MONTHYEARNPL-99-0569, Monthly Operating Repts for Sept 1999 for Pbnp,Units 1 & 2. with1999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Pbnp,Units 1 & 2. with NPL-99-0051, Monthly Operating Repts for Aug 1999 for Pbnp,Units 1 & 2. with1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Pbnp,Units 1 & 2. with NPL-99-0449, Monthly Operating Repts for July 1999 for Pbnp,Units 1 & 2. with1999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Pbnp,Units 1 & 2. with ML20209D2691999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Pbnps,Units 1 & 2 NPL-99-0328, Monthly Operating Repts for May 1999 for Pbnp,Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Pbnp,Units 1 & 2. with ML20209D2751999-05-31031 May 1999 Revised MORs for May 1999 for Pbnps,Units 1 & 2 NPL-99-0273, Monthly Operating Repts for Apr 1999 for Point Beach Nuclear Plant,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Point Beach Nuclear Plant,Units 1 & 2.With NPL-99-0193, Monthly Operating Repts for Mar 1999 for Pbnp,Units 1 & 2. with1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Pbnp,Units 1 & 2. with NPL-99-0134, Monthly Operating Repts for Feb 1999 for Pbnp,Units 1 & 2. with1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Pbnp,Units 1 & 2. with NPL-99-0008, Monthly Operating Repts for Dec 1998 for Pbnp,Units 1 & 2. with1998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Pbnp,Units 1 & 2. with NPL-98-1006, Monthly Operating Repts for Nov 1998 for Point Beach Nuclear Plant,Units 1 & 2.With1998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Point Beach Nuclear Plant,Units 1 & 2.With NPL-98-0948, Monthly Operating Repts for Oct 1998 for Point Beach Nuclear Plant,Units 1 & 2.With1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Point Beach Nuclear Plant,Units 1 & 2.With NPL-98-0826, Monthly Operating Repts for Sept 1998 for Point Beach Nuclear Plant,Units 1 & 2.With1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Point Beach Nuclear Plant,Units 1 & 2.With ML20151W3851998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Pbnp Units 1 & 2 ML20151W4541998-07-31031 July 1998 Corrected Page to MOR for July 1998 for Pbnp Unit 1 ML20151W4471998-07-31031 July 1998 Corrected Page to MOR for July 1998 for Pbnp Unit 2 NPL-98-0653, Monthly Operating Repts for July 1998 for Point Beach Nuclear Plant,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Point Beach Nuclear Plant,Units 1 & 2 NPL-98-0558, Monthly Operating Repts for June 1998 for Pbnp,Units 1 & 21998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Pbnp,Units 1 & 2 ML20151W4261998-06-30030 June 1998 Corrected Page to MOR for June 1998 for Pbnp Unit 2 ML20151W4221998-05-31031 May 1998 Corrected Page to MOR for May 1998 for Pbnp Unit 2 NPL-98-0481, Monthly Operating Repts for May 1998 for Point Beach Nuclear Plant,Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W4011998-04-30030 April 1998 Corrected Page to MOR for April 1998 for Pbnp Unit 2 NPL-98-0356, Monthly Operating Repts for April 1998 for Point Beach Nuclear Plant,Units 1 & 21998-04-30030 April 1998 Monthly Operating Repts for April 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20216D7071998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W3981998-03-31031 March 1998 Corrected Page to MOR for March for Pbnp Unit 2 NPL-98-0159, Monthly Operating Repts for Feb 1998 for Point Beach Nuclear Plant,Units 1 & 21998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W3891998-02-28028 February 1998 Corrected Page to MOR for Feb 1998 for Pbnp Unit 2 ML20216D7121998-02-28028 February 1998 Revised Corrected MOR for Feb 1998 for Point Beach Nuclear Plant,Unit 2 NPL-98-0084, Monthly Operating Repts for Jan 1998 for Point