| | title = Notification of Potential Part 21 on Deviation Identified by Flowserve Us, Inc | | | title = Notification of Potential Part 21 on Deviation Identified by Flowserve Us, Inc |
| | author name = Barry R D | | | author name = Barry R |
| | author affiliation = Flowserve US, Inc | | | author affiliation = Flowserve US, Inc |
| | addressee name = | | | addressee name = |
Line 18: |
Line 18: |
|
| |
|
| ==Subject:== | | ==Subject:== |
| US NRC 10CFR Part 21 Notification This is to notify the US Nuclear Regulatory Commission, in accordance with the provisions of 10 CFR Part 21 of a deviation identified by Flowserve US Inc.On July 13, 2009, Flowserve US Inc, Raleigh, NC was notified by Exelon -Byron Nuclear Power Station that a Borg -Warner (BW/IP) Solenoid Valve (BW/IP Part No: 86868) received by Exelon was being tested by their Electrical Maintenance Technician who stated "That the coil works correctly, but the valve did not actuate".On July 14, 2009 after inquiry by Flowserve, Exelon provided the following information: "The item was received and issued for installation. | | US NRC 10CFR Part 21 Notification This is to notify the US Nuclear Regulatory Commission, in accordance with the provisions of 10 CFR Part 21 of a deviation identified by Flowserve US Inc. |
| The Solenoid Valve was installed in the SV2 position on a PORV actuator that was removed from the plant and being rebuilt in the maintenance shop. When the PORV actuator was tested in the maintenance shop, the SR2 solenoid did not work correctly. | | On July 13, 2009, Flowserve US Inc, Raleigh, NC was notified by Exelon - Byron Nuclear Power Station that a Borg -Warner (BW/IP) Solenoid Valve (BW/IP Part No: 86868) received by Exelon was being tested by their Electrical Maintenance Technician who stated "That the coil works correctly, but the valve did not actuate". |
| This was on 7/09/2009. | | On July 14, 2009 after inquiry by Flowserve, Exelon provided the following information: |
| The failed solenoid was removed from the SV2 application and a new solenoid from stock installed in the SV2 application". | | "The item was received and issued for installation. The Solenoid Valve was installed in the SV2 position on a PORV actuator that was removed from the plant and being rebuilt in the maintenance shop. When the PORV actuator was tested in the maintenance shop, the SR2 solenoid did not work correctly. This was on 7/09/2009. The failed solenoid was removed from the SV2 application and a new solenoid from stock installed in the SV2 application". |
| On July 15, 2009 Flowserve informed Exelon, Mr. Randal Ciesiel, via email that a Return Material Authorization was being issued to have the Solenoid Valve returned and that a Part 21 Evaluation was opened within the Flowserve Quality System. Furthermore, Flowserve identified that they did no have the capability to perform the evaluation of this deviation to determine if a defect exists that could created a substantial safety hazard, as Flowserve is not knowledgeable of the application in which the Solenoid Valve is used.On July 24, 2009 Flowserve received correspondence from Exelon, Byron Nuclear Power Plant which outlined the problems encountered during a MS PORV actuator overhaul and how they concluded the subject Solenoid Valve was defective. | | On July 15, 2009 Flowserve informed Exelon, Mr. Randal Ciesiel, via email that a Return Material Authorization was being issued to have the Solenoid Valve returned and that a Part 21 Evaluation was opened within the Flowserve Quality System. Furthermore, Flowserve identified that they did no have the capability to perform the evaluation of this deviation to determine if a defect exists that could created a substantial safety hazard, as Flowserve is not knowledgeable of the application in which the Solenoid Valve is used. |
