BSEP-91-0020, Special Rept 1-SR-90-005:on 901130,Zone 1 of Svc Water Bldg Fire Detection Sys Declared Inoperable Due to Spurious Alarms on Main Control Room Annunicator.Caused by Defective Pull Station.Fire Detection Panel Replaced

From kanterella
Jump to navigation Jump to search
Special Rept 1-SR-90-005:on 901130,Zone 1 of Svc Water Bldg Fire Detection Sys Declared Inoperable Due to Spurious Alarms on Main Control Room Annunicator.Caused by Defective Pull Station.Fire Detection Panel Replaced
ML20066D567
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 01/10/1991
From: Harness J
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
1-SR-90-005, BSEP-91-0020, NUDOCS 9101150186
Download: ML20066D567 (1)


Text

"

i I.?

sii y ,

d!I

.. ~

Carolina Power & Light Company l BrunswIbKNucleae~i~fo3EE P. O. Box 10429 Southport, N.O. 28461 0429 =

January 10,1991 m

FILE:

SERIAL:

B09 13510C 3 g

BSEP/91-0020 U.S. Nuclear Regulatory Commission $

ATTN: Document Control Desk  !

Washington, D. C. 20555 [.

BkUNSVICK STEAM ELECTRIC PLANT UNIT 1 DOCKET NO. 50 325 --

LICENSE NO DPR-71 '

SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.3.5.7 AND PURSUANT TO TCCHNICAL SPECIFICATION 6.9.2 (1-SR-90 005) m-Centlemen: M During Unit 2 power operation concurrent. with tLe Unit 1 Refuel 7 and Maintenance Outage, Zone 1 of the Service Water Building Fire Detection System was declared I inoperable (annunciator pulled) on November 30, 1990. This limiting condition for .

operation (LCO) was established due to spurious alarms on the Main Control Room annunciator. The 14-day time frame of the subject LCO was exceeded on December 14,1990.

A Vork Request / Job Order (VR/J0) was initiated on September 20, 1990 to replace al a defective pull station which was suspected of causing the alarms; however, was d interrupted due, to problems in obtaining correct replacement parts. A Procurement j Amendment, Reorder, and Turnover Sheet (P,A.R.T.S) was submitted to order a replacement pull station. During the interim, further investigation identified E

=

a defective Fire Detection Panel which is believed to be the cause of the 4 problem. The panel has been replaced, the system returned to service, and is ]

being monitored to ensure the spurious afarm problem has been corrected, Firewatches remained in place until the Service Water Building Fire Detection (j System was returned to service, a h

Very truly yours, 3 o

J. L. Harness, General Manager J Brunswick Nuclear Project j