Applicant Exhibit A-23,consisting of Unit 1 Diesel Generator 1B
ML20085M811
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 05/16/1995
From:
GEORGIA POWER CO.
To:
References
OLA-3-A-023, OLA-3-A-23, NUDOCS 9506290352
Download: ML20085M811 (6)


Text

CC3

~ GPC EXIIIBir 23 l CASil EX. B UNIT 1 DIESEL M TOR 1s 00CKETE0 USNRC  !

DATE TIIE C0f0ENTS

'95 JUN -6 Pl2:25 ~

02/24/90 1425 Started for 24 Hour Run 02/25/90 2206 Secured from 24 Hour Run OFFICE OF SECRETARY 2336 Started for ESFAS Testing 00CXETlHG & SERVICE 2348 Secured for ESFAS BRANCH 02/27/90 0312 Started for ESFAS 4 l

0424 Secured for ESFAS l

0605 Started for ESFAS l 0642 Secured for ESFAS  ;

03/13/90 1518 Start for fiaint. Test .,

03/14/90 0146 Stopped 03/21/90 2149 Failed to start due to insufficient fuel in fuel ,

lines after maintenance. j 2156 Failed to Start Again 2202 Started and Governor Vented ,

2217 Stopped j 2259 Started for Overspeed Trip Test l 2301 Stopped Manually due to Low Lube Oil Pressure j and High 011 Filter DP ,

2314 Started 2318 Stopped 03/22/90 0017 Started 0023 Stopped for Maintenance 0428 Started for Testing 0429 Stopped 0714 Locally Started for Maintenance and Engineering Testing 03/22/90 1030 Locally Shutdown 03/22/90 1106 Started from CR l 1243 Tripped on D/G High Lube 011 Temp.  ;

e

<NE 03/23/90 0509 Started for Maintenance Run 1202 p is{

bif)

SteppMR REGULATORY COMMISSION so 4ttoLA 3 M DocketNo. oo 4ts'M 3 Ctf.cialExh.No. CrPC. 23 b tM mabr cf Mc, eh,A D Mo7Ec~I-

[

fppier,t C -

05S909 4 Intcarnor HEJEcTED

$$ Cc::rg Offr Ceratx . DATE 5 l& 45 01Tr __ _ Witss CAA

%0 tit .. Git C{ _

CC3

. UNIT 1 DIESEL GENER M 18 (CONT'D)

DATE TIE CO M NTS 03/23/90 1730 Started for 4 Hour Run 1731 Tripped on Low Jacket Water Pressure / Turbo Lube Oil Pressure Low 1744 5 tarted for 4 Hour Run 2222 Stopped 03/24/90 0048 Started for Maintenance 0049 "Hi Jacket Water Temp" Alarm In. Temp Verified to be Normal.

0121 Nomal Stop 03/27/90 if,49 Emergency Start Test

1
42 2 Normal Shutdown 1909 Normal Start 1948 Stopped. Simulated Hi Temp Lube Oil Trip 1951 Started. Simulated LOSP at Engine Panel 1954 Stopped. Simulated Hi Vibration Trip 1957 Normal Start 1959 Stopped. Simulated Hi Crankcase Pressure Trip 2004 Started. Simulated SI at Engine Panel 2010 Stopped. Simulated Lo Lube Oil Pressure Trip 2220 Started. Simulated Bus UV Signal 2317 Nomal Shutdown 03/28/90 0403 Started. Surveillance 14980-1 0537 Nomal Shutdown 1350 Start to Perfom Functional Test for ElO 1-89-03281 (Lo Lube Oil Pressure Trip Flow Orifices) 1355 Nomal Shutdown 1356 Started. Simulated UV for Functional on MWO 1-89-03281 1400 Normal Shutdown 04/01/90 1623 Nomal Start 1744 Normal Shutdown 04/04/90 1632 Started for Maintenance 1744 Stopped N E M CT 053910

CL5 Ull!T 1 j DIESEL GENEN1B (CollT'D)

DATE TIIE COMENTS 04/05/90 0030 Started. T-ENG-90-17 0035 Stopped 0307 Started. 14980 0509 Stopped '

i 9.1 PRb;TECT O5!.is11

1 b

. i UNIT 1 I DIESEL M TOR 1A DATE TIE CONGTS 02/26/90 1509 Started. 24 Hour Run for ESFAS 02/28/90 0226 Secured from 24 Hour Run 02/28/90 0945 Started for ESFAS Testing 1210 Secured for ESFAS Testing  ;

02/28/90 1700 Started 3 Times in Series During ESFAS Testing 02/29/90 0218 Secured for ESFAS Testing j

- 03/01/90 0128 Started for ESFAS l l

03/02/90 0215 Secured for ESFAS l

0912 Started for Maintenance l 1944 Secured for Maintenance j 03/12/90 1306 Started 2137 Stopped 03/13/90 0009 Started l 0506 Stopped j LOSP Occurred - Lost "A" RAT - DG1A Tied and l 03/20/90 0820 Tripped (Several Alarms came in - not noted in thelog.) l 0841 Auto Started after Sequencer Reset and Tripped on Low Jacket Water Pressure  ;

0856 Emergency Break Glass Start Locally to Recover from Station Blackout.

1029 RAT "B" Energized 18A03 Energized from "B" RAT  !

1040 1326 Shutdown 2119 Started for Troubleshooting 2206 Shutdown  :

2223 Started for Troubleshooting 2228 Secured 2233 Started for Troubleshooting )

2254 Secured '

03/23/90 0254 Started for Maintenance Troubleshooting 0450 Secured 92 PfoTEcT

05U912 i

t

  • . . - . . . . . - . - , , ...r,- - < . + ..-w.. - ,,. , , < - --.-4-e,r...,.- w ,.-

., ,m. .e , e ere-"-+-ww<=ier---

OCk UNIT 1 DIESEL M TOR 1A DATE TIE C0f0 G TS 03/23/90 1724 Started and Manually Stopped from CR 03/29/90 1109 Started. UV Test, Tied to 1AA02 1158 Normal Shutdown 03/30/90 1920 Emergency Start 2115 Stopped 2235 Local Start 2241 Trip Hi Temp Lube Oil 2254 Local 2300 Trip High Vibration 2313 Normal Start 2316 Stopped. H1 Crank Case Pressure 2328 SI 2334 Low Lube Oil Pressure 2343 Normal Start 2347 Nonnal Stop 2348 Nonnal Start 2358 Stop 03/31/90 0012 Normal Start 0014 Normal Stop 0016 SI 0019 CR l 1827 Start Local Local Stop 1837 j -

1846 Local Start j 1847 Stop

! 1856 Local Start 1857 Local Stop

. 1904 Local Start

1906 Local Stop 1921 Local Start 1922 Local Stop i 4A brect i

0 53913 i

i t

DDb f

(- -

UNIT 1 DIESEL'R NER TOR 1A

]

DATE TIE CopeENTS l

03/31/90 1955 Local Start 2012 Local Stop 3

2254 Started. UV Test. Tied to 1AA02 4 2320 Normal Shutdown 04/01/90 0423 Started. Surveillance 14980-1 0556 Normal Shutdown 04/06/90 1345 Start. T-ENG-90-16 1346 Stop 1404 Start. T-ENG-90-16 1405 Stop 1419 Start. T-ENG-90-16 1430 Stop 2347 Start. T-ENG-90-11 04/07/90 0213 Stop 02 fROTECT O SiiSL4