| Upon receipt of this information and return of the Solenoid Valves, Flowserve continued our evaluation. | | On July 24, 2009 Flowserve received correspondence from Exelon, Byron Nuclear Power Plant which outlined the problems encountered during a MS PORV actuator overhaul and how they concluded the subject Solenoid Valve was defective. Upon receipt of this information and return of the Solenoid Valves, Flowserve continued our evaluation. |
| Flowserve's evaluation discovered that on the returned Solenoid Valve "Body" part, there existed dimensional deviations that may cause the Solenoid Valve not to perform its intended FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: | | Flowserve's evaluation discovered that on the returned Solenoid Valve "Body" part, there existed dimensional deviations that may cause the Solenoid Valve not to perform its intended FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: 919 831 3369 www.flowserve.com zjE~c1 |
| 919 831 3369 www.flowserve.com zjE~c1 Page 2 function. | | |
| A check of these "Body" parts in the Flowserve inventory discovered that the dimensional deviation also existed on the 8 Body parts in the current inventory. | | Page 2 function. A check of these "Body" parts in the Flowserve inventory discovered that the dimensional deviation also existed on the 8 Body parts in the current inventory. It was determined that this part has been produced by the same subcontracted machining supplier since 2004, and therefore renders the Solenoid Valve Body parts suspect from that time. This Solenoid Valve Body part is used in Solenoid Valve assembly models identified by Borg-Warner/ Flowserve Part Numbers: |
| It was determined that this part has been produced by the same subcontracted machining supplier since 2004, and therefore renders the Solenoid Valve Body parts suspect from that time. This Solenoid Valve Body part is used in Solenoid Valve assembly models identified by Borg-Warner/ Flowserve Part Numbers: 86868 86868-1 90628 90628-1-Solenoid Valve Assembly -Normally Open-Solenoid Valve Assembly -Normally Closed-Solenoid Valve Assembly -Normally Open-Solenoid Valve Assembly -Normally Closed Based upon Flowserve, Raleigh information, Solenoid Valve Assemblies with the above model/part numbers have been provided to the following licensees and purchasers as Safety-Related products: Exelon Company -Byron Station: P.O. 00000375 REL 13388 P.O. 00000375 REL 13573 P.O. 00000375 REL 13613 P.O. 00000375 REL 13650 Exelon Company -Braidwood Station: P.O. 00000375 REL 13439 P.O. 00000375 REL 13514 P.O. 00000375 REL 13522 P.O. 00000375 REL 13566 P.O. 00000375 REL 13661 Korea Hydro & Nuclear Power: P.O. U050425333 Control Components Inc.: P.O. 304835 P.O. 306820 Qty.: 3 each.Qty.: 3 each.Qty.: 3 each.Qty.: 2 each.Qty.: I each.Qty.: 1 each.Qty.: 1 each.Qty.: 8 each.Qty.: 2 each.Qty.: 6 each.Qty.: 2 each.Qty.: 6 each.As Flowserve, Raleigh is not capable of determining if the defect could cause a substantial safety hazard based upon the service application which the Solenoid Valve Assembly may-be in, the licensees | | 86868 - Solenoid Valve Assembly - Normally Open 86868-1 - Solenoid Valve Assembly - Normally Closed 90628 - Solenoid Valve Assembly - Normally Open 90628-1 - Solenoid Valve Assembly - Normally Closed Based upon Flowserve, Raleigh information, Solenoid Valve Assemblies with the above model/part numbers have been provided to the following licensees and purchasers as Safety-Related products: |
| / purchasers of the subject Solenoid Valve Assembly will need to evaluate their applications to make this determination. | | Exelon Company - Byron Station: |
| FLOWSERVE US INC.FLOW CONTROL DIVISION 1900 S SAUNDERS RALEIGH, NC 27603 USA Telephone 919 831 0525 Facsimile: | | P.O. 00000375 REL 13388 Qty.: 3 each. |
| 919 831 3369 www.flowserve.com Page 3 Flowserve Raleigh is in the process of manufacturing the Solenoid Valve Assembly Bodies and will rebuild the Solenoid Valve Assemblies as they are returned by the licensees | | P.O. 00000375 REL 13573 Qty.: 3 each. |
| /purchasers.
