ML17305A941

From kanterella
Revision as of 19:17, 18 June 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Forwards Response to NRC Bulletin 90-001, Loss of Fill Oil in Transmitters Mfg by Rosemount.
ML17305A941
Person / Time
Site: Palo Verde  Arizona Public Service icon.png
Issue date: 07/20/1990
From: Conway W
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
REF-PT21-90 161-03348-WFC-R, 161-3348-WFC-R, IEB-90-001, IEB-90-1, NUDOCS 9007230325
Download: ML17305A941 (52)


Text

A'C<;ELERATED TRIBUTION DEMONS~ATION SYSTEM l r REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)ACCESSION NBR:9007230325 DOC.DATE: 90/07/20 NOTARIZED:

YES DOCKET FACIL:STN-50-528 Palo Verde Nuclear Station, Unit 1, Arizona Publi 05000528 STN-50-529 Palo Verde Nuclear Station, Unit 2, Arizona Publi 05000529 STN-,50-530 Palo Verde Nuclear Station, Unit 3, Arizona Publi 05000530 AUTH.NAME AUTHOR AFFILIATION CONWAY,W.F.

Arizona Public Service Co.(formerly.

Arizona Nuclear Power RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control-Desk)

I

SUBJECT:

Responds NRC Bulletin 90-001,"Loss of Fill Oil in Transmitters Mfg by Rosemount." DISTRIBUTION CODE: IE39D COPIES RECEIVED:LTR ENCL SIZE: TITLE: NRC Bulletin 90-001, Loss of Fill Oil i Transmit.tters Mfg by NOTES: Standardized plant.Standardized plant.D S Rosemoun/05000528 05000529 A 05000530 D RECIPIENT ID CODE/NAME PD5 LA PETERSON,S.

INTERNAL: NRR LE,N RAM Y,J REG 02 FILE 01 EXTERNAL: LPDR NSIC NOTES: COPIES LTTR ENCL 1 0 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 RECIPIENT I D CODE/NAME PD5 PD.CHAN,T NRR PERCH,R NRR/DRIS/RVIB.

RES FARMER,W NRC PDR COPIES LTTR ENCL 1.1 1 1 1 1 1 1 1 1 1 1 D D NOTE TO ALL"RIDS" RECIPIENTS:

A D D PLEASE HELP US TO REDUCE WASTE!CONTACT THE DOCUMENT CONTROL DESK, ROOiXI P 1-37 (EXT.20079)TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!TOTAL NUMBER OF COPIES REQUIRED: LTTR 16 ENCL 15 l, 4 f I I Arizona Public Service Company P.O.BOX 53999~PHOENIX, ARIZONA 85072-3999 WILLIAM F.CONWAY EXECUTIVE VICE PRESIDENT NUCLEAR 161-03348-WFC/RAB July 20, 1990 Docket Nos.STN 50-528/529/530 Document Control Desk U.S.Nuclear Regulatory Commission Mail Station Pl-137 Washington, D.C.20555

Reference:

NRC Bulletin No.90-01, Loss of Fill-,Oil In Transmitters Manufactured by Rosemount

Dear Sirs:

Subject:

Palo Verde Nuclear Generating Station (PVNGS)Units 1, 2, and 3 Response to Actions Requested of NRC Bulletin 90-01 File: 90-055-026 The attached text contains APS'esponse as required by NRC Bulletin 90-01, concerning suspect transmitters manufa'ctured by Rosemount.

Corrective actions that have been taken and that are currently underway at PVNGS are also noted within this response.If you have additional questions, please contact Mr.A.C.Rogers of my staff at (602)340-4104.Sincerely, WFC/RAB/j le'ttachment cc: J.B.Martin S.R.Peterson A.H.Gutterman A.C.Gehr D.H.Coe qOO723A325 90072')pDR pooch>>O~R(.)00~12i9 9 PDC<n4 W WE9P l t I If STATE OF ARIZONA))ss.COUNTY OF MARICOPA)I, J.M.Levine, represent that'am Vice President, Nuclear Production, that the foregoing document has been signed by me on behalf of Arizona Public Service Company with full authority to do so, that I have read such document and know its contents, and that to the best of my knowledge and belief, the statements made therein are true and correct.J.M.Levine Sworn To Before Me This a70 Day Of 1990.Nota Public My Commission Expires My Commission Expires April 6, 1991 f[IP I V 5 Document Control Desk U.S.Nuclear Regulatory Commission Page 2 161-03348-WFC/RAB July 20, 1990 bcc: J.N.Bailey W.F.Quinn R.A.Bernier W.E.Ide D.R.Heinicke R.J.Adney J.S.Summy K.L.Cutler (1966)(1502)(1515)(6932)(7294)(6915)(6076)'(6934)

III l I t j I ATTACHMENT FINAL RESPONSE TO NRC BULLETIN 90-01 OPERATING REACTORS REPORTING RE UIREMENTS (1)Provide, within 120 days after receipt of this bulletin, a response that: (la)ACTION Confirms that Items 1, 2, 3, 4, and 5 of Requested Actions for Operating Reactors have been completed.

