800 - lLLUMINATING BloG- - 55 PUBLICSoVARE Serving The Best !.ocation in the Nation July 5, 1986 j~ ~ ~
MURRAY R. EDELMAN SR VICE PRESIDENT NUCUAR Mr. Charles E. Norelius, Director Division of Reactor Projects U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL. 60137 Perry Nuclear Power Plant Docket No. 50-440 50-440/86011 Noncompliance Response
Dear Mr. Norelius:
This letter acknowledges receipt of Inspection Report 50-440/86011 attached to your letter dated June 6,1986. The report identifies areas examined by Messrs. J. A. Grobe, K. A. Connaughton and J. W. McCormick-Barger from April 9 through May 12, 1986 at Perry Nuclear Power Plant, Unit 1.
Our response to the Notice of Violation contained within your report is included as Attachment 1. Attachment 2 provides our response to concerns raised in your cover letter concerning corrective actions to preclude future occurrences of personnel errors. As you will notice f rom our' response, prompt senior management attention has been taken to correct these situations and to preclude similar occurrences in the future. Our present schedule does not appear to be a contributor to the types of situations identified in your report. We believe the actions taken and the additional training provided will cause the number of these occurrences to diminish rapidly as we proceed with startup.
This response has been submitted to you within the required thirty days of the date of your Notice. If you have any additonal questions, please feel free to contact me.
Very truly rs.
8608040125 860705 0 d
PDR ADOCK 05000 Murray R. Edelman G Senior Vice President Nuclear Group MRE:n; Attachment cc: Jay Silberg, Esq.
John Stefano (2)
J. Grobe J. Keppler Document Control Desk Washington, D.C.
JUL 71999 l 112E;oi t i l
Atttchment 1 PY-CE1/01E-0215 L
- 1. Restatement of Violation l
Perry Unit 1 Technical Specification 3.3.7.10 requires, in part, that with the Unit 1 Vent Radiation Monitor Noble Gas Activity Monitor inoperable, except as the result of a nonconservative setpoint, immediately suspend containment /drywell purge and vent.
Contrary to the above, on April 13, 1986, as a result of a planned -
maintenance activity the Plant Vent Radiation Monitor Noble Gas Activity Monitor was rendered inoperable for reasons other than a nonconservative setpoint for a period of approximately three and one-half hours without a suspension of containment /drywell purge operations.
This is a Severity Level IV violation.
Corrective Steps Which Have Been Taken and Results Achieved This event resulted from a misunderstanding of system design and failure to properly respond to alarm indications. In preparing the tagout to perform preventive maintenance on the Unit 2 Plant Vent Radiation Monitor, the Unit Supervisor (US) failed to realize that a common breaker supplied power to both the Unit I and Unit 2 Plant Vent Radiation Monitors.
Tagging out this breaker, results in a loss of power to both monitors.
The US also incorrectly ascumed that only the sample pump for the isokinetic probe was being tagged out. The sample analysis blower, a Technical Specification required component was actually tagged out. The Repetitive Task Card associated with this maintenance activity also failed to identify this as a Technical Specification related activity.
i After hanging the tags and opening the breaker associated with the Unit 1 and Unit 2 Plant Vent Radiation Monitors, the Unit 1 Plant Vent Air Radiation Monitor Flow Low Alarm was actuated. Shift operators silenced the alarm but failed to take further action as called for in the Alarm Response Instruction. As a result, containment /drywell purging was not stopped as required by Technical Specifications. This situation existed j for approximately 3.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> until the tags were cleared and the breaker
- closed. The Unit Supervisor on the next shift, while reviewing the i cleared tags, identified the problem and initiated a condition report which was followed by LER 86-004.
I Shift operators have received additional training on the Airborne Radiation Monitoring System (ABRM) operating characteristics, design and
- electrical diagrams. This training also reinforced the need to adhere to '
l Alarm Response Instructions. The Repetitive Task Cards associated with
' radioactive effluent systems were reviewed, and a note was added to the
- cards to indicate their relationship to Technical Specifications.