| | P.O. 00000375 REL 13613 Qty.: 3 each. |
| Please contact Gary Shaw (919-831-3331) or Edna Ulsamar (919-831-3331) to obtain a Return Material Authorization. | | P.O. 00000375 REL 13650 Qty.: 2 each. |
| Respectfully Submitted, Robert D. Barry Manager, Quality Assurance Flowserve US Inc Flow Control Division Raleigh, NC 27603 FLOWSERVE US INC.FLOW CONTROL DIVISION 1900 S SAUNDERS RALEIGH, NC 27603 USA Telephone 919 831 0525 Facsimile: | | Exelon Company - Braidwood Station: |
| 919 831 3369 www.flowserve.com}} | | P.O. 00000375 REL 13439 Qty.: I each. |
| | P.O. 00000375 REL 13514 Qty.: 1 each. |
| | P.O. 00000375 REL 13522 Qty.: 1 each. |
| | P.O. 00000375 REL 13566 Qty.: 8 each. |
| | P.O. 00000375 REL 13661 Qty.: 2 each. |
| | Korea Hydro & Nuclear Power: |
| | P.O. U050425333 Qty.: 6 each. |
| | Control Components Inc.: |
| | P.O. 304835 Qty.: 2 each. |
| | P.O. 306820 Qty.: 6 each. |
| | As Flowserve, Raleigh is not capable of determining if the defect could cause a substantial safety hazard based upon the service application which the Solenoid Valve Assembly may-be in, the licensees / purchasers of the subject Solenoid Valve Assembly will need to evaluate their applications to make this determination. |
| | FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: 919 831 3369 www.flowserve.com |
| | |
| | Page 3 Flowserve Raleigh is in the process of manufacturing the Solenoid Valve Assembly Bodies and will rebuild the Solenoid Valve Assemblies as they are returned by the licensees / |
| | purchasers. Please contact Gary Shaw (919-831-3331) or Edna Ulsamar (919-831-3331) to obtain a Return Material Authorization. |
| | Respectfully Submitted, Robert D. Barry Manager, Quality Assurance Flowserve US Inc Flow Control Division Raleigh, NC 27603 FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: 919 831 3369 www.flowserve.com}} |
|
---|
Category:Deficiency Report (per 10CFR50.55e and Part 21)
MONTHYEARML21260A0072021-09-0909 September 2021 Ametek Solidstate Controls, Notification of Potential Defect - 10CFR Part 21 Report Re Omron Timer Relay ML19346H8732019-12-12012 December 2019 Westinghouse Electric Company - Notification of the Potential Existence of Defect Pursuant to 10 CFR Part 21 ML19120A1062019-04-17017 April 2019 Interim Report of Potential 10 CFR Part 21, Eaton Size 1 and 2 A200 Series Starters/Contactors ML19080A0592019-03-0808 March 2019 Interim Report of Potential 10CFR Part 21, Eaton A200 Series Starters/Contactors ML19053A5002019-02-0101 February 2019 Sor, Inc. Part 21 Notification of Deviation Sor R-Series Housing with Terminal Block ML18225A1182018-07-27027 July 2018 Ametek Solidstate Controls - Notification of Potential Defect-10CFR Part 21 ML17081A4532017-03-20020 March 2017 Part 21 - Plastic Jar Dedication Sampling ML17026A4142017-01-20020 January 2017 C&D Technologies, Inc. - Part 21 - Plastic Jar Dedication Sampling ML16342A9802016-11-28028 November 2016 Part 21 - Incorrect Capacitor Used on Circuit Boards ML16281A2712016-09-30030 September 2016 Part 21 - Safety Related Component Welding by an Unqualified Welder ML16243A4752016-08-26026 August 2016 Part 21 Safety Related Component Welding by an Unqualified Welder ML16162A6832016-06-0606 June 2016 Notification of Potential Defect- 10CFR Part 21 - Not Approved Current Transformers Installed in Safety Related Equipment ML16162A6802016-06-0303 June 2016 Part 21 - Not Approved Current Transformers Installed in Safety Related Equipment ML15103A4852015-04-0707 April 2015 Itt Engineered Valves - 2nd Interim Report to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M I Diaphragms, Customer Testing ML15049A4582015-02-0606 February 2015 Thermo Gamma-Metrics, LLC - Part 21 Report Regarding Shutdown Margin Monitor Environmental Qualification Noncompliance ML15022A6502015-01-20020 January 2015 Letter from Steven R. Eisenberg USNRC 10CFR Part 21 Notification ML14274A0522014-09-22022 September 2014 Final Report 10CFR Part 21 Evaluation Regarding Misaligned Separators in LCR-25 Standby Batteries, Revision 1 - Original Letter Did Not Include the List of Affected Utilities ML14261A1502014-09-17017 September 2014 Interim Report to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M1 Diaphragms, Customer