RESPONSE OPERATING REACTOR RE VESTED ACTIONS ACTION Identify Model 1153 Series B, 1153 Series D, and Model 1154 pressure or differential pressure transmitters, excluding Model 1153 Series B, 1153 Series D, and Model 1154 transmitters manufactured by Rosemount subsequent to July 11, 1989, that are currently utilized in either safety-related sys'tems or systems installed in accordance with 10 CFR 50.62 (the ATWS rule).RESPONSE All Model 1153 Series B, 1153 Series D, and Model 1154 pressure and differential pressure transmitters that are currently installed at Palo Verde Nuclear Generating Station have been identified.

Tables Al, A2, and A3 contain a list of transmitters sorted by unit and listed by instrument number with a description of the instruments'unction.

A review of the reactor protection (RPS), the engineered safety features actuation (ESFAS), and the supplementary protection systems (SPS)has identified that only four functions use Rosemount Model 1153 or 1154 transmitters.

These are: (a)(b)(c)(d)Containment Pressure-High Containment Pressure-High-High Refueling Water Tank Level-Low Pressurizer Pressure-High (SPS)(2)ACTION Determine whether any transmitters identified in Item 1 are from'the manufacturing lots that have been identified by Rosemount as having a high failure fraction due to loss of fill-oil.Addressees are requested not to utilize transmitters from these suspect lots in the reactor protection or engineered safety features actuation systems;therefore, addressees are requested to develop and implement a program to replace, at the earliest appropriate opportunity, II Final Res onse to NRC Bulletin 90"-01 Page 2 transmitters from these suspect lots in use in the reactor protection or engineered safety features actuation systems.RESPONSE Thus far we have identified five (5)transmitters that were listed on the"Rosemount Model 1153 and 1154 Pressure Transmitter Suspect List", dated December 22, 1989, that are/were installed at Palo Verde.None of these suspect transmitters are in the reactor protection or engineered safety features actuation systems of any of the three units;however, we have decided to replace all transmitters listed on Rosemount's suspect transmitter list that are inst:alled in any of the units.No suspect transmitters have been identified as being installed in Unit 1.One (1)suspect transmit:ter was found to be installed in Unit: 2;however, it has been replaced with a transmitter that is not listed on the suspect list.Four (4)suspect transmitters were found to be installed in Unit 3.Three (3)of the four (4)have been replaced with non-suspect transmitters.

The fourth transmitter, 3JSIBFT0311 (High Pressure Safety Injection Flow to Reactor Coolant Loop 2A), will be replaced at the earliest opportunity but no later than the end of the next refueling outage.The spare Rosemount Model 1153 Series B, 1153 Series D, and Model 1154 transmitters in Palo Verde's warehouse have been inspected and eleven (11)transmitters listed on Rosemount's suspect list were identified.

Warehouse Deficiency Notices (WDN's)were issued against the transmitters and they have been placed in the warehouse's QA quarantine area until Rosemount authorizes returning them for replacement.

Another Model 1153 transmitter listed on Rosemount's suspect list was located in the I&C rework stock.It has been segrated to prevent its inadvertant installation in any of the units.Including the five (5)transmitters identified above in the units, thus far seventeen (17)transmitters list:ed on Rosemount's suspect list have been located and have been or will be segregated.

(3)ACTION Review plant records (for example, the three most recent calibration records)associated with the transmitters identified in Item 1 above to determine whether any of these transmitters may have already exhibited symptoms indicative of loss of fill-oil.Appropriate operability acceptance criteria should be developed and applied to transmitters identified as having exhibited symptoms indicative of loss of fill-oil that do not conform to the operability acceptance criteria and are not addressed in the technical specifications should be replaced at the earliest appropriate opportunity.

I Final Res onse to NRC Bu11etin 90-01 Page 3 RESPONSE We have reviewed the Palo Verde Failure Data Trending records for every Rosemount Model 1153 and 1154 transmitter.

There is no record in this data base of a Model 1153 and/or 1154 failing with symptoms indicative of a possible loss of fill fluid failure, i.e.sluggish response to pressure changes, excessive'calibration shift.However, any confirmed transmitter fill-oil failure, which is an NPRDS reportable component, will be reported on NPRDS.We are currently reviewing the calibration records for the Model 1153 and 1154 transmitters installed in all three units.The review has not yet been completed due to the number of documents involved with the maintenance and calibration of over 260 model 1153 and 1154 transmitters.

