Location: Engineering Conference Room 0FFICE OF SECRETARY 5

Service Building - 3rd Floo00CKETlH', & SERVICE 6

BRANCH 7

8 They are preparing the diesel 1A for the bubble 9

VOICE:

10 test (Inaudible).

Il VOICE:

They took all the temp switches out last night, 12 cal'd them, and they found one switch, high tube oil temperature, had a little leak around the cover and 0-ring and they also 13 14 menticned that the switch was appearing to stick.

15 VC~CE:

I couldn't find out (Inaudible).

Is this in 16 cur faver cr (Inaudible).

17 HORTC:::

You can't say for a fact that it is.

You've ge a number of pneumatic lides with.006 inch orifices that are 18 And its, its passing 60 pound pressure through that orifice.

19 20 anybcdy's guess as to whether or not this leak is sufficient to have drug dcwn the pressure low enough to have caused the P3 21 22 trip.

I think it is, based on the faith I have in the I&C tech 23 this mcrning, his description of the leak being significant 24 enough to where " snoop" would not even bubble.

It was just 25 blewing back in his face.

26 WILLIAMS:

Blowing all -- That's a hell of a --

27 HORTON:

That's enough to allow a.006 orifice to not provide enough pressure to keep a minimum of 45 pounds in the 28 29 line.

But yeah, I think we lucked out on the UV test yesterday 30.

mcrning.

A number of things, see they tightened up some lines j

We did not between your UV yesterday and the original condition.