Testing ML14226A6412014-08-14014 August 2014 Written Notification to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M1 Diaphragms, Customer Testing ML13165A3422013-06-12012 June 2013 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML13116A3032013-04-23023 April 2013 Notification of Potential Part 21 Report Re ESI Refurbished Emergency Diesel Generator Cylinder Heads May Have Valve Keeper Seals Missing ML12352A1232012-12-13013 December 2012 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML12348A1362012-12-13013 December 2012 Part 21 60-Day Interim Report Notification: Adequacy of Design Change in Am Magne-Blast Circuit Breakers ML12258A3992012-09-10010 September 2012 Potential Part 21 Issue Related to Tyco Timing Relay ML12255A0522012-09-0707 September 2012 Part 21 Report - Improper Specification of Inverter Capacitors ML1219103372012-07-0202 July 2012 Update 10 CFR Part 21 Notification of Defective Moore 535 Controllers ML12160A3642012-06-0707 June 2012 USNRC 10CFR Part 21 Notification Re Issue Concerning Potentially Reduced Flow Capacity of Wkm PORVs in Sizes 2 and Above ML12163A1282012-06-0707 June 2012 Part 21 Report - Published Flow Coefficients for Pilot Operated Relief Valves Greater than Actual ML12094A3712012-04-0202 April 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML12075A1062012-03-14014 March 2012 Notification of Potential Part 21 Re Defect on Arvan Electrical Terminal Blocks ML12066A1182012-03-0202 March 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML12097A3162012-03-0202 March 2012 Part 21 Report - Rosemont Pressure Tranmitters Out of Tolerance Condition ML12058A1412012-02-23023 February 2012 Part 21 Report - Rosemount Nuclear Instruments, Inc., Pressure Transmitter with Nonzero Based Calibrations ML11342A0722011-12-0606 December 2011 Limitorque Part 21 Notification Interim Report - Potential Defective Part in SMB-0 Heavy Spring Pack ML11363A1882011-12-0202 December 2011 10CFR21 Reporting of Defects and Non-Compliance - Engine Systems, Inc. Report No. 10CFR21-0098, Rev. 3, Amot Thermostatic Valve Element P/N: 9760X ML11336A3692011-12-0101 December 2011 Notification of Potential Part 21 Interim Report on Thermostatic Valve Failure on Palo Verde EDG ML11140A0872011-05-13013 May 2011 Sor Event 46821 Evaluation of Deviation for Defect ML11126A0152011-05-0404 May 2011 Sor, Inc., Pressure Switch with Possible Sub-Standard Electrical Lead Terminations ML1109701512011-04-0101 April 2011 Interim Report on Thermostatic Valve Failure on Palo Verde EDG ML1030601022010-10-29029 October 2010 Notification of Potential Part 21 Transfer of Information Concerning Control Components Inc. (CCI) Drag Valves ML1017204862010-06-16016 June 2010 Part 21 Notification - Tyco Electronic Relay Recall ML0934301402009-12-0202 December 2009 10CFR21 Reporting of Defects and Non-Compliance - Engine Systems, Inc. Report No. 1OCFR21-0098, Rev. 0, Amot Thermostatic Valve Element, P/N: 9760X ML0926802462009-09-23023 September 2009 Notification of Potential Part 21 on Reportable Occurrence Under 10 CFR Part 21: Firmware Anomaly in the Model RM-80 Radiation Monitoring System ML0925302432009-09-0808 September 2009 Notification of Potential Part 21 on Deviation Identified by Flowserve Us, Inc ML0907611882009-03-11011 March 2009 Part 21 Notification - Defective Hk and K-Line Circuit Breaker Tension Springs ML0823901062008-08-25025 August 2008 Notification of Potential Part 21 on Failure of F and G Switches ML0809906342008-04-0404 April 2008 Part 21 Notification Regarding Failure to Comply with the Requirements for Dedication of Commercial Grade Items ML0710002292007-04-0606 April 2007 Rosemount Nuclear Instruments, Inc., Submittal of Notification Under 10 CFR Part 21 for Certain Model 1152 Pressure Transmitters ML0709303812007-03-30030 March 2007 Rosemount Nuclear Part 21 - Rosemount Pressure Transmitter May Not Be Seismically Qualified ML0706802882007-03-0707 March 2007 Notification of Potential Part 21 on Defect in E7000 Relays 2021-09-09
[Table view] Category:Letter