Beach Nuclear Plant,Units 1 & 21998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20198M2251997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20198M2331997-11-30030 November 1997 Corrected Monthly Operating Repts for Nov 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20203F9171997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Point Beach Nuclear Plant,Units 1 & 2 NPL-97-0715, Monthly Operating Repts for Oct 1997 for Point Beach Nuclear Plant,Units 1 & 21997-10-31031 October 1997 Monthly Operating Repts for Oct 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20203F9361997-10-31031 October 1997 Revised Monthly Operating Rept for Oct 1997 for Point Beach Nuclear Plant,Unit 2 NPL-97-0621, Monthly Operating Repts for Sept 1997 for Point Beach Nuclear Plant,Units 1 & 21997-09-30030 September 1997 Monthly Operating Repts for Sept 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20203F9311997-09-30030 September 1997 Revised Monthly Operating Rept for Sept 1997 for Point Beach Nuclear Plant,Unit 2 NPL-97-0553, Monthly Operating Repts for Aug 1997 for Point Beach Nuclear Plant,Units 1 & 21997-08-31031 August 1997 Monthly Operating Repts for Aug 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20203F9261997-08-31031 August 1997 Revised Monthly Operating Rept for Aug 1997 for Point Beach Nuclear Plant,Unit 2 ML20210H9531997-07-31031 July 1997 Monthly Operating Repts for Jul 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20210H9601997-06-30030 June 1997 Revised Monthly Operating Rept for June 1997 for Point Beach Nuclear Plant,Units 1 & 2,which Provides Corrected Forced Outage Rates NPL-97-0318, Monthly Operating Repts for May 1997 for Point Beach Nuclear Plant,Unit 1 & 21997-05-31031 May 1997 Monthly Operating Repts for May 1997 for Point Beach Nuclear Plant,Unit 1 & 2 ML20141C2381997-04-30030 April 1997 Monthly Operating Repts for Apr 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20141C2461997-03-31031 March 1997 Corrected Operating Data Rept for Mar 1997 for Point Beach Nuclear Plant,Unit 1 ML20137P5781997-03-31031 March 1997 Monthly Operating Repts for March 1997 for Point Beach Nuclear Plant Units 1 & 2 ML20137P5711997-02-28028 February 1997 Corrected MOR for Feb 1997 for Point Beach Nuclear Plant Unit 1 ML20135F2721997-02-28028 February 1997 Monthly Operating Repts for Feb 1997 for Point Beach Nuclear Plant,Units 1 & 2 ML20134J8711997-01-31031 January 1997 Monthly Operating Repts for Jan 1996 for Point Beach Nuclear Plant,Units 1 & 2 ML20135F2771997-01-31031 January 1997 Revised Monthly Operating Rept for Jan 1997 for Point Beach Nuclear Plant,Unit 2 ML20133N0601996-12-31031 December 1996 Revised MOR Rept for Dec 1996 for Point Beach Nuclear Plant, Units 1 & 2 ML20133F6471996-12-31031 December 1996 Monthly Operating Repts for Dec 1996 for Point Beach Nuclear Plant,Unit 1 & 2 1999-09-30
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARNPL-99-0569, Monthly Operating Repts for Sept 1999 for Pbnp,Units 1 & 2. with1999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Pbnp,Units 1 & 2. with ML20212D5961999-09-15015 September 1999 Safety Evaluation Supporting Licensee IPEEE Process.Plant Has Met Intent of Suppl 4 to GL 88-20 NPL-99-0051, Monthly Operating Repts for Aug 1999 for Pbnp,Units 1 & 2. with1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Pbnp,Units 1 & 2. with NPL-99-0449, Monthly Operating Repts for July 1999 for Pbnp,Units 1 & 2. with1999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Pbnp,Units 1 & 2. with ML20196J4251999-06-30030 June 1999 Safety Evaluation Authorizing Proposed Alternatives Described in Relief Requests VRR-01,ROJ-16,PRR-01 & VRR-02 