LR-N13-0021, Inservice Inspection Activities - 90-Day Report

From kanterella
Jump to navigation Jump to search
Inservice Inspection Activities - 90-Day Report
ML13039A335
Person / Time
Site: Salem PSEG icon.png
Issue date: 02/01/2013
From: Fricker C
Public Service Enterprise Group
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
LR-N13-0021
Download: ML13039A335 (5)


Text

PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, NJ 08038-0236 Ol>SE(i Nuclear LLC FEB 01 2013 AS:ME Code Case N-532-4 LR-NB-0021 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-001 Salem Nuclear Generating Station Unit 2 Renewed Facility Operating License No. DPR-75 NRC Docket No. 50-31 1

Subject:

Inservice Inspection Activities Day Report This letter submits the Owner's Activity Report for Inservice Inspection (ISI) activities conducted at the Salem Generating Station Unit 2 during the ninteenth refueling outage. This report is submitted in accordance with Code Case N-532A "Repair/Replacement Activity Documentation Requirements and In-service Summary Report Preparation and Submission Section XI, Division l," and within its ninety (90) day reporting requirement. to this letter contains the required Salem Unit 2 Owner's Activity Report. There are no commitments contained in this letter.

Should you have any questions regarding this submittal, please contact C.M. Dahms at (856) 339-5456.

Si" ?) )

0(

Carl J. Fncker

-N12.. (, ;:pz.Jt:145p_

Site Vice President - Salem Enclosures (1)

P'EB 01 2013 Document Control Desk Page2 LR-NB-0021 C Mr. W. Dean, Administrator, Region I, NRC Mr. l Hughey, Project Manager, NRC Ms. E. Bonney, NRC Senior Resident Inspector, Salem

.iVIr. P. Mulligan, Manager IV, NJBNE Mr. L. Marabella, Corporate Commitment Tracking Coordinator Mr. T. Cachaza, Salem Commitment Tracking Coordinator Mr. Milton Washington, Chieflnspector- Occupational Safety and Health Bureau of Boiler and Pressure Vessel Compliance

Document Control Desk LR-N1 3-0021 Salen1 Unit 2 Owners Activity Report - S2R19 In Accordance With ASME Section XI Code Case N-532-4

FORI"1 OAR-1 OWNER'S ACTIVITY REPORT Report Number S2RF019 O wner PSEG Nuclear LLC, PO Box 236, Hancocks Bridge, NJ 08038 Plant Salem Ge11erating Station Unit No. 2 Commercial Service Date Oct. 13, 1981 Refueling Outage No. 19 Current Inspection Interval lSI - Third (3rd) {Containment IWE/IWI, - Second (2n d)}

Current Inspection Perio d !SI-Third (31'd) {Containment IWE/IWL - First (1'}

Edition and Addenda of Section XI Applicable ISI - 1998 Edition - 2000 Alldend a to the inspection plan CJSI - (IWE/IWL) - 2004 Edition Date and revision of inspection plan ISI - July 2012, Revision 2 {CISI - October 2010, Revision O}

Co de Cases used N-460, N-498-4, N-532-4, N-533-1, N-706, N-722-1 and N-731 CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests n1eet the Inspection Plan as required by the ASME Code,Section XI; and (c) the repair/replacement activities and evaluations supportin the completion of S 1RF02 l conform to t requirements of Section XI.

Signed EdleyT.Giles/ISIPro ramManager 01/11.J/13 Owner or Owner's Designee, Title Date CERTIFICATE OF INSERVICE INSPECTION I, th e undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of New Jersey and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the items described in this Owner's Activity Report, during the period May 8, 2011 to November 8, 2012, and state that, to the best of my knowledge and belief: the Owner has performed all activities represented by this report in accordance with the requirements of Section XL By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described in llris report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. <""

Ro:'..':'. s..:...

s Goodwin!!._ ___t,l:fi::_f.:f]--Commissions NB 14086 A,N,I NJ955 Inspector's Signature National Board, State, Province, and Endorsements FORM OA.R 1 OWNER'S ACTIVITY REPORT TABLE1 ITEMS WITH FLAWS OR RELEVA_NT CONDITIONS THAT REQUIRED EVALUATION FOR CONTINUED SERVICE Exam Item ItemDescdption Evaluation Desi:.'.t'iption Category Number NIA N/A None N/A TABLE2 ABSTRACT OF REPAIR/REPLACEMENT ACTITIES REQUIRED FOR CONTINUED SERVICE Code Item Description Description of Work Date Repair/

Class Completed Replacement PlanNumbet' 3/8" tubing leak downstream Replaced 3/S" SS tubing and fittings 07/11/2012 60104374 3 22SW234 3/8" tubing leak downstream Replaced 3/8" SS tubing 09/18/2012 60105576 3 of22SW235 1" weld leak Up$tream of l" AL6XN elbow to flange butt weld 2SW310 on 90° elbow to excavated and re-welded 08/30/2012 60105108 3 flange bi1tt weld 3/8" tubing leak downstream Replaced 3/8" SS tubing and fittings 11/14/2012 60106944 3 of2SW186 3/8" tubing to tee weld leak Replaced 3/8" SS tubing and fitl'ings downstream of2RC3 11/14/2012 60106394 2

3/8" tubing leak downstream R(lplaced 3/8" SS tu.bing and fittings 60107143 11/20/2012 2 of22BF24 2 -