ML17305A941
ML17305A941 | |
Person / Time | |
---|---|
Site: | Palo Verde ![]() |
Issue date: | 07/20/1990 |
From: | Conway W ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR |
To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
References | |
REF-PT21-90 161-03348-WFC-R, 161-3348-WFC-R, IEB-90-001, IEB-90-1, NUDOCS 9007230325 | |
Download: ML17305A941 (52) | |
Text
l A'C<;ELERATED TRIBUTION DEMONS~ATION SYSTEM r
REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:9007230325 DOC.DATE: 90/07/20 NOTARIZED: YES DOCKET FACIL:STN-50-528 Palo Verde Nuclear Station, Unit 1, Arizona Publi 05000528 STN-50-529 Palo Verde Nuclear Station, Unit 2, Arizona Publi 05000529 STN-,50-530 Palo Verde Nuclear Station, Unit 3, Arizona Publi 05000530 AUTH. NAME AUTHOR AFFILIATION CONWAY,W.F. Arizona Public Service Co. (formerly. Arizona Nuclear Power RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control-Desk) I
SUBJECT:
Responds NRC Bulletin 90-001, "Loss of Transmitters Mfg by Rosemount."
Fill Oil in D DISTRIBUTION CODE: IE39D COPIES RECEIVED:LTR ENCL SIZE: S TITLE: NRC Bulletin 90-001, Loss of Fill Oil i Transmit.tters Mfg by Rosemoun
/
NOTES: 05000528 Standardized plant. 05000529 A Standardized plant. 05000530 D
RECIPIENT COPIES RECIPIENT COPIES D ID PD5 LA CODE/NAME LTTR ENCL 1 0 I D CODE/NAME PD5 PD LTTR ENCL
. 1 .1 PETERSON,S. 1 1 CHAN,T 1 1 INTERNAL: NRR LE,N 1 1 NRR PERCH,R 1 1 RAM Y,J 2 2 NRR/DRIS/RVIB. 1 1 REG 02 1 1 RES FARMER,W 1 1 FILE 01 1 1 EXTERNAL: LPDR 1 1 NRC PDR 1 1 NSIC 1 1 NOTES: 1 1 D
A D
D NOTE TO ALL "RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOiXI P 1-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!
TOTAL NUMBER OF COPIES REQUIRED: LTTR 16 ENCL 15
l, 4
f I
I
Arizona Public Service Company P.O. BOX 53999 ~ PHOENIX, ARIZONA 85072-3999 WILLIAMF. CONWAY 161-03348-WFC/RAB EXECUTIVEVICE PRESIDENT NUCLEAR July 20, 1990 Docket Nos. STN 50-528/529/530 Document Control Desk U. S. Nuclear Regulatory Commission Mail Station Pl-137 Washington, D.C. 20555
Reference:
NRC Bulletin No. 90-01, Loss of Fill-,Oil In Transmitters Manufactured by Rosemount
Dear Sirs:
Subject:
Palo Verde Nuclear Generating Station (PVNGS)
Units 1, 2, and 3 Response to Actions Requested of NRC Bulletin 90-01 File: 90-055-026 The attached text contains APS'esponse as required by NRC Bulletin 90-01, concerning suspect transmitters manufa'ctured by Rosemount. Corrective actions that have been taken and that are currently underway at PVNGS are also noted within this response.
If you have additional questions, please contact Mr. A. C. Rogers of my staff at (602) 340-4104.
Sincerely, WFC/RAB/j le
'ttachment cc: J. B. Martin S. R. Peterson A. H. Gutterman A. C. Gehr D. H. Coe qOO723A325 90072')
pDR pooch>> O~R(.)00~12i9 PDC 9
<n4 W WE9P l
t I
If
STATE OF ARIZONA )
)ss.
COUNTY OF MARICOPA )
I, J. M. Levine, represent that' am Vice President, Nuclear Production, that the foregoing document has been signed by me on behalf of Arizona Public Service Company with full authority to do so, that I have read such document and know its contents, and that to the best of my knowledge and belief, the statements made therein are true and correct.
J. M. Levine Sworn To Before Me This a70 Day Of 1990.
Nota Public My Commission Expires My Commission Expires April 6, 1991
f[
IP I
V 5
Document Control Desk 161-03348-WFC/RAB U. S. Nuclear Regulatory Commission July 20, 1990 Page 2 bcc: J. N. Bailey (1966)
W. F. Quinn (1502)
R. A. Bernier (1515)
W. E. Ide (6932)
D. R. Heinicke (7294)
R. J. Adney (6915)
J. S. Summy (6076)
K. L. Cutler '(6934)
III l
I t
j I
ATTACHMENT FINAL RESPONSE TO NRC BULLETIN 90-01 OPERATING REACTORS REPORTING RE UIREMENTS (1) Provide, within 120 days after receipt of this bulletin, a response that:
(la) ACTION Confirms that Items 1, 2, 3, 4, and 5 of Requested Actions for Operating Reactors have been completed.