MONTHYEARML24297A2702024-10-23023 October 2024 Notification of NRC Baseline Inspection and Request for Information: Inspection Report 05000455/2025002 RS-24-098, Units 1 and 2 - Supplement to License Amendment Request to Revise Technical Specifications 3.7.15, Spent Fuel Pool Boron Concentration, 3.7.16, Spent Fuel Assembly Storage, 4.3.1, Fuel Storage, Criticality2024-10-23023 October 2024 Units 1 and 2 - Supplement to License Amendment Request to Revise Technical Specifications 3.7.15, Spent Fuel Pool Boron Concentration, 3.7.16, Spent Fuel Assembly Storage, 4.3.1, Fuel Storage, Criticality ML24291A0012024-10-17017 October 2024 Submittal of Core Operating Limits Report, Cycle 25 RS-24-093, Response to Request for Additional Information - Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests2024-10-10010 October 2024 Response to Request for Additional Information - Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests RS-24-095, Relief Request I4R-19 and I4R-26, Associated with the Fourth and Fifth Inservice Inspection Intervals2024-10-10010 October 2024 Relief Request I4R-19 and I4R-26, Associated with the Fourth and Fifth Inservice Inspection Intervals ML24281A1502024-10-0707 October 2024 Request for Information for NRC Commercial Grade Dedication Inspection Report 05000454/2025010 and 05000455/2025010 ML24275A2442024-10-0303 October 2024 Reassignment of the U.S. Nuclear Regulatory Commission Branch Chief, Division of Operating Reactor Licensing ML24263A1272024-09-23023 September 2024 – Request for Additional Information (EPID 2023-LLA-0136) - Non-Proprietary BYRON 2024-0046, Cycle 27 Core Operating Limits Report2024-09-19019 September 2024 Cycle 27 Core Operating Limits Report RS-24-088, Relief Requests Associated with the Fifth Inservice Inspection Interval2024-09-13013 September 2024 Relief Requests Associated with the Fifth Inservice Inspection Interval IR 05000456/20240112024-09-12012 September 2024 Biennial Problem Identification and Resolution Inspection Report 05000456/2024011 and 05000457/2024011 ML24164A0032024-09-10010 September 2024 Issuance of Amendment Nos. 235 and 235 Revision of Technical Specifications for the Ultimate Heat Sink ML24250A1182024-09-0606 September 2024 Notification of an NRC Biennial Licensed Operator Requalification Program Inspection and Request for Information 05000454/LER-2024-001, Both Trains of Control Room Ventilation Temperature Control System Inoperable2024-09-0505 September 2024 Both Trains of Control Room Ventilation Temperature Control System Inoperable ML24227A0522024-08-29029 August 2024 Audit Plan for LAR to Remove ATWS Mtc Limit IR 05000456/20240052024-08-29029 August 2024 Updated Inspection Plan and Assessment Follow-Up Letter for Braidwood Station, Units 1 and 2 (Report 05000456/2024005 and 05000457/2024005) IR 05000454/20240052024-08-28028 August 2024 Updated Inspection Plan and Assessment Follow-Up Letter for Byron Station, Units 1 and 2 (Report 05000455/2024005 and 05000454/2024005) ML24225A1112024-08-13013 August 2024 Notification of NRC Fire Protection Team Inspection Request for Information ML24222A6772024-08-0909 August 2024 Response to Request for Additional Information for Application to Revise Technical Specifications to Adopt TSTF-591-A, Revise Risk Informed Completion Time (RICT) Program Revision 0 and Revise 10 CFR 50.69 License Condition IR 05000454/20240112024-08-0808 August 2024 Phase 2 Post- Approval License Renewal Report 05000454/2024011 IR 05000456/20240022024-08-0808 August 2024 Integrated Inspection Report 05000456/2024002 and 05000457/2024002 ML24172A1252024-07-26026 July 2024 Environmental Assessment and Finding of No Significant Impact Related to a Requested Increase in Ultimate Heat Sink Temperature (EPID L-2024-LLA-0075) - Transmittal Letter IR 05000454/20240022024-07-26026 July 2024 Integrated Inspection Report 05000454/2024002 and 05000455/2024002, and Exercise of Enforcement Discretion ML24179A3262024-07-23023 July 2024 LTR - Constellation - SG Welds and Nozzles (L-2023-LLR-0053, L-2023-LLR-0054, L-2023-LLR-0055, L-2023-LLR-0056) RS-24-064, Nuclear Radiological Emergency Plan Document Revisions2024-06-28028 June 2024 Nuclear Radiological Emergency Plan Document Revisions RS-24-066, Inservice Testing Interval Extension for Essential Service Water Valves Due to Required Use of Containment Chiller2024-06-25025 June 2024 Inservice Testing Interval Extension for Essential Service Water Valves