ML20209D2691999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Pbnps,Units 1 & 2 ML20196F3341999-06-22022 June 1999 Safety Evaluation for Implementation of 422V+ Fuel Assemblies at Pbnp Units 1 & 2 ML20195F9781999-06-10010 June 1999 Unit 2 Refueling 23 Inservice Insp Summary Rept for Form NIS-1 ML20209D2751999-05-31031 May 1999 Revised MORs for May 1999 for Pbnps,Units 1 & 2 NPL-99-0328, Monthly Operating Repts for May 1999 for Pbnp,Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Pbnp,Units 1 & 2. with NPL-99-0273, Monthly Operating Repts for Apr 1999 for Point Beach Nuclear Plant,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Point Beach Nuclear Plant,Units 1 & 2.With ML20196F3521999-04-30030 April 1999 Non-proprietary WCAP-14788, W Revised Thermal Design Procedure Instrument Uncertainty Methodology for Wepc Point Beach Units 1 & 2 (Fuel Upgrade & Uprate to 1656 Mwt - NSSS Power) NPL-99-0193, Monthly Operating Repts for Mar 1999 for Pbnp,Units 1 & 2. with1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Pbnp,Units 1 & 2. with NPL-99-0134, Monthly Operating Repts for Feb 1999 for Pbnp,Units 1 & 2. with1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Pbnp,Units 1 & 2. with ML20207D6751999-02-22022 February 1999 Assessment of Design Info on Piping Restraints for Point Beach Nuclear Plant,Units 1 & 2.Staff Concludes That Licensee Unable to Retrieve Original Analyses That May Have Been Performed to Justify Removal of Shim Collars ML20206R9001999-01-13013 January 1999 SER Accepting Nuclear Quality Assurance Program Changes for Point Beach Nuclear Plant,Units 1 & 2 NPL-99-0008, Monthly Operating Repts for Dec 1998 for Pbnp,Units 1 & 2. with1998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Pbnp,Units 1 & 2. with NPL-99-0091, 1998 Annual Results & Data Rept for Pbnps,Units 1 & 2. with1998-12-31031 December 1998 1998 Annual Results & Data Rept for Pbnps,Units 1 & 2. with ML20198C7671998-12-10010 December 1998 Safety Evaluation Accepting Licensee Proposed Alternative to ASME BPV Code,1986 Edition,Section XI Requirement IWA-2232, to Use Performance Demonstration Initiative Program During RPV Third 10-yr ISI for Plant,Unit 2 NPL-98-1006, Monthly Operating Repts for Nov 1998 for Point Beach Nuclear Plant,Units 1 & 2.With1998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Point Beach Nuclear Plant,Units 1 & 2.With ML20195J5101998-11-16016 November 1998 Proposed Revs to Section 1.3 of FSAR for Pbnp QA Program ML20198J5941998-11-0303 November 1998 1998 Graded Exercise,Conducted on 981103 NPL-98-0948, Monthly Operating Repts for Oct 1998 for Point Beach Nuclear Plant,Units 1 & 2.With1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Point Beach Nuclear Plant,Units 1 & 2.With NPL-98-0880, Special Rept:On 980913,fire Alarm Control Panels Inoperable for More That Fourteen Days.Troubleshooting of D-401 Panel Following Installation of Replacement Batteries Revealed No Apparent Cause for Spurious Alarms.Panel D-401 Restored1998-10-21021 October 1998 Special Rept:On 980913,fire Alarm Control Panels Inoperable for More That Fourteen Days.Troubleshooting of D-401 Panel Following Installation of Replacement Batteries Revealed No Apparent Cause for Spurious Alarms.Panel D-401 Restored ML20154M9121998-10-14014 October 1998 Unit 1 Refueling 24 Repair/Replacement Summary Rept for Form NIS-2 ML20154L6751998-10-14014 October 1998 Unit 1 Refueling 24 ISI Summary Rept for Form NIS-1 NPL-98-0826, Monthly Operating Repts for Sept 1998 for Point Beach Nuclear Plant,Units 1 & 2.With1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Point Beach Nuclear Plant,Units 1 & 2.With ML20151W3851998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Pbnp Units 1 & 2 NPL-98-0653, Monthly