THE-CLEVELAND ELECTRIC ILLUMINATING COMPANY P.O. BOX 97 5
PERRY, OHIO 44001 - B TELEPHONE (216) 259 3737.
B ADDRESS 10 CENTER ROAD ~
FROM CLEVELAND: 4 4 1260
.B TELEX: 241500 AN8WERBACK: CEIPRYO l
Al Kaplan Serving The Best location in the Nation i
PERRY NUCLEAR POWER PLANT VICE PRESIDENT NUCdAR GHOUP January 9, 1990 PT-CEI/NRR-1118 L U.S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.
20555 Perry Nuclear Power Plant Docket No. 50-440 I
Request for Additional'Information.-
NRC Bulletin 88-04 (TAC No.J69954)-
i Gentlemen:
i Our letter PY-CEI/NRR-1081L dated December' 13, 1989 provided the following'
(
information on RCIC pump minimum flow limitations from PNPP operating
-j instructions, however, the inequality signs were. inadvertently _omitted
" Maintain the RCIC Pump flow greater than or equal..to the following-
. I limitations:
'30 minutes-10' minutes RPM Continuous Duty in 24' hour ~ period in 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period
- i
< 2250 140 GPM 85 GPM
.NA 7 2250 345 GPM 225 GPM 120 GPM NOTE: RCIC MIN FLOW VALVE, 1E51-F019, passes.120 GPM'.'
l The RCIC pump manufacturer has confirmed that operation of the system'within
{
the limits of this table will not result in pump degradation. 'If you have any 1
questions, please, feel free to call.
Very truly 8,.
Al Kaplan Vice President-Nuclear Group AK:nje cc:
T. Colburn P. Hiland h
USNRC, Region III 7
1 g.
9001170408.900109 7
/
.PDR..ADOCK 05000440 f.
g PDC a
7