(4)ACTION Develop and implement an enhanced surveillance program to moni.tor transmitters identified in Item 1 for symptoms of loss of fill-oil.This enhanced surveillance program should consider the following or equally effective actions: (a)ACTION, Ensuring appropriate licensee personnel are aware of the symptoms that a transmitter, both during operation and during calibration activities, may exhibit if it is experiencing a loss of fill-oil and the need for prompt identification of transmitters that may exhibit these symptoms.RESPONSE The operations and I&C maintenance staff have been notified of the typical responses that the Model 1153, and 1154 transmitters exhibit when they experience a loss of fill fluid and the need for prompt corrective action.This notification required the acknowledgement of the above staff.(b)ACTION Enhanced transmitter monitoring=

to identify sustained transmitter drift.RESPONSE The transmitters are periodically calibrated using approved procedures to demonstrate compliance with established tolerances as part of the APS maintenance program.If there is suspicion that a transmitter is not operating correctly,

Final Res onse to NRC Bulletin 90-01 Page 4 its operation is typically verified by performing a calibration using the calibration procedure as part of the work document.We have revised the applicable I&C calibration procedures for Model 1153 and 1154 transmitters to incorporate a requirement that the I&C technicians are to notify I&C Engineering if they find that a transmitter:

,(1)is found with the 4mA.and/or 20mA.calibration

'oints to be outside the accepted calibration tolerances, (2)is found to respond sluggisly to the calibration pressure changes, (3)does not appear to be responding correctly, based on the opinion of the technician.

This should identify any transmitter that experiences symptoms that could be indicative of a possible loss of sensor fill fluid.I&C Engineering will then perform a detailed investigation as defined by the"Engineering Evaluation Request" procedure, 73AC-OEEOl, for any transmitter that is identified as suspect to determine if it i's experiencing a loss of fluid failure.(c)ACTION Review of transmitter performance following planned or unplanned plant transients or tests to identify sluggish transmitter response.RESPONSE As part of the reactor trip events required data from the"Incident Investigation Category 1 and 2 Events," procedure 79AC-OIP01, App.B, the RPS/ESFAS response is verfied to assure that the actuation signals were initiated when required.For Rosemount transmitters installed in these systems, data is sent to a sequence of events recorder.Anomalies in response performance would be analyzed by a post trip review committee.(d)ACTION Enhanced awareness of sluggish transmitter response to either increasing or decreasing test pressures during calibration activities.

1 (f t Final Res onse to NRC Bulletin 90-01 Page 5 RESPONSE Reference response to 4b.The I&C calibration, procedures that, are applicable to Model 1153 and 1154 transmitters have been revised to incorporate guidelines regarding identification of sluggish transmitter response during calibration with instructions to notify I&C Engineering should this beidentified.

'&C Engineering will then evaluate the transmitter's operation and response in more detail.(e)ACTION Development and implementation of a program to detect changes in process noise.RESPONSE Although the NRC Staff has concluded that process noise analysis provides a sufficient basis for detecting fill-oil leakage, APS has not been able to confirm this.The primary reason being lack of any definitive acceptance or rejection criteria.This is based on the information contained in Rosemount's Technical Bulletin No.4, dated December 22, 1989.This stated that noise data is difficult to analyze and interpret.

For this reason Rosemount has not provided any guidelines for analyzing process noise.(f)ACTION Development and application to transmitters identified as having.exhibited symptoms indicative of loss of fill-oil of an appropriate operability acceptance criteria.Transmitters identified as having exhibited symptoms indicative of loss of fill-oil that do not conform to the operability acceptance criteria should be addressed in accordance with the applicable technical specification.

Transmitters identified as having exhibited symptoms indicative of loss of fill-oil that do not conform to the operability acceptance criteria and are not addressed in the technical specifications should be replaced at the earliest appropriate opportunity.

RESPONSE The operability of any transmitter that exhibits the symptoms that could be indicative of a loss of fill-oil (ie.significant and/or continuing zero and/or span shifts, sluggish response)must be questioned as to whether it is actually experiencing a loss of fill-oil or some other failure.Therefore, we conclude it would be undesirable to establish operability acceptance criteria for any transmitter that is identified as

Final Res onse to NRC Bulletin 90-01 Page 6 having exhibited symptoms indicative of loss of fill-oil.We have established criteria for identifing possible loss of fill-oil and that criteria has been incorporated into the calibration procedures for the Model 1153 and 1154 transmitters.

Any transmitter that exceeds these criteria will be evaluated thoroughly by the I&C Engineering group to determine the rea on for its suspect operation and appropriate corrective action will be performed.

(5)ACTION Document and maintain in accordance with existing plant procedures a basis for continued plant operation covering the time period from the present until such time that the Model 1153 Series B, 1153 Series D, and Model 1154 transmitters from the manufacturing lots that have been identified by Rosemount as having a high failure" fraction due to loss of fill-oil in use in the reactor protection or engineered safety features actuation systems can be replaced.In addition, while performing the actions requested above, addressees may identify transmitters exhibiting symptoms indicative of loss of fill-oil that'do not conform to the established operability acceptance criteria and are not addressed in the technical specifications.