Corrective Steps Which Will Be Taken to Prevent Recurrence In addition to the action already taken, the System Operating Instruction for the ABRM system, 50I-D17, will be reviewed and appropriate changes made to clarify ABRM system operability requirements.
i 1
-,,- e .n m - -,,. -~v.,n. -.r-----,- - - - - - - - - -..a-, .n, , - - - - - -
. Attechment 1
, PY-CEI/01E-0215 L Date of Tull Compliance Full Compliance with Technical Specification 3.3.7.10 was achieved when the sample analysis blower was returned to service. S01-D17, " Airborne Radiation Monitoring System" will be reviewed and revised as appropriate by July 21, 1986.
i l
. Attachsznt 1
. PY-CEI/0IE-0215 L
- 2. Restatment of Violation Perry Unit 1 Technical Specification 3.6.1.1.2 requires, in part, that Primary Containment Integrity be maintained during core alterations.
Contrary to the above, Primary Containment Integrity was not maintained during core alterations conducted between:
- a. April 14 and 23, 1986, in that automatic containment isolation valve 1G33-F004 was open and inoperable due ta an improperly processed facility modification while redundant artomatic isolation valve 1G33-F001 was not closed and deactivated in its closed position.
- b. March 12 and April 30, 1986, in that redundant manual containment isolation valves IP54-F726 and IP54-F727 were not closed.
This is a Severity Level IV violation.
2.a) Corrective Steps Which Have Been Taken and Results Achieved On March 11, 1986, an Instrument and Control Test Support Engineer (I&C TSE) performed an as-built walkdown (visual verification) of an electrical panel using an out-of-date drawing (dated January 30, 1986). The TSE observed a jumper in the panel that was not shown on tha out-of-date print. The TSE assumed the jumper in the panel was a spare and initiated a Work Order to remove it. The jumper was removed on April 14, 1986. The G33 system engineer was not contacted prior to removal of this jumper, nor was the work order process followed correctly in that an authorizing design change document was not utilized.
On April 21, 1986, a review of the Work Order which removed toe jumper revealed that the jumper had originally been installed correctly using approved procedures to supply power to the closing circuit of valve G33-F004. The Work Order was returned to the work planner, but no other corrective actions were taken at that time. On April 23, 1986 during routine surveillance testing, valve G33-F004 f ailed to close as required.
Immediately upon failure of G33-F004 to close, operations personnel closed and tagged out valve G33-F001, the inboard isolation valve which restored containment integrity. A condition report was initiated followed by LER-86-007. The jumper was replaced, using approved procedures by April 25, 1986.
I&C personnel have been counseled regarding the necessity for researching outstanding design changes, the requirements for using the latest revision of drawings in the field and for ensuring that identified discrepancies receive appropriate engineering evaluation. I&C planners have been counseled regarding the importance of using proper engineering documents and of contacting the appropriate System Engineer to establish retest requirements when planning Work Orders. Procedure TPI-24, "As-Built Drawings", has been revised to require formal engineering review of discrepancies identified during walkdowns. System Engineers are being trained concerning the requirements for identifying and initiating immediate corrective action following discovery of design deficiencies.
--,-_,c. - - - - - - - - - -
Attachrent 1 PY-CEI/01E-0215 L 4
The appropriate Operations Section personnel have been instructed as to their responsibility for ensuring that design change documents accompany Work Orders. Similar retraining is being conducted for Quality Assurance Section personnel. Procedure PAP-0607. " Perry Plant Drawing Control,"
which was recently revised, stresses the responsibility of all individuals to assure that only the latest revision of any drawing is used for testing, verification or component manipulation. It also states that "Each Work Order being worked shall be accompanied by a Controlled Copy of the Design Change Package (DCP)."
Corrective Steps Which Will Be Taken to Prevent Recurrence In addition to the steps already taken, the Nuclear Quality Assurance Department is in the process of conducting an audit of the As-Built Walkdown Program for Electrical Elementary Diagrams and Electrical Interconnection Wiring Diagrams to verify appropriate design configuration control.
Date of Full Compliance Full compliance with Technical Specification 3.6.1.1.2 was met when valve G33-F001 was closed and tagged out on April 23, 1986. The NQAD audit will be completed by August 1, 1986. Training will be completed by August 1, 1986.
i i
- Attachment 1
- PY-CEI/01E-0215 L 2.b) Corrective Steps Which Have Been Taken and Results Achieved On April 30, 1986, shift operators discovered that the containment fire hose reel inboard / outboard supply isolation valves were in the open position. These valves are required to be closed during core alterations in accordance with Technical Specification 3.6.1.1.2 for primary containment integrity. Investigation revealed that the valves had been opened prior to beginning core alterations and that shif t operators had neglected to initiate proper administrative controls to track their positions. Additionally, review of completed valve lineups during the interval March 21, 1986 - Apt;* 30, 1986 failed to identify this error.