RESPONSE
OPERATING REACTOR RE VESTED ACTIONS ACTION Identify Model 1153 Series B, 1153 Series D, and Model 1154 pressure or differential pressure transmitters, excluding Model 1153 Series B, 1153 Series D, and Model 1154 transmitters manufactured by Rosemount subsequent to July 11, 1989, that are currently utilized in either safety-related sys'tems or systems installed in accordance with 10 CFR 50.62 (the ATWS rule).
RESPONSE
All Model 1153 Series B, 1153 Series D, and Model 1154 pressure and differential pressure transmitters that are currently installed at Palo Verde Nuclear Generating Station have been identified. Tables Al, A2, and A3 contain a list of transmitters sorted by unit and listed by instrument number with a description of the instruments'unction.
A review of the reactor protection (RPS), the engineered safety features actuation (ESFAS), and the supplementary protection systems (SPS) has identified that only four functions use Rosemount Model 1153 or 1154 transmitters. These are:
(a) Containment Pressure - High (b) Containment Pressure - High-High (c) Refueling Water Tank Level - Low (d) Pressurizer Pressure - High (SPS)
(2) ACTION Determine whether any transmitters identified in Item 1 are from'the manufacturing lots that have been identified by Rosemount as having a high failure fraction due to loss of fill-oil. Addressees are requested not to utilize transmitters from these suspect lots in the reactor protection or engineered safety features actuation systems; therefore, addressees are requested to develop and implement a program to replace, at the earliest appropriate opportunity,
II Final Res onse to NRC Bulletin 90"-01 Page 2 transmitters from these suspect lots in use in the reactor protection or engineered safety features actuation systems.
RESPONSE
Thus far we have identified five (5) transmitters that were listed on the "Rosemount Model 1153 and 1154 Pressure Transmitter Suspect List", dated December 22, 1989, that are/were installed at Palo Verde. None of these suspect transmitters are in the reactor protection or engineered safety features actuation systems of any of the three units; however, we have decided to replace all transmitters listed on Rosemount's suspect transmitter list that are inst:alled in any of the units.
No suspect transmitters have been identified as being installed in Unit 1. One (1) suspect transmit:ter was found to be installed in Unit: 2; however, it has been replaced with a transmitter that is not listed on the suspect list. Four (4) suspect transmitters were found to be installed in Unit 3. Three (3) of the four (4) have been replaced with non-suspect transmitters. The fourth transmitter, 3JSIBFT0311 (High Pressure Safety Injection Flow to Reactor Coolant Loop 2A), will be replaced at the earliest opportunity but no later than the end of the next refueling outage.
The spare Rosemount Model 1153 Series B, 1153 Series D, and Model 1154 transmitters in Palo Verde's warehouse have been inspected and eleven (11) transmitters listed on Rosemount's suspect list were identified. Warehouse Deficiency Notices (WDN's) were issued against the transmitters and they have been placed in the warehouse's QA quarantine area until Rosemount authorizes returning them for replacement. Another Model 1153 transmitter listed on Rosemount's suspect list was located in the I&C rework stock. It has been segrated to prevent its inadvertant installation in any of the units.
Including the five (5) transmitters identified above in the units, thus far seventeen (17) transmitters list:ed on Rosemount's suspect list have been located and have been or will be segregated.
(3) ACTION Review plant records (for example, the three most recent calibration records) associated with the transmitters identified in Item 1 above to determine whether any of these transmitters may have already exhibited symptoms indicative of loss of fill-oil. Appropriate operability acceptance criteria should be developed and applied to transmitters identified as having exhibited symptoms indicative of loss of fill-oilthat do not conform to the operability acceptance criteria and are not addressed in the technical specifications should be replaced at the earliest appropriate opportunity.
I Final Res onse to NRC Bu11etin 90-01 Page 3
RESPONSE
We have reviewed the Palo Verde Failure Data Trending records for every Rosemount Model 1153 and 1154 transmitter. There is no record in this data base of a Model 1153 and/or 1154 failing with symptoms indicative of to a possible loss of pressure changes, fill fluid failure, i.e. sluggish excessive'calibration shift. However, response any confirmed transmitter fill-oil failure, which is an NPRDS reportable component, will be reported on NPRDS.
We are currently reviewing the calibration records for the Model 1153 and 1154 transmitters installed in all three units. The review has not yet been completed due to the number of documents involved with the maintenance and calibration of over 260 model 1153 and 1154 transmitters.
(4) ACTION Develop and implement an enhanced surveillance program to moni.tor transmitters identified in Item 1 for symptoms of loss of fill-oil.
This enhanced surveillance program should consider the following or equally effective actions:
(a) ACTION, Ensuring appropriate licensee personnel are aware of the symptoms that a transmitter, both during operation and during calibration activities, may exhibit if it is experiencing a loss of fill-oil and the need for prompt identification of transmitters that may exhibit these symptoms.
RESPONSE
The operations and I&C maintenance staff have been notified of the typical responses that the Model 1153, and 1154 transmitters exhibit when they experience a loss of fill fluid and the need for prompt corrective action. This notification required the acknowledgement of the above staff.