As these transmitters are identified, this basisfor continued plant operation should be updated to address these transmitters covering the time period from the time these transmitters are identified until such time that these transmitters can be replaced.When developing and updati'ng this basis for continued plant operation, addressees may wish to consider transmitter diversity and redundancy, diverse trip functions (a separate trip function that may also provide a corresponding trip signal), special system and/or component tests, or (if necessary) immediate replacement of certain suspect transmitters.

RESPONSE No justification for continued plant operation is required for any of the three (3)units at Palo Verde because there are no transmitters listed in the Rosemount suspect transmitter list, dated December 22, 1989, installed in the reactor protection or engineered safety features actuation systems.(lb)ACTION Identifies the indicated manufacturer; the model number;"the system the transmitter was utilized in;the approximate amount of time at pressure;the corrective actions taken;and the disposition (e.g., returned to vendor for analysis)of Rosemount Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters that are believed to have exhibited symptoms indicative of loss of fill-oil or have been confirmed to have

Final Res onse to NRC Bu1letin 90-01 Page 7 experienced a loss of fill-oil.This should include Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters manufactured after July 11, 1989.RESPONSE No Model 1153 or Model 1154 transmitters at Palo Verde have exhibited symptoms indicative of loss of fill-oil thus far.We will provide the requested information for any transmitters that exhibit symptoms indicative of loss of fill-oil in the future.(lc)ACTION Indentifies the system in which the Model 1153 Series B, 1153 Series D, and Model 1154 transmitters from the manufact'uring lots that have been identified by Rosemount as having a high failure fraction due to loss of fill-oil are utilized and provides a schedule for replacement of these transmitters which are in use in the reactor protection or engineered safety features actuation systems.RESPONSE Unit 3 currently has one (1)Rosemount Model 1153 transmitter installed that is listed on Rosemount's suspect list;however, this transmitter is not part of the reactor protection or engineered safety features actuation systems.This transmitter, 3JSIBFT0311 (High Pressure Safety Injection Flow to Reactor Coolant Loop 2A), will be replaced at the earliest opportunity but no later than the end of the next refueling outage.No transmitters listed on Rosemount's suspect list have been identified as being currently installed in either Unit 1 or 2.(2)ACTION Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters that, subsequent to providing the response required by Item 1 above, exhibit symptoms of loss of fill-oil or are confirmed to have experienced a loss of fill-oil should be, reviewed for reportability under existing NRC regulations.

If determined not to be reportable, addressees are requested to document and maintain, in accordance with existing plant procedures, information consistent with that requested in Item lb above for each transmitter identified.

RESPONSE This will be done in accordance with PVNGS procedures.

II I I(

TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION 1 JAFAFT0040A 1 JAFAFT0040B 1JAFAPT0018 1JAFBFT0041A 1JAFBFT0041B 1JAFBPT0017 1JCHALT0200 1JCHALT0203A 1JCHAPT0212 1JCHBFT0212 1JCHBLT0201 1JCHBLT0203B 1JCHCLT0203C 1JCHDLT0203D 1JCTALT0035 1JCTBLT0036 1JECAFT0533 1JECALT0015 1JECBFT0534 1JECBLT0016 AFW FLOW TO SG 1 AFWFLOW TO SG 2 AF PP A DISCH PRESS AFW FLOW TO SG 1 AFW FLOW TO SG 2 AF PP B DISCH REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL CHARGING PUMPS TO REGEN HX CHARGING PUMPS TO REGEN HX REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL CNDS TK LEVEL CNDS TK LEVEL ESS CHW A FLOW ESS CHLD WTR SURGE TK A LEVEL ESS CHW B FLOW ESS CHLD WTR SURGE TK B LEVEL llSSDB5 1153DB5 1153GB9 1153DB5 1153DB5 1153GB9 1153DB5 1153DB5 1153GB9 1153HB5 1153DB5 1153DB5 1153DB5 1153DB5 1153 DB5 1153 DB4 1153 DB3 1153DB4 1153DB3

