ML12258A399

From kanterella
Jump to navigation Jump to search
Potential Part 21 Issue Related to Tyco Timing Relay
ML12258A399
Person / Time
Site: Dresden, Peach Bottom, Byron, Braidwood, Limerick, Quad Cities, Zion, LaSalle  Constellation icon.png
Issue date: 09/10/2012
From: Franchuk T
Curtiss-Wright Flow Control Corp, Qualtech NP
To:
Office of Nuclear Reactor Regulation
References
48146
Download: ML12258A399 (5)


Text

09/11012012 U.S. Nuclear Regulatory Commission Operations Center Event Report Page I Part 21 (PAR)

Event#

48146 Rep Org: QUALTECH NP CURTISS WRIGHT Notification Date I Time: 08/01/2012 10:56 (EDT)

Supplier: QUALTECH NP CURTISS WRIGHT Event Date / Time: 08/01/2012 (EDT)

Last Modification: 09/10/2012 Region:

3 Docket #:

City:

CINCINNATI Agreement State:

Yes County:

License #:

State:

OH NRC Notified by: TIM FRANCHUK Notifications: TAMARA BLOOMER R3DO HQ Ops Officer: BILL HUFFMAN PART 21 GROUP EMAIL Emergency Class: NON EMERGENCY 10 CFR Section:

21.21 (d)(3)(i)

DEFECTS AND NONCOMPLIANCE POTENTIAL PART 21 ISSUE RELATED TO TYCO TIMING RELAY The following information was provided via facsimile:

"QualTech NP is providing this notification as a potential 10 CFR Part 21 issue. We have discovered a manufacturing defect in a timing relay which prevents the relay from operating at a specific setting. This relay was purchased as a commercial grade item and dedicated through our dedication process for safety related applications at our Cincinnati facility.

"The subject equipment is TYCO Model CNT-35-96, a timing relay with adjustable trip ranges from seconds up to 9,990 hours0.0115 days <br />0.275 hours <br />0.00164 weeks <br />3.76695e-4 months <br />. QualTech NP has recently identified a failure mode for this relay in that the device will not trip in the 10H setting. In communications with the manufacturer, they have confirmed that there is a flaw in the design that prevents this specific setting from tripping.

"QualTech NP has only sold this unit to two plants, both Exelon. We recognize, however that other utilities could have these installed. Based on the information in hand we are evaluating the need for a 10 CFR Part 21 notification. Since the item was qualified under the EPRI SQURTS [Seismic Qualification Reporting and Testing Standardization] Program, the recommended corrective action is to notify EPRI of the condition in order for SQURTS members to perform an impact evaluation.

"Additional details will be provided in the formal written report. Please contact Tim Franchuk at 513-528-7900, ext.

176 (office), [redacted] or via email tfranchuk@curtisswright.com for any additional information."

      • UPDATE ON 8/2/12 AT 1659 EDT FROM MARGIE BREWER TO DONG PARK ***

0911012012 U.S. Nuclear Regulatory Commission Operations Center Event Report Page2 Part 21 (PAR)

Event#

48146 The licensee has revised the third paragraph to read as follows:

"QualTech NP has only sold this unit to two plants, Exelon LaSalle and Quad Cities. We recognize, however that other utilities could have these installed. Based on the information in hand we are evaluating the need for a 10 CFR Part 21 notification. Since the item was qualified under the EPRI SQURTS [Seismic Qualification Reporting and Testing Standardization] Program, QualTech NP recognizes that other SQURTS members may have used the qualification basis as part of licensee dedication activities, and therefore, will notify EPRI of the condition."

Notified R3DO (Kunowski) and Part 21 group via email.

  • *
  • UPDATE AT 1803 EDT ON 09/10/12 FROM TIM FRANCHUK TO S. SANDIN ***

The following update was received via fax:

"QualTech NP is issuing this letter to provide additional details from our initial notification dated July 31, 2012 with regard to a potential defect in a timing relay (Log No. 2012-31-00 and 2012-031-01). The affected equipment is TYCO Model CNT 35-96 and the defect is the failure of the component to trip in the 10H setting. The following actions have been taken since the time of the initial notification.

