ML12097A316

From kanterella
Jump to navigation Jump to search
Part 21 Report - Rosemont Pressure Tranmitters Out of Tolerance Condition
ML12097A316
Person / Time
Site: Millstone, Calvert Cliffs, Davis Besse, Salem, Oconee, Palo Verde, Catawba, Wolf Creek, Saint Lucie, Point Beach, Watts Bar, Hope Creek, Arkansas Nuclear, Braidwood, Crystal River, Diablo Canyon, Vogtle, Waterford, Farley, South Texas, San Onofre, Cook, Comanche Peak, LaSalle, 05000240  
Issue date: 03/02/2012
From: Pham D
Rosemount Nuclear Instruments
To:
Office of Nuclear Reactor Regulation
References
47716
Download: ML12097A316 (72)


Text

04103120O12 U.S. Nuclear Regulatory Commission Operations Center Event Report Pa.ee I Part 21 (PAR)

Event#

47716 Rep Org: ROSEMOUNT NUCLEAR Notification Date / Time: 03/02/2012 16:51 (EDT)

Supplier: ROSEMOUNT NUCLEAR Event Date / Time: 02/16/2012 (CST)

Last Modification: 04/03/2012 Region:

3 Docket #:

City:

CHANHASSEN Agreement State:

Yes County:

License #:

State:

MN NRC Notified by: DUYEN PHAM Notifications:

LAWRENCE DOERFLEIN R1DO HQ Ops Officer: JOHN KNOKE MARK FRANKE R2DO Emergency Class: NON EMERGENCY MARK RING R3DO 10 CFR Section:

JACK WHITTEN R4DO 21.21 UNSPECIFIED PARAGRAPH PART 21 GROUP-EMAIL PART 21 REPORT - ROSEMONT PRESSURE TRANSMITTERS OUT OF TOLERANCE CONDITION The following information was received by facsimile:

"During the course of qualification testing to replace certain diodes identified for obsolescence, an out of tolerance

.condition during steam pressure/temperature testing was observed on a test pressure transmitter in the qualification program. Through investigation into the out of tolerance condition, it was determined that the condition was not related to the replacement diode, but rather the result of the magnitude of a resistance change made to the transmitter temperature compensation circuitry during a final factory acceptance test. A brief description of the final acceptance test follows.

"During pressure transmitter final processing, a test is conducted on Model 1154 Series H pressure transmitters to assess the effects of ambient temperature changes on the 4mA to 20mA analog output. The temperature test is performed on each transmitter to verify the transmitter accuracy performance over normal operating temperatures from 40 F to 200 F. If the transmitter does not meet the acceptance criteria for the test, changes can be made to the compensating resistor values to optimize performance in the normal operating temperature range. If the resistance adjustment is too large, it has been determined that the accuracy of the pressure transmitter relative to the published steam pressure/temperature profile and accuracy specification may be exceeded during a steam pressure/temperature event.

"The magnitude of output shift during steam pressure/temperature conditions, that is attributable to the resistance changes made in final processing, is predictable based on the specific amount of resistance added or subtracted during the compensation process for each transmitter. Accordingly, RNII [Rosemount Nuclear Instruments, Inc]

has reviewed the production records for the potentially affected transmitters and a revised steam pressure/temperature accuracy specification has been established for each shipped pressure transmitter. The

04/03/2012 U.S. Nuclear Regulatory Commission Operations Center Event Report Pa-Part 21 (PAR)

Event#

47716 revised steam pressure/temperature accuracy specification has been listed by serial number.

"This revised specification supersedes the published steam pressure/temperature accuracy specification for all Model 1154 Series H pressure transmitters affected by this notification. Also note that for certain calibrations with large zero elevation and suppressions as defined in RNII's Part 21 Notification, dated February 23, 2012, an alternate steam pressure/temperature accuracy specification is also provided for pressure transmitters that are affected by both notifications. All other 1154 Series H published specifications remain unchanged.

"On February 23, 2012, it was concluded that a substantial safety hazard may exist. RNII does not have sufficient information to determine the potential safety impact in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased affected 1154 Series H pressure transmitters.

