Line 39: Line 39:
The area in question above the reactor water cleanup pump rooms has become a locked high radiation area in order to preclude future occurrences.      In addition, self-closing barriers will be constructed to replace the chains presently used to barricade permanent high radiation areas.      This modification will be completed by January 1, 1979.
The area in question above the reactor water cleanup pump rooms has become a locked high radiation area in order to preclude future occurrences.      In addition, self-closing barriers will be constructed to replace the chains presently used to barricade permanent high radiation areas.      This modification will be completed by January 1, 1979.
We trust this information will be satisfactory. Should      additional information be required, please feel free to contact me.
We trust this information will be satisfactory. Should      additional information be required, please feel free to contact me.
Very truly yours, VERMONT YANKEE NUCLEAR POWER CORPORATION r-{>v- {{ ~ ~ h'(
Very truly yours, VERMONT YANKEE NUCLEAR POWER CORPORATION r-{>v- (( ~ ~ h'(
D. E. Moody Manager of Operations DEM/em}}
D. E. Moody Manager of Operations DEM/em}}

Latest revision as of 00:00, 28 February 2020

Responds to NRC 781108 Ltr Re Violations Noted in Insp Rept 50-271/78-20.Corrective Actions:Personnel re-instruction, Locking of Areas,Installation of self-closing Doors. Doors
ML19256A311
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 12/05/1978
From: Moody D
VERMONT YANKEE NUCLEAR POWER CORP.
To: Brunner E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19256A310 List:
References
NUDOCS 7901050017
Download: ML19256A311 (2)


Text

{{#Wiki_filter:. p'I NER 10NT Y AN KEE NUCLEAR POWER CORPORATION %J SEVENTY SEV EN GROVE STR EET RuTLAso, VERMONT 05701 ENGINEERING OFFICE TURNPIKE RO AD WESTDORO. M ASS ACHUSETTS 01581 TELEPHONE 617 366-9011 WVY 78-101 December 5, 1978 United States Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention: Office of Inspection and Enforcement Mr. Eldon J. Brunner, Chief Reactor Operations and Nuclear Support Branch

Reference:

(a) License No. DPR-28 (Docket No. 50-271) (b) USNRC Letter to VYNPC, dated November 8, 1978 (Inspection Report 50-271/78-20)

Dear Sir:

Subject:

Response to I & E Inspection Report No. 78-20 This letter is written in response to Reference (b) which indicates that one of our activities was not conducted in full compliance with Nuclear Regulatory requirements. This alleged infraction was noted during an inspection conducted on September 18-22, 1978, at the Vermont Yankee Nuclear Power Station in Vernon, Vermont. Infor=ation is submitted as follows in answer to the alleged infraction contained in the enclosure to your letter: Item: Technical Specification 6.5.B.1 requires that in lieu of the " control device" or alarm signal required by paragraph

20. 203 (c) (2) of 10 CFR 20, each high radiation area in which the intetisity of radiation is 1000 mrem /hr or less be barricaded and conspicuously posted as a high radiation area.

Contrary to the above requirement, on September 20, 1978, an entrance providing access to a high radiation area was posted as a radiation area and the barricade was not distin-guishable as a barricade to a high radiation area. This area included the reactor water cleanup pump cubicles and adjacent areas with radiation levels as high as 900 mrem /hr. Contrary to the above requirement, on September 20, 1978, an entrance on the 252 ft. elevation of the Reactor Building 790105OO/7 m

United States Nuclear Regulatory Commission December 5, 1978

     ,       Attention: Office of Inspection and Enforcer;ent                        Page 2 leading to a high radiation area on a catwalk on top of the torus was not barricaded. Another entrance to the catwalk from the 213 ft. elevation of the Reactor Building was neither posted nor barricaded. Radiation levels on parts of the catwalk were as high as 200 mrem /hr.

Response: Plant personnel were reinformed and reminded of the require-ments for barricading and locking high radiation areas. The area in question above the reactor water cleanup pump rooms has become a locked high radiation area in order to preclude future occurrences. In addition, self-closing barriers will be constructed to replace the chains presently used to barricade permanent high radiation areas. This modification will be completed by January 1, 1979. We trust this information will be satisfactory. Should additional information be required, please feel free to contact me. Very truly yours, VERMONT YANKEE NUCLEAR POWER CORPORATION r-{>v- (( ~ ~ h'( D. E. Moody Manager of Operations DEM/em}}