(b) ACTION Enhanced transmitter monitoring= to identify sustained transmitter drift.
RESPONSE
The transmitters are periodically calibrated using approved procedures to demonstrate compliance with established tolerances as part of the APS maintenance program. If there is suspicion that a transmitter is not operating correctly,
Final Res onse to NRC Bulletin 90-01 Page 4 its operation is typically verified by performing a calibration using the calibration procedure as part of the work document.
We have revised the applicable I&C calibration procedures for Model 1153 and 1154 transmitters to incorporate a requirement that the I&C technicians are to notify I&C Engineering if they find that a transmitter:
,(1) is found with the 4mA. and/or 20mA. calibration
'oints to be outside the accepted calibration tolerances, (2) is found to respond sluggisly to the calibration pressure changes, (3) does not appear to be responding correctly, based on the opinion of the technician.
This should identify any transmitter that experiences symptoms that could be indicative of a possible loss of sensor fill fluid.
I&C Engineering will then perform a detailed investigation as defined by the "Engineering Evaluation Request" procedure, 73AC-OEEOl, for transmitter that is identified as suspect to determine if any it i's experiencing a loss of fluid failure.
(c) ACTION Review of transmitter performance following planned or unplanned plant transients or tests to identify sluggish transmitter response.
RESPONSE
As part of the reactor trip events required data from the "Incident Investigation Category 1 and 2 Events," procedure 79AC-OIP01, App. B, the RPS/ESFAS response is verfied to assure that the actuation signals were initiated when required. For Rosemount transmitters installed in these systems, data is sent to a sequence of events recorder. Anomalies in response performance would be analyzed by a post trip review committee.
(d) ACTION Enhanced awareness of sluggish transmitter response to either increasing or decreasing test pressures during calibration activities.
1
(
f t
Final Res onse to NRC Bulletin 90-01 Page 5
RESPONSE
Reference response to 4b. The I&C calibration, procedures that, are applicable to Model 1153 and 1154 transmitters have been revised to incorporate guidelines regarding identification of sluggish transmitter response during calibration with instructions to notify I&C Engineering should this beidentified. '&C Engineering will then evaluate the transmitter's operation and response in more detail.
(e) ACTION Development and implementation of a program to detect changes in process noise.
RESPONSE
Although the NRC Staff has concluded that process noise analysis provides a sufficient basis for detecting fill-oil leakage, APS has not been able to confirm this. The primary reason being lack of any definitive acceptance or rejection criteria. This is based on the information contained in Rosemount's Technical Bulletin No. 4, dated December 22, 1989.
This stated that noise data is difficult to analyze and interpret. For this reason Rosemount has not provided any guidelines for analyzing process noise.
(f) ACTION Development and application to transmitters identified as having .exhibited symptoms indicative of loss of fill-oil of an appropriate operability acceptance criteria. Transmitters identified as having exhibited symptoms indicative of loss of fill-oil that do not conform to the operability acceptance criteria should be addressed in accordance with the applicable technical specification. Transmitters identified as having exhibited symptoms indicative of loss of fill-oilthat do not conform to the operability acceptance criteria and are not addressed in the technical specifications should be replaced at the earliest appropriate opportunity.
RESPONSE
The operability of any transmitter that exhibits the symptoms that could be indicative of a loss of fill-oil(ie. significant and/or continuing zero and/or span shifts, sluggish response) must be questioned as to whether it is actually experiencing a loss of fill-oilor some other failure. Therefore, we conclude it would be undesirable to establish operability acceptance criteria for any transmitter that is identified as
Final Res onse to NRC Bulletin 90-01 Page 6 having exhibited symptoms indicative of loss of fill-oil. We have established criteria for identifing possible loss of fill-oil and that criteria has been incorporated into the calibration procedures for the Model 1153 and 1154 transmitters. Any transmitter that exceeds these criteria will be evaluated thoroughly by the I&C Engineering group to determine the rea on for its suspect operation and appropriate corrective action will be performed.
(5) ACTION Document and maintain in accordance with existing plant procedures a basis for continued plant operation covering the time period from the present until such time that the Model 1153 Series B, 1153 Series D, and Model 1154 transmitters from the manufacturing lots that have been identified by Rosemount as having a high failure" fraction due to loss of fill-oil in use in the reactor protection or engineered safety features actuation systems can be replaced. In addition, while performing the actions requested above, addressees may identify transmitters exhibiting symptoms indicative of loss of fill-oil that 'do not conform to the established operability acceptance criteria and are not addressed in the technical specifications. As these transmitters are identified, this basis for continued plant operation should be updated to address these transmitters covering the time period from the time these transmitters are identified until such time that these transmitters can be replaced. When developing and updati'ng this basis for continued plant operation, addressees may wish to consider transmitter diversity and redundancy, diverse trip functions ( a separate trip function that may also provide a corresponding trip signal), special system and/or component tests, or (if necessary) immediate replacement of certain suspect transmitters.