"The manufacturing rework procedure 01153-3000 has been updated to limit the amount of acceptable resistance that may be added or subtracted during final testing. A revised steam pressure/temperature accuracy specification for each pressure transmitter impacted by this notification has been determined.

"RNII recommends that users review the application where 1154 Series H pressure transmitters are used to determine if there are safety considerations related to the revised steam pressure/temperature accuracy specification."

The United States nuclear sites associated with this Part 21 are: Farley, D.C. Cook, Palo Verde, ANO-1, Calvert Cliffs, Point Beach, Oconee, Catawba, Waterford 3, Braidwood, La Salle, Davis Besse, Crystal River 3, Vogtle, Millstone, Diablo Canyon, Salem, Hope Creek, San Onofre, South Texas, Watts Bar, Comanche Peak, Wolf Creek, St. Lucie, Dominion Energy - Unspecified, and Northeast Nuclear Energy - Unspecified.

UPDATE FROM DUYEN PHAM TO PETE SNYDER ON 4/2/12 AT 1531 EDT***

The following information was received by facsimile:

This revision potentially affects the following commercial nuclear power plant sites in the United States:

1. Calvert Cliffs, 2. Millstone, 3. Hope Creek, 4. Salem, 5. Catawba, 6. Crystal River, 7. Farley, 8. Oconee, 9. St.

Lucie, 10. Vogtle, 11. Watts bar,

12. Braidwood, 13. Davis Besse, 14. D.C. Cook, 15. LaSalle, 16. Point Beach, 17. Arkansas Nuclear One, 18.

Comanche Peak, 19. Diablo Canyon, 20. Palo Verde, 21. San Onofre, 22. South Texas Project, 23. Waterford 3, and 24. Wolf Creek.

"Note Notification #1 [EN #47693], dated 23 February 2012 (and revised on 2 April 2012) impacts ALL 1154 Series H pressure transmitters range codes 4 to 8 shipped since 1988. This does NOT impact the 1154SH9 since the 11 54SH9 has a wider steam pressure/temperature specification. The revised specification is the same for all affected transmitters.

"Note Notification #2 [this report - EN #47716], dated 2 March 2012 (and revised as of today [3 April 2012]) impacts only a subset of 1154 Series H pressure transmitters range codes 4 to 9 shipped from March 1994 to February 2012. This is a smaller affected population and does include the range 9 in the scope. The revised specification for this second issue is serial number dependent and only affects the transmitters listed in Appendix A [of the full part 21 report]."

Notified R1 DO(Caruso), R2DO(McCoy), R3DO(Bloomer), R4DO(Haire), and Part 21 Group via email.

2

  • k * * * * * * * * * * * **

8200 Market Boulevard Chanhassen, MN 55317 USA Tel 1 (952) 949-5210 Fax 1 (952) 949-5201 www.RosemountNuclear.com RNII.Info@EmersonProcess.com No. of Pages:

Including cover page 70 To:

NRC Operations Center Fax Number:

(301) 816-5151 Date:

Friday, March 2, 2012 Tuesday, April 3, 2012 From:

Duyen Pham, Quality Manager Phone:

(952) 949-5363 E-Mail:

Duyen.Pham@Emerson.com

Subject:

Revision to 02 MARCH 2012 Notification under 10 CFR Part 21 on certain Rosemount Model 1154 Series H Pressure Transmitters Rosemount Nuclear Instruments, Inc. is submitting the attached revised notification.

This revision affects the Appendix A attachments for seven companies and/or pant sites and Appendix B which was revised on 2 April 2012.

Below is a list of the seven companies and/or plant sites with the revised Appendix A attachments:

1. American Electric Power Co Inc / DC Cook Nuclear Plant
2. Bechtel Power Corp / Point Beach Nuclear Plant
3. Emerson Process Management Asia Pacific Pte Ltd
4. Emerson Process Management SL
5. Korea Hydro and Nuclear Power Co Ltd
6. Southern California Edison Co
7. Westinghouse Electric Co LLC Note Notification #1, dated 23 February 2012 (and revised on 2 April 2012) impacts ALL 1154 Series H pressure transmitters range codes 4 to 8 shipped since 1988. This does NOT impact the 1154SH9 since the 1154SH9 has a wider steam pressure/temperature specification. The revised specification is the same for all affected transmitters.