Operating Repts for July 1998 for Point Beach Nuclear Plant,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W4471998-07-31031 July 1998 Corrected Page to MOR for July 1998 for Pbnp Unit 2 ML20151W4541998-07-31031 July 1998 Corrected Page to MOR for July 1998 for Pbnp Unit 1 ML20236Q3161998-07-10010 July 1998 Safety Evaluation Accepting Licensee Proposed Alternative to ASME Code Requirements PTP-3-01 & PTP-3-02 ML20236L6771998-07-0707 July 1998 Safety Evaluation Approving Wepco Implementation Program to Resolve USI A-46 at Point Beach NPP Units 1 & 2 NPL-98-0558, Monthly Operating Repts for June 1998 for Pbnp,Units 1 & 21998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Pbnp,Units 1 & 2 ML20151W4261998-06-30030 June 1998 Corrected Page to MOR for June 1998 for Pbnp Unit 2 ML20151W4221998-05-31031 May 1998 Corrected Page to MOR for May 1998 for Pbnp Unit 2 NPL-98-0481, Monthly Operating Repts for May 1998 for Point Beach Nuclear Plant,Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W4011998-04-30030 April 1998 Corrected Page to MOR for April 1998 for Pbnp Unit 2 NPL-98-0356, Monthly Operating Repts for April 1998 for Point Beach Nuclear Plant,Units 1 & 21998-04-30030 April 1998 Monthly Operating Repts for April 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20217F3131998-04-17017 April 1998 Safety Evaluation Accepting Proposed Alternative to ASME Code for Surface Exam of Nonstructural Seal Welds,For Plant, Unit 1 ML20216D7071998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W3981998-03-31031 March 1998 Corrected Page to MOR for March for Pbnp Unit 2 NPL-98-0209, Special Rept Re Fire Barrier Inoperable for Greater than Seven Days.Compensatory Measures Implemented in Accordance W/Fire Protection Program Requirements During Time That Barriers Were Inoperable1998-03-30030 March 1998 Special Rept Re Fire Barrier Inoperable for Greater than Seven Days.Compensatory Measures Implemented in Accordance W/Fire Protection Program Requirements During Time That Barriers Were Inoperable ML20217A8501998-03-19019 March 1998 SER Accepting Proposed Changes Submitted on 980226 by Wiep to Pbnp Final SAR Section 1.8 Which Will Impact Commitments Made in Pbnp QA Program Description.Changes Concern Approval Authority for Procedures & Interviewing Authority ML20216J0101998-03-17017 March 1998 Safety Evaluation Accepting Third 10-yr Inservice Insp Interval Relief Request RR-1-18 for Plant NPL-98-0159, Monthly Operating Repts for Feb 1998 for Point Beach Nuclear Plant,Units 1 & 21998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20151W3891998-02-28028 February 1998 Corrected Page to MOR for Feb 1998 for Pbnp Unit 2 ML20216D7121998-02-28028 February 1998 Revised Corrected MOR for Feb 1998 for Point Beach Nuclear Plant,Unit 2 NPL-98-0084, Monthly Operating Repts for Jan 1998 for Point Beach Nuclear Plant,Units 1 & 21998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Point Beach Nuclear Plant,Units 1 & 2 ML20198L1151998-01-0808 January 1998 SER Accepting Licensee Response to GL 95-07, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves, for Point Beach Nuclear Plant,Units 1 & 2 1999-09-30
[Table view] |
Text
. _ _ _ _ - _ -
\
[ ,
f f g '. .
e q J Wisconsin
'Electnc i POWER COMPANY l - Point Beach Nuclear Plant
! 6610 Nuclear Rd., Two Riwrs.VA 54241 (414) 755-2321 l PBL 95-0147 L
l i June 7, 1995 Document Control Desk l U. S. NUCLEAR REGULATORY COMMISSION I Mail. Station P1-137 Washington, DC 20555 l
Gentlemen:
( DOCKETS 50-266 AND 50-301 MONTHLY OPERATING REPORTS EQT,NT BEACH NUCLEAR PLANT, UNITS 1 AND 2 Attached are monthly operating reports for Units 1 and 2 of the Point Beach
- -Nuclear Plant for the calendar month of May 1995.
