Text

{{#Wiki_filter:, hAwgAapproveepgpW3Wza0090.100 s Effective Date: IW17/94 Print Date: 10/13/94 HOUSTON LIGHUNG AND POWER COMPANY SOtJTH TEXAS PROJECT EUECTRIC GENERATmG STATION PLANT PROCEDURES MANUAL STATION PROCEDURE e0PGP03-ZK.D090' NON SAFETY-RELATED (O) Rev.10 (General) Page 1 of 38 Wed Pmeess Parana' Effective Date: 10/17/94 PROCEDURE USE CONTROL: AVAILABLE Imy Reynolds Robert Hehon Work Control PREPARER "ECHNICAL COGNIZANT DEPT Table of Contents Page 1.0 Purpose, Scope and Objectives..................................... 2 1.1 Pu rpo se................................................ 2 1.2 Scope................................................. 2 1.3 Obj ecti ves.............................................. 4 2.0 De finiti ons................................................... 4 3.0 Responsibilities................................................ 8 3.1 Engi neeri ng............................................. 8 3.2 The Initiator of a Condition Report............................. 9 3.3 M ainten ance............................................. 9 3.4 Nuclear Purchasing and Materials Management.................... 9 3.5 Nuclear Quality Control.................................... 9 3.6 Operations Work Control Group............................... 9 3.7 Work Control - Planning 9 3.8 Work Control - Scheduling.................................. 10 3.9 Work Package Control Center................................ 10 3.10 Work Start Authority...................................... 10 4.0 Pme ed u re.................................................... 10 4.1 Condition Identification..................................... 10 4.2 Work Order Evaluation..................................... 12 4.3 Work Activity Scheduling................................... 14 4.4 Work Activity Planning..................................... 16 i 4.5 Work Release and Implementation............................. 18 1 4.6 Work Package Closure..................................... 23 5.0 References................................................... 23 6.0 S upport Documents............................................. 23 Addendum 1 Condition Report Completion.......................... 24 Addendum 2 Work Process Priorities.............................. 26 Addendum 3 Rover / Minor Maintenance Guidelines.................... 27 Addendum 4 Priority 1 and 2 Work Activity Action Plans............... 29 Addendum 5 Work Risk Assessment 32 Addendum 6 Work Process Flowchart 38 9502220044 950216 'h 9 5 PDR ADOCK 05000498 9 I P PDR

e Work Process Pmeram OPGP03-ZA-0090 Rev.10 Page 2 of 38 1.0 Puroone. Scone and Objectives i 1.1 Purpose His procedure describes the process for evaluating, planning, scheduling and implementing work activities to support the safe and reliable operation of the plant. It provides the whanism for plant material problems or deficiencies identified in accordance with OPGP03-ZX-0002, Condition Reporting Process, to be evaluated and dispositioned. 1.2 Scope 1.2.1 The Work Process Program encompasses the activities of all organizations related to performing work on plant systems, components and structures including corrective maintenance, preventive maintenance, surveillance inspections, special tests and modifications. The process extends from the identification of a work requirement or deficiency through planning, scheduling, and implementation, to final closure. The process elements are shown in Addendum 6. 1.2.2 This procedure applies to work activities (including modifications) performed on permanent plant components, systems and structures, including work in support areas or buildings that may impact plant j cperations. 1.2.3 The Work Process Program utilizes a two-tiered approach to correcting equipment deficiencies. The two methods are Work Orders and Rover / Minor maintenance. His tiered approach to maintenance applies the appropriate level of requirements and resources to perform work / resolve equipment deficiencies increasing the overall efficiency of the Work Process Program. All deficiencies identified on Condition Reports are evaluated to determine the most appropriate method to perform the work / resolve the deficiency. Deficiencies that do not require Work Orders are resolved using the Rover / Minor maintenance program (see Addendum

3) and are assigned directly to maintenance for implementation.

Deficiencies that require Work Orders, are planned, scheduled, and implemented using the Work Process Program. i

e Work Process Program OPGP03-ZA-0090 Rev.10 Page 3 of 38 s 1.2.4 The Condition Report (CR) is the document used to identify conditions which require maintenance work to correct, or to request the Maintenance Department or Certified Contractors to perform specific work. A Work Order (WO) is generated from the CR, and the work is performed using the WO as the work authorization document. Work authorizing documents include Work Orders, Preventive Maintenance Tasks and Surveillances. When no administrative controls are required, work MAY be performed without a work authorizing document. 1.2.5 Work Authorization documents are not required for: Work on non-plant systems or systems excluded from configuration management listed in reference 5.8. Inspection or non-destructive examination for information only where no Work Start notification or maintenance support is required. I Minor housekeeping, cleanliness, and adminstrative items where no degradation of plant components and structures is involved. Items in this category MAY be identified and tracked by a punchlist. Facilities Management activities. 1.2.6 When a component has been removed from service, it is not required that its configuration be kept consistent with the approved design i configuration. Intentional actions (ie., Work at Risk) are permitted which cause the actual configuratian of the out-of-service component to deviate from the approved design configuration by documenting in accordance with OPGP03-ZM-0021, provided that, prior to returning the component to service, or declaring the component OPERABLE, the inconsistency is resolved, by taking one of the following actions: 1.2.6.1 The configuration of the component is restored to be consistent with the approved design configuration. 1 1.2.6.2 An engineering evaluation is performed and documented providing the basis for allowing the component to be returned to service with the deviation still existing. 1.2.63 The approved design configuration is revised to be consistent with the actual configuration of the component.

] o Work Process Piegreiii OPGP03-ZA-0090 Rev.10 Page 4 of 38 1.2.7 When deviations have been intentionally made as described above with the expectation that the inconsistency will be resolved, such deviations are undertaken as " Work at Risk" (not approved by Engineering ). 1.2.8

  • the work process uses the Corrective Action Program (CAP) and Work Management System (WMS) computer databases to develop, process and track the formal records and information needed to support the planning and scheduling process. To facilitate the Work Fim CRs SHAIL be initiated for work activities except as noted in 1.2.5.

A single CR can cause the generation of one or more work orders. 1.2.9 Work Packages written prior to the effective date of this revision MAY be worked to completion without revision (Speakout 12266). 13 Objectives 13.1 To support safe and reliable plant operation. l 13.2 To maintain an integrated schedule of approved plant maintenance and modification work activities, including preventative maintenance and surveillance activities. 133 To manage support activities to meet the implementation schedule 13.4 To allow the activities in the Control Room to focus on plant 3 operations by requiring work management functions to be performed i by the Operations Work Control Group. 2.0 Definitions 4 2.1 BLANKET WORK PACKAGE: A Work Package which is maintained in a " ready to work" status and utilized upon demand. Specific work activities are documented by the use of individual " episode" sheets attached as past of the work package. 'Ibese work packages are closedhenewed periodically as determined by the work discipline. j i 2.2 CONDITION REPORT (CR): A Form used to identify Conditions (formerly a i Service Request). P ? L k V

~. Work Process Pmpram OPGP03-ZA-0090 Rev.10-Page 5 of 38 2.3 CORRECITVE MAIN 7ENANCE: De process by which the operating and p#onnance characteris0cs of a non. conforming plant component are restored to spw.fications by clanning, replacing parts, repacking, rewiring, calibrating, i realigning, machining, welding, grinding, plating or other corrective means (ie., return hardware to its original design intent with no update of design documentation required). Activities of this type are designated as work type "C" in WMS (NOV 92-35). 2A DEFICIENCY: A deficiency is any condition whese a component. aystem or i structure does not meet its design criteria or cannot perform its in'. ended function. Results of deficiency identification include: Rework, Replacement, Repair, Use-As-Is, or Modification. The determination of Reprir, Ure-As-Is, or Modification is made by Engineering. 2.5 DEFICIENCY TAG: A tag which provides a six digit identification number which will be entered as the (DEPT #) on the CR Form (formerly the SR tag). ] This number will also be used to track items in WMS. 'L6 MAINTENANCE VERIFICATION POINT (MVP): A work hold point which t requires the Craftsmen to stop work and notify the Work Supervisor to perform an inspection or to ensure another group performs an inspectica. Maintenance Verification Points SHOULD be signed by the Work Supervisor. (NOV 91-23) l 2.7 MINOR MAINTENANCE: Work activities that may be performed using a Condition Report. These activities are of such a simple nature that qualified individuals can perform the work without written instructions. Criteria is provided in Addendum 3.

2.8 MODIFICATION

nose activities performed to implement physical design changes to systems, structures and components. Design Change Packages (DCPs) are Documents used to specify Modifications. Activities of this type are designated as Work Type *M" in WMS. j i 2.9 NEED DATE: Ris is the date set by OWCG as the date the work is to be accomplished. This date is controlled by the OWCG. 1 2.10 NONCONPORMANCE: For purpose of the work process, a deficiency where i the component, system or structure cannot perform its intended function or does l not meet the original desgn. p i f i

7 l Work Process Program OPGP03-ZA-0090 -l Rev.10 l Page 6 of 38 l t i 2.11 OPERABIllTY 1ES13: A Technical Specifications required functional or similar test, which is performed to verify that the systems, structures and components affected by the corrective or preventive maintenance work activity, are OPERABLE and ready to be returned to service (ie., capable of performing l their intended and specified design function), in accordance with the Technical Specifications, Updated Pinal Safety Analysis Report, design requirements and applicable codes and industry standards. 2.12 OPERATIONS NOTIFICA110N POINT (ONP): A preselected step in any - work process that identifies when the craft Crew leader or supervisor is required to contact the Shift Supervisor. 2.13 PLANNER: Person assigned the responsibility for developing or revising maintenance Work Instructions. This includes Maintenance Craft and. Supervision. 2.14 POST-MAINTENANCE 7EST: A test, inspection or check which provides a verification that a corrective OR preventive maintenance activity corrected the original component deficiency, did not introduce a new deficiency, and provides l a high degree of confidence that a suh e=t return to service Operability Test, if required, can be perferrned satisfactorily. l 2.15 POST MODIFICA110N 1EST: Test performed subsequent to desigt. change implementation as specified by the Cognizan'. Engmeer. l 2.16 PREVEN 11VE MAINTENANCE: M ~r.nenance activitier, performed to maintain equipment within designed operation conditions and ex'end its life. Preventive Maintenance includes predictive, periodic and planned maintenance activities. j Activities of this type are designated as Work Type P" in WMS. 2.17 QUALITY INSPECTION POINT (QIP): A preselected step in any procedure or work process that identifies a portion of the work process which requires l Nuclear Quality Control inspection. *Ihe inspection MAY be performed after j the activity is complete if full verification is possible without disassembly of thr. ] component / item. 2.18 RADIOIDGICAL HOLD POINT (RHP): A preselected step in any work process that identifies when Health Physics coverage is required prior to pr== ting with the work. 2.19 REJECT: "Ihe nonacceptance of an item. The item MAY be scrapped, returned to its supplier or, if otherwise acceptable, used in applications outside the scope of the Quality Assurance Program. l 1 \\