Notification #2, dated 2 March 2012 (and revised as of today), impacts only a subset of 1154 Series H pressure transmitters range codes 4 to 9 shipped from March 1994 to February 2012. This is a smaller affected population and does include the range 9 in the scope. The revised specification for this second issue is serial number dependant and only affects the transmitters listed in Appendix A.

Please contact me if you have any questions.

Sincerely, Duyen Pham Quality Manager Rosemount Nuclear Instruments, Inc.

Page 1 of 3 Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 USA Tel 1 (952) 949-5210 Fax 1 (952) 949-5201 www.RosemountNuclear.com 3 April 2012 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk Re: Revision to 02 MARCH 2012 Notification under 10 CFR Part 21 on certain Rosemount Model 1154 Series H Pressure Transmitters Note: This revision to the 02 March 2012 notification only affects the following:

x Appendix A: The List of Affected Transmitters by Company Name and/or Plant Site was revised for seven companies and/or plant sites.

x Appendix B: Was updated on 2 April 2012 to include a revision to the 23 February 2012 notification.

Following is the 02 MARCH 2012 notification letter in its entirety. In addition, the revised Appendices A & B as noted above are attached:

Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that certain Model 1154 Series H pressure transmitters may not perform within the published steam pressure/temperature accuracy specification.

Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.

The potentially affected Model 1154 Series H pressure transmitters were shipped from RNII from March 1994 to February 2012. Model 1154 pressure transmitters (versus Model 1154 Series H) are not affected by this notification.

1.0 Name and address of the individual providing the information:

Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 2.0 Identification of items supplied:

See the enclosed Attachment A for the list of transmitters shipped by customer and/or plant site.

Page 2 of 3 3.0 Identification of firm supplying the item:

Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:

During the course of qualification testing to replace certaindiodes identified for obsolescence, an out of tolerance condition during steam pressure/temperature testing was observed on a test pressure transmitter in the qualification program. Through investigation into the out of tolerance condition, it was determined that the condition was not related to the replacement diode, but rather the result of the magnitude of a resistance change made to the transmitter temperature compensation circuitry during a final factory acceptance test. A brief description of the final acceptance test follows.

During pressure transmitter final processing, a test is conducted on Model 1154 Series H pressure transmitters to assess the effects of ambient temperature changes on the 4mA to 20mA analog output. The temperature test is performed on each transmitter to verify the transmitter accuracy performance over normal operating temperatures from 40°F to 200°F. If the transmitter does not meet the acceptance criteria for the test, changes can be made to the compensating resistor values to optimize performance in the normal operating temperature range. If the resistance adjustment is too large, it has been determined that the accuracy of the pressure transmitter relative to the published steam pressure/temperature profile and accuracy specification may be exceeded during a steam pressure/temperature event.

The magnitude of output shift during steam pressure/temperature conditions, that is attributable to the resistance changes made in final processing, is predictable based on the specific amount of resistance added or subtracted during the compensation process for each transmitter. Accordingly, RNII has reviewed the production records for the potentially affected transmitters and a revised steam pressure/temperature accuracy specification has been established for each shipped pressure transmitter. The revised steam pressure/temperature accuracy specification is listed in the enclosed attachments by serial number.

This revised specification supersedes the published steam pressure/temperature accuracy specification for all Model 1154 Series H pressure transmitters affected by this notification.

Also note that for certain calibrations with large zero elevation and suppressions as defined in Rosemount Nuclear Instruments, Inc.s Part 21 Notification dated February 23, 2012 (included as Attachment B), an alternate steam pressure/temperature accuracy specification is also provided for pressure transmitters that are affected by both notifications. All other 1154 Series H published specifications remain unchanged.

On February 23, 2012, it was concluded that a substantial safety hazard may exist.