RESPONSE
No justification for continued plant operation is required for any of the three (3) units at Palo Verde because there are no transmitters listed in the Rosemount suspect transmitter list, dated December 22, 1989, installed in the reactor protection or engineered safety features actuation systems.
(lb) ACTION Identifies the indicated manufacturer; the model number; "the system the transmitter was utilized in; the approximate amount of time at pressure; the corrective actions taken; and the disposition (e.g., returned to vendor for analysis) of Rosemount Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters that are believed to have exhibited symptoms indicative of loss of fill-oil or have been confirmed to have
Final Res onse to NRC Bu1letin 90-01 Page 7 experienced a loss of fill-oil. This should include Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters manufactured after July 11, 1989.
RESPONSE
No Model 1153 or Model 1154 transmitters at Palo Verde have exhibited symptoms indicative of loss of fill-oil thus far.
We will provide the requested information for any transmitters that exhibit symptoms indicative of loss of fill-oil in the future.
(lc) ACTION Indentifies the system in which the Model 1153 Series B, 1153 Series D, and Model 1154 transmitters from the manufact'uring lots that have been identified by Rosemount as having a high failure fraction due to loss of fill-oil are utilized and provides a schedule for replacement of these transmitters which are in use in the reactor protection or engineered safety features actuation systems.
RESPONSE
Unit 3 currently has one (1) Rosemount Model 1153 transmitter installed that is listed on Rosemount's suspect list; however, this transmitter is not part of the reactor protection or engineered safety features actuation systems. This transmitter, 3JSIBFT0311 (High Pressure Safety Injection Flow to Reactor Coolant Loop 2A), will be replaced at the earliest opportunity but no later than the end of the next refueling outage.
No transmitters listed on Rosemount's suspect list have been identified as being currently installed in either Unit 1 or 2.
(2) ACTION Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters that, subsequent to providing the response required by Item 1 above, exhibit symptoms of loss of fill-oil or are confirmed to have experienced a loss of fill-oil should be, reviewed for reportability under existing NRC regulations. If determined not to be reportable, addressees are requested to document and maintain, in accordance with existing plant procedures, information consistent with that requested in Item lb above for each transmitter identified.
RESPONSE
This will be done in accordance with PVNGS procedures.
II I
I(
TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION 1 JAFAFT0040A AFW FLOW TO SG 1 llSSDB5 1 JAFAFT0040B AFW FLOW TO SG 2 1153DB5 1JAFAPT0018 AF PP A DISCH PRESS 1153GB9 1JAFBFT0041A AFW FLOW TO SG 1 1153DB5 1JAFBFT0041B AFW FLOW TO SG 2 1153DB5 1JAFBPT0017 AF PP B DISCH 1153GB9 1JCHALT0200 REFUELING WATER TANK LEVEL 1153DB5 1JCHALT0203A REFUELING WATER TANK LEVEL 1153DB5 1JCHAPT0212 CHARGING PUMPS TO REGEN HX 1153GB9 1JCHBFT0212 CHARGING PUMPS TO REGEN HX 1153HB5 1JCHBLT0201 REFUELING WATER TANK LEVEL 1153DB5 1JCHBLT0203B REFUELING WATER TANK LEVEL 1153DB5 1JCHCLT0203C REFUELING WATER TANK LEVEL 1153DB5 1JCHDLT0203D REFUELING WATER TANK LEVEL 1153DB5 1JCTALT0035 CNDS TK LEVEL 1JCTBLT0036 CNDS TK LEVEL 1153 DB5 1JECAFT0533 ESS CHW A FLOW 1153 DB4 1JECALT0015 ESS CHLD WTR SURGE TK A LEVEL 1153 DB3 1JECBFT0534 ESS CHW B FLOW 1153DB4 1JECBLT0016 ESS CHLD WTR SURGE TK B LEVEL 1153DB3
[
4i k
TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION MODEL 1JEWAFT0013 ECW PP A DISCH FLOW 1153GB5 1JEWAFT0151 ECWS FLOW TO ESS CHILLER A 1153DB5 1JEWALT0091 ESS LG WTR SURGE TK A LEVEL 1153DB4 1JEWBFT0014 ECW PP B DISCH FLOW 1153DB5 1JEWBFT0152 ECWS FLOW TO ESS CHILLER B 1153DB5 1JEWBLT0092 ESS LG WTR SURGE TK B LEVEL 1153DB4 1JHCAPT0351A CONTMT PRESS A HI 1153GB6 1JHCAPT0352A CONTMT PRESS A 1153GB6 1JHCAPT0353A CONTMT PRESS WIDE RANGE A 1153GB7 1JHCAFT0492 CONTMNT PRESSURE 1153GB3 1JHCBPT0351B CONTMT PRESS B HI 1153GB6 1JHCBPT0352B CONTMT PRESS B 1153GB6 1JHCBPT0353B CONTMT PRESS WIDE RANGE B 1153GB7 1JHCBPT0493 CONTMNT PRESSURE 1153GB3 1JHCCPT0351C CONTMT PRESS C HI 1153GB6
'153GB6 1JHCCPT0352C CONTMT PRESS C 1JHCDPT0351D CONTMT PRESS D HI 1153GB6 1JHCDPT0352D CONTMT PRESS D 1153GB6 1JNCAFT0474 RCP 1B CLR OUT 1153DB4 1JNCAFT0475 RCP lA CLR OUT 1153DB4
II TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION MODEL 1JNCAFT0476 RCP 2B CLR OUT 1153DB4 1JNCAFT0477 RCP 2A CLR OUT 1153DB4 1JNCBFT0494 RCP 1B CLR OUTLET 1153DB4 1JNCBFT0495 RCP 1A CLR OUTLET 1153DB4 1JNCBFT0496 RCP 2B,CLR OUTLET 1153DB4 1JNCBFT0497 RCP 2A CLR OUTLET 1153DB4 1JNCNFT0487 CEDM NORMAL ACU HXS OUT 1153DA5 1JNCNFT0507 CEDM NORM ACU A OUTLET FLOW 1153DA5 1JPCAPT0009 FL PO CLG PF 1 DSCH 1153GB6 1JPCBPT0010 FL PO CLG PP 1 DSCH 1153GB6 1JRCAPT0190A RCS PRESSURE WIDE RANGE 1153GDO 1JRCAPT0199A PZR OVER-PRESS TRIP TO SPS 1153GD9 1JRCBPT0190B RCS PRESSURE WIDE RANGE 1153GDO 1JRCBPT0199B PZR OVER-PRESS TRIP TO SPS 1153GD9 1JRCCPT0105 PRZR PRESS 1153GD9 1JRCCPT0199C PZR OVER-PRESS TRIP TO SPS 1153GD9 1JRCDPT0106 PRZR PRESS 1153GD9 1JRCDPT0199D PZR OVER-PRESS TRIP TO SPS 1153GD9 1JRCEPT0138 PRESSURIZER/RV HEAD VENT LEAK 1153GB9 1JRCNLT0752A N.R. REFUELING WATER LEVEL 1154HP5
f
't l
TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION MODEL 1JRCNLT0752B W.R. REFUELING WATER LEVEL 1154HP5 1JRCNLT0753A N.R. REFUELING WATER LEVEL 1154HP5 1JRCNLT0753B W.R. REFUELING WATER LEVEL 1154HP5 1JSGAPT0308 SG2 LN2 ATM DUMP N2 TANK PRESS 115 3GB8 1JSGAPT0313 SG2 LN SG1 LNl DUMP AIR SPPLY 115 3GB6 1JSGAPT0315 SG1 LN1 ATM DUMP N2 TANK PRESS 115 3GB8 1JSGBPT0301 SG1 LN2 ATM DMP N2 TANK PRESS 1153GB8 1JSGBPT0306 SGI LN2 SG2 LNl DUMP AIR SPPLY 115 3GB6 1JSGBPT0321 SG2 LNl ATM DUMP N2 TANK PRESS 1153GB8 1JSIAFT0306 LPSI PP A HDR DSCH FLOW 1153DB5 1JSIAFT0331 HPSI FLOW TO RC 1A 1153HB5 1JSIAFT0338 CONT SPRAY PP A DSCH FLOW 1153HB5 1JSIAFT0341 HPSI FLOW TO RC 1B 1153HB5 1JSIAFT0390 HPSI PP A LONG TERM CLG -1153HB7 1JSIALT0345 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 1JSIALT0349 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 1JSIALT0704 CONTMT SPRAY SYS A HDR WTR LVL 1153GB5 1JSIBFT0307 LPSI PP B HDR DSCH FLOW 1153DB5 1JSIBFT0311 HPSI FLOW TO RC 2A 1153HB5 1JSIBFT0321 HPSI FLOW TO RC 2B 1153HB5