i Work Pmeess Program OPGP03-ZA.0090 Rev.10 i Page 7 of 38 l 2.20 REPAIR: The process of restoring a nonconforming characteristic to a condition such that the capability of an item to function reliably and safely is l unimpaired, even though that item still may not conform to the original design requirement. l l 2.21 REPLACEMENT: The installation of spare or renewal parts, components, l =<venaaries or subassemblies of a component or system. i I 2.22 REWORK: 1he process by which a nonconforming item is made to conform to j a prior specified requirement by completion, remachining, reassembling or other l corrective enanna l 1' 2.23 ROVER WORK ORDER: A corrective maintenance Work Order developed and implemented in accordance with the criteria provided in Addendum 3. i 2.24 SCOPE: The scope of a Work Package is the physical boundaries established by the equipment or component. If, for example, the work is to be on a valve seat in a valve with a specific TPNS number and it is determined that other l work on that valve is nanamanry, a scope change has not occurred. 2.25 SKILleOF-THE-CRAFr: 1he' level of knowledge / skill expected of a certified technician. Maintenance technicians are trained (formally and OTT) and certified to perform certain tasks. Skill-of-the craft is considered to be armarimrd industry practices that do not require detailed work instructions to implement. The use of skill-of-the. craft in the performance of an activity is a method where the skills of the technician can be utilized to enhance the work process. 2.26 SUPPORT CONDI110N REPORT: A Condition Report which identifies support activities including, but not limited to, the refurbishment of warehouse, shop or spare equiprnent; coating upgrade of plant c~apaaaats and structures, i insulation work, etc.; requests for manpower support for outage, operations, engineering; fabrication of specialty tools, stands, carts, etc.; and contingency ) work instructions for potential work scope that does not have an existing 6 corrective / preventative problern. Condition reports for these activities are designated as Work Type "S" in WMS. j i 2.27 TROUBLESHOOTING: The process of locating and identifying malfunctions through deductive and inductive reasoning. The process may include activities - I such as taking acadings, pulling fuses, stroking valves, changing electronic modules, partial or complete disassembly of a component or other activities. l l l i l l e

1 Work Pra== h, gem OPGP03-ZA-0090 Rev.10 l ^ Page 8 of 38 2.28 USB AS-IS: A disposition which may be imposed for a nonconforming ) condition when it can be established that the discrepancy will result in no adverse conditions and that the item under consideration will continue to meet .i all engineering functional requirements including performance, maintaina',ility, l St and safety. r 2.29 VISUAL INSPECHON: To perform an examination by using sight alone (WR 1-91021). 230 WORK ATRISK: Iby.dsg work instructions and performing work activities using proposed disposition of engineering h-ts. Work At Risk SHOULD be held to a minimum. bowever this option exists in critical situations provided j Maintenance Department Manager direction is obtained. Equipment which is to be worked ander the " Work At Risk" provisions is declared out of nervice (inoperable for Technical Specification equipment) during the performance of the job. I 231 WORK ORDER (WO): Form used to document Work Instructions in a Work Package and to provide approval and completion signoffs for the work activity. 232 WORK PACKAGE: A package containing a Condition Report, Work Order, Preventive Maintenance Work Order or Modification Work Order and other information required to perform and verify the work (e.g., drawings, technical manuals, etc.). 233 WORK START AITIMORITY (WSA): The person designated for authorizing work start (release of system or equipment for maintenance) and work acceptance (return of system or equipment to service after maintenance). Work Start Authorities include, but are not limited to, Plant Operations, Security and Maintenance. t 234 WORK SUPERVISOR: The person assigned the responsibility / accountability for the performance of a specific work activity. ' Ibis normally will be a craft supervisor or above, but MAY be a certified journeyman in an acting supervisor position (NOV 91-23). 3.0 Responsibilities i 3.1 Engineering is responsible: To prepare Operability reviews. To suppoit Work Package development and implementation. To develop Post-Modification Test (s) and Special Test (s).

Work Process Pmeram OPGP03-ZA-0090 Rev.10 Page 9 of 38 32 The Initiator of a Condition Report is responsible: To provide complete (quantify, etc.), accurate information on the CR. To complete and attach a deficiency tag to the affected equipment or component, when possible. To enter deficiency tag number in (DEPr#) block on CR form. 33 Maintenance is responsible: To support the daily work schedule. To review applicable Work Week Activity List (s) for implementation requirements, including craft certification, estimated duration and man-hours. To provide Work Control - Scheduling the plan of available resources for each craft discipline. To ensure Post Maintenance Testing is performed. 3.4 Nuclear Purchasing and Materials Management (NPMM) is responsible: To provide the materials necessary to support scheduled maintenance. To stage and deliver materials required for work. 3.5 Nuclear Quality Control - Quality Inspection Planning is responsible: To review Work Packages for inaertion of Quality Inspection Points I.A.W. the Quality Control Inspection Matrix. .To Review ' Pen and Ink". changes and revisions to Work P-hye that effect previously identified QIPs. ~' ~ ~ ~ To perform final review of modification Work Packages and Weld Inspection Checklists for safety related activities. 3.6 Operations Work Control Group (OWCG) is responsible: To evaluate CRs in accordance with this procedure and OPGP03-ZX-0002. To act as WSA for Plant Operations To specify and coordinate OPERABILITY test (s) prior to returning Technical Specification equipment to operation. 3.7 Work Control - Planning is responsible: To generate Work Packages in support of the Integrated Schedule. To source / identify materials required for the work. To specify Post-Maintenance Test (s).

Work Process Procram OPGP03-ZA-0090 Rev.10 Page 10 of 38 3.8 Work Control - Scheduling is responsible: To develop and maintain the Integrated Schedule. To provide a daily schedule of work activities for Maintenance and support organizations which includes routine and emergent work activitier To develop logic schedules, as w=y, to support complex work activities. To develop forced outage logic and schedules and maintain a list of forced outage Work Packages. 3.9 Work Package Control Center (WPCC) is responsible: To maintain a centralized location from which work packages are stored, released, and returned. To assist in maintaining work package status. To route work packages as determined by Planning, OWCG, etc. To assist in work package closures. 3.10 Work Start Authority is responsible: To develop and authorize Equipment Clearance Orders (ECOs) (SPR 910039). To release a system or component for maintenance. To coordinate Post-Maintenance / Modification Testing. To return the system or component to service. 4.0 Procedure i 4.1 Condition Identification is the first phase of the Work Process Program. A condition Aeport is used to idendfy conditions that affect plant components, systems and structures. 4.1.1 The individual discovering the problem SHOULD: Examine the component and the adjacent structures to determine if a deficiency tag aheady exists and a CR has been initiated. IF a deficiency tag exists THEN no further action is required.

Work Process Program OPGP03-ZA-0090 Rev.10 Page 11 of 38 IF a deficiency tag is not evident, THEN hang a Tag in a conspicuous place on or near the affected equipment. IF the environment in which the equipment is located could affect the legibility of the tag or entry is prohibited by ALARA THEN hang the tag near the affected equipment or, outside the door. Tags SHOULD not be hung in the Reactor Containment Building. Initiate a condition report including the deficiency tag number in the (DEPT #) block of the CR form. IF the CR identifies support work, not a material deficiency, THEN the supervisor SHOULD submit the CR directly to Planning or applicable organization for processing (ie., manpower request to MSSD). Deficiency tags SHOULD NOT be hung to identify support work. 4.1.2 IF it is known or suspected that the condition affects OPERABILITY or SAFETY, THEN the individual discovering the problem SHALL immediately notify the Shift Supervisor. 4.1.3 'Ihe OWCG SRO/on duty Shift Supervisor SHALL immediately evaluate the CR and determine if it is an Emergency, Priority I or Priority 2 condition. Addendum 2 defines the priorities for the Work Management Process. IF the reported condition is evaluated as not being an Emergency, Priority 1 or Priority 2, THEN the Shift Supervisor SHAIL initiate any actions deemed mary and provide the appropriate priority for the CR. 4.1.4 IF the problem is evaluated as an Emergency. THEN the Shift Superv;sor SHAIL immediately: Initiate actions to mitigate safety concerns and to maintain safe operating conditions in accordance with established pro.edures. Notify the appropriate personnel (Engineering, Maintenance, etc.) of the condition and direct the immediate implementation of corrective actions. Make appropriate management notifications.

l 2 Work Process Prorrarn OPGP03-ZA-0090 l Rev.10 Page 12 of 38 4.1.5 IF the problem is evaluated as a Priority 1 or Priority 2 condition, THEN the OWCG/on duty SRO SHAllinform me applicable e Maintenance / Planning Supervisor of the equipment status and any special requirements that need to be followed. Work MAY commence in accordance with 0PMP01-ZA-0041, Troubleshoot and Rework Process, provided that: An action plan has been developed in accordance with Addendum 4. l l A Work Package, if required, is prepared as soon as possible and the work accomplished is fully documented in, and reconciled with, the approved Work Package prior to returning the system, equipment or component to service / OPERABLE, as required. 4.2 Work Order Evaluation is the second phase of the Work Control Program. The OWCG/on duty SRO evaluates the Condition Report for deficient or degraded material conditions, technical validity, completeness and scheduling in accordance with Addendum 1. 4.2.1 The OWCG SHOULD screen, vslidate, prioritize and disposition CRs which identify material deficiencies within two working days of receipt. 4.2.2 'Ihe OWCG/on duty SRO SHOULD review and evaluate the reported condition to determine if plant OPERABILITY OR SAFETY are affected (LER l-88-010; SPR 921589). IF the deficiency affects the ability of the component to perform its intended function and the component is Tech Spec / Safety Related, and the component is to remain operable /in-service, THEN the OWCGlon duty SRO SHALL contact Engineering for an OPERABILITY review. For l non-Tech Spec /non-Safety Related components, an Operability review is not required (IR 92-04, LER l-92-003, LER l-93416). 4.2.3 The OWCG Planner SHOULD review the CR after initial screening and check the existing CRs on the equipment with the same tag /TPNS number to determine if the reported problem duplicates a previously reported condition.