Rosemount Nuclear Instruments, Inc. does not have sufficient information to determine the potential safety impact in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased affected 1154 Series H pressure transmitters.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALESORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

QP070495 1154DH5RH 0534662 3May07 FARLEYNUCLEARPLANT 1905858

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

QP070495 1154DH5RH 0534664 4May07 FARLEYNUCLEARPLANT 1905858

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 ALABAMAPOWERCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALESORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

501177 1154HH5RBN0166 0539862 16Sep09 KOEBERG 2396525

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 ALPRETCONTROLSPECIALISTSLTD

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

UPDATE 01535464 1154SH9RCN0156 0539215 5Jun09 DCCOOKNUCLEARPLANT 2347513

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 01536923 1154DH5RCN0156 0539870 16Sep09 DCCOOKNUCLEARPLANT 2392690

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 01536923 1154DH5RCN0156 0539871 16Sep09 DCCOOKNUCLEARPLANT 2392690

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 01536923 1154DH5RCN0156 0539873 16Sep09 DCCOOKNUCLEARPLANT 2392690

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 01537316 1154DH4RCN0156 0539932 30Sep09 DCCOOKNUCLEARPLANT 2403584

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 01537316 1154DH4RCN0156 0539937 30Sep09 DCCOOKNUCLEARPLANT 2403584

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 01541723 1154DH4RCN0156 0541250 5May10 DCCOOKNUCLEARPLANT 2512645

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 01541723 1154DH4RCN0156 0541262 5May10 DCCOOKNUCLEARPLANT 2512645

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 01541723 1154DH4RCN0156 0541267 5May10 DCCOOKNUCLEARPLANT 2512645

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 01541729 1154SH9RCN0156 0541212 27Apr10 DCCOOKNUCLEARPLANT 2513136

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 01541803 1154DH6RCN0156 0541277 7May10 DCCOOKNUCLEARPLANT 2513761

+/-(1%URL+1%span)

+/-(1%URL+4.75%span)

+/-(2%URL+3.75%span) 01542901 1154SH9RCN0156 0541418 22Jun10 DCCOOKNUCLEARPLANT 2546636

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 01542912 1154DH5RCN0156 0541478 22Jun10 DCCOOKNUCLEARPLANT 2548806

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 01542912 1154DH5RCN0156 0541479 22Jun10 DCCOOKNUCLEARPLANT 2548806

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A CHANGED

+/-(2%URL+0.75%span)

N/A

+/-(2%URL+3.75%span)

N/A CHANGED

+/-(2%URL+0.75%span)

N/A

+/-(2%URL+2%span)

N/A CHANGED

+/-(2%URL+0.75%span)

N/A 01531736REV002 1154DH5RCN0156 0538609 12Feb09 DCCOOKNUCLEARPLANT 2260137

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 01539862REV001 1154HH5RAN0156 0540447 16Dec09 DCCOOKNUCLEARPLANT 2456616

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 01541692REV002 1154DH5RCN0156 0541232 21Apr10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 01541692REV002 1154DH5RCN0156 0541234 21Apr10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 01541692REV002 1154DH5RCN0156 0541235 21Apr10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 01541692REV002 1154DH5RCN0156 0541236 21Apr10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 01541692REV002 1154DH5RCN0156 0541272 10May10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 01541692REV002 1154DH5RCN0156 0541273 10May10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 01541692REV002 1154DH5RCN0156 0541274 10May10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 01541692REV002 1154DH5RCN0156 0541275 10May10 DCCOOKNUCLEARPLANT 2512693

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(2%URL+0.5%span) 01547364 1154SH9RCN0156 0544571 27Aug11 DCCOOKNUCLEARPLANT 3072523

+/-(2%URL+0.5%span)

APPENDIXA:10CFRPART21NOTIFICATIONREVISED20MARCH2012 AMERICANELECTRICPOWERCOINC

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

01547364 1154SH9RCN0156 0544564 31Aug11 DCCOOKNUCLEARPLANT 3072523

+/-(2%URL+0.5%span) 01547364 1154SH9RCN0156 0544569 27Aug11 DCCOOKNUCLEARPLANT 3072523 REVISED

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

500228062 1154SH9RA 0519798 4Aug00 PALOVERDEWHSE 617500

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 500228062 1154SH9RA 0519799 4Aug00 PALOVERDEWHSE 617500

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 500528113 1154SH9RA 0538867 26Mar09 PALOVERDEWHSE 2267348

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 500528113 1154SH9RA 0538866 26Mar09 PALOVERDEWHSE 2267348