Sincerely,
( )
S G.t I fie l PBNE l 1
l cah j Attachments
.. \
cc: L. L. Smith, PSCW .
NRC Regional Administrator, . Region III ,
NRC Resident Inspector 9506200012 950531 PDR ADOCK 05000266 R PDR
\
{
, - _ . _. ~
OPERATING DATA REPORT DOCKET NO. 50-266 ,
~
DATE: 06/07/95 COMPLETED BY: M. B. Koudelka TELEPHONE: 414 755-6480
?
OPERATING STATUS
- 1. UNIT NAME: POINT BEACH NUCLEAR PLANT - UNIT 1 . NOTES '
- 2. REPORTING PERIOD: May - 1995 . .
- 3. LICENC"O THERMAL POWER (MWT): 1518.5
- 4. NAMEPLATE RATING (GROSS - MWE) : 523.8 . . -
- 5. DESIGN ELECTRICAL RATING (NET MWE) : 497.0 . .
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE) : 509.0 . .
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE) : 485.0 . . . . . . . . . . . . . . . .
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:
~
NA
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NA
- 10. REASONS FOR RESTRICTIONS, (IF ANY) :
NA THIS MONTH YEAR TO DATE CUMULATIVE
- 11. HOURS IN REPORTING DERIOD 744.0 3,623.0 215,351.0
- 12. NUMBER OF HOURS REACTO.' WAS CRITICAL 744.0 2,745.0 179,584.6
- 13. REACTOR RESERVE SHUTDOWN OURS 0.0 0.0 667.3
- 14. HOURS GENERATOR ON LINE 744.0 2,731.3 176,444.3
- 15. UNIT RESERVE SHUTDOWN HCURS. 0.0 0.0 846.9
- 16. GROSS THERMAL ENERGY GENERATED (MWI!) 1 129,725 4,059,305 249,604,302 17 GROSS ELECTRICAL ENERGY GENERATED 563 HO '
1,385,020 84,323,670 '
- 18. NET ELECTRICAL ENERGY GENERATED _(MWE) 371,247 1,322,637 80,383,288
- 19. UNIT SERVICE FACTOR 100.0% '75.4% 81.9%
- 20. UNIT AVAILABILITY FACTOR 100.0% 75.4% 82.3%
- 21. UNIT CAPACITY FACTOR (USING MDC NE'.?). 102.9% 75.3% 76.6%
- 22. UNIT CAPACITY FACTOR (USING DER NET; 100.4% 73.5% 75.1%
- 23. UNIT FORCED OUTAGE RATE . _
0.0% 0.0% 1.5%
- 24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH) :
NONE.
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP; NA DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER DATED SEPTEMBER 22, 1977
,m*. - _ _. _ . _ _ _ _ - _ _ . _ __-- - - 6 _a___ _
POINT BEACH NUCLEAR PLANT Docket No. 50-266 .
Unit Name Point Beach. Unit 1 UNIT SilUTDOWNS AND POWER REDUCTIONS Date June 7.1995 -
Completed By M. B. Koudelka ..
REPORT MONTil MAY - 1995 Telephone No. 414n55-6480 Method of Shutting No, Date Type' Duration Reason' Down, Licensee Event System Component Cause and Corrective Action NA NA NA NA NA NA NA NA NA NA s
7
'F: Forced Reason: 3 Method: ' Exhibit G - Instructions S: Scheduled A - Equipment Failure (explain) 1 - Manual for preparation of B - Maintenance or Testing 2 - Manual Scram data entry sheets C - Refueling 3 - Automatic Scram LER file (NUREG4161)
D - Regulatory Restriction 4 - Continuation of E - Operator Training & Previous Shutdown Licensing Exam 5 - Reduced lead F - Administrative 6 - Other (explain) 5 Exhibit 1 - Same Source G - Operational Error (explain)
II - Other (explain) 4 PB N 8b (o3-90)
i POINT BEACH NUCLEAR PLANT DOCKET NO. 50-266 ",
AVERAGE DAILY UNIT POWER LEVEL UNIT NAME Point Beach, Unit l'
^
MONTH M AY' . 1995 DATE 6/7/95 COMPLETED BY M. B. Koudelka s.