-_~ - j Work Process Preira. OPGP03-ZA-00M Rev.10 Page 13 of 38 IF the new CR duplicates or can be combined with an i existing CR, THEN the Planner SHOULD add the new CR problem description and Date/ Time to the niming CR, ] notify planning, remove the deficiency tag, void and retum the new CR to the Originator with the disposition. j 4 IF the new CR does not duplicate a previously reported condition, THEN the Planner SHOULD assign the j appropriate Work Type Code to the CR (Addendum 1). i IF a Preventive Maintenance (PM) task can be utilized, THEN the Planner coordinates scheduling the PM, voids the CR pending completion of the PM and enters PM and WAN numbers in CR database. The PM planner adds a step to the PM to remove the deficiency tag. 4.2.4 The OWCG Maintenance Supervisor evaluates the need to perform a field walkdown of identified maintenance problems. During walkdown, the OWCG Maintenance Supervisor SHALL: Verify the Equipment / Component 'IPNS Number is appropriate for the described condition. IF it is determined that the problem has been corrected or no l longer exists, THEN remove the deficiency tag, void CR, enterjustification in data base, and return the CR to the originator with the disposition. Determine if troubleshooting in accordance with OPMP01-ZA-0041. Troubleshoot and Rework Process, is required. Determine if maintenance can be implemented via the Rover process as described in Addendum 3. I 1 Provide a manhour estimate for the anticipated corrective action and identify the support requirements such as additional craft, the need for scaffolding and insulation removal and other information that may be of assistance in planning and scheduling the necessary corrective action. 4 } I r* v <m-- o .4-r

i Work Process Procram OPGP03-ZA-0090 Rev.10 i Page 14 of 38 4.2.5 The OWCG/on Shift SRO determines the Priority in accordance with Addendum 2, performs a preliminary risk assessment in accordance with Addendum 5, and assigns a Need Date based on Plant requirements. 'Ibe OWCG Schedular assigns appropriate schedule target date based on the Integrated Scheduling Matrix and priority (SPR 920864). 4.2.6 In addition to prioritizing the CR, the OWCG performs the following actions as described in the Operations Work Control Group Guide: 1 ContactsWgineering'to evaluate valid conditions, determined not to b detrimental to plant operations or reliability, that do not appear to warrant the cost (time and exposure) of corrective action. Contacts Engineering if assistance is necessary to determine the nature of the problem. Approves and routes CRs categorized as Rover Maintenance = directly to Maintenance for implementation. Routes applicable CRs to the Chem Ops Supervisor or Operational Authority for action as applicable. Routes security discrepancies directly to the Security Supervisor for action. Submits valid CRs to planning and scheduling. 43 Work Activity Scheduling is the third phase of the Work Precess Program. { Work Control-Scheduling is responsible for developing the various schedules used in the work management process as described in the Schedular's Guide. 43.1

  • Ihe Integrated Schedule is used to schedule on-line work activities including Corrective Maintenance, Preventive Maintenance, Surveillance Testing, and support tasks. This Schedule is based on a 12 Week Schedule Cycle which specifies when a system, sub-system or component MAY be taken out of service for maintenance or special activities (e.g., special testing requested by Engineering).

43.2 Resources SHOULD be scheduled and aligned to fully support Unit I and Unit 2 activities cencurrently (i.e., staggering of Unit I-and Unit 2 LCO work weeks, scheduling of specialty crews, etc.).

~_ i Work Process Prorram OPGP03-ZA-0090 Rev.10 i Page 15 of 38 433 Schedule dates for work activities are developed considering the following: Recurring, planned work activities (surveillance, EQ j program items, preventative maintenance items, and non-technical specification surveillance), SHOULD be scheduled for implementation in the appropriate on-line week based on assigned periodicities. Non-recurring work activities (corrective maintenance, modifications, post maintenace tests, etc.) SHOULD be added to the appropriate on-line week based on assigned priorities, nesources, work scope and other information available to the scheduler. t Related work activities SHOULD be grouped, tied together and concurrently scheduled on a component or system basis to the maximum extent feasible. "Ihe Scheduler has the authority to adjust the due dates for Preventive Maintenance items forward or backward in order to align related work items so that the number of times equipment is taken out of service for maintenance is minimized. IF the schedule for a j preventive maintenance item exceeds the allowable periodicity window, THEN a PM deferral SHOULD be processed in accordance with OPGP03-ZM-0002. The work scope is finalized 3 weeks prior to Work Week (N) with the following exceptions: Priority 1 or 2 work. Work activities scheduled within this 3 week period MAY be adjusted to facilitate the process. Priority 3 work MAY be added with concurrence from the Plant Manager or designee. MCBs, IAPOs, IAFrs, and CHMs may be added with concurrence from WSA, Work Control, and Maintenance. Activities that may challenge or present a risk to the operation of the plant SHALL be evaluated in accordance with the guidance provided in Addendum 5. 1

J Work Process Prorram OPGP03-ZA-0090 Rev.10 Page 16 of 38 High priority / Task Ready work activities that require a unit outage or present a High Risk when at-power SHOULD be includd in forced outage work lists that can be implemented on short notice. Schedules SHOULD be resource loaded to the maximum extent feasible. Schedule changes based on resource limitations SHOULD include management review and approval at a level commensurate with the change involved. The status of planning activities to prepare for work implementation SHOULD be monitored on a continuous basis. Items that will not be " Task Ready" for i:nplementation 3 weeks prior to their scheduled date SHOULD be rescheduled to the next earliest opportunity in the 12 week cycle. 43.4 The Daily Schedule SHOULD be reviewed by OWCG, Operations Shift Supervisor, Chemops, Health Physics, Maintenance, Engineering, NPMM, Security and Work Control and SHOULD be approved by the Operations Manager and the Maintenance Manager. 4.4 Work Activity Planning is the fourth phase of the Work Control Program. Work Control Planning is responsible for developing or assisting in the preparation the Work Instructions needed to perform required work as described in the Planner's Guide. 4A.1 The Planner writes work instructions in sufficient detail such that qualified individuals can perform the activity safely and correctly. The Planner MAY take into account " Skill of the Craft" and write the instructions such that they do not describe step by step actions that the craft are trained on. IF the activity requires step by step instmetions, THEN the instructions SHOULD be definitive enough to ensure that the required results are achieved (LER l-90-01). 4A.2 Troubleshooting work instructions are in accordance with OPMP01-ZA-0041, Troubleshoot and Remk Process.

t W ork ' --- ~ OPGP03-ZA-0090 Rev.10 Page 17 of 38 4.43 Identify material early enough to ensure availability prior to the work package scheduled start date. Identify material W to support emergent work promptly, and expedite as necessary to minimize r schedule i=,and l Planners MAY reallocate parts reserved for a non forced outage work package scheduled later to satisfy a high priority, near term need, with the approval of the Planmng Supervisor. 4A.4 Test Requirements Planners specifies Post-Maintenance Test Requirements. Engineering specifies Post-Modification Tests and/or Special Tests. Operations (OWCG/on duty SRO) specifies OPERABILITY Tests. 4.4.5 Work Package Review and Approvai 4.4.5.1 Work Packages are reviewed for technical content and accuracy and approved by Planning or a Work Group Supervisor (LERs 1-91-013, 1-91 021, 2-89-006). 4.4.5.2 Upon completion of planning activities and a final review, the Planner transmits the Work Package to the Work Package Control Center (WPCC) where the Work Package is routed for other approvals, as requested. Once the approvals are obtained, Work Packages are held by the WPCC until released for work start. 4.4.53 Work Packages are routed for other approval as follows (SPRs 921543,900407,900503): Work Packages are routed to Quality Control based on the Quality Classification and the QC Review Matrix. ~ Work Packages are roused so Engineering as required by dhigineeriiig progradiisocedures (SPR 940350).'" =

i Work Process Procram 0PGP03-ZA-0090 Rev.10 ~ Page 18 of 38 4.4.5.4 Additional Work Instructions, or clarifications, that do not alter the Scope or Intent of work activities MAY be added asIPen and Ink Changes"r 'Ihe Work Supervisor is responsible and authorized to make Pen and Ink changes. Pen and ink changes which alter or change previously identified QC inspection points, are routed to QC for review or, for work in progress, QC SHOULD be contacted for assistance. IF the changes affect radiological conditions, PMT, etc. THEN, the work supervisor is responsible for making the appropriate notification and coordination. 4.4.5.5 A' Work Pselinge Revision is required en additional instructions or clarifications change the Scope or Intent of the work activity. Revisions are required to be routed the same as the original Work Package, including WSA (SPR 910151). 4.5 Work Release and Implementation is the fifth phase of the Work Process Program. The Work Supervisor is responsible for performing the work in a safe and quality manner within the constraints of the implementation schedule. 4.5.1 Work Release 4.5.1.1 The Work Start Authority (WSA) SHALL: Review the daily schedule and determine the activities scheduled to be released for work. Perform a final review of the work package to ensure that current plant conditions support accomplishment of the work package as currently scheduled. Determine if the activity may challenge or present a risk to the safe operation of the plant in accordance with the guidance provided in Addendum 5. Authorize the Equipment Clearance Order (ECO) to be established.

u t. Work Process Proeram OPGP03-ZA-0090 Rev.10 Page 19 of 38 Release the work package for implementation. 4.5.2 Work Assignment 4.5.2.1 The Work Supervisor SHALL ensure personnel have the necessary skills, experience and training certification specific to the work task (OMR 85-21, LER 1-93-07). 4.53 Work Performance 4.53.1 With the exception of Emergency work and as noted in 1.2.5, personnel SHALL not perform maintenance, alter, change or modify plant equipment without an approved work document and authorization from the WSA. 4.53.2 IF the configuration of the equipment does not match the configuration of the work documents, THEN notify the Work Supervisor (SPR 910484; DR 91-027; SER 84-069). 4.533 The Work Supervisor reviews Work Packages prior to work performance to ensure the package is " Task Ready". This includes (LER 2-91-010): Sufficient information and direction is contained to support work performance by qualified craftsmen. Activities which have been evaluated as a risk potential, are pre-job briefed and directly supervised as described in Addendum 5. i Required permits and clearances are in order. Parts are available. Documents, or appropriate extracts, listed in the t implementing reference section are in the package and are the latest revision. l 4.53.4

  • Ihe Work Supervisor SHALL evaluate the need to conduct i

a pre-job brief prior to work start (SPR 910422, IR 93-03). l 1

f w Work Process Program OPGP03-ZA-0090 Rev.10 Page 20 of 38 i 4.53.5 IF during work in progress, a discrepancy is discovered that is not within the Scope or Intent of the work document, THEN a revision and/or a Condition Report is written. 5 Changes, revisions, additions or modifications to work i documents are accomplished in accordance with Steps 4.4.5.4 or 4.4.5.5. l A 4.53.6 IF conditions prevent performance of a PM, THEN the following actions are performed as required: IF the cause is apparent, (ie., broken part, leaking l fitting, etc.) THEN make a one time change to the PM l to allow completion of the PM (SPR 933531). IF the cause is NOT apparent, THEN correct the condition using 0PMP01-ZA-0041, to allow completion of the PM (SPR 933531). IP a change to the work instructions is required due to a temporary condition, THEN the Work Supervisor is authorized to make " Pen and Ink Changes" to the PM in accordance with 4.4.5.4. i For condition (s) that will affect the next performance of the PM (ie., changes to the PM work instructions are required), a Feedback SHALL be initiated. 4.53.7 A " Working Copy" MAY be used under certain conditions such as work in a contamination area or in areas where oil, water, etc. could damage the original Work Package or if multiple crews are used to complete the activity. A " Working Copy" MAY also be used to continue work while the original work package is being revised if the revision will not impact the work being performed. Following completion of work, all data, work = information, signatures, initials and dates from the " Working Copy" SHOULD be transcribed to the original work document and the " Working Copy" properly discarded / destroyed. QC signatures SHALL be transcribed by QC personnel. l i t V 6 'm-- ~ c w

l ~ Work Process Pmgram OPGP03-ZA-0090 Rev.10 Page 21 of 38 4.53.8 IF the work document contains a hold point or verification point, THEN the craft ensures the appropriate group is l notified and the hold or verification point is complete prior to continuing the work (SPR 870304). 453.9 Proper documentation of work performed is the responsibility of the craft performing the work. Work documentation includes, but is not limited to: Detailed as-found, as-left, difficulties in job completion, and/or potential failure mechanism. Repeating the 4 Work Instructions or procedure steps is not required. i Start / completion times / dates Parts and material information that provide pertinent equipment historical data not detailed in the job step. 4.53.10 The back-dating of any work document is prohibited. Late - entries MAY be made by the Performer or the Supervisor by stating the entry is a " Late Entry" and using the date the activity occurred. 'Ihe entry SHALL then be initialed and dated by the person making the late entry, using the date the late entry is made (Speakout 12266). 4.5.4 Work Completion 4.5.4.1 Work Package SHOULD not be considered complete unless the equipment is in design configuration (e.g., approved drawing, approved engineering documents, etc.). 4.5.4.2 Upon completion of the work, the Work Supervisor ensures the fo' lowing: Review of the Work Package to verify signatures, signoffs and summary documentation are complete and correct. Part retention requirements for Root Cause Analysis are 4: evaluated for conditions identified as a CAQ-S or SCAQ, with assistance from Engineering as required. All required QC inspections are performed. 1 l )