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 500545364 1154SH9RA 0541426 22Jun10 PALOVERDEWHSE 2551739

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 ARIZONAPUBLICSERVICECO/PINNACLEWESTCAPITAL

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

1154SH9RB 0508189 1994 ANO1 B600329 +/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A 1154SH9RB 0508250 1994 ANO1 B600329 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 ARKANSASPOWER

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

14458GX 1154SH9RC 0511104 26Sep96 CALVERTCLIFFSNPP CC98013

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 14458GX 1154SH9RC 0511103 26Sep96 CALVERTCLIFFSNPP CC98013

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 BALTIMOREGAS&ELECTRIC

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

UPDATE

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

DUPLICATES/N

DELETED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

DUPLICATES/N

DELETED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 25494824FPAJP0200001REV0 1154DH6RC 0543974 25May11 POINTBEACHNUCLEARPLANT 3064364

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 25494824FPAJP0200001REV0 1154DH6RC 0543855 17Jun11 POINTBEACHNUCLEARPLANT 3072024

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

DUPLICATES/N

DELETED 25494824FPAJP0200002REV0 1154DH6RC 0543855 17Jun11 POINTBEACHNUCLEARPLANT 3064364

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

CHANGED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3%span)

+/-(2%URL+2%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3%span)

+/-(2%URL+2%span) 2678974

+/-(1%URL+1%span) 10Feb11 25494924FPAJP0200002REV0 1154DH6RC 0542896 10Feb11 POINTBEACHNUCLEARPLANT 2678431

+/-(1%URL+1%span) 25494924FPAJP0200002REV0 1154DH6RC 0542870 21Feb11 POINTBEACHNUCLEARPLANT 2678974

+/-(1%URL+1%span) 25494924FPAJP0200001REV.0 1154DH6RC 0542708 4Feb11 POINTBEACHNUCLEARPLANT 2678431

+/-(1%URL+1%span) 25494924FPAJP0200001REV.0 1154DH6RC 0542707 21Feb11 POINTBEACHNUCLEARPLANT 2678431

+/-(1%URL+1%span) 25494924FPAJP0200001REV.0 1154DH6RC 0542706 4Feb11 POINTBEACHNUCLEARPLANT

+/-(1%URL+1%span) 25494924FPAJP0200001REV.0 1154DH6RC 0542704 POINTBEACHNUCLEARPLANT 2678431

+/-(1%URL+1%span)

APPENDIXA:10CFRPART21NOTIFICATIONREVISED20MARCH2012 BECHTELPOWERCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

25494824FPAJP0200001REV0 1154DH6RC 0543853 17Jun11 POINTBEACHNUCLEARPLANT 3072024

+/-(1%URL+1%span) 25494824FPAJP0200001REV0 1154DH6RC 0543854 17Jun11 POINTBEACHNUCLEARPLANT 3072024 REVISED

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00088847 1154DH7RCN0120 0522841 23Jan02 BRUCESTORES 968604

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

P.O.00092464 1154SH9RCN0120 0523868 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+2.5%span)

N/A P.O.00092464 1154SH9RCN0120 0523866 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A P.O.00092464 1154SH9RCN0120 0523948 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A P.O.00092464 1154SH9RCN0120 0523865 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A P.O.00092464 1154SH9RCN0120 0523890 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A P.O.00092464 1154SH9RCN0120 0523947 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A P.O.00092464 1154SH9RCN0120 0523864 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A P.O.00092464 1154SH9RCN0120 0523867 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A P.O.00092464 1154SH9RCN0120 0523950 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A P.O.00092464 1154SH9RCN0120 0523949 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A P.O.00092464 1154SH9RCN0120 0523952 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A P.O.00092464 1154SH9RCN0120 0523863 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A P.O.00092464 1154SH9RCN0120 0523889 25Sep02 BRUCESTORES 1044852

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A PO00092466 1154DH5RCN0120 0523873 27Jun02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

PO00092466 1154DH5RCN0120 0523937 25Sep02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

PO00092466 1154DH5RCN0120 0523936 25Sep02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

PO00092466 1154DH5RCN0120 0523870 27Jun02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

PO00092466 1154DH5RCN0120 0523874 27Jun02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

