BSEP-84-0271, Ro:On 840103,diesel Driven Fire Pump Inoperable.Cause Due to Unavailability of Replacement Parts Allowing 7-day Time Frame to Be Exceeded.Starter Motor Repaired & Diesel Fire Pump Returned to Svc on 840124

From kanterella
Jump to navigation Jump to search
Ro:On 840103,diesel Driven Fire Pump Inoperable.Cause Due to Unavailability of Replacement Parts Allowing 7-day Time Frame to Be Exceeded.Starter Motor Repaired & Diesel Fire Pump Returned to Svc on 840124
ML20080K247
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 02/09/1984
From: Dietz C
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
BSEP-84-0271, BSEP-84-271, NUDOCS 8402150344
Download: ML20080K247 (1)


Text

,. _ .-

CP&L g g glingw...er,a Ught company...y..........._.

Brynswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 February 9, 1984 TILE: B09-13510C' SERIAL: BSEP/84'-0271 Mr. James P. O'Reilly, Administrator U. S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W.

Atlanta, GA -30303 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 DOCKET NO. 50-324 LICENSE NO. DPR-62 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.7.1

,AND PURSUANT TO TECHNICAL SPECIFICATION 6.9.2 (2-SR-84-1]

Dear Mr. O'Reilly:

On January 3, 1984, while performing the weekly operability test of the Fire Suppression Water System, PT-35.1, the diesel driven fire pump was rendered inoperable due to the failure of the diesel starter motor solenoid. Due to an

' unavailability of replacement parts needed to repair-the starter motor, the seven-day time frame of the involved LCO on the diesel driven fire pump was exceeded. The needed replacement parts, which were evaluated by plant Engineering as acceptable in meeting the Fire Protection Q-list criteria, were obt'ained and on January 24, 1984, the diesci fire pump was returned to service.

Very truly yours,

'Y C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/dgr/MSCGC1 cc: Mr. R. C. DeYoung hPC Document Control Desk OFFICIAL CCPY QEE ,