05000336/LER-1997-003, Corrected Page One to LER 97-003-01:on 961216,discovered Discrepancy in Plant Procedure Utilized to Perform Periodic Insp of Fire Protection Sys Smoke Detectors.Caused by Failure to Properly Incorporate Ts.Ts Partially Revised

From kanterella
(Redirected from 05000336/LER-1997-003)
Jump to navigation Jump to search
Corrected Page One to LER 97-003-01:on 961216,discovered Discrepancy in Plant Procedure Utilized to Perform Periodic Insp of Fire Protection Sys Smoke Detectors.Caused by Failure to Properly Incorporate Ts.Ts Partially Revised
ML20137Y710
Person / Time
Site: Millstone Dominion icon.png
Issue date: 04/15/1997
From: Joshi R
NORTHEAST NUCLEAR ENERGY CO.
To:
Shared Package
ML20137Y667 List:
References
LER-97-003-ERR, LER-97-3-ERR, NUDOCS 9704230188
Download: ML20137Y710 (1)


LER-2097-003, Corrected Page One to LER 97-003-01:on 961216,discovered Discrepancy in Plant Procedure Utilized to Perform Periodic Insp of Fire Protection Sys Smoke Detectors.Caused by Failure to Properly Incorporate Ts.Ts Partially Revised
Event date:
Report date:
3362097003R00 - NRC Website

text

_. _ .._m _ __. .. _ _ _ . - .. . . ~m . _ _ _ _ _ _ _ .m. _ _ _

l I

.'NRC FORM 366 U.s. NUCLEAR REGULATORY Commission APPROYED BY OMB NO. 3160-0104 EXPtRES 04/30/98 LICENSEE EVENT REPORT (LER) woe'E U Mr"la" E M O s*""iUn"# E E t'A"No^LM'P."P"^'!%3i, 'E!@~"14"%7ffs'io 5

^WI (See reverse for required number of E"u? Er'fa""n'sSEa'r*oSv"$Es"sfo*u?w"a'sfisSETc digits / Characters for each block) owc' EAuiSelrElloEsY UfsEr*oE!NE'3P" FACILITY NAME (13 DOCKET NUMBER (2) PAGE (3) l Millstone Nuclear Power Station Unit 2 05000336 1OF4 TITLE m HistoricalTechnical Specification Noncompliance of Plant Surveillance Procedure Used to Perform Periodic inspection of Fire Protection System Smoke Detectors EVENT DATE (5) LER NUMBER (6) REPORT DATE (7) oTHER FACILITIES INVOLVED (8)

MONTH oAY YEAR YEAR sE ^L " N MONTH DAY YEAR NU NU R 12 16 96 97 -- 003 -- 01 04 15 97 OPERATING THIS REPORT IS SUBMITTED PURSUANT To THE REQUIREMENTS oF 10 CFR 1: (Check one or more) (11)

MODE (9) 5 20.2201(b) 20.2203(a)(2)(v) X 50.73(a)(2)D) 50.73(a)(2)(viii)

POWER 20.2203(a)(1) 20.2203(a)(3)D) 50.73(a)(2)Di) 50.73(a)(2)(x)

LEVEL (10) 000 20.2203(aH2>0) 20.2203(a)(3)(ii) 50.73(a)(2)0ii) 73.71 20.2203(a)(2)Di) 20.2203(a)(4) 50.73(a)(2)0v) oTHER 20.2203(aH2)Dii) 50.36(c)(1) 50.73(a)(2)(v) specify in Abstract below 20.2203(a)(2)Uv) 50.36(c)(2) 50.73(a)(2)(vii) in NRC Form 366A LICENSEE CONTACT FoR THIS LER (12)

NAME TELEPHONE NUMBER pnclude Area Codel R. G. Joshi, MP2 Nuclear Licensing (860)440-2080 COMPLETE ONE LINE FoR EACH COMPONENT FAILURE DESCRIBED IN THis REPORT (13)

CAUSE SYSTEM COMPONENT MANUFACTURER CAUSE SYSTEM COMPONENT MANUFACTURER O PRDS O PRDS sVPPLEMENTAL REPORT EXPECTED (14) EXPECTED MONTH DAY YEAR YES SuBMISsloN (If yes, complete EXPECTED submission DAT E). X No DATE (15)

ABSTRACT (Limit to 1400 spaces,i.e., approximately 15 single-spacedtypewnttentines) (16)

On December 16,1996, a discrepancy was discovered in the plant procedure utilized to perform the periodic ,

inspection of the fire protection system smoke detectors. On January 13,1997, a review of this discrepancy identified I that the surveillance procedure utilized prior to November 1995 (Surveillance Procedure (SP) 2618C, " Fire Protection System Smoke Detector Test") did not ensure that the requirements of Technical Specification (TS) Surveillance Requirement 4.3.3.7.1 were met. In addition, on March 16,1997, it was discovered that SP2618C did not adequately document the trip functions of associated components during the testing of smoke detectors.

Fire protection requirements are no longer contained in the Technical Specifications. These requirements were removed by Millstone Unit No. 2 License Amendment No.191 which was issued on November 3,1995. Prior to Amendment No.191, Technical Specification Surveillance Requirement 4.3.3.7.1 included requirements for smoke detectors in the Auxiliary Building (-5 foot elevation). The requirements for the fire protection equipment were relocated to the Technical Requirements Manual (TRM) which is a plant controlled document.

The cause of both events was failure to properly incorporate Technical Specification surveillance reauirements into j plant surveillance procedures.

This event reports the historical noncompliance with Technical Specification Surveillance Requirement 4.3.3.7.1.

SP2618C has been partially revised to ensure compliance with the fire protection system requirements in the TRM for the smoke detectors.

9704230188 970416 PDR ADOCK 05000336 S PDR