i 'a Work Process Pieer-si OPGP03-ZA-0090 Rev.10 Page 22 of 38 Work areas are restored to original cleanliness or better. I Deficiency tag is removed and discarded. t i 'Ihe revision level of the documents used is verified. IF a revision change occurred, THEN an evaluation is performed to determine if the revision invalidated the l work performed and the need for revising the Work Package (ISEG RIT 9-87; DR 89-07). IF the Work Group used References that were not listed f in the Reference Section, THEN the Work Supervisor ensures the References used are added to the Reference f Section. All specified tests have S:en completed, a technical l justification for not performing the PMT is provided in the Work Package, or document performing the PMT is i referenced in the work package prior to the WO bemg complete. 4.5.5 Maintenance Shift Tumover i 4.5.5.1 Shift turnovers, written or oral, are conducted suci that essential information is transferred in a timely and accurate manner (IEN 86-007). Work Packages are updated to reflect current work status, w-*y tumover instructions, problems encountered or any other important information about the job. As a minimum, a review of the latest sequence of completed / documented Work Instruction steps are done j at turnover. i 4.5.6 Work Start Authority Review 4.5.6.1 The WSA reviews the package for: ) 1 Work completion. Post-Maintenance, Post-Modification test completion.

') 7 e Work Process Program OPGP03-ZA-0090 Rev.10 i PaF,23 of ?8 'Ibe OWCGlon duty SRO will evaluatchpecify :h OPERABILITY testing requirements. 4.5.6.2 "Ihe WSA will update package status and forward the l package to WPCC for closure. I 4.6 Work Package Closure is the final phase of the Work Process Program. The WPCC is responsible for preparing the Work Package for final review and record retention. 4.6.1 WPCC SHOULD remove and destroy documentation not required for retention. Documentation required to be retained with the package and forwarded for retention includes, but is not limited to, all l documentation that contain sign-offs, initials or M&TE data. i Retrievable documents must be referenced in the Work Package but need not be kept as part of the package. 4.6.2 WPCC updates the Work Package status in WMS and forwards Work j Packages to Engineering for final review / equipment history. l 1 5.0 References I 5.1 OWCG Guide [ 5.2 Planner's Guide 53 Scheduler's Guide 5.4 WPCC Guide 5.5 INPO 90-023 Maintenance Work Package Planning I 5.6 INPO 92-001 Guidehnes for the Conduct of Maintenance at Nuclear j Power Stations 1 5.7 OPGP03-ZA-0010 Performing and Verifying Station Activities i 5.8 OPGP03-ZA-0109 Configuration Management Program 5.9 OPGP03-ZM-0002 Preventive Maintenance Program 5.10 OPGP03-ZM-0021 Control of Configuration Changes 5.11 OPGP03-ZM-0025 Post Maintenance Testing Program 5.12 OPGP03-ZX-0002 Condition Reporting Process 5.13 OPMP01-ZA-0041 Troubleshoot and Rework Process 6.0 Support Documents 6.1 Addendum 1 Condition Report Completion 6.2 Addendum 2 Work Process Priorities 63 Addendum 3 Rover / Minor Maintenance Guidelines 6.4 Addendum 4 Priority I and 2 Work Activity Action Plans. 6.5 Addendum 5 Work Risk Assessment 6.6 Addendum 6 Work Process Flowchart i

Work Process Program OPGP03-ZA-0090 Rev.10 Page 24 of 38 ADDENDUM 1 l CONDITION REPORT WORK ORDER EVALUATION (Page 1 of 2) WORK ORDER EVALUATION PRIOPJTY Enter the priority assigned to this activity. OTL # Enter the OTL number (if assigned from the appropriate unit's contml room OTL log.) LCO EXP. If the identified condition or problem has placed the unit in mi LCO DATE/ TIME situsion, enter the date/ time by which the condition must be conected to mitigate additloc,1 actions. WSA Enter the acronym for the appropriate Work Start Authority for the system (component). MODE Enter the applicable Mode which the activity may be worked in or is required to be worked in (Select modes I thmugh 6, any combination of I through 6, Defueled or all). SPECIAL ErJer the special program code (if one applies to the equipment and its PROGRAM condition). These codes are used to group special interest, significant/important activities. (MCB,IAFO,IAFT,CIfM) NEED DATE Enter the nea.d date which ddves the planning, material procurement and scheduling of this activity.. (This date SHOULD be established to support any identified commitments oc as detennined from a review of the scheduling cycle for the affected system /componen! and the priority.) LCO (Y/N) Enter Yes or No indleating if the problem described or the intended maintenance places the unit in an LCO. WAN Enter the WAN (work actielty number) assigned by WMS for the Work Order after 4 1 entry into WMS. FCD MLST Enter the appropriate Milestone code from the milestone coding chart. WORK GROUP Enter the lead Maintenance craft assigned to perfonn the work. Refer to the Maintenance Department division.d responsibility matrix. l 1 i

r o Work Process Program OPGP03-ZA-0090 l Rev.10 ~' Page 25 of 38 ADDENDUM I h CONDITION REPORT WORK ORDER EVALUATION i (Page 2 of 2) WORK TYPE Enter the code for the type of wod activity identified by the defecthequest block. i These codes include C<onective, P-Preventive, M-Modification and S-Support. [ Select one of the action choices from the block. VOID - Retum the CR to the Originssor with comments. WORK ORDER - Enter the CR into WMS and plan as a Woi Order. MINOR MAINT. - Process the CR as Rover / Minor Maintenance. INVALID - Retum the CR to the Originator with justification / comments. l COMMENTS / Enter significant recommendations, observations and RECOMMENDATION: investigation (e.g., system, train or component taken out of service due to deficiency, etc). This block MAY also be used to document actions taken under minor woA activities. ) i IF THE ACTIVITY IS PERFORMED AS MINOR WORK THE WORK SUPERVISOR l ENSURES THE FOLLOWING FIELDS ARE COMPLETED. START Print the nane of the WSA contacted prior to perfonning the activity as minor woi and the date/ time of the contact.

  1. PERSON Enter the ideal number of caft personnel required to perfonn the activity.

[ CII)SEOUT Sign and date to indicate that all wo& perfonned under this CR as minor SIGNATURE wo& was adequately documented and the minor woi activity has been reviewed and completed. COMPL Print the nane of the WSA contacted upon completion of the minor work activity and the date/ time of the contact. HOURS Enter the total number of craft person hours expended to perfonn the activity as minor woi. I DISCOVERY CODES STAT 11S CODES SYMPTOM CODES DETECTION CODES l SYSTEM A - PHYSICAL FAULT A - OPERATIONAL ABNORMALITY A - IN SERVICE B OUTOG SPECIFICATION B - IN. SERVICE INSPECTION (OPERAT1NG/ STANDBY) C - DEMAND FAULT C - SURVEILLANCE TESTING B - IN 1EST D - ABNORMAL D PREVENT 1VE MAINTENANCE C - IN MAINTENANCE CHARACTERIST1C E - SPECIAL INSPECT 10N D - OUT OF SERVICE (NOT IN E - RELEASED LEAKAGE F - AUDIOVISUAL ALARM MAINTENANCE) F - CONTAINED LEAKAGE H - ROUTINE OBSERVATION N - NOT APPLICABLE J - INCIDENTAL OBSERVATION IRAIN K - CORRECTIVE MAINTENANCE E - IN SERVICE O OTHER (USE ONLY IF NOT A (OPERATING / STANDBY) FAILURE) F - IN TEST G - IN MAINTENANCE H - OUT OF SERVICE (NOT IN MAINTENANCE)

Work Process Program OPGP03-ZA-0090 l Rev.10 i 1 Page 26 of 38 j i ADDENDUM 2 f WORK PROCESS PRIORITIES l (Page 1 of !) This priority system provides guidance for determining the appropriate schedule for activities within the Work Process. \\ EMERGENCY Emergency maintenance actions required to be parformed immediately to prevent or I mitigate the consequences of an accident, prevent the release of radioactive material to i the environment or to protect human life and/or property. Emergency maintenance is l performed at the discretion of the Shift Supervisor / Emergency Director and MAY start f without an approved work package. Emergency Maintenance SHOULD only be used during Emergency Plan events (SPR 930125). PRIORITY 1 Actions required to restore a system or function to OPERABLE status to decrease the risk of radiation exposure, eliminate a personnel safety hazard, return the plant to full power operation, or satisfy a Tech Spec Limiting Condition for Operation (LCO) action statement. The work SHOULD continue until completed or until the circumstances requiring the priority action no longer applies. PRIORITY 2 Actions required to mitigate or resolve equipment or component problems which restrict the desired level of plant operation. Priority 2 SHOULD be used only for important i activities that must override the normal work schedule. j PRIORITY 3 t Actions assigned and coordinated on a routine basis. Priority 3 SHALL be assigned to I corrective work that supports plant operations. Priority 3 work MAY be further governed by a scheduling milestone. I PRIORITY 4 Activities whicli do not impact plant operation or prevent accomplishment of program events or milestanes (e.g., rework of non-essential or non-plant equipment, painting, inspections, etc.). PRIORITY 5 Activities which can be deferred (e.g., outage activities, modifications, activities on hold for budgetary purposes, etc.). Preparatory or prerequisite activities which support a Priority 5 item SHOULD be assigned the priority necessary to provide the required level of support. l

h l Work Process Procram OPGP03-ZA-0090 Rev.10 Page 27 of 38 t ADDENDUM 3 l ROVER / MINOR MAINTENANCE GUIDELINES / CRITERIA i (Page 1 of 2) l The Rover process is a method by which relatively simple maintenance tasks can be i accomplished. Tasks of this nature typically do not require detailed work instructions. This i process utilizes the skill / certification of the individuals assigned, in conjunction with specific criteria, to determine when maintenance MAY be implemented via a Minor Maintenance or OPMP01-ZA-0041 Work Package (SPR 933531). i Maintenance implemented via the Rover / Minor Maintenance Process is not required to be scheduled. Rover / Minor maintenance work is used to increase process efficiency by allowing qualified / certified technicians to implement the work directly. Rover / Minor mamtenance expedites the work process and ensures that work is available (ie., discretionary / fill in) should the scheduled activities not be performed as planned. New Condition Reports are evaluated by the OWCG staff to determine their applicability to the Rover / Minor Maintenance process. If the item can be worked as Minor Maintenance as defined in 2.7, the CR itself can be used to document the work performed including parts used. The controlling document for a OPMP01-ZA-0041 Work Package is the CR. Rover Work Packages MAY be used to perform maintenance activities within the following limitations: The task SHALL be within the skill / certification level of the individual assigned technician (s). The scope of work does not require testing in accordance with Generic letter 89-10 1 Program. j 'Ihe scobogram.rk does not require testing in accordance with the ASME XI Inserv of wo Testing Minimal coordination is required (scaffold, ECO, etc.) i c 7 -~ .---a

t Work Process Procram OPGP03-ZA-0090 Rev.10 Page 28 of 38 ADDENDUM 3 ROVERMINOR MAINTENANCE GUIDRIINF3/ CRITERIA (Page 2 of 2) Processing a Rover Condition Report: Evaluate the CR for RoverMinor Maintenance criteria compliance. If the CR fits the RoverMinor Maintenance criteria, annotate the CR in WMS as a i Rover / Minor Maintenance. For a Rover Work Package, attach the CR to the OPMP01-ZA-0041 Work Package. For Minor Maintenance, the work MAY be i documented dire ~tly on the CR. For both Rover and Minor Maintenance, status the CR in accordance with the WMS status codes. Route / Notify QC for inspection planning per OPMP01-ZA-0041. If the problem is corrected under the RoverMinor Maintenance, process the CR through closure. If the problem is not corrected under the Rover / Minor Maintenance, then the original I CR, SHOULD be forwarded to planning with comments addressing the recommended i actions. i I i i s l r f i l