Due to Required Use of Containment Chiller ML24163A3922024-06-25025 June 2024 Individual Notice of Consideration of Issuance of Amendments to Renewed Facility Operating Licenses, Proposed No Significant Hazards Consideration Determination, & Opportunity for a Hearing (EPID L-2024-LLA-0075)- Letter ML24170A7652024-06-19019 June 2024 Confirmation of Initial License Examination RS-24-061, Constellation Energy Generation, LLC, Response to NRC Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Examinations2024-06-14014 June 2024 Constellation Energy Generation, LLC, Response to NRC Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Examinations ML24164A2132024-06-13013 June 2024 Information Request to Support Upcoming Problem Identification and Resolution (Pi&R) Inspection at Braidwood Nuclear Plant RS-24-057, License Amendment to Technical Specification 3.7.9, Ultimate Heat Sink2024-06-0404 June 2024 License Amendment to Technical Specification 3.7.9, Ultimate Heat Sink IR 05000456/20240102024-05-31031 May 2024 License Renewal Phase 1 Report 05000456/2024010 RS-24-044, License Amendment to Transition to Framatome Gaia Fuel and Exemptions to 10 CFR 50.46 and 10 CFR 50 Appendix K. Attachments 1 to 11 Enclosed2024-05-28028 May 2024 License Amendment to Transition to Framatome Gaia Fuel and Exemptions to 10 CFR 50.46 and 10 CFR 50 Appendix K. Attachments 1 to 11 Enclosed RS-24-043, Application to Remove Power Distribution Monitoring System (Pdms) Details from Technical Specifications2024-05-24024 May 2024 Application to Remove Power Distribution Monitoring System (Pdms) Details from Technical Specifications ML24079A0762024-05-23023 May 2024 Issuance of Amendments to Adopt TSTF 264 ML24142A3352024-05-21021 May 2024 Quad Cities—Information Request to Support the NRC Annual Baseline Emergency Action Level and Emergency Plan Changes RS-24-055, 2023 Corporate Regulatory Commitment Change Summary Report2024-05-17017 May 2024 2023 Corporate Regulatory Commitment Change Summary Report BYRON 2024-0031, Completion of License Renewal Activities Prior to Entering the Period of Extended Operation2024-05-16016 May 2024 Completion of License Renewal Activities Prior to Entering the Period of Extended Operation ML24136A0132024-05-15015 May 2024 2023 Annual Radiological Environmental Operating Report ML24136A2452024-05-15015 May 2024 Notification of NRC Baseline Inspection and Request for Information; Inspection Report 05000457/2024004 IR 05000454/20240012024-05-10010 May 2024 Integrated Inspection Report 05000454/2024001; 05000455/2024001 and 07200068/2024001 BYRON 2024-0028, Annual Radiological Environmental Operating Report (AREOR)2024-05-0909 May 2024 Annual Radiological Environmental Operating Report (AREOR) ML24128A1212024-05-0707 May 2024 Response to Braidwood and Dresden FOF Dates Change Request (2025) BYRON 2024-0022, 2023 Regulatory Commitment Change Summary Report2024-05-0202 May 2024 2023 Regulatory Commitment Change Summary Report ML24122A6522024-05-0101 May 2024 Submittal of 2023 Annual Radioactive Effluent Release Report RS-24-041, Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests2024-04-30030 April 2024 Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests IR 05000456/20243012024-04-29029 April 2024 NRC Initial License Examination Report 05000456/2024301; 05000457/2024301 ML24116A0052024-04-25025 April 2024 Transmittal of Braidwood Station, Unit 1, Core Operating Limits Report, Braidwood Unit 1 Cycle 25 RS-24-026, License Amendment to Braidwood Station, Units 1 and 2, and Byron Station, Units 1 and 2, Technical Specifications 5.6.5, Core Operating Limits Report (COLR)2024-04-25025 April 2024 License Amendment to Braidwood Station, Units 1 and 2, and Byron Station, Units 1 and 2, Technical Specifications 5.6.5, Core Operating Limits Report (COLR) ML24116A1192024-04-25025 April 2024 2023 Annual Radioactive Effluent Release Report (ARERR) 2024-09-06
[Table view] |
Text
FLOWSERVE RALEIGH, 1 September 8, 2009 NRC Document Control Desk US Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
US NRC 10CFR Part 21 Notification This is to notify the US Nuclear Regulatory Commission, in accordance with the provisions of 10 CFR Part 21 of a deviation identified by Flowserve US Inc.