"QualTech NP has notified EPRI, who in turn has notified SQURTS members of the defect in the 10H setting. In addition, supplemental testing has been performed to provide reasonable assurance that the defect is limited to the 10H setting.

"Please contact Tim Franchuk at 513-528-7900 ext. 176 (office) or via email ffranchuk@curtisswright.com for any additional information."

Notified R3DO Giessner) and Part 21 group via email.

From:

Brewer, Mamie To:

Cc:

Nemier. Maraik;a Green. Kevn; Franchuk. Timothy; BelMk

Subject:

Follow-up Letter Providing Additional Details from July 31, 2012 Notification Date:

Monday, September 10, 2012 6:14:47 PM Attachments:

Additional details letter ner initial 7-31-2012 Notification.Ddf Good evening:

Please confirm receipt of the submitted document referenced above faxed 9/10/2012 at 16:59.

I have attached a copy of the letter for reference.

Thank you.

Margie Brewer.

Document Control Supervisor QualTech NP, a business unit of Curtiss-Wright Flow Control Company 4600 East Tech Drive, Cincinnati, OH 45245 Office: 513.528.7900 ext.101 httoýllualtechno.cwfc com This e-mail and any files transmitted with it are proprietary and intended solely for the use of the individual or entity to whom they are addressed. If you have reason to believe that you have received this e-mail in error, please notify the sender and destroy this email and any attached files. Please note that any views or opinions presented in this e-mail are solely those of the author and do not necessarily represent those of the Curtiss-Wright Corporation or any of its subsidiaries.

Documents attached hereto may contain technology subject to government export regulations. Recipient is solely responsible for ensuring that any re-export, transfer or disclosure of this information is in accordance with applicable government export regulations. The recipient should check this e-mail and any attachments for the presence of viruses. Curtiss-Wright Corporation and its subsidiaries accept no liability for any damage caused by any virus transmitted by this e-mail.

QualTech NP 4600 East Tech Dr.

  • Cincinnati, Ohio 45245 Phone: 513.528.7900 e Fax: 513.528.9292 www. qualtechnp. cwfc.com cujil CDFIow Control Company QualTech NP September 10, 2012 To Whom It May Concern:

QualTech NP is issuing this letter to provide additional details from our initial notification dated July 31, 2012 with regard to a potential defect in a timing relay (Log No. 2012-31-00 and 2012-31-01). The affected equipment is TYCO Model CNT-35-96 and the defect is the failure of the component to trip in the 1 OH setting. The following actions have been taken since the time of the initial notification.

QualTech NP has notified EPRI, who in turn has notified SQURTS members of the defect in the I OH setting.

In addition, supplemental testing has been performed to provide reasonable assurance that the defect is limited to the I OH setting.

Please contact Tim Franchuk at 513-528-7900 ext.

176 (office) or via email tfranchukicurtisswright.com for any additional information.

Sincerly, Tim Franchuk Quality Assurance Director QualTech NP, a business unit of Curtiss-Wright Flow Control Company Office: 513-528-7900 ext. 176 tfranchuk@curtisswriaht.com

09/10/2012 MON 17:00 FAX 513 528 3845 o001/001 QualTech NP 4600 East Tech Dr. e Cincinnati, Ohio 45245 Phone: 513.528.7900 e Fax: 513.528.9292 www.qwaltechnp.cf-com QualTech NP September 10, 2012 To Whom It May Concern:

QualTech NP is issuing this letter to provide additional details from our initial notification dated July 31, 2012 with regard to a potential defect in a timing relay (Log No. 2012-31-00 and 2012-31-01). The affected equipment is TYCO Model CNT-35-96 and the defect is the failure of the component to trip in the 1 OH setting. The following actions have been taken since the time of the initial notification.

QualTech NP has notified EPRI, who in turn has notified SQURTS members of the defect in the 1011 setting.

In addition, supplemental testing has been performed to provide reasonable assurance that the defect is limited to the I OH setting.

Please contact Tim Franchuk at 513-528-7900 ext.

176 (office) or via email tfranchuk(curtisswridht.com for any additional information, Tim Franchuk Quality Assurance Director QualTech NP, a business unit of Curtiss-Wright Flow Control Company Office: 513-528-7900 ext. 176 tfranchukqcurtisswrightcom