[4i k TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER 1JEWAFT0013 1JEWAFT0151 1JEWALT0091 1JEWBFT0014 1JEWBFT0152 1JEWBLT0092 1JHCAPT0351A 1JHCAPT0352A 1JHCAPT0353A 1JHCAFT0492 1JHCBPT0351B 1JHCBPT0352B 1JHCBPT0353B 1JHCBPT0493 1JHCCPT0351C 1JHCCPT0352C 1JHCDPT0351D 1JHCDPT0352D 1JNCAFT0474 1JNCAFT0475 DESCRIPTION ECW PP A DISCH FLOW ECWS FLOW TO ESS CHILLER A ESS LG WTR SURGE TK A LEVEL ECW PP B DISCH FLOW ECWS FLOW TO ESS CHILLER B ESS LG WTR SURGE TK B LEVEL CONTMT PRESS A HI CONTMT PRESS A CONTMT PRESS WIDE RANGE A CONTMNT PRESSURE CONTMT PRESS B HI CONTMT PRESS B CONTMT PRESS WIDE RANGE B CONTMNT PRESSURE CONTMT PRESS C HI CONTMT PRESS C CONTMT PRESS D HI CONTMT PRESS D RCP 1B CLR OUT RCP lA CLR OUT MODEL 1153GB5 1153DB5 1153DB4 1153DB5 1153DB5 1153DB4 1153GB6 1153GB6 1153GB7 1153GB3 1153GB6 1153GB6 1153GB7 1153GB3 1153GB6'153GB6 1153GB6 1153GB6 1153DB4 1153DB4 II TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER 1JNCAFT0476 1JNCAFT0477 1JNCBFT0494 1JNCBFT0495 1JNCBFT0496 1JNCBFT0497 1JNCNFT0487 1JNCNFT0507 1JPCAPT0009 1JPCBPT0010 1JRCAPT0190A 1JRCAPT0199A 1JRCBPT0190B 1JRCBPT0199B 1JRCCPT0105 1JRCCPT0199C 1JRCDPT0106 1JRCDPT0199D 1JRCEPT0138 1JRCNLT0752A DESCRIPTION RCP 2B CLR OUT RCP 2A CLR OUT RCP 1B CLR OUTLET RCP 1A CLR OUTLET RCP 2B,CLR OUTLET RCP 2A CLR OUTLET CEDM NORMAL ACU HXS OUT CEDM NORM ACU A OUTLET FLOW FL PO CLG PF 1 DSCH FL PO CLG PP 1 DSCH RCS PRESSURE WIDE RANGE PZR OVER-PRESS TRIP TO SPS RCS PRESSURE WIDE RANGE PZR OVER-PRESS TRIP TO SPS PRZR PRESS PZR OVER-PRESS TRIP TO SPS PRZR PRESS PZR OVER-PRESS TRIP TO SPS PRESSURIZER/RV HEAD VENT LEAK N.R.REFUELING WATER LEVEL MODEL 1153DB4 1153DB4 1153DB4 1153DB4 1153DB4 1153DB4 1153DA5 1153DA5 1153GB6 1153GB6 1153GDO 1153GD9 1153GDO 1153GD9 1153GD9 1153GD9 1153GD9 1153GD9 1153GB9 1154HP5 f't l TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION MODEL 1JRCNLT0752B 1JRCNLT0753A 1JRCNLT0753B 1JSGAPT0308 1JSGAPT0313 1JSGAPT0315 1JSGBPT0301 1JSGBPT0306 1JSGBPT0321 1JSIAFT0306 1JSIAFT0331 1JSIAFT0338 1JSIAFT0341 1JSIAFT0390 1JSIALT0345 1JSIALT0349 1JSIALT0704 1JSIBFT0307 1JSIBFT0311 1JSIBFT0321 W.R.REFUELING WATER LEVEL N.R.REFUELING WATER LEVEL W.R.REFUELING WATER LEVEL SG2 LN2 ATM DUMP N2 TANK PRESS SG2 LN SG1 LNl DUMP AIR SPPLY SG1 LN1 ATM DUMP N2 TANK PRESS SG1 LN2 ATM DMP N2 TANK PRESS SGI LN2 SG2 LNl DUMP AIR SPPLY SG2 LNl ATM DUMP N2 TANK PRESS LPSI PP A HDR DSCH FLOW HPSI FLOW TO RC 1A CONT SPRAY PP A DSCH FLOW HPSI FLOW TO RC 1B HPSI PP A LONG TERM CLG SPRAY CHEM STORAGE TANK LEVEL SPRAY CHEM STORAGE TANK LEVEL CONTMT SPRAY SYS A HDR WTR LVL LPSI PP B HDR DSCH FLOW HPSI FLOW TO RC 2A HPSI FLOW TO RC 2B 1154HP5 1154HP5 1154HP5 115 3GB8 115 3GB6 115 3GB8 1153GB8 115 3GB6 1153GB8 1153DB5 1153HB5 1153HB5 1153HB5-1153HB7 1153DB4 1153DB4 1153GB5 1153DB5 1153HB5 1153HB5 l I t J l I i' TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION MODEL 1JSIBFT0348 1JSIBFT0391 1JSIBLT0344 1JSIBLT0348 1JSIBLT0705 1JSPAFT0005 1JSPBFT0006 CONT SPRAY PP B DSCH FLOW HPSI PP B LONG TERM CLG SPRAY CHEM STORAGE TANK SPRAY CHEM STORAGE TANK LEVEL CONTMT SPRAY SYS B HDR WTR LVL ESP PP A DISCH FLOW ESP PP B DISCH FLOW 1153DB5 1153HB7 1153DB4 1153DB4 1153GB5 1153DB4 1153DB4 li l l l I t TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JAFAFT0040A 2JAFAFT0040B 2JAFAPT0018 2JAFBFT0041A 2JAFBFT0041B 2JAFBPT0017 2JCHALT0200 2JCHALT0203A 2JCHAPT0212 2JCHBFT0212 2JCHBLT0201 2JCHBLT0203B 2JCHCLT0203C 2JCHDLT0203D 2JCTALT0035 2JCTBLT0036 2JECAFT0533 2JECALT0015 2JECBFT0534 2JECBLT0016 AFW FLOW TO SG 1 AFW FLOW TO SG 2 AF PP A DISCH PRESS AFW FLOW TO SG 1 AFW FLOW TO SG 2 AF PP B DISCH PRESS REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL CHARGING PUMPS TO REGEN HX CHARGING PUMPS TO REGEN HX REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL CNDS TK LEVEL CNDS TK LEVEL ESS CHW A FLOW ESS CHLD WTR SURGE TK A LEVEL ESS CHW B FLOW-ESS CHLD WTR SURGE TK B LEVEL 1153DB5 1153DB5 1153GB9 1153DB5 1153DB5 1153GB9 1153DB5 1153DB5 1153GP9 1153HB5 1153DB5 1153DB5 1153DB5'1153DB5 1153DB5 1153DB5 1153DB4 1153DB3 1153DB4 1153DB3