The immediate corrective action upon identification of this problem was to close the subject valves. A condition report was initiated followed by LER 86-008. Shift operators have been retrained concerning Technical Specification requirements for containment integrity, the surveillance test control program and the Fire Protection System, System Operating Instruction (S01). Shift personnel directly involved in the event have been counseled regarding their responsibility to properly review SVI acceptance criteria (including valve lineups) and on the need to initiate the necessary administrative controls when Technical Specification related equipment is involved.
Corrective Steps Which Will Be Taken to Prevent Recurrence As described above, all corrective actions have been taken.
Date of Full Compliance Full compliance with Technical Specification 3.6.4.1.2 was achieved when the inboard / outboard supply isolation valves were closed on April 30, 1986.
1 I
- Attachment 1
. .- PY-CEI/01E-0215 L
}
)
j
- 3. Restatement of Violation
! Perry Unit 1 Operating License Condition C.(6) requires implementation of i
the licensee's approved fire protection program.
i i
The licensee's approved fire protection program as implemented by Plant J
Administrative Procedure (PAP)-1923 requires, in part, that compensatory i measures be taken for inoperable automatic fire suppression equipment 2
protecting the diesel generators (when the diesel generators are required j operable) and for inoperable manual hose reels protecting areas of the control complex.
Contrary to the above, compensatory measures were not taken while the l Control Complex and Diesel Generator Building CO2Systems were inoperable between April 26 and May 7,1986.
! Corrective Steps Which Have Been Taken and Results Achieved i
On April 7, 1986 shift operators authorized a tagout to tag closed the CO 2
- suppression control valve OP54-F5622 to prevent discharge of CO 2 during
] maintenance on C0 9 control panels. On the same day, a second tagout which 1- tagged additonal CO 2 system valves, was written to isolate the CO 2 hose j reels for maintenance. Both tagouts impaired C0 fire protection
! capabilitytotheDieselGeneratorBuildingandksolatedtheCO 28uPply to j- the fire hose reels in the Control Complex Building. Due to these
{
impairments, appropriate compensatory measures were taken.
I j Work on the CO 2 e ntrol panels was completed on April 8, 1986, the first tagout was cleared and the tags were removed. Concerned with the safety of the personnel still performing maintenance on the CO, hose reel, the Unit Supervisor (US) decided to leave valve OP54-F5622 In the closed 3
position and to tag it closed under the remaining tagout. The US did not, j however, subsequently modify the existing tagout. Maintenance on the CO 2 j_ hose reels was completed on April 26, 1986 and the second tagout was i cleared. The tags were removed and all valves listed on the tagout were restored to their proper positions. Since OP54-F5622 had not been added to the second tagout, it was not repositioned and therefore remained in
?
the closed position.
i
! On May 7, another tagout was initiated and compensatory measures taken to
+
again work on the CO2 panels. While hanging the tag on OP54-F5622, operators discovered the valve already to be in the closed position.
Compensatory measures remained in effect until the valve was again opened.
i A condition report was written, followed by LER 86-010. Although this
- impairment did not adversely affect the ability of the plant to achieve
- and maintain safe shutdown, it was a violation of the tagout procedures '
and resulted in an uncompensated loss of a supplemental fire protection system.
k J
l 4
W
4 Attcchment 1 PY-CEI/01E-0215 L The Unit Supervisor has been counseled with respect to his responsibilities and the importance of strictly adhering to tagout procedures. This event was also discussed with other control room operators.
Corrective Steps Which Will Be Taken To Prevent Recurrence All corrective actions have been taken.
Date of Full Compliance Full compliance with Operating License Condition C.(6) was achieved when control valve OP54-F5622 was opened on May 7, 1986.
I l
i D16/26
-_ _ _ _- ~__ _ _.-_ ~ _-_ - _- _. _ .- .. _ ._ ___ _ ..._-.-_.__.--_._. ._.