Work Process Program OPGP03-ZA-0090 Rev.10 Page 29 of 38 ADDENDUM 4 i PRIORITY 1 and 2 WORK ACTIVITY ACTION PLANS ~ (Page 1 of 3) PRIORITY 1 & 2 CONDITION REPORT ACTION PLANS The proper and expedient completion of Priority 1 & 2 Condition Reports is essential to efficient operation of the Plant. 'Iherefore, Priority 1 & 2 work activities require additional review and coonlination. The attached checklist is designed to provide a clear understanding of the impact on the Plant and to develop a plan of action that will i ensure expedient completion of Priority 1 and 2 activities. Each Priority 1 & 2 Condition Report will require Operations to initiate the Operations Impact Checklist; and comunicate with the Planner and Maintenance Supervisor to develop expectations, a plan of action and a task owner. The plan of action SHOULD include a need date, special coordination of activities and a fragnet if deemed necessary. These actions will help ensure Priority 1 & 2 activities are effectively communicated and completed as soon as possible to minimize impact on the plant. I l I l l l

Work Process Procram 0PGP03-ZA-0090 Rev.10 Page 30 of 38 ADDENDUM 4 PRIORITY 1 and 2 WORK ACTIVITY ACTION PLANS (Page 2 of 3) (SAMPLE) PRIORITY 1 & 2 ACTION PLANS Managemert Expectation:

  • Comphtion of Operations Impact Checklist
  • Plan of Action Meeting Completion 1.

Review by Operations, Planner, Maintenance Supervisor of Priority 1 & 2 issues Operations needed start Date/ Time Operations impact LCO O Expiration Date/ rime Licensing Agreement D Management Initiative o Power Reduction Required D Power Production Efficiency 0 Ifealth/ Safety Concerns D Environmental Impact a Management Notification a Reactor Trip /ESF Potential u Planning estimated work package preparation completion date/ time: Planning evaluate / estimate parts availability: Discuss potential contingency plans, factor worst case scenario / factor best case scenario. Comments: Discuss anticipated Maintenance and Operations Testing. Comments: Implementing craft estimated work start date/ time: Consider Craft cenification, Ops needs, resource availability, coordination with other craft, Engineering support, QC support, vibration, ECO, scaffold, insulation etc. Work around the clock? D (Check applicable) Day shift only? O Weekends? o Call outs? O -...i

Work Process Program OPGP03-ZA-0090 Rev.10 Page 31 of 38 ADDENDUM 4 PRIORITY 1 and 2 WORK ACTIVITY ACTION PLANS (Page 3 of 3) (SAMPLE) PRIORITY 1 & 2 ACTION PLANS L Schedule plan of action based on knpactfrom item #1. Fragnet worst case scenario. Overlay best case scenario. Overlay anticipated plan of action. Allow time for all work expected to require one (1) bour or greater (eg. briefings, ECO, scaffold, insulation, PMT, vibration, engineering hold points, QC hold points, shift turnover). Factor durations based on resource availability including RPO, RO, MSSD, Crafts, Supervisors, etc. Flag field work start, field work complete, PMT complete, LCO exit, power resumption, event termination. Assign task owners by name, extension numbers, beepers for each scheduled activity. Assign the overall owner by name, organization, phone number, beeper.

^ Work Prt cess Program OPGP03-ZA-0090 Rev.10 j Page 32 of 38 ADDENDUM 5 WORK RISK ASSESSMENT ] (Page 1 of 6) Activities which may challenge or present a risk to the operation or safe shutdown of the plant SHALL be evaluated to provide a high degree of assurance that the activity is planned, scheduled and executed in a manner that minimires risk (LER 1-94-011). Table I identifies the systems / procedures with risk potential. Activities associated with these systems / procedures SHALL be evaluated in accordance with the " Work Risk Assessment" screening forre This form accompanies the Work Package through activity implementation. Once the activity has been satisfactorily completed, the form SHOULD be forwarded to the appropriate Operations Manager with any comments. Activities which are deemed a risk are subject to the following requirements: 1. Pre-job briefing in the Control Room in accordance with the " Actuation Risk Briefing Checklist" (required for low. Medium and High Risk) i 2. Direct / Field Supervision (required for High Risk) ] J 3. Operations Manager approval (required for High Risk) l 1

r Work Process Procram OPGP03-ZA-0090 ~~ Rev.10 Page 33 of 38 ADDENDUM 5 WORK RISK ASSESSMENT (Page ' of 6) t TABLE 1 SYSTEM SYSTEM NAME SYSTEM SYSTEM NAME AC CIDSED IDOP AUXILIARY COOLING DG STANDBY DIESEL GENERATOR WATER (MECHANICAL) AF AUXILIARY FEEDWATEit DG STANDBY DIESEL GENERATOR (EIICTRICAL) AN ANNUNCIATOR DI STANDBY DIESEL COMBUST 10N AIR INTAKE BS 7300 PROCESSOR SUPPORT DJ 125V DC CLASS IE l CC COMPONENT COOLNG WATER EH ELECTRO-HYDRAULIC CONTROLS CD CONDENSATE EW ESSEN11AL COOLING WATER & ECW SCREEN WASH Of ESSENTIAL CHILLWATER ONLY FC SPENT FUEL POOL COOLING & CLEANUP j SYSTEM & REACTOR CAVTlY FILTRATION SYSTEM CM CONTANMENT MONTIORING FP FIRE PROTECTION-FOAM WATER CP CONDENSATE POLISHER FP FIRE PROTCC110N-HAIDN CR CONDENSER AIR REMOVAL FW FEEDWATER CS CONTANMENT SPRAY FW FEEDWATER SYSTEMS TURBINES & PUMPS ONLY NCLUDES SGFFF CONTROL SYSTEM CV CHEMICAL & VOLUME CONTROL GC STATOR COOLNG WATER CW CIRCULATNG WATER GE MAIN GENERATOR EXCTIER DA 125V DC NONCLASS IE GM MAIN GENERATOR (W/O AUXILIARIES) DB DIESEL GENERA 1DR (BOP, TSC & EOF) GS TURBINE GLAN SEAL l DC 250V DC NONCLASS IE HB HVAC4ONTROL ROOM DE 48V DC NONCLASS IE HC HVAC-CONTAINMENT BUILDING

Work Process Prc,g-si OPGP03-ZA-0090 Rev.10 Page 34 of 38 ADDENDUM 5 WORK RISK ASSESSMENT (Page 3 of 6) TABLE 1 SYS1EM SYSTEM NAME SYSTEM SYSTEM NAME l HF HVAC-PUEL HANDLNG PG 132 KV EMERGENCY POWER i 1A ESTRUMENT AIR PK. 4 K VAC CLASS 1E POWER II INCORE NSTRUME! CATION PL 480 VAC CLASS lE IDAD CC'1ERS l JW STANDBY DIESEL GENERATOR JACKET PM 480 VAC CLASS lE MCC & DISTRIBUTION WATER PANELS LP FEED PUMP TURBINE LUllE OIL SYSTEM RA RADIA110N MONTIORNG LT MAIN TURBINE LUBE OIL SYSTEM RC REACTOR COOLANT LU STANDBY DIESEL GENERATOR LUBE OIL RH RESkDUAL HEAT REMOVAL l MS MAN STEAM RI DIGITAL ROD POSr!10N NDICA110N i NI NUCLEAR NSTRUMENTA110N (NEUTRON RS ROD CONTROL FLUX) NN ISO-PHASE BUS. NON-SQNC BUS VAT. GEN SD STANDBY DIESEL GENERA 1DR STAR 11NG C/B AIR OC OPEN LOOP AUXILIARY COOLING SF ENGINEERED SAFETY PEATURES ACTUATION PA STANDBY TRANSIORMER SI SAFETY NJEC110N i PB MAN & AUXIEJARY 1RANSIURMERS SM ESF STATUS MONrrORING l INCLUDING GEN GCB & BUS DUCT i COOtJNG j i PC 132 K VAC AUXILIARY POWER SP SOLID STA1E PROTECTION PD 4 K VAC NONCLASS lE TM MAN TURBINE l PE 440 VAC NON 1E IDAD CENTERS VA 120 VAC CIASS IE VrrAL POWER l 1 PF 480 VAC NON IE MCC & DISTRIBUTION VC 120 VAC NON IE VITAL POWER j PANNELS J ) l I

r-Work Process Procram 0PGP03-ZA-0090 Rev.10 Page 35 of 38 ADDENDUMS WORK RISK ASSESSMENT (Page 4 of 6) TABLE 2 OPERATIONS DEPARTMENT SURVEILLANCES PROCEDURE NUMBER DESCRIPTION OPSP03-CS4001 CONTAWMENT SPRAY PUMP TESTS ' PSP 03CS4002 THRU PSP 03-CS-0006 CONTANMENT SPRAY PUMP TESTS OPSP03-IM.0001 FEEDWATER SYSTEM VALVE OPERABILTTY TEST OPSP03-MS4001 MANSTEAM SYSTEM VALVE OPERABILTTY TEST OPSP03-MS-0003 MAN TURBINE INIET VALVE OPERABILTTY ' PSP 03-SB4001 STEAM GENERATOR BLDWDOWN SYSTEM VALVE OPERABILTIY TEST OPSP03-SP-0005R SSPS LDGIC TRAW R FUNCTIONAL TEST OPSP03-SP4005S SSPS EDGIC TRAN S FUNCT10NAL TEST OPSP03-SP-0006R TRAN R REACICR 'lRIP BREAKER TADOT OPSIO3-SP-0006S TRAIN S REACTOR 'IRIP BREAKER TADOT OPSP03-SP4007A. B. C SSPS ACIUATION 'IRAIN MASTER RELAY 'IESTS OPSP03-SP4008 A. B. C SSPS 1 RAIN SLAVE RELAY TESTS OtJIPLTTS BIDCKED OPSP03-SP4009A. B. C SSPS ACIUATION TRAIN SLAVE RELAY 'IEST3 OPSP03-SP-0010A, B. C TRAN DIESEL SEQUFNCER MANUAL LOCAL TESTS OPSP03-SP-001I A. B. C TRAIN DIESEL GENERATOR SLAVE RELAY TES13 OPSP03-NI4001 DAILY POWER RANGE CHANNEL CALIBRATION OPOP07.TM4001 , IURBINE OVERSPEED TEST MONTHLY ENGINEERING SURVEILLANCES PROCEDURE NUMBER DESCRIPTION OPSP10-RC-0001 RCS FIDW DEIERMINAT10N t

Work Process Program OPGP03-ZA-0090 Rev.10 Page 36 of 38 ADDENDUM 5 WORK RISK ASSESSMENT SAMPLE (Page 5 of 6) (SAMPLE) WORK RISK ASSESSMENT f C/PM/ PROCEDURE NO. SYC.! UNIT WAN NO. COMPONENT MODE: POWER:

  • * ^ "

Does this activity:

1) Require any bistables tripped?
2) Affect a circuit that inputs to a Reactor trip, Turbine trip or ESF actuation?
3) Affect equipment in more than one train at a time?
4) Affect systems that if lost could result in a Reactor trip, Turbine trip or ESF actuation?
5) Will be performed by NON-Certified Technicians?