PO00092466 1154DH5RCN0120 0523932 25Sep02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

PO00092466 1154DH5RCN0120 0523872 27Jun02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

PO00092466 1154DH5RCN0120 0523933 25Sep02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

PO00092466 1154DH5RCN0120 0523935 25Sep02 BRUCESTORES 1037558

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 BRUCEPOWERLP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

421866 1154SH9RBN0034 0536224 4Feb08 UNSPECIFIED 2060266

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 421866 1154SH9RBN0034 0536223 6Feb08 UNSPECIFIED 2060266

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 424595 1154HH5RCN0148 0538435 22Jan09 CALVERTCLIFFSNPP 2228993

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 424595 1154HH5RCN0088 0538408 22Jan09 CALVERTCLIFFSNPP 2228993

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 424595 1154HH5RCN0148 0538433 22Jan09 CALVERTCLIFFSNPP 2228993

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 427145 1154HH5RCN0148 0540233 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 427145 1154HH5RCN0148 0540231 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 427145 1154HH5RCN0148 0540228 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 427145 1154SH9RCN0132 0540206 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 427145 1154HH5RCN0148 0540229 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 427145 1154HH5RCN0148 0540232 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 427145 1154SH9RCN0132 0540200 8Dec09 CALVERTCLIFFSNPP 2437563

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 429122 1154HH5RCN0148 0541579 16Jul10 CALVERTCLIFFSNPP 2546395

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 429122 1154HH5RCN0148 0541580 16Jul10 CALVERTCLIFFSNPP 2546395

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 429122 1154HH5RCN0148 0541581 16Jul10 CALVERTCLIFFSNPP 2546395

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 CONSTELLATIONENERGYGROUP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

45590738 1154SH9RCN0034 0537250 4Aug08 UNSPECIFIED 2113239 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 DOMINIONENERGY

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00080497 1154SH9RB 0534225 27Feb07 OCONEESITE 1799802

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 00080497 1154SH9RB 0534226 27Feb07 OCONEESITE 1799802

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 00081158 1154SH9RB 0534228 27Mar07 OCONEESITE 1806682

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 00100642 1154SH9RB 0536303 29Feb08 CATAWBANUCLEARSTA 2071534

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 00100987REV001 1154SH9RB 0536437 18Mar08 OCONEESITE 2081256

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 00100987REV001 1154SH9RB 0536433 18Mar08 OCONEESITE 2081256

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 00120544REV002 1154HH5RB 0539907 9Oct09 OCONEESITE 2382468

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00120544REV002 1154HH5RB 0539904 9Oct09 OCONEESITE 2382468

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00120544REV002 1154HH5RB 0539905 9Oct09 OCONEESITE 2382468

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00120544REV002 1154HH5RB 0539906 9Oct09 OCONEESITE 2382468

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00120544REV002 1154HH5RB 0539884 14Sep09 OCONEESITE 2382468

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 00120544REV002 1154HH5RB 0539883 14Sep09 OCONEESITE 2382468

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

NE23301 1154SH9RB 0532613 17Jul06 OCONEESITE 1726450

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A NE23301 1154SH9RB 0532614 17Jul06 OCONEESITE 1726450

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 DUKEENERGYCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

EPMJS/36RCZ0007P 1154DH4RC 0533943 15Feb07 MITSUBISHIHEAVYINDUSTRIES 1829988

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 EMERSONJAPANLTD

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

41634362 1154SH9RA 0541178 16Apr10 NEKPOWERPLANTKRSKO 2506770

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 EMERSONPROCESSMANAGEMENTAG

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

UPDATE 808051991 1154DH5RAN0167 0545190 13Dec11 FUJIANFUQINGNUCLEARPOWERCOLTD 3177991

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 808052061 1154DH5RAN0167 0545191 13Dec11 FANGJIASHANNUCLEARPOWERPLANT 3177430

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 808052061 1154DH5RAN0167 0545192 13Dec11 FANGJIASHANNUCLEARPOWERPLANT 3177430

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A CHANGED

+/-(2%URL+1.25%span)

N/A

+/-(2%URL+2.25%span)

N/A CHANGED

+/-(2%URL+0.75%span)