,h TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JRCNLT0752B 2JRCNLT0753A 2JRCNLT0753B 2JSGAPT0308 2JSGAPT0313 2JSGAPT0315 2JSGBPT0301 2JSGBPT0306 2JSGBPT0321 2JSIAFT0306 2JSIAFT0308 2JSIAFT0331 2JSIAFT0338 2JSIAFT0341 2JSIAFT0390 2JSIALT0345 2JSIALT0349 2JSIALT0704 2JSIBFT0307 2JSIBFT0309 W.R.REFUELING WATER LEVEL N.R.REFUELING WATER LEVEL W.R.REFUELING WATER LEVEL SG2 LN2 ATM DUMP N2 TANK SG2 LN2 SG1 ON1 DUMP AIR SPPLY SG1 LNl ATM DUMP N2 TANK-SG1 LN2 ATM DUMP N2 TANK SGl LN2 SG2LN1 DUMP AIR SPPLY SG2 LN1 ATM.DUMP N2 TANK LPSI PP A HDR DISCH FLOW SPRAY CHEM PP A DISCH HPSI FLOW TO RC lA CONT SPRAY PP A DISCH FLOW HPSI FLOW TO RC 1B HPSI PP A LONG TERM CLG SPRAY CHEM STORAGE TANK SPRAY CHEM STORAGE TANK CONTMT SPRAY SYS A HDR WTR LVL LPSI PP B HDR DISCH FLOW SPRAY CHEM PP B DISCH 1154HP5 1154HP5 1154HP5 1153GBS 1153GB6 1153GBS 1153GB8 1153GB6 1153GB8 1153DB5 1153DB3 1153HB5 1153DB5 1153HB5 1153HB7 1153DB4 1153DB4 1153GB5 1153DB5 1153DB3

'l l l f'f i]i TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JEWAFT0013 2JEWAFT0151 2JEWALT0091 2JEWBFT0014 2 J EWBFT0152 2JEWBLT0092 2JHCAPT0351A 2JHCAPT0352A 2JHCAPT0353A 2JHCAPT0492 2JHCBPT0351B 2JHCBPT0352B 2JHCBPT0353B 2JHCBPT0493 2JHCCPT0351C 2JHCCPT0352C 2JHCDPT0351D 2JHCDPT0352D 2JNCAFT0474 2JNCAFT0475 ECW PP A DISCH FLOW ECWS FLOW TO ESS CHILLER A ESS LG WTG SURGE TK A LEVEL ECW PP B DISCH FLOW ECWS FLOW TO ESS CHILLER B ESS LG WTR SURGE TK B LEVEL CONTMT PRESS A HI CONTMT PRESS A CONTMT PRESS WIDE RANGE A CONTMNT PRESSURE CONTMT PRESS B HI CONTMT PRESS B CONTMT PRESS WIDE RANGE B CONTMNT PRESSURE CONTMT PRESS C HI CONTMT PRESS C CONTMT PRESS D HI CONTMT PRESS D RCP 1B CLR OUTLET FLOW RCP lA CLR OUTLET FLOW 1153DB5 1153DB5 1153DB4 1153DB5 1153DB5 1153DB4 1153GB6 1153GB6 1153GB7 1153GB3 1153GB6 1153GB6 1153GB7 1153GB3 1153GB6 115 3GB6 1153GB6 1153GB6 1153DB4 1153DB4 II TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JNCAFT0476 2JNCAFT0477 2JNCBFT0494 2JNCBFT0495 2JNCBFT0496 2JNCBFT0497 2JNCNFT0487 2JNCNFT0507 2JPCAPT0009 2JPCBPT0010 2JRCAPT0190A 2JRCAPT0199A 2JRCBPT0190B 2JRCBPT0199B 2JRCCPT0105