SCREENED BY DATE Work Supervisor IF ANY OF THE ABOVE ANSWERS ARE YES, the WORK START AUTHORITY SHOULD COMPLETE THE FOLLOWING: REACTOR TRIP POTENTIAL LOW MEDIUM HIGH NONE TURBINE TRIP POTENTIAL LOW MEDIUM HIGH NONE ESF ACTUATION POTENTIAL LOW MEDIUM HIGH NONE COMPENSATORY ACTIONS IF REQUIRED: CONTROL ROOM PRE-JOB BRIEF REQUIRED YES NO-(Requaed tw Low, Med.& High Risk) DIRECT SUPERVISION REQUIRED (aequii.a fa non Riso YES NO APPROVED / Work Start SRO DATO APPROVED / SHIFT SUPERVISOR dan (Required for Low, Medium and High Risk) APPROVED / OPS MANAGER dan (Required for High Risk) NOTE: 1. Operations SHOULD attach this sheet to the front of the work package / procedure submitted for approval to start work.

F ~ ~^ Work Process Proeram OPGP03-ZA-0090 Rev.10 Page 37 of 38 ADDENDUM 5 WORK RISK ASSESSMENT (Page 6 of 6) Actuation Risk Briefing Checklist: The supervisor responsible for the activity SHOULD dis:uss the following items with the crew performing the activity (Ensure the On-Shift crew is rerresented in the briefing). The scope of the activity to be performed. The potential actuation (s) that could occur during the performance of this activity. The critical manipulations or steps in the activity when the actuation could occur. The barriers in place to prevent the actuation from occurring and any additional barriers that may be needed. The communication network used to control the pace and communicate the status of the activity. The Command and Control function of the activity supervisor. The activity termination criteria and potential contingency actions if an actuation occurs. The impact the activity pe formance could have on other concurrent activities or plant conditions. Any compensatory measures to be taken to minimize the risk. Assign responsibility for these actions, as appropriate.

i j ? l 3 Work Process Program OPGP03-ZA-0090 Rev.10 Page 38 of 38 i ADDENDUM 6 i WORK PROCESS FLOWCHART (Page 1 of 1) l l lg H* [ 3 [ 3 F .i 3 lll 8 = <l b l ~~ J lli ui e g lk e a i, g :: o il o g i l1l i i i 8 Ia gl o g gl I e , I i I i J-I I g,, ~ l o o. I = q 8ll ~ R n 3 lI s = l :. 6 l a = -,---e-r-+- w- --e'+ g w-wu---ew w u- %e w-w .m,- y-e

\\ lb Cfv:I ~ STP 466 (04/93) SOUTH TEXAS PROKCT ELECTRIC GENERATWG STATION opcp03-Zx.0002 ' l STATION PROBLEM REPORT 'L s 9 V 857. 7 [ cAc cAxcoRv Di O2 ds 04 Os Os sen no. 4 PART 1: IDENTIFICATION OF CONCERN E. E. P. cree oc,T rSE6-A. um i O i O couuon muro: uAu[ 02 2 s0Tw posm0N sf,ff Ener- ,wo.E.0._ se ts DATE I"I"94 M SI4f h DISCOVERY: DATE 3*3*T4 M iI 4f" Ane - EVENT: DATE M M.ul. haaukerelb DATE M iuuCDIAE SUPERMSR siCNATURC (NOT RE0d.4EO) e0auCurs Race;oed FAX 4ransmoWel from UQULe CarbormTne'n[%e Elmehrieb' n41 M& keel. PRostEu CESCRPTION B.mkh C medien neommendr ensudinuin Ee. uce 4 L u-</u n miac'eraA ma;as Msf -tralleu fseanee % kaoa..C.. a i:eaine,r _bnerskss_proMen 1< boHeX wa.e%c in % ennaf at-i aanKer.slaat kaulu, s:,e;lar otorS,ai ~ '

  • TV.s enoucewf~ con made bs UL% G<beco;% h ace.ordence.

ect K +L ru u\\renok e4-to c%.z. I. ' Q 'Th> %fo schytrsenul coere. loame=hdad xcl.'4,[o]r : AL ApTIONS TAKEN CONTNUAT10N SHEET ATTACHED o C. suuCDIAT(COMPENSATORY OR REuCD: y n s(a.C+ sasero) sore ~n bsK an& g e nexw thw.neF;u,. c.v;WMdual 4, vert P "4 v _ frl M C24(ChA.Q l Nec$AAsbN NO t_. I s ate c:,ahw, / d v D. IDENTiflCATION ( ) C04TNUAT:0N SHECT ATTACHED SYSTEW COMPONENT NAME bd & AMI A F' @W 4-1 Clot NCP tot & ec~$ CouPONtnf NO. ewC o _.7 Clot Atc P2ot A INSTRUCTIONS FOR PART 1 COUPLET 10N DESCRtDE iVUR CONCf'.N QVING AS WUCH sNf0RuATION AS POSSIBLE. r:LL N ALL APPLICALLI $ECTONS OR ATTACH 00CouCNTAT)o'd. NDICATE YMAT. VMEN. WHO. Mir, wHERE. HOW. LIST ANY REFERCNCES. J 1 DESCRIBE Att suuCOLATE CouPENSATORY/R[uCOIAL ACTIONS TAJEN HO T E.: 1E POTENitALLY REPORTA8LE. OR IF ANY OCU8T EKISYS REC ARDlHC REPORTA81LITY.,1,.!*.Laf OtttVER ikuCDtATELY TO THE SHIFT SUPERvtSOR. OTHERMSE. OELivtR TO THE C AC ADulNtSTR ATOR. l

sPR M A'lCFla ~7 PART 2: REPORTABILITY u00c

a. P,
n. P,
a. T,

w a, usr i y a n c-Je Aus insr : uu 'o 4 44 acto I

a. croucurY/ntP0aTAsuir octohawAnow

[d0renAsuTv acvicw accumen ( )unau 24 Nouns ( ) one (s c t.) I g I ) arronTAsts eca unaw law /PDhaT/uctust aug.N0uas h [ ] REPORTASUTY RCvtEW RE0udtCD ( ) NOT REPORTAsLE i MM

  1. 8T 8 "/8 " [

COWnOT5 e e Ns 5g NOTFICAT40NS j OATC/ Inst JT-J-ffff g,,, Qp,,,, DUTY PLANT WANACER ( ) N/A PERSON CONTACTED * [U 9-NitC RE5100:T W5P [ efM/A PERSON CONTACTED DATE/TadC pahALS g NAC OPS CCNTER ( M/A PERSON CONTACTED DATE/nWE pahALS CTHEA ( )N/A PERSON CONTACTED NM I* pahILS OATC/insC s,.rfs m & M L - f sl-w//s VD 0A,E/,,e C. REPORTASUTT REVIEW { ] REPORTABLE FEA WD4N (, ) NOT ACPORTABLE - l law /PERneT/UCENSC TmE: HOURS UCENSWO REPRESENTATivt DATE IL mRITTEN REPORT TO NRC TYPE DUC DATE ~ t PART 3: ACTION ASSIGNMENT CAc nCCicvc0 DATc Duc 07cf2 - EvCNT CODES EKn oEPARTw MT 0 8 P f O W (-ACnw /W657(6#77 #W ouc 4-3-TT l a 4 i DEPARhdCNT ACDON O b o'8-' W DUC N# I 0e0 ner M,/_ < m ,,, 2., o -t y/<w ocruttuCNr AC,0, t g PART 4: ACTIONS TO BE COMPLETED (R se/C p.a twy (R), wo. (C)) 1 I .2* t g PRioleTY DUE DATC APP. AUTH0fttTY OATE l 1 se r I. 4 t o N P20%IT DVE DATE - APP. AUTHORITY DATE I 2-s CAu. s CtosuRE APPROVAL AUTHORITY DATL CA/0C DAIC O CATE S/6 CLOSURE cac oatt ( ) CMDNUAtl0N SHEET ATTACMED j i I f

,a-WHITING CORPORATIQN TELEX: 25 3274 FAX-(312) 7850755 (312) 468-9400 e 15700 LATHROP. HARVEY,IL 60426 5198 March 2, 1994 VIA FA1: (512) 972-8298 HOUSTON LIGHT & POWER South Texas Project 8 Miles West of Wadsworth on FM 521 Wadsworth, Texas 77483 Joe Sheppard, Manager Nuclear Licensing Attention J. 11256 and 11257 Whiting Crane Serial Nos. Reference!