l TELEPHONE . (414)755-6480 AVERAGE AVERAGE AVERAGE DAILY DAILY ! DAILY POWER LEVEL POWER LEVEL .l POWER LEVEL DAY MWe NET - DAY MWe NET $ DAY MWe NET i
1 500 11 -505 L 21 499
~
2 498 . 12 494 22 498 3 500 13 499 23 498 i
4 499 14- 503 A 24 497 5 502 15 497 25 499 ,
~
6 -497 .16 - 499 26 499 7 500 17 499 27 498 8 500 18 499 28 ~498 9 500 -19 499 -
29 -499 10 500 20- 499 30 497
.I 31. 498
~
I.
i
-i g
-[
.)
-t.
i .l
s.
DOCKET NO. ~50-266 UNIT NAME Point Beach Unit 1
- DATE June;7, 1995
- COMPLETED BY M. B. Koudelka TELEPHONE 414/755-6480 Unit 1 operated at an average of 499 MWe net for.the report. period.
Licensee Event Report 50/266/95-005-00,- Manual Reactor Trlip During Startup Physics Testing, was submitted.
Safety-related maintenance included:
~ ~
- 1. 1FT-477 HX-1B steam generator feedwater flow transmitter calibrated.
- 2. 1HX-1A&B steam generator J-tubes,vi.sual inspection. ---- . - -- -- -
- 3. HX-105A&B primary auxiliary building battery room vent coolers-flushed.
- 4. HX-266A&B G03/G04 emergency diesel generators. lube oil coolers repaired.
- 5. 1SC-966B pressurizer liquid sample containment isolation: valve stroked and packing adjusted.
- 6. SW-2911-BS north service water header Zurn strainer speed reducer bearings greased.
sa_ m. , ,, m.s-N
i OPERATING DATA RE ORT h DOCKET NO. 50-301 ,
DATE: 06/07/95 l COMPLETED BY: M'. B. Koudelka 3
TELEPHONE: 414 755-6480 OPERATING STATUS
- 1. . UNIT NAME: POINT BEACH NUC'M PLANT !- UNIT 2 . NOTES .
- 2. REPORTING PERIOD: May - 1995 ! . .
- 3. LICENSED THERMAL POWER (MWT) : '1518.5, . .
- 4. NAMEPLATE RATING (GROSS MWE) : 523.8 . .
- 5. DESIGN ELECTRICAL RATING (NET 'MWE) : 497.0 . .
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE) : 509.0 . .
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE) : 485.0 . . . . . . . . . . . . . . . . . .
8.'IF CHANGES OCCUR IN CAPACITY EATINGS (ITEMS 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS: ;
'NA 1
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY - (NET MWE) : NA
- 10. REASONS FOR RESTRICTIONS, (IF ANY) : i-NA 7 )
THIS MONTH YEAR TO DATE CUMULATIVE i
- 11. HOURS IN REPORTING PERIOD 744.0 3,623.0 ~ 200,136.0
- 12. NUMBER OF POURS REACTOR WAS CRITICAL ! 744.0 3,477.4
~
l175,529.0 13 :. REACTOR RESERVE SHUTDOWN HOURS + !, 0.0 0.0 .233.9
{
' 14 . HOURS GENERATOR ON LINE 744.0 3,396.3 l173,091.0
- 15. UNIT RESERVE SHUTDOWN HOURS l 0.0- 0.0 ; 302.2
- 16. GROSS THERMAL ENERGY GENERATED '(MWH) l_ 1,070,303 5,046,513 249,028,438
- 17. GROSS ELECTRICAL ENERGY GENERATED 'i -363,200 1,705.520 84,656,630
- 18. NET ELECTRICAL ENe2.GY GENERATED (MWH)l 346,506 1,627,079 . 80,707,594
- 19. UNIT SERVICE FACTOR t 100.0% 93.7% '.; 86.5%
- 20. UNIT AVAILABILITY FACTOR . [ 100.0% 93.7% ~
} 86.6%
- 21. UNIT CAPACITY FACTOR (USING MDC NET) [ 96.0% 92.6% l 82.6%
- 22. UNIT CAPACITY-FACTOR (USING DER NET) 93.7%- 90.4% 81.1%
- 23. UNIT. FORCED OUTAGE RATE , ,
- 0. 0 % . 0.0% j O.9%
, 24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH): l Refueling,. 09/30/95,.38 days j
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
NA. .