On July 13, 2009, Flowserve US Inc, Raleigh, NC was notified by Exelon - Byron Nuclear Power Station that a Borg -Warner (BW/IP) Solenoid Valve (BW/IP Part No: 86868) received by Exelon was being tested by their Electrical Maintenance Technician who stated "That the coil works correctly, but the valve did not actuate".
On July 14, 2009 after inquiry by Flowserve, Exelon provided the following information:
"The item was received and issued for installation. The Solenoid Valve was installed in the SV2 position on a PORV actuator that was removed from the plant and being rebuilt in the maintenance shop. When the PORV actuator was tested in the maintenance shop, the SR2 solenoid did not work correctly. This was on 7/09/2009. The failed solenoid was removed from the SV2 application and a new solenoid from stock installed in the SV2 application".
On July 15, 2009 Flowserve informed Exelon, Mr. Randal Ciesiel, via email that a Return Material Authorization was being issued to have the Solenoid Valve returned and that a Part 21 Evaluation was opened within the Flowserve Quality System. Furthermore, Flowserve identified that they did no have the capability to perform the evaluation of this deviation to determine if a defect exists that could created a substantial safety hazard, as Flowserve is not knowledgeable of the application in which the Solenoid Valve is used.
On July 24, 2009 Flowserve received correspondence from Exelon, Byron Nuclear Power Plant which outlined the problems encountered during a MS PORV actuator overhaul and how they concluded the subject Solenoid Valve was defective. Upon receipt of this information and return of the Solenoid Valves, Flowserve continued our evaluation.
Flowserve's evaluation discovered that on the returned Solenoid Valve "Body" part, there existed dimensional deviations that may cause the Solenoid Valve not to perform its intended FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: 919 831 3369 www.flowserve.com zjE~c1
Page 2 function. A check of these "Body" parts in the Flowserve inventory discovered that the dimensional deviation also existed on the 8 Body parts in the current inventory. It was determined that this part has been produced by the same subcontracted machining supplier since 2004, and therefore renders the Solenoid Valve Body parts suspect from that time. This Solenoid Valve Body part is used in Solenoid Valve assembly models identified by Borg-Warner/ Flowserve Part Numbers:
86868 - Solenoid Valve Assembly - Normally Open 86868-1 - Solenoid Valve Assembly - Normally Closed 90628 - Solenoid Valve Assembly - Normally Open 90628-1 - Solenoid Valve Assembly - Normally Closed Based upon Flowserve, Raleigh information, Solenoid Valve Assemblies with the above model/part numbers have been provided to the following licensees and purchasers as Safety-Related products:
Exelon Company - Byron Station:
P.O. 00000375 REL 13388 Qty.: 3 each.
P.O. 00000375 REL 13573 Qty.: 3 each.
P.O. 00000375 REL 13613 Qty.: 3 each.
P.O. 00000375 REL 13650 Qty.: 2 each.
Exelon Company - Braidwood Station:
P.O. 00000375 REL 13439 Qty.: I each.
P.O. 00000375 REL 13514 Qty.: 1 each.
P.O. 00000375 REL 13522 Qty.: 1 each.
P.O. 00000375 REL 13566 Qty.: 8 each.
P.O. 00000375 REL 13661 Qty.: 2 each.
Korea Hydro & Nuclear Power:
P.O. U050425333 Qty.: 6 each.
Control Components Inc.:
P.O. 304835 Qty.: 2 each.
P.O. 306820 Qty.: 6 each.
As Flowserve, Raleigh is not capable of determining if the defect could cause a substantial safety hazard based upon the service application which the Solenoid Valve Assembly may-be in, the licensees / purchasers of the subject Solenoid Valve Assembly will need to evaluate their applications to make this determination.
FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: 919 831 3369 www.flowserve.com
Page 3 Flowserve Raleigh is in the process of manufacturing the Solenoid Valve Assembly Bodies and will rebuild the Solenoid Valve Assemblies as they are returned by the licensees /
purchasers. Please contact Gary Shaw (919-831-3331) or Edna Ulsamar (919-831-3331) to obtain a Return Material Authorization.
Respectfully Submitted, Robert D. Barry Manager, Quality Assurance Flowserve US Inc Flow Control Division Raleigh, NC 27603 FLOWSERVE US INC. 1900 S SAUNDERS Telephone 919 831 0525 FLOW CONTROL DIVISION RALEIGH, NC 27603 USA Facsimile: 919 831 3369 www.flowserve.com