Dear Joe:

This letter is to inform you of a safety concern related to operation of the referenced crane (s). On a crane of similar design to yours, an analysis revealed significant overstress on bolted connection points of the trolley These overstressed conditions can result in main hoist components. Failure et the connection points could metal fatigue and failure. It cause a dropped load and components falling from the trolley. is very likely that your crane has the same condition. likely to result in personal Serious accidents of this type are injury or death to persons working in the area of the crane and cause significant property damage. Whiting Corporation, a Delaware corporation, has no direct responsibility for the design of equipment sold in 1983 or earlier We are, however, by Whiting Corporation, an Illinois corporation. obligated to info accordance with 10 CFR 21. Until the time that analysis and any necessary repairs can be made, we recommend that you discontinue use of the main hoist on the referenced crane (s) to avoid the risk of a failure as previousiv describeq. a Delaware corporation, is willing to assist Whiting Corporation,in repair of these trolleys by providing engineering, repair pa e ;L J =tri:2, 'M fiald cervice supervision at a reasonable coct. In most cases the trolley can ce repaired wrahcut a In addition, Whiting Corporation may be expenditure. significant in establishing a temporary derating for the crane able to assist capacity lower than originally specificd. i t.o a

4 WHITING CORRORATION J. Joe Sheppard March 2, 1994 Page At your earliest convenience please contact Mr. Mark Kwasny, Customer Service Manager, at (312) 468-9400, extension 4020 concerning specific repair requirements. Very truly yours, WHITING CORPORATION 'd; w William R. Guzaski Engineering Manager w 4 i WRC/ra

i I SPR SCREENING CRITERIA FOR START-UP ISSUES

'M NI8tilli:H _

L) b 5G7 Ylf.9 NO CRITERIA + [J [ Is the pr6blem described in the SPR needed to comply with the STP Technical-Specifications or other license commitments? [J [/ Do the consequences of not correctir,g the p.oblem affect the ability of a safety system to satisfy its design function? [J Do the consequences of not correcting the problem create or could creat.e a condition that jeopardizes the safe or reliable operation of the Units? [] (( Do the consequences of not cor. M ing the problem create or have the potential to. create a condition that will or could affect the . station's ability to effectively support, unit operation or nitigata emergency situations? g [] Does the problem descri$ed is the SPR %d J the reliability of.the system to per(orsr its design function? [] (( Is the problem described in the SPR coEsidered-to be a mode restraint? 1 (which node - 1[], 2 [J, 3 [ ], 4 [],, 5[ J ) e i If the answer to any of the above criteria is Yss, the problem described in the 6PR needs to be corrected prior to mode change.or unit start-up, unless ustification for deferral is p dad. COGNIZANT DEPT. M OPERATIONS CAG DATABASE UPDATED DATE 7" ~ e e -n-

Houston Lighting & Power Corupany mo omCE MEMORANDUM March 09, 1994 To Unit 2 Shift Supervisor ST-HS-HS-28111 File No.: Z23 I From S. E. Thomas subject OPERABILITY REVIEW POLAR CRANE - SPR 94-0567

References:

1) ST HS HS-28048, OPERABILITY REVIEW POLAR CRANE, Dated 3/4/94 2) PCF 157308A The previously issued operability review for the polar crane (Reference 1) allowed the use of the main hoist for 20 tons. In evaluating the polar crane's capacity to accommodate the reactor head lift, Whiting has recommended that some bolts be changed out on a gear box on the main hoist. PCF 157308A was issued on March 9,1994 to change out the bolts in Unit 2 as recommended by Whiting. Upon completion of the bolt change out per the referenced PCF, DED recommends that the main hoist on the Unit 2 polar crane be considered operable for up to 310 ton lifts based on recommendation from Whiting. Lifting for additionalloading is not recommended at this time. DED will be working with Whiting to obtain the full rated capacity. DED will also be working with the System Engineering Department, the Maintenance Department and Whiting to evaluate the configuration on the Unit 1 polar crane. Both these actions to obtain the full load rating and Unit 1 evaluation will be accomplished via Corrective Action (s) to SPR 940567. Should you have any questions, contact myself or R. L Engen at extension 7162 or 7337 respectively. RLE/hg ~ ATTACHMENT pc: T. H. Cloninger Unit 1 Shift Supervisor J. F. Groth J. P. Bleau 7 L W. Myers R. M. Attar,[,g O. L Parkey D. W. Stonestreet J. J. Sheppard RMS Correspondence H. H. Butterworth R. G. Asbury W. M. Dowdy

ocne,et. a:nva eviecopaer, , :- :- s t.

/
1 GAM ;

70f '5032* CCITT G31# 2 W WHITING CORPOWIATION 15700 LATHROR HARVEUt. 60426 5196

  • (312) 468 9400 FAX-(312) 7854755 e

TELEX: 25 3274 March 8, 1994 Houston Lighting & Power Company South Texas Project Generating Station P.O. Box 289 Wadsworth, TX 77483 Attention: Mr. Rob 5?ngen Manager Design Engineering Dept. (Fax. 512-972-8041)

Subject:

Reactor Building Polar Cranes (Units 1 & 2) S/N 11256 &13257 500/15 Ton capacity Built on Whiting Regn. 68918-30 (1976) Trolley bolted connections related to a 10 CFR Part 21 notification. Main Hoist Unit Replacement Bolts N

Dear Mr. Engen:

As requested, attached are a set of marked drawings (U-77587 & U75473) and copies of the pages in Whiting's Bill of Materials (BOM) (Regn. 68919, page 13 of 126, and Reqn. page 13 of 126) which identifies the Main Hoist Unit support bolts that were in question. HL&P's letter to Whiting (dated 3/8/94) states that an inspection on crans S/N 11256 (unit 2) discovered that at each of the four corners of the main hoist unit (gear box), one of the two bolts is marked as an A325 bolt and the other is not marked. This is contrary to what is specified in Whiting's BoM, which specifies all eight bolta' to be A325 (see attached BOM). Therefore, based on this informa' tion and the results of an engineering review, it'is recommended that for the scheduled lift of 310 Tons on 3/10/94, the two hoist unit support bolts in the l corner identified as #1' on the attached marke.1 drawing U-77587, be replaced with A325 bolts (3/4" diameter 2-1/2 or 2-3/4" long) on crane S/N 11256. Since these bolts are in tolerance holes, the replacement bolts must be tolerance bolts (see attachment L-2695-

1). When installing them, the bolte should be torqued to 200 to 230 foot-pounds. The bolts in the other three corners need not be replaced at this time, but they should be checked for tightness (200 to 230 foot-pounds cf torque for A325 bolts and 130 to 150 foot-pounds of torque for the unmarked bolts). In the future, the remaining unmarked bolts will need to be changed before using the main hoist for loads greater than 310 Tons.

l

SENT BV: xER0x Telecocier 70. 3-9-94 : 7:13AM ; 708i.05032* CCITT G3:# 3 i Also, before using the main hoist on crane s/N 11257 (unit 1) an inspection of the sheave nest bolts, bearing support bolts and the main hoist unit bolts (all previously identified) will need to be performed and the proper corrective action taken before using it to lift a load. This inspection and the expected corrective action should be similar to the action taken on crane S/N 11256. l l Sincerely, ~ We William A Horvath, P.E. Engineering Supervisor Engineering Analysis Group pc: R. Norby ^ M. Kwasny Guzaski/QA File .. Taggelaar

c. Skorpinski S. Pendrick/ Engr File E. Toretta (WSI)

M. hhite (WSI) file i l

i SENT BY: XEROX Telecopier M, 3-9-94 : 7*13AN : 7082..:5032-* CCITT G3:s 4 .e a 2 % in k, g, t. i i I j !,b 22:*.2rt.c

===' .s, _ r-m p = g A x N,N s n m v i . ig amt.I'm. j l ay m ( l -N f + gy J y l +s x (. \\ r w. a.a ,a y 4,. . I, [ . / D dNE,*~ ".

  • ~ ~ ' *
  • i."n\\7 a..s. oe =y _

i, a li W f (Lj $25.3.Siit*%%.t. "2 li ~ Jh 7 GkYh%.~.? w I i ^^" "*** \\,, 0 / r1 i, 1 t Offi". *;.W u m. }.'p; t +- .j i 1a. -..,u_u*.T?d.,-.. y pi l/, l M/M,y ~+!.**t ,J c:% -{

'4"t l

l m / .,y

..?

I s .d-21U*A'Ali,' t i/q'

==/ i. -- e.. , u rf'q gr&e.p.. t m rme-- - l l=- p!fr + ar.. u ,V. d._= g / Tw i T -"-a = f r.. G_%r"s V:. -- v. %. n q...,n - l w-ah a L , i &.r - \\ p --:-., s$ W z i ,w. L.w = n.. M y : ii,ef 7 3 ,,, ~.-. w- ~ "" M .l '.. g ]

p +4 t

og, 3,. m n - 7 n t i .s @$'b$j$.. lM " M'Y* 1 I p a:,r e - .i f ~ ) WM t W _., luris

sl [

f i @@ $'gg,$,,8,, 132Rt. t p';L/ 2 V l~ l !!ll%rT.bM @ h .h j ra 3-g a[._ _ '3,31". M 1 ~ c, 'i_ - T * * ". -.ea,=mse.. m ;. \\ ~ d2GRemaarsevmuam ,o d WHiflNG CotPotAfl0N gif. b "" " ? **

  • T( ' g N'9 P. 7; W*2" mar ans i

4... .t - o *w. = r

m. =.-

an e m m. n i .tr.. - e ro.,- +-. ym::u r

  1. r- - _ _

.<i w,, ~,.

  • A.~.=.~m.

aO.~g/**** "'** *" ##" 4 e v.., w a ws,w mo ~ ma view t . g~gg, .vc:,~ f*= m w iu.v, SC::'3 1 r 2. < s * - s.sj " "y ) '* Q yy;*,g', p*,'y A ** ***

  • r l

1)77587 7 u,..w~,. _, I f

m,, g., 3 .. t m. o - 1 O-..,yg ~,* + r=w'm,b,,,,:m e.L p'em e an -Q e- -- P,-T c 2_- .: y-r, a. n r2 :. .., Ti.., u,,__ m i M ua.',t s t : a'ers; \\ s + t h.a:n.w~ 4 's m*;'A% gi \\- I' adA / wur-y r-s w N u.' _ \\ p m. p.,c \\ ~~- e e A 4 ! i o L si v 99 gl ; I g l i t i f d i l T? f 1 ..I t l 'r i l' r T,[ + t-A \\ l a Wili M 'd / N wan t..Q P-i p p i t li p-i. pt ,1m -l gy, !,'I. L i c ; ... c.~, a. , P 6-4. Imme. r .t I djl! $w3 n~ ~ n ,I 3 a -J \\ t j y/a = im p ry...,

  • ~

1I .d ik mw II 9l NEL.._ [ _!. # !aikn.rL, t I,/,r* s ~' q w g .~ i.-- i.h F .i m l 4.^ ~^< *I% $ 'f M Q,-*j i m. = i y a L s ht-s

5) m M)h

+-b, . e L. ~~ m-u v!e_ Q. t \\.NLl y T..[ +. M S [N

n e %d

,di_ i s N L i ~ . i. 1. .k. .1.- x_ I 1a r..s N 4.~ m <. a 'N %.i /.L \\ \\ W~ // \\\\ ,..e,e %... _.. =,..,w.. =.<,..=. m.-. ~~,.m-.m...,..-] ' t. _ r Y + M S, ph an .-- u ~ ~ 5 -a ai

  • 4(= = i ' *)

TM ll3",',A*",. H M - ?759 7 co u r,

t. z. u n t L....-

T -.. : v s. u. :, s,.. a. u.w.., - w., u e c., n, _en n ;

SENT BY' XEROX Telecopier 1017; 3-9-9t ; 7:15AM ; 7082105032* CCITT G3:# 6 """ 7' 1 _,,84 Sweu os pe.s'A 5fo4 *n me a.. Is'F* ~ M.e4 e 2 ,se. e. l 88 ,,, _._ _ '88 C - shan,ses.* q g g, 5 g 8 8 = -. ; e.,ge... m 4 8 %e4,a5 se.ungg .-ga ,%q _s e paensus oms. asses a e N WY884"WB.W' Ige

  • * (.ggg,

,1 St._ -._-- GWas uhe.pett,mpt 516694_ i j I fE. M 'TeW45 ) 9 1

    • ma uus,,, ass.

e, + ()+ 4 isos eu,su uus, assie TG ~/ .i-a q]

' +

) - s[ 44 4 6 $$6. M gg.eyt 8 F,, is --i-. esen .,AC m e e omaan sua p 89 3 h 9EE. 415Temees m.ff. ..Al t e a caen e.s.ges snur .E

  1. 1 4

nameses ses., ras.ats.een / ,de P f .N 4 emet-w (M2:N e s. I g( l-ggg 40 4 %d tbempeast saw ( 64 te a mes.4ms.anet t a.sm gerg] ~ 1/3 g 5 e es _u.s - m.a .y - +. -m-1 f vs ea musum=* inn we unee's Jj l C Hot W H Te v = ~ --- - w a.a s o.**'a .iri= -1 i j i

e. 4 s.., a. wx.:,.--

j ygat g2 fa ei.. a.u. n a. i e l \\ \\ x- \\g p Q+---. j g. s. ui. A 12 C' 00e.T ,. w u ne. ua u n.m. a --k .t..: _.t.t'- WorH Hoy'910 a i 1 a<< w,e m w r ,a m Fa.n r Wngsp. \\g. n us v wa ~~ >.=> s n

s. w w, S.,..c u, n...

i (#A k / 2 y'd )s +I + l \\ T. e i t... me ng w. x \\ -rie. is e .= ~.. u_ m. m,. % e3* 13I'*H P=7 L * '.> - - - "M } !.l e, m i u m.v - i c.W* - um.t,4. u. " a, rw. n,.. i r em -., - -.. y ; \\\\ \\ r w 1 secci .s w,,,; w

aa

- 5 e i \\. \\ 2 i y*./ h@- 3 c.

e.,4

> Cg l i' e see U n a

  • '* W.".