DATA REPORTED AND FACTORS CALCULATED A'3 REQUESTED IN NRC LETTFR DATED SEPTEMBER 22, 1977 j .
c i
i
_ _ _ _ . . . _ _ _ _ _ _ _ _ . _ _ _ _ . _ _ _ . _ _ _ _ _ _ . _ _ _ s .
POINT BEACH NUCLEAR PLANT Docket No. 50-301 ~ -
Unit Name Point Beach. Unit 2 .
UNIT SIIUrDOWNS AND POWER REDUCTIONS Date June 7.1995 Completed By M. B. Koudelka -
REPORT MONTH M AY - 1995 Telephone No. 414n55-6480 Method of Shutting Durau.on po,o Licensee Event System Component Cause and Corrective Action No. Date Type' (Hours) Reason 2 Reactop Report No. Code' Code' To Prevent Recurrence -
3 05/05 NA o 11 6 NA. IIB PUMPXX "the unit was reduced to $5 % power in support of repairs to 2P28B, the main feedwater pump.
During pump disassembly, the throttle relief valves were reposi:ioned and die rotating assembly, including seals, were replaced.
4 F
'F: Forced 2 Reason: 2 Method: ' Exhibit G - Instra.ctions S: Scheduled A - Equipment Failure (explain) 1 - Manual for preparation of B - Maintenance or Testing 2 - Manual Scram data entry sheets C - Refueling 3 - Automatic Scram LER file (NUREG-0161)
D - Regulatory Restriction 4 - Continuation of E - Operator Training & Previous Shutdown Licensing Exam 5 - Reduced Load F - Administrative 6 - Other (explain) 5 Exhibit I - Same Source G - Operational Error (explain)
H - Other (explain)
PBF4028b
' (03-90)
i
'e - ,
~
POINT BEACH NUCLEAR PLANT DOCKET NO. 50-301 ..
AVERAGE DAILY UNIT POWER LEVEL UNIT NAME Point Beach, Unit 2 i
MONTH MAY- 1995 DATE 6/7/95 COMPLETED BY - M. B. Koudelka TELEPHONE (414)755-6480 t
1 AVERAGE AVERAGE AVERAGE ,
. DAILY DAILY DAILY 1
POWER LEVEL POWER LEVEL POWER LEVEL DAY MWe NET DAY MWe NET DAY MWe NET j 1 487 11 483 21 485 2 485 12 484 22 485 3 488 13 486 23 486 4 486 14 489 24 485 i,
5 394 15 485 25 486 i 6 263 16 48S 26 485 7 266 17 485 27 485 l
! 8 403 18 486 28 484 i
i 9 486 19 486 29 486 10 490 20 485 30 484
, 31 485 9
i ' '
. a r:: a[* ,
. . ~ .
J. '
. DOCKET NO. 50-301 UNIT'NAME -
Point. Beach Unit 2 '
-:DATE .
May'8,..'1995. .
' COMPLETED BYc M. B..Koudelka. '
_ TELEPHONE- J414/755-6480i ..,.
i Unit 21 operated'.at an~averagefof 466L.MWe-net for;theTreport period.
. Safety-relatedfmaintenance4 included: -
- t
- 1. 2P2C charging pump infrared:in'spection performed.-
2.- 2SI-854A&B'T13_ refueling water. storage tank:outletito P10A&B-residual"heati removal pump suction header check valve Ldiscs .
~
replaced, a-
)
l l- ;
o L
t l
l l
F-
[
L ,
L l'
l i.
'i .
i . . . . . - _ -. - _. . . _ _ .. _ _ . . . _ . . _ ._.a = . _ .