. Attechosnt 2
,' '* , . PY-CEI/01E-0215 L Management Initiatives You requested that we specifically address our program for identification of root cause(s) of the violations and those steps we plan or have already taken to assure prompt and comprehensive corrective action is taken to preclude occurrences involving similar personnel errors. You also requested that we consider the contribution to these occurrences to the ambitious scheduling of work activities requiring the congnizance and support of operating personnel.
The following discussion addresses your concerns:
CEI management places utmost importance on the safe and efficient operation of th,e Perry Nuclear Power Plant. We continually strive to maintain the necessary level of resources and training to ensure the highest quality of operations.
As evidenced by our approach to fuel loading activities, all project resources are directed support of operations activities and sufficient time is allowed to complete the necessary work to support each operational milestone. Daily operations overview meetings, which includes the management of all project support elements, are a primary vehicle for operations to ensure project resources are properly focused and the level of activities is one that operations can support. Upper management awareness and attention is focused on both progress of activities, as well as on the type, cause, and corrective action for problems encountered during each work phase. Personnel errors, such as identified in your report, receive immediate attention by all levels of managment, for both root cause evaluation as well as ensuring immediate and long-term corrective action is taken to preclude reoccurrence.
Program For Identification of Root Causes CEI employs several levels of review for identifying and correcting root causes of conditions and events. Conditions or events are documented on Condition Reports (CR), and supplemented by Nonconformance Reports (NR), Action Requests (AR), or Corrective Action Requests (CAR), in accordance with procedures. The procedures associated with these documents require that corrective actions be taken to preclude recurrence. These actions may be specific to the described event and may also reach out into a much broader scope. Condition reports and resulting LER's are reviewed by various levels of management, depending upon the significance of the event. These reviews assure a management overview of the event or condition as well as an analysis of the corrective actions taken.
In addition to specific trending of conditions or events as required by procedures, a significant amount of further management overview of plant events takes place. On a daily basis, a report describing plant status, evolutions and conditions reports generated is distributed to all supervision on the project and upper management. The conditions or events are discussed at a daily operations overview meeting involving all operations support elements.
Emerging trends, as identified by similar events or commonality in cause, are assigned to a responsible section for followup corrective action. Other management meetings, including the Plant Operations Review Committee, Nuclear Safety Review Committee, and weekly Nuclear Group Management meetings monitor the plant conditions or events trends and discuss causes and corrective actions.
I
- Attachment 2
. PY-CEI/01E-0215 L l
In addition, the Independent Safety Engineering Group monitors condition report information to define areas for further ISEG investigation and studies.
These various mechanisms, both formal, and informal assure management awareness and attention to assure prompt and corrective action is taken to learn from our events and preclude reoccurrence. Finally, an overall project performance monitoring program is under development that will provide corporate and plant management with quantitative, graphical presentation of numerous plant performance trends, including condition reports and LERs. CEI believes that our efforts to date have been useful and have caused significant improvements in our programs. We intend to continue refining our monitoring and corrective action trending efforts to enhance their overall effectivenes.
Steps to Minimize Further Personnel Error Occurrence Although many of the events which have occurred to date can be attributed to design and equipment problems which have been or are being resolved, several have involved personnel error, and these are being given considerable attention by upper management.
In recent months, CEI has conducted substantial additional training related to work processes, operational activities, and procedural and Technical Specification compliance. Senior management has specifically established a training program to ensure total project awareness of Tehenical Specification requirements and the need to communicate fully with the Control Room. Specific efforts have been undertaken to enhance the work order process, such as adding an experienced individual to the Maintenance work order process which centralizes the interface between Operations and Maintenance personnel.
Special surveillance and assessments have, and will continue to be, performed to identify and correct potential problem areas. Areas assessed to date include Operations, Maintenance, Surveillance and Administrative Controls.
Work related procedures and processes have been significantly modified to improve operational phase activities, particularly the tagout procedure and work order procedure.
CEI management has instituted controls to manage and support the number of operator related work activities (design change packages, work orders, etc.)
that are processed on a daily basis. As noted in previous discussions we had instituted the Project Work Center (PWC) staffed with an SRO qualified individual, to centralize the control of work and activities that affect the plant. CEI believes that this technique has been beneficial to plant safety and has been helpful in supporting operations control of work activities. CEI will continue to employ our overall approach of monitoring and evaluating performance, enhancing work processes, providing additional training and support resources to minimize occurrences involving similar personnel error.
We will make adjustments based upon future operations experiences and event root cause reviews.
D16/36