I 3 " e so.e I' f.... l 'W /g h i 'Y rmu Pts ~,' 4 w 2. .a P' s }f - f -_i., n it *- a <.w 5 4 r I. d .. I" v. 96 "TY8picAL StefW::m[ WO *E - 2:, I. pos c=.r.. o~ c o.a .1 j f* *kU$ bum.w$a " [ C @ Me!L5%, m.M ~ ~m

  • '*.;~Y g 't roa. u:,o ann coasD.ncGss<. s n.ph, <

5 p m ~ .g 3 - 3, derrf. 'C *= ' M ' 7 ". J '4 7 % * ? -O", s s et - s,s

r. =.5. ii!m.=rs Ld

-1 y':.'lQ"w.,sMiEi'WHilW.Mll:hT-- / $;rof

  • s.. A*

' A. .1, WHITlHQ CORPORATIO fn u '/ an'=" - a'a t t 3y= 1,",yb 3 c:W v. 2Mir' = .s ,G ,u g.m. n .-n m ./ / x Asamos w M.t w o"& sgW ,x g 5 #' w..,. ,N. a ,a G. -...' gQ%%*** 'ad***s

  • m= v n * **

M

  • h ^'"**" '

W ~F Q V....:thbCO'W U~"A ' N mr 1.~ +.. p'htM';f D 75473.(M I[' Y $ [. %%.M, u. d* 4 f t.. 2a

s. : _

i ,.. m an+r-.x.m.m, ~~ /

SENT B7: XEROX Telesopier 7

3-9-94 : 7:15AM ;

70. J5032* CCITT G3:# 7 1 m,


y,

  • Me -i. - d~

.,L3' r p nu s,uin a,a a_ I,=== mm m, W mmt-os yog ~~ s ,s. +a-~ ' ' ' '. '. O 6 ~ nna .,r e. ~ e n p f %) j . y, v se es

  1. 2 IM e'

gk D4. 3 a.o = ?,, , c ' W-RIN + 4 l N ).pl:, i ./, Jx ix .y m (v NN f s_ / s u z,: ll N \\ N. s e ~ 4 L4 4 < /. i l

    • /

l P ] l _ (* u.vm \\ N g-d h { f 3 6 NWN.i f /l /

  • /

i t Y } I h)l i' 'd ^ f / ,.) rA l // i s I //_ \\ ),,..;, I g\\\\\\ \\ I _ y \\ 'I L* * **n j..**'. . _\\.... \\. (10 Q g. = OPTW 'A i se 2 q* g ,/ i Jk db Jh JL I J m m 4,4 f'+4

=

x) vi w + ( +y ~ i, ,g j \\ N. / } {. , w y, 4 g .u - ( -i i 7 ,g p Ms g bi 6.' g'.,.., f-f 3 Co y 7~ W"Y * ? ' ? ' '). '~

SENT BY: XEROX Telec: ': 3-9-94 ; 7:16AM : 70s.05032-* CCITT G3*at 9 Wier*4 -.~

.p.;

[.- WHITING C0kPD. RATIO nigr urum(5 ?*', 35-1197-8013 BROWN-R0OT INC.s - HOU570N,. , -,,$, A. .ust.' m A5 PROJECT -, R BM ,__,,.I/ZU/7 //3 $*y Mu.r' 1 c:,w _ ,,n. _ gays.a. ~ .. a L - 500/15 TON 5 MOTOR TROLLEY zo'-0 C C i

  • AOOC U775 8 7-3 e U 7 758 8-2 DUP MATL 3EE REQN '68919 eGA LEVEL 1 4AM*dG NL'M4EA O TY.

D4 8C AiPT1ON S0WACg Co e' I !#25 FC MAIN HOIST UNIT CONTD NAA. &*7/'4 7 7 i 1l 1 ICAS E FC 25 HOIST DR SUS-ASSEM $73943 1 50979 /O :,

  • l_I 8!3/4 X 2-1/2 A325 HS SOLT T

l 29931 ! MI i t 3li 8 !)/4 HARDENED WASHER 5 l ~I g,. ~1 4:. 8!3/4 FLEX-LOC NUT 830FA1210 0 l 16 -- T lt l l i i I't% Itse

2. 3 ou u-75y'77 t

t' j l . :.,ih$&,.; -k's' -q ( I; w. .i g sw 4 : .mt.;k%k,p:sg...,jgpAn;, v,. ,.u.v .:.];~. jy;,. m:gpgg _ pt9p l 4 1 i i t 1 l g. ,r. - i \\ is, .. q.t;- .: V. i' l-j e 5,,. t;g. g - - p,.'.. f l 7% hn'- 3%%ffe%.'.hij ' s l

i. c... - l

% :u ..,..a

sigg gh ;gg% % 4-l 4

i l: { ~ ...., ;g. - lftsRN.T. = l

. 3

L

e. '
  • ;~

.' *'hkO*,'. h 5Y.kh, -Qk.. Rkh i .l . r qqqgMy13 v .g. 12.- MV$945 l l

u. :

wepprW- ! D. 2 7,.: p e u m w w.. a.o-m.a .a =..- ., :+ M cr.aws.vas. .mit., = .nn-as .ac> J cowtaact. L ero.a o. roace evauctu=AL ivi~- -'*a + ,p.. e. v.e.

i SENI BY: Xt:HUX lelecopier 7C 3-9-94 ; 7:17AM ! 7081 J032-CCITT G3;#10 WHITING CORPORATION -- F 4 S T E E R S ENGINEERING STANDAR08 - T XEADen DJ M : VALOUR T! i I ll A lNOTh 3l h A NOTE 4} K SEE NOTE 3 - - l NOTE 71 -. +~ 3 g ._ p .A l III .. g e ...........7 'Q r men + (AEF) 30' t ^; set arr so - Le I _,,,,7,,, L ~ [ f ( l I t it 81 3 J t!3l' ~ r!N' eh!!st ggy, Ett I!: In lit lu 31a las lit 8at fit hals In ha l 3{E [.l8lf.jfl C lfi 0.158 1.8 9 n.f tt f.2"! l or ' l' l1 .t t .-o 1 .t t.o.! e.F j.u

!'.:"<?

'11 ':.1 ' :l?

r'

?

.d
,
n, l

>.m 1.m i,$ i:

+

<.t 1 1,la

.la.

e.u i,i nt 1 1.100 1.111 1.Ill 1,515 1,1)) 1,138 g,gt; g.ggj g,gs) g, ggt 1,tg g,31 g,ggg t g lealsel $134 1/2 5/8 J/4to1 11.08 (J,11 ea,M-~ to 8 lael -i.12 .L,1; .j,u 01stt +. Il 48,98 11, l l.16 1. POINT i Point shall be chamfered or rounded at manufacturer ~a option. (NATERIAL Q ASTM A325 or A490 ggh As bpeo led All dimensione are in inches. ! For General Requiremente and Notes see L2696 'i HEAVY HEX STRUCTURAL BOLTS WITH RESTRICTED BODY TOLERANCEL-2695-1

"9 =^ m m Hwston Lighting & Power Coi..p:ny OFTICE MEMORANDUM March 10, 1994 To Unit I and Unit 2 Shift Supervisors FILE NO. M13.04 ST-HS-HS-028119 from S. E. Thomas subject REPORTABILITY REVIEW POLAR CRANE - SPR 94-0567

References:

1) SPR 940567 Operability Review; ST-HS-HS-28048 Dated March 4, 1994 and ST-HS-HS-28111 dated March 9,1994 2) ST-HS-WG-00002; Letter to Whiting Documenting the Unit 2 Polar Crane Inspecdon.Results 3) OPGP03-ZA-0069 - Heavy Loads Promdure Station Problem Report 940567 was written on 3/3/94 to document a 10CFR part 21 repon written by Whiting Corp. on the polar crane. Whiting's report to STP stated; "On a crane of similar design to yours, an analysis revealed significant overstress on bolted connection points of the trolley main hoist components. These overstressed conditions can result in metal fatigue and failure. Failure at the connection points could cause a dropped load and components falling from the trolley. It is very likely that your crane has the same condition." Whiting later clarified the areas of concern on the cranes supplied to STP as being: connection of the output shaft of the main hoist gear box to the bearing pedestal (or bearing pedestal bolts), connection of the main hoist gear box, upper sheave nest girder connections, and bearing cap studs. Based on inspection of the Unit 2 polar crane (Reference 2), Whiting has evaluated the stresses on the polar crane for the specific configuration at STP. Whiting's evaluation shows that for loads applied during constmetion, some of the connections may have been overstressed above the allowable stresses. However, none of the stresses exceeded the yield strength for the connections / bolts. Whiting has also determined that none of the connections were overstressed for the loads applied since the plant has been in operation. The maximum load which occurs during plant operation is 310 tons (Reference 3, Addendum 1). Accordingly, there is no concem with metal fatigue or loads applied during plant operatio'n. The Unit I polar crane has one connection on the bearing pedestal which is different than Unit 2. This connection may be overstressed during the plant operation lifts but these stresses would not exceed yield. This connection is not considered a problem since the polar crane has been tested during construction for loads significantly higher than the operational loads and the connection does not show any visible signs of distress or loose bolts. I

i ST-HS-HS-028119 Therefore, this condition has been evaluated against, but not reportable, under the requirements of 10CFR50.73 (aX2Xii, y, & vi) in that there is no evidence to demonstrate that this condition is outside of the design basis of the plant. If you have any questions regarding this reportability review, please contact R. M. Attar or R. Engen at site extension 8155 or 7337 respectively. 1 AL-3/loAq. , Nuc'I Licensing Concurrence 'Date RLFJ pc: T. H. Cloninger R. G. Asbury J. F. Groth J. P. Bleau L. W. Myers R. M. Attargd G. L. Parkey D. W. Stonestreet H. H. Butterwonh J. J. Sheppard W. M. Dowdy RMS Correspondence A. W. Harrison i - \\}}