l I
t J
l I
i'
TABLE Al ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 1 INSTRUMENT NUMBER DESCRIPTION MODEL 1JSIBFT0348 CONT SPRAY PP B DSCH FLOW 1153DB5 1JSIBFT0391 HPSI PP B LONG TERM CLG 1153HB7 1JSIBLT0344 SPRAY CHEM STORAGE TANK 1153DB4 1JSIBLT0348 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 1JSIBLT0705 CONTMT SPRAY SYS B HDR WTR LVL 1153GB5 1JSPAFT0005 ESP PP A DISCH FLOW 1153DB4 1JSPBFT0006 ESP PP B DISCH FLOW 1153DB4
li l
l l
I t
TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JAFAFT0040A AFW FLOW TO SG 1 1153DB5 2JAFAFT0040B AFW FLOW TO SG 2 1153DB5 2JAFAPT0018 AF PP A DISCH PRESS 1153GB9 2JAFBFT0041A AFW FLOW TO SG 1 1153DB5 2JAFBFT0041B AFW FLOW TO SG 2 1153DB5 2JAFBPT0017 AF PP B DISCH PRESS 1153GB9 2JCHALT0200 REFUELING WATER TANK LEVEL 1153DB5 2JCHALT0203A REFUELING WATER TANK LEVEL 1153DB5 2JCHAPT0212 CHARGING PUMPS TO REGEN HX 1153GP9 2JCHBFT0212 CHARGING PUMPS TO REGEN HX 1153HB5 2JCHBLT0201 REFUELING WATER TANK LEVEL 1153DB5 2JCHBLT0203B REFUELING WATER TANK LEVEL 1153DB5 2JCHCLT0203C REFUELING WATER TANK LEVEL 1153DB5 2JCHDLT0203D REFUELING WATER TANK LEVEL '1153DB5 2JCTALT0035 CNDS TK LEVEL 1153DB5 2JCTBLT0036 CNDS TK LEVEL 1153DB5 2JECAFT0533 ESS CHW A FLOW 1153DB4 2JECALT0015 ESS CHLD WTR SURGE TK A LEVEL 1153DB3 2JECBFT0534 ESS CHW B FLOW 1153DB4 2JECBLT0016 -
ESS CHLD WTR SURGE TK B LEVEL 1153DB3
,h TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JRCNLT0752B W.R. REFUELING WATER LEVEL 1154HP5 2JRCNLT0753A N.R. REFUELING WATER LEVEL 1154HP5 2JRCNLT0753B W.R. REFUELING WATER LEVEL 1154HP5 2JSGAPT0308 SG2 LN2 ATM DUMP N2 TANK 1153GBS 2JSGAPT0313 SG2 LN2 SG1 ON1 DUMP AIR SPPLY 1153GB6 2JSGAPT0315 SG1 LNl ATM DUMP N2 TANK- 1153GBS 2JSGBPT0301 SG1 LN2 ATM DUMP N2 TANK 1153GB8 2JSGBPT0306 SGl LN2 SG2LN1 DUMP AIR SPPLY 1153GB6 2JSGBPT0321 SG2 LN1 ATM. DUMP N2 TANK 1153GB8 2JSIAFT0306 LPSI PP A HDR DISCH FLOW 1153DB5 2JSIAFT0308 SPRAY CHEM PP A DISCH 1153DB3 2JSIAFT0331 HPSI FLOW TO RC lA 1153HB5 2JSIAFT0338 CONT SPRAY PP A DISCH FLOW 1153DB5 2JSIAFT0341 HPSI FLOW TO RC 1B 1153HB5 2JSIAFT0390 HPSI PP A LONG TERM CLG 1153HB7 2JSIALT0345 SPRAY CHEM STORAGE TANK 1153DB4 2JSIALT0349 SPRAY CHEM STORAGE TANK 1153DB4 2JSIALT0704 CONTMT SPRAY SYS A HDR WTR LVL 1153GB5 2JSIBFT0307 LPSI PP B HDR DISCH FLOW 1153DB5 2JSIBFT0309 SPRAY CHEM PP B DISCH 1153DB3
'l l
l f
'f i]i
TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JEWAFT0013 ECW PP A DISCH FLOW 1153DB5 2JEWAFT0151 ECWS FLOW TO ESS CHILLER A 1153DB5 2JEWALT0091 ESS LG WTG SURGE TK A LEVEL 1153DB4 2JEWBFT0014 ECW PP B DISCH FLOW 1153DB5 2 J EWBFT0152 ECWS FLOW TO ESS CHILLER B 1153DB5 2JEWBLT0092 ESS LG WTR SURGE TK B LEVEL 1153DB4 2JHCAPT0351A CONTMT PRESS A HI 1153GB6 2JHCAPT0352A CONTMT PRESS A 1153GB6 2JHCAPT0353A CONTMT PRESS WIDE RANGE A 1153GB7 2JHCAPT0492 CONTMNT PRESSURE 1153GB3 2JHCBPT0351B CONTMT PRESS B HI 1153GB6 2JHCBPT0352B CONTMT PRESS B 1153GB6 2JHCBPT0353B CONTMT PRESS WIDE RANGE B 1153GB7 2JHCBPT0493 CONTMNT PRESSURE 1153GB3 2JHCCPT0351C CONTMT PRESS C HI 1153GB6 2JHCCPT0352C CONTMT PRESS C 115 3GB6 2JHCDPT0351D CONTMT PRESS D HI 1153GB6 2JHCDPT0352D CONTMT PRESS D 1153GB6 2JNCAFT0474 RCP 1B CLR OUTLET FLOW 1153DB4 2JNCAFT0475 RCP lA CLR OUTLET FLOW 1153DB4
II TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JNCAFT0476 RCP 2B CLR OUTLET FLOW 1153DB4 2JNCAFT0477 RCP 2A CLR OUTLET FLOW 1153DB4 2JNCBFT0494 RCP 1B CLR OUTLET FLOW 1153DB4 2JNCBFT0495 RCP 1A CLR OUTLET FLOW 1153DB4 2JNCBFT0496 RCP 2B CLR OUTLET FLOW 1153DB4 2JNCBFT0497 RCP 2A CLR OUTLET FLOW 1153DB4 2JNCNFT0487 CEDM NORMAL ACU HXS OUT 1153DA5 2JNCNFT0507 CEDM NORM ACU A OUTLET FLOW 1153DA5 2JPCAPT0009 FL PO CLG PP 1 DISCH 1153GB6:
2JPCBPT0010 FL PO CLG PP 1 DISCH 1153GB6 2JRCAPT0190A RCS PRESSURE WIDE RANGE 1153GDO 2JRCAPT0199A PZR OVER-PRESS TRIP TO SPS 1153GD9 2JRCBPT0190B RCS PRESSURE WIDE RANGE 1153GDO 2JRCBPT0199B PZR OVER-PRESS TRIP TO SPS 1153GD9 2JRCCPT0105 PRESSURIZER PRESSURE 1153GD9
'JRCCPT0199C PZR OVER-PRESS TRIP TO SPS 1153GD9 2JRCDPT0106 PRESSURIZER PRESSURE 1153GD9 2JRCDPT0199D PZR OVER-PRESS TRIP TO SPS 1153GD9 2JRCEPT0138 PRESSURIZER/RV HEAD VENT LEAK 1153GB9 2JRCNLT0752A NOR. REFUELING WATER LEVEL 1154HP5
1
'i
TABLE A2 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 2 INSTRUMENT NUMBER DESCRIPTION MODEL 2JSIBFT0311 HPSI FLOW TO RC 2A 1153HB5 2JSIBFT0321 HPSI FLOW TO RC 2B 1153HB5 2JSIBFT0348 CONT SPRAY PP B DISCH FLOW 1153DB5 2JSIBFT0391 HPSI PP B LONG TERM CLG 1153HB7 2JSIBLT0344 SPRAY CHEM STORAGE TANK 1153DB4 2JSIBLT0348 SPRAY CHEM STORAGE TANK 1153DB4 2JSIBLT0705 CONTMT SPRAY SYS B HDR WTR LVL 1153GB5 2JSPAFT0005 ESP PP A DISCH FLOW 1153DB4 2JSPBFT0006 ESP PP B DISCH FLOW 1154DB4 2JSSNFT0056 PASS LIQ SAMPLE FLOW 1153DB3
j 1
f
(
f
'jl t
TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3 JAFAFT0040A AFW FLOW TO SG 1 1153DB5 3 JAFAFT0040B AFW FLOW TO SG 2 1153DB5 3JAFAPT0018 AF PP A DISCH PRESS 1153GB9 3JAFBFT0041A - AFW FLOW TO SG 1 1153DB5 3JAFBFT0041B AFW FLOW TO SG 2 1153DB5 =
3JAFBPT0017 AF PP B DISCH PRESS 1153GB9 3JCHALT0200 REFUELING WATER TANK LEVEL 1153DB5 3JCHALT0203A REFUELING WATER TANK LEVEL 1153DB5 3JCHAPT0212 CHARGING PUMPS TO REGEN HX 1153GB9 3JCHBFT0212 CHARGING PUMPS TO REGEN HX 1153HB5 3JCHBLT0201 REFUELING WATER TANK LEVEL 1153DB5 3JCHBLT0203B REFUELING WATER TANK LEVEL 1153DB5 3JCHCLT0203C REFUELING WATER TANK LEVEL 1153DB5 3JCHDLT0203D REFUELING WATER TANK LEVEL 1153DB5 3JCTALT0035 CNDS TK LEVEL 1153DB5 3JCTBLT0036 CNDS TK LEVEL 1153DB5 3JECAFT0533 ESS CHW A FLOW 1153DB4 3JECALT0015 ESS CHLD WTR SURGE TK A LEVEL 1153DB3 3JECBFT0534 ESS CHW B FLOW 1153DB4 3JECBLT0016 ESS CHLD WTR SURGE TK B LEVEL 1153DB3
~ ~
TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3JNCAFT0476 RCP 2B CLR OUTLET FLOW 1153DB4 3JNCAFT0477 RCP 2A CLR OUTLET FLOW 1153DB4 3JNCBFT0494 RCP 1B CLR OUTLET FLOW 1153DB4 3JNCBFT0495 RCP 1A CLR OUTLET FLOW 1153DB4 3JNCBFT0496 RCP 2B CLR OUTLET FLOW 1153DB4 3JNCBFT0497 RCP 2A CLR OUTLET FLOW 1153DB4 3JNCNFT0487 CEDM NORMAL ACU HXS OUTLET 1153DA5 3JNCNFT0507 CEDM NORM ACU A OUTLET FLOW 1153DA5 3JPCAPT0009 FL PO CLG PP 1 DISCH PRESS 1153GB6 3JPCBPT0010 FL PO CLG PP 1 DISCH PRESS 1153GB6 3JRCAPT0190A RCS PRESSURE WIDE RANGE 1153GDO 3JRCAPT0199A PZR OVER-PRESS TRIP TO SPS 1153GD9 3JRCBPT0190B RCS PRESSURE WIDE RANGE 1153GIO 3JRCBPT0199B PZR OVER-PRESS TRIP TO SPS 1153GD9 3JRCCPT0105 PRESSURIZER PRESSURE 1153GD9 3JRCCPT0199C PZR OVER-PRESS TRIP TO SPS 1153GIS 3JRCDPT0106 PRESSURIZER PRESSURE 1153GD9 3JRCDPT0199D PZR OVER-PRESS TRIP TO SPS 1153GD9 3JRCEPT0138 PRESSURIZER/RV HEAD VENT LEAK 1153GB9 3JRCNLT0752A N.R. REFUELING WATER LEVEL 1154HP5
~ I
,a
TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3 J EWAFT0013 ECW PP A DISCH FLOW 1153DB5 3 J EWAFT0151 ECWS FLOW TO ESS CHILLER A 1153DB5 3JEWALT0091 ESS LG WTR SURGE TK A LEVEL 1153DB4 t
3JEWBFT0014 ECW PP B DISCH FLOW 1153DB5 3JEWBFT0152 ECWS FLOW TO ESS CHILLER B 1153DB5 3JEWBLT0092 ESS LG WTR SURGE TK B LEVEL 1153DB4 3JHCAPT0351A CONTMT PRESS A HI 1153GB6 3JHCAPT0352A CONTMT PRESS A 1153GB6 3JHCAPT0353A CONTMT PRESS WIDE RANGE A 1153GB7 3JHCAPT0492 CONTMNT PRESSURE 1153GB3 3JHCBPT0351B CONTMT PRESS B HI 1153GB6 3JHCBPT0352B CONTMT PRESS B 1153GB6 3JHCBPT0353B CONTMT PRESS WIDE RANGE B 1153GB7 3JHCBPT0493 CONTMNT PRESSURE 1153GB3 3JHCCPT0351C CONTMT PRESS C HI 1153GB6 3JHCCPT0352C CONTMT PRESS C 1153GB6 3JHCDPT0351D CONTMT PRESS D HI 1153GB6 3JHCDPT0352D CONTMT PRESS D 1153GB6 3JNCAFT0474 RCP 18 CLR OUTLET FLOW 1153DB4 3JNCAFT0475 RCP 1A CLR OUTLET FLOW 1153DB4
TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER UNIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3JRCNLT0752B W.R. REFUELING WATER LEVEL 1154HP5 3JRCNLT0753A N.R. REFUELING WATER LEVEL 1154HP5 3JRCNLT0753B W.R. REFUELING WATER LEVEL 1154HP5 3JSGAPT0308 SG2 LN2 ATM DUMP N2 TANK PRESS 1153GB8 3JSGAPT0313 SG2 LN2 SGl LN1 DUMP AIR SPPLY 1153GB6 3JSGAPT0315 SG1 LN1 ATM DUMP N2 TANK'RESS 1153GB8 3JSGBPT0301 SGl LN2 ATM DUMP N2 TANK PRESS 1153GB8 3JSGBPT0306 SGl LN2 SG2 LN1 DUMP AIR SPPLY 1153GB6 3JSGBPT0321 SG2 LN1 ATM DUMP N2 TANK PRESS 1153GB8 3JSIAFT0306 LPSI PP A HDR DISCH FLOW 1153DB5 3JSIAFT0331 HPSI FLOW,TO RC 1A 1153HB5 3JSIAFT0338 CONT SPRAY PP A DISCH FLOW 1153DB5 3JSIAFT0341 HPSI FLOW TO RC 1B 1153HB5 3JSIAFT0390 HPSI PP A LONG TERM CLG FLOW 1153HB7 3JSIALT0345 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 3JSIALT0349 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 3JSIALT0704 ~ CONTMT SPRAY SYS A HDR WTR LVL 1153GB5 3JSIBFT0307 LPSI PP B HDR DISCH FLOW 1153DB5 3JSIBFT0311 HPSI FLOW TO RC 2A 1153HB5 3JSIBFT0321 HPSI FLOW TO RC 2B 1153HB5
TABLE A3 ROSEMOUNT TRANSMITTER INFORMATION SORTED BY UNIT AND INSTRUMENT NUMBER
'NIT 3 INSTRUMENT NUMBER DESCRIPTION MODEL 3JSIBFT0348 CONT SPRAY PP B DISCH FLOW 1153DB5 3JSIBFT0391 HPSI PP B LONG TERM CLG FLOW 1153HB7 3JSIBLT0344 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 3JSIBLT0348 SPRAY CHEM STORAGE TANK LEVEL 1153DB4 3JSIBLT0705 CONTMT SPRAY SYS B HDR WTR LVL 1153GB5 3JSPAFT0005 ESP PP A DISCH FLOW 1153DB4 3JSPBFT0006 ESP PP B DISCH FLOW 1153DB4 3JSSNFT0056 PASS LIQ SAMPLE FLOW 1153DB3
H J