N/A

+/-(2%URL+1.25%span)

N/A CHANGED

+/-(2%URL+1.5%span)

N/A HP80800664/CPB 1154SH9RAN0170 0544621 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A HP80800664/CPB 1154DH5RAN0152 0544657 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800664/CPB 1154DH5RAN0152 0544659 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800664/CPB 1154DH6RAN0152 0544734 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80800664/CPB 1154DH5RAN0152 0544752 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80800664/CPB 1154DH5RAN0152 0544753 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800664/CPB 1154DH5RAN0152 0544754 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800664/CPB 1154DH5RAN0152 0544757 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316475

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80800666/CPB 1154DH6RAN0152 0544619 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316478

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800666/CPB 1154DH4RAN0152 0544652 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316478

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP 80800666/CPB 1154DH5RAN0152 0544653 3 Nov 11 HONGYANHE NUCLEAR POWER STATION 2316478

+/-(1%URL+1%span)

+/-(1%URL+1 5%span)

+/-(2%URL+0 5%span)

+/-(2%URL+0.5%span)

HP80800662/CPB 1154SH9RAN0170 0542681 8Feb11 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(2%URL+0.5%span)

APPENDIXA:10CFRPART21NOTIFICATION20MARCH2012 EMERSONPROCESSMANAGEMENTASIAPACIFICPTELTD HP80800662/CPB 1154SH9RAN0170 0542679 8Feb11 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(2%URL+0.5%span)

HP80800662/CPB 1154SH9RAN0170 0542680 8Feb11 HONGYANHENUCLEARPOWERSTATION 2316473 HP80800666/CPB 1154DH5RAN0152 0544653 3Nov11 HONGYANHENUCLEARPOWERSTATION 2316478

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

DUPLICATES/N DELETED

+/-(1%URL+2%span)

+/-(2%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

DUPLICATES/N DELETED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span)

CHANGED

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

DUPLICATES/N DELETED

+/-(1%URL+3%span)

+/-(2%URL+2%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

CHANGED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542739 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542738 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542737 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542736 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH6RAN0152 0542735 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH6RAN0152 0542734 13May11 FUJIANNINGDENUCLEARPOWERSTATION REVISED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

CHANGED

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

CHANGED

+/-(1%URL+2%span)

+/-(2%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

CHANGED

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

DUPLICATES/N DELETED

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

+/-(2%URL+2.75%span)

N/A CHANGED

+/-(2%URL+0.75%span)

N/A

+/-(1%URL+3%span)

+/-(2%URL+2%span)

DUPLICATES/N DELETED

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80805197/CP1 1154DH5RAN0172 0543017 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80805197/CP1 1154DH4RAN0173 0543062 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80805197/CP1 1154DH5RAN0167 0543063 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80805197/CP1 1154DH5RAN0167 0543064 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80805197/CP1 1154DH5RAN0167 0543065 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

HP80805197/CP1 1154DH5RAN0167 0543066 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80805197/CP1 1154DH5RAN0167 0543099 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH4RAN0152 0543595 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154SH9RAN0170 0542880 30Mar11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(2%URL+0.5%span)

HP80800669/CPB 1154DH5RAN0152 0542856 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542855 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542854 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542741 13May11 FUJIANNINGDENUCLEARPOWERSTATION 2316461

+/-(1%URL+1%span)

HP80800669/CPB 1154DH5RAN0152 0542740 13May11 FUJIANNINGDENUCLEARPOWERSTATION HP80805197/CP1 1154DH5RAN0167 0543100 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80805197/CP1 1154DH5RAN0167 0543101 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

HP80805197/CP1 1154DH5RAN0167 0543103 20Apr11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597429

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80805204/CP1 1154DH5RAN0167 0543109 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80805204/CP1 1154DH5RAN0167 0543110 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80805204/CP1 1154DH5RAN0167 0543111 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

HP80805204/CP1 1154DH5RAN0172 0543178 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80805204/CP1 1154DH5RAN0167 0543198 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80805204/CP1 1154DH5RAN0167 0543199 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80805204/CP1 1154DH5RAN0167 0543200 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span)

HP80805204/CP1 1154DH5RAN0167 0543201 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