'JRCCPT0199C 2JRCDPT0106 2JRCDPT0199D 2JRCEPT0138

,, 2JRCNLT0752A RCP 2B CLR OUTLET FLOW RCP 2A CLR OUTLET FLOW RCP 1B CLR OUTLET FLOW RCP 1A CLR OUTLET FLOW RCP 2B CLR OUTLET FLOW RCP 2A CLR OUTLET FLOW CEDM NORMAL ACU HXS OUT CEDM NORM ACU A OUTLET FLOW FL PO CLG PP 1 DISCH FL PO CLG PP 1 DISCH RCS PRESSURE WIDE RANGE PZR OVER-PRESS TRIP TO SPS RCS PRESSURE WIDE RANGE PZR OVER-PRESS TRIP TO SPS PRESSURIZER PRESSURE PZR OVER-PRESS TRIP TO SPS PRESSURIZER PRESSURE PZR OVER-PRESS TRIP TO SPS PRESSURIZER/RV HEAD VENT LEAK NOR.REFUELING WATER LEVEL 1153DB4 1153DB4 1153DB4 1153DB4 1153DB4 1153DB4 1153DA5 1153DA5 1153GB6: 1153GB6 1153GDO 1153GD9 1153GDO 1153GD9 1153GD9 1153GD9 1153GD9 1153GD9 1153GB9 1154HP5 1'i TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JSIBFT0311 2JSIBFT0321 2JSIBFT0348 2JSIBFT0391 2JSIBLT0344 2JSIBLT0348 2JSIBLT0705 2JSPAFT0005 2JSPBFT0006 2JSSNFT0056 HPSI FLOW TO RC 2A HPSI FLOW TO RC 2B CONT SPRAY PP B DISCH FLOW HPSI PP B LONG TERM CLG SPRAY CHEM STORAGE TANK SPRAY CHEM STORAGE TANK CONTMT SPRAY SYS B HDR WTR LVL ESP PP A DISCH FLOW ESP PP B DISCH FLOW PASS LIQ SAMPLE FLOW 1153HB5 1153HB5 1153DB5 1153HB7 1153DB4 1153DB4 1153GB5 1153DB4 1154DB4 1153DB3 j 1 f (f'jl t TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3 JAFAFT0040A 3 JAFAFT0040B 3JAFAPT0018 3JAFBFT0041A 3JAFBFT0041B 3JAFBPT0017 3JCHALT0200 3JCHALT0203A 3JCHAPT0212 3JCHBFT0212 3JCHBLT0201 3JCHBLT0203B 3JCHCLT0203C 3JCHDLT0203D 3JCTALT0035 3JCTBLT0036 3JECAFT0533 3JECALT0015 3JECBFT0534 3JECBLT0016 AFW FLOW TO SG 1 AFW FLOW TO SG 2 AF PP A DISCH PRESS-AFW FLOW TO SG 1 AFW FLOW TO SG 2 AF PP B DISCH PRESS REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL CHARGING PUMPS TO REGEN HX CHARGING PUMPS TO REGEN HX REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL REFUELING WATER TANK LEVEL CNDS TK LEVEL CNDS TK LEVEL ESS CHW A FLOW ESS CHLD WTR SURGE TK A LEVEL ESS CHW B FLOW ESS CHLD WTR SURGE TK B LEVEL 1153DB5 1153DB5 1153GB9 1153DB5 1153DB5=1153GB9 1153DB5 1153DB5 1153GB9 1153HB5 1153DB5 1153DB5 1153DB5 1153DB5 1153DB5 1153DB5 1153DB4 1153DB3 1153DB4 1153DB3

~~

TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3JNCAFT0476 3JNCAFT0477 3JNCBFT0494 3JNCBFT0495 3JNCBFT0496 3JNCBFT0497 3JNCNFT0487 3JNCNFT0507 3JPCAPT0009 3JPCBPT0010 3JRCAPT0190A 3JRCAPT0199A 3JRCBPT0190B 3JRCBPT0199B 3JRCCPT0105 3JRCCPT0199C 3JRCDPT0106 3JRCDPT0199D 3JRCEPT0138 3JRCNLT0752A RCP 2B CLR OUTLET FLOW RCP 2A CLR OUTLET FLOW RCP 1B CLR OUTLET FLOW RCP 1A CLR OUTLET FLOW RCP 2B CLR OUTLET FLOW RCP 2A CLR OUTLET FLOW CEDM NORMAL ACU HXS OUTLET CEDM NORM ACU A OUTLET FLOW FL PO CLG PP 1 DISCH PRESS FL PO CLG PP 1 DISCH PRESS RCS PRESSURE WIDE RANGE PZR OVER-PRESS TRIP TO SPS RCS PRESSURE WIDE RANGE PZR OVER-PRESS TRIP TO SPS PRESSURIZER PRESSURE PZR OVER-PRESS TRIP TO SPS PRESSURIZER PRESSURE PZR OVER-PRESS TRIP TO SPS PRESSURIZER/RV HEAD VENT LEAK N.R.REFUELING WATER LEVEL 1153DB4 1153DB4 1153DB4 1153DB4 1153DB4 1153DB4 1153DA5 1153DA5 1153GB6 1153GB6 1153GDO 1153GD9 1153GIO 1153GD9 1153GD9 1153GIS 1153GD9 1153GD9 1153GB9 1154HP5

