BSEP-88-0854, Special Rept 1-SR-88-001:limiting Condition for Operation (LCO) Established on 880405 for Fire Protection Deluge Valve 1-FP-DV-22 to Sprinkler Sys.Specified 14-day Time Frame of LCO Exceeded on 880419.Fire Watches Remain in Effect

From kanterella
(Redirected from BSEP-88-0854)
Jump to navigation Jump to search
Special Rept 1-SR-88-001:limiting Condition for Operation (LCO) Established on 880405 for Fire Protection Deluge Valve 1-FP-DV-22 to Sprinkler Sys.Specified 14-day Time Frame of LCO Exceeded on 880419.Fire Watches Remain in Effect
ML20153H094
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 09/01/1988
From: Harness J
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
1-SR-88-001, 1-SR-88-1, BSEP-88-0854, BSEP-88-854, NUDOCS 8809090083
Download: ML20153H094 (1)


Text

. _ _ _ _

. ao CD&L Carolina Power & Ught Company Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 September 1, 1988 FILE: B09-13510C SERIAL: BSEP/88 0854 U.S. Nudlear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT UNITS 1 AND 2 DOCKET NOS, 50 325 AND 50-324 LICENSE NOS. DPR-71 AND DPR-62 FOLLOV-UP TO SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.7.2 AND PURSUANT TO TECHNICAL SPECIFICATION 6.9.2 (1-SR-88-001)

Gentlemen:

During Unit 1 power operation concurrent with the Unit 2 1988 refueling / main-tenance outage, a limiting condition for operation (LCO) was established on April 5, 1988, for fire protection deluge valve 1-FP-DV-22 to the sprinkler system of the units' common Service Water Building. This was done to permit isolation of the valve for repair of a leak involving the valve clappper latch seat ring. Due to a temporary unavailability of qualified replacement parts, the specified 14-day time frame of the LCO was exceeded on April 19, 1988.

Replacement parts to repair the valve are on-site and presently awaiting an  ;

Engineering evaluation prior to acceptance. It is expected required repairs and return of the valve to service will be accomplished during the upcoming Unit i refueling / maintenance outage, scheduled to commence on November 12, 1988.

Until completion of the required repairs and return of the valve to service, the subject LCO, with appropriate fire watches and backup fire suppression equipment, will remain in effect.

Very truly yours, Q%~

(J. L. Harness, General Manager Brunswick Steam Electric Plant MJP/byc Encleaure cc: Mr. B. C. Buckley Dr. J. N. Grace i BSEP NRC Resident Office  !

ss09090093 880901 SE DR ADOCK0500fy4