q A

THE-CLEVELAND ELECTRIC ILLUMINATING COMPANY P.O. BOX 97 5

PERRY, OHIO 44001 - B TELEPHONE (216) 259 3737.

B ADDRESS 10 CENTER ROAD ~

FROM CLEVELAND: 4 4 1260

.B TELEX: 241500 AN8WERBACK: CEIPRYO l

Al Kaplan Serving The Best location in the Nation i

PERRY NUCLEAR POWER PLANT VICE PRESIDENT NUCdAR GHOUP January 9, 1990 PT-CEI/NRR-1118 L U.S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.

20555 Perry Nuclear Power Plant Docket No. 50-440 I

Request for Additional'Information.-

NRC Bulletin 88-04 (TAC No.J69954)-

i Gentlemen:

i Our letter PY-CEI/NRR-1081L dated December' 13, 1989 provided the following'

(

information on RCIC pump minimum flow limitations from PNPP operating

-j instructions, however, the inequality signs were. inadvertently _omitted

" Maintain the RCIC Pump flow greater than or equal..to the following-

. I limitations:

'30 minutes-10' minutes RPM Continuous Duty in 24' hour ~ period in 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period

i

< 2250 140 GPM 85 GPM

.NA 7 2250 345 GPM 225 GPM 120 GPM NOTE: RCIC MIN FLOW VALVE, 1E51-F019, passes.120 GPM'.'

l The RCIC pump manufacturer has confirmed that operation of the system'within

{

the limits of this table will not result in pump degradation. 'If you have any 1

questions, please, feel free to call.

Very truly 8,.

Al Kaplan Vice President-Nuclear Group AK:nje cc:

T. Colburn P. Hiland h

USNRC, Region III 7

1 g.

9001170408.900109 7

/

.PDR..ADOCK 05000440 f.

g PDC a

7