~I ,a TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3 J EWAFT0013 3 J EWAFT0151 3JEWALT0091 3JEWBFT0014 3JEWBFT0152 3JEWBLT0092 3JHCAPT0351A 3JHCAPT0352A 3JHCAPT0353A 3JHCAPT0492 3JHCBPT0351B 3JHCBPT0352B 3JHCBPT0353B 3JHCBPT0493 3JHCCPT0351C 3JHCCPT0352C 3JHCDPT0351D 3JHCDPT0352D 3JNCAFT0474 3JNCAFT0475 ECW PP A DISCH FLOW ECWS FLOW TO ESS CHILLER A ESS LG WTR SURGE TK A LEVEL t ECW PP B DISCH FLOW ECWS FLOW TO ESS CHILLER B ESS LG WTR SURGE TK B LEVEL CONTMT PRESS A HI CONTMT PRESS A CONTMT PRESS WIDE RANGE A CONTMNT PRESSURE CONTMT PRESS B HI CONTMT PRESS B CONTMT PRESS WIDE RANGE B CONTMNT PRESSURE CONTMT PRESS C HI CONTMT PRESS C CONTMT PRESS D HI CONTMT PRESS D RCP 18 CLR OUTLET FLOW RCP 1A CLR OUTLET FLOW 1153DB5 1153DB5 1153DB4 1153DB5 1153DB5 1153DB4 1153GB6 1153GB6 1153GB7 1153GB3 1153GB6 1153GB6 1153GB7 1153GB3 1153GB6 1153GB6 1153GB6 1153GB6 1153DB4 1153DB4

TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3JRCNLT0752B 3JRCNLT0753A 3JRCNLT0753B 3JSGAPT0308 3JSGAPT0313 3JSGAPT0315 3JSGBPT0301 3JSGBPT0306 3JSGBPT0321 3JSIAFT0306 3JSIAFT0331 3JSIAFT0338 3JSIAFT0341 3JSIAFT0390 3JSIALT0345 3JSIALT0349 3JSIALT0704

~3JSIBFT0307 3JSIBFT0311 3JSIBFT0321 W.R.REFUELING WATER LEVEL N.R.REFUELING WATER LEVEL W.R.REFUELING WATER LEVEL SG2 LN2 ATM DUMP N2 TANK PRESS SG2 LN2 SGl LN1 DUMP AIR SPPLY SG1 LN1 ATM DUMP N2 TANK'RESS SGl LN2 ATM DUMP N2 TANK PRESS SGl LN2 SG2 LN1 DUMP AIR SPPLY SG2 LN1 ATM DUMP N2 TANK PRESS LPSI PP A HDR DISCH FLOW HPSI FLOW,TO RC 1A CONT SPRAY PP A DISCH FLOW HPSI FLOW TO RC 1B HPSI PP A LONG TERM CLG FLOW SPRAY CHEM STORAGE TANK LEVEL SPRAY CHEM STORAGE TANK LEVEL CONTMT SPRAY SYS A HDR WTR LVL LPSI PP B HDR DISCH FLOW HPSI FLOW TO RC 2A HPSI FLOW TO RC 2B 1154HP5 1154HP5 1154HP5 1153GB8 1153GB6 1153GB8 1153GB8 1153GB6 1153GB8 1153DB5 1153HB5 1153DB5 1153HB5 1153HB7 1153DB4 1153DB4 1153GB5 1153DB5 1153HB5 1153HB5

TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER'NIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3JSIBFT0348 3JSIBFT0391 3JSIBLT0344 3JSIBLT0348 3JSIBLT0705 3JSPAFT0005 3JSPBFT0006 3JSSNFT0056 CONT SPRAY PP B DISCH FLOW HPSI PP B LONG TERM CLG FLOW SPRAY CHEM STORAGE TANK LEVEL SPRAY CHEM STORAGE TANK LEVEL CONTMT SPRAY SYS B HDR WTR LVL ESP PP A DISCH FLOW ESP PP B DISCH FLOW PASS LIQ SAMPLE FLOW 1153DB5 1153HB7 1153DB4 1153DB4 1153GB5 1153DB4 1153DB4 1153DB3 H J