Submits Addl Items Found Not to Meet Criteria of Position 7 of Suppl 1 to NRC Bulletin 88-010 Re Nonconforming Molded Case Circuit Breakers.Current Status of Four Breakers Not Meeting Criteria Discussed
ML17347B412
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 11/07/1989
From: Goldberg J
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-88-010, IEB-88-10, L-89-394, NUDOCS 8911150250
Download: ML17347B412 (4)


Text

ACCELERATED D'RIBUTION DEMONSATION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR: 8911150250 DOC. DATE: 89/11/07 NOTARIZED: YES DOCKET g FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH. NAME AUTHOR AFFILIATION GOLDBERG,J.H. Florida Power & Light 'Co.

RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Provides addi items found not to meet criteria of position 7 of Suppl 1 to NRC Bulletin 88-010.

DISTRIBUTION CODE:. IE21D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: Bulletin Response 88-10 Nonconforming Molded JCase Circuit Brea ers.

NOTES:

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-2 LA 1 0 PD2-2 PD 1 1 EDISON,G 1 1 INTERNAL: AEOD/DOA 1 1 AEOD/DS P/TPAB 1 1 NRR DOEA/GCB 11 1 1 NRR GILL,A.S. 1 - 1 NRR GUILLEN,J 1 1 NRR POTAPOUSiU 1 1 NRR STONE,J.C. 1 1 NRR/DEST/ADS 7E 1 1 NRR/DEST/MEB 9H ' 1 NRR/DOEA/EAB 11 1 1 NRR/DOEA/GCB 11 1 1 NRR/DREP/EPB 10 1 1 LRB12 1 1 NUDOCS-ABSTRACT 1 1 REG 02 1 1 RES/DSIR/EIB 1 1 GN2 FILE 01 1 1 EXTERNAL'PDR 1 1 NRC PDR 1 1 NSIC 1 1 NOTE TO ALL "RIDS" RECIPIENTS PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED: LTTR 23 ENCL 22

0:

P.O. Box14000,Juno Beach, FL 33408 0420 NOVEMBER 0 7 19B9 L-89-394 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

,Gentlemen:

Re: Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 NRC Bulletin No. 88-10 NONCONFORMING MOLDED-CASE CIRCUIT BREAKERS NRC Bulletin No. 88-10, "Nonconforming Molded-Case Circuit Breakers," issued November 22, 1988, requested that licensees take actions to provide reasonable assurance that molded-case 'circuit breakers (CBs), including CBs issued with motor controllers, purchased for use in safety-related applications without verifiable traceability to the CB manufacturer perform their safety function.

Florida Power 6 Light Company provided a response to that bulletin for Turkey Point Units 3 and 4 by letter (FPL letter No. L-89-119) dated April 3, 1989.

On August 3,-1989 the NRC issued Supplement 1 to NRC Bulletin 88-

10. This supplement provided specific examples of common deficiencies identified by the NRC during their preliminary review of responses to the bull'etin. In addition, it NRC position on issues that were not specifically addressed by the also provided the bulletin.

FPL has reviewed its April 3, 1989 submittal in accordance with NRC Bulletin 88-10, Supplement 1. Based on additional investigation with suppliers, the following additional items were found not to meet the criteria of position 7 of Supplement 1 to NRC Bulletin 88-10.

Number Item Purchase Order ~su lier Model Q0230 488655-90064 Atlas Electric Square D Turkey Point 1111 West 22nd Street circuit breakers Hialeah, FL 33010 89ill50250 89ii07' PDR ADOCK 0 000 9 PDC an FPl Group compai,1

L-89-394 Page 2 The above breakers were traced from the supplier (Atlas Electric to Electrical Supplies, Inc. (ESI), Miami, FL (ESI invoice No.

235563 dated January 8, 1988). Efforts to trace ESI's documentation to the original manufacturer have not been successful.

The current status of these four breakers is as follows. One breaker is in use in a nonsafety-related application. One breaker is in stores and its use has been restricted. The location of the other two breakers has not been determined. FPL is continuing its efforts to locate these breakers, and will provide an update to this response by December 7, 1989.

This information supplements that provided in our April 3, 1989 response. The other actions required by the original bulletin will be completed as previously stated in our April 3, 1989 submittal.

Should you have any questions, please contact us.

Very truly yours, J. H. Goldberg )

Executive Vice President JHG/TCG/gmp CC'tewart USNRC D. Ebneter, Regional Administrator, Region II, Senior Resident Inspector, USNRC, Turkey Point Plant

STATE OF FLORIDA ')

)

COUNTY OF PALM BEACH ) ss'.

J. Acosta being first duly sworn, deposes and says:

That he is an Acting Vice President Nuclear Energy, of Florida Power and Light Company, the Licensee herein; That he has executed the foregoing docum'ent; that the statements made in this document are true and correct to the best of his knowledge, information and belief, and that he is authorized to execute the document on behalf of said Licensee.

R. J. Acosta Subscribed and sworn to before day of Wo~~ ~, me this 19~8 NOTARY PUBL..C, in and for the County of Palm Beach, State of Florida hGiSRY Pl. .C lATc GF'LOP 04 My Commission expires h! CON"IE.".kC!! Elf'. OCE.30 144