HP80805204/CP1 1154DH5RAN0167 0543202 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

HP80805204/CP1 1154DH4RAN0173 0543222 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597397

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 2597497

+/-(1%URL+1%span)

HP80805206/CP1 1154DH5RAN0167 0543698 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597497

+/-(1%URL+1%span)

HP80805206/CP1 1154DH5RAN0167 0543697 20May11 FANGJIASHANNUCLEARPOWERPLANT HP80805199/CP1 1154DH5RAN0167 0543643 20May11 FUJIANFUQINGNUCLEARPOWERCOLTD 2597488

+/-(1%URL+1%span)

REVISED

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

CHANGED

+/-(1%URL+2%span)

+/-(2%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

CHANGED

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

DUPLICATES/N DELETED

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

DUPLICATES/N DELETED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(1%URL+6.5%span)

+/-(2%URL+5.5%span)

CHANGED

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543411 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543410 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH6RAN0152 0543344 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2598572

+/-(1%URL+1%span)

HP80805673/CPB 1154DH6RAN0152 0543343 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805313/CPB 1154DH5RAN0141 0542391 14Jan11 LINGAONUCLEARPLANT 2598572

+/-(1%URL+1%span)

HP80805313/CPB 1154DH5RAN0141 0542390 14Jan11 LINGAONUCLEARPLANT 2598572

+/-(1%URL+1%span)

HP80805313/CPB 1154DH6RAN0141 0542389 14Jan11 LINGAONUCLEARPLANT 2597497

+/-(1%URL+1%span)

HP80805206/CP1 1154DH5RAN0172 0543710 20May11 FANGJIASHANNUCLEARPOWERPLANT 2597497

+/-(1%URL+1%span)

HP80805206/CP1 1154DH5RAN0167 0543699 20May11 FANGJIASHANNUCLEARPOWERPLANT

+/-(1%URL+3%span)

+/-(2%URL+2%span)

CHANGED

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80805673/CPB 1154DH4RAN0152 0543555 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

CHANGED

+/-(1%URL+3%span)

+/-(2%URL+2%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

CHANGED

+/-(1%URL+3%span)

+/-(2%URL+2%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

CHANGED

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

DUPLICATES/N DELETED

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543563 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543562 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543561 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543560 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543559 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

HP80805673/CPB 1154DH5RAN0152 0543558 20Apr11 YANGJIANGNUCLEARPOWERCOLTD HP80805673/CPB 1154DH4RAN0152 0543552 20Apr11 YANGJIANGNUCLEARPOWERCOLTD 2626350

+/-(1%URL+1%span)

REVISED

HP80805674/CPB 1154SH9RAN0170 0545077 2Dec11 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A HP80805674/CPB 1154DH5RAN0152 0545147 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80805674/CPB 1154DH4RAN0152 0545364 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

HP80805674/CPB 1154DH6RAN0152 0545397 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80805674/CPB 1154DH6RAN0152 0545398 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80805674/CPB 1154DH5RAN0152 0545400 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80805674/CPB 1154DH5RAN0152 0545401 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80805674/CPB 1154DH5RAN0152 0545402 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

HP80805674/CPB 1154DH5RAN0152 0545404 5Jan12 YANGJIANGNUCLEARPOWERCOLTD 2626827

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

DUPLICATES/N DELETED

+/-(1%URL+5%span)

+/-(2%URL+4%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80805675/CPB 1154SH9RAN0170 0543401 6May11 YANGJIANGNUCLEARPOWERCOLTD 2627660

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A ADDED

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span)

CHANGED

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

CHANGED 2673688

+/-(1%URL+1%span)

HP80806213/CPB 1154DH4RAN0141 0542968 25Mar11 LINGAONUCLEARPLANT 2627660

+/-(1%URL+1%span)

HP80806213/CPB 1154DH4RAN0141 0542966 25Mar11 LINGAONUCLEARPLANT 2673688

+/-(1%URL+1%span)

HP80805675/CPB 1154DH5RAN0152 0543378 6May11 YANGJIANGNUCLEARPOWERCOLTD 2627660

+/-(1%URL+1%span)

HP80805675/CPB 1154DH6RAN0152 0543377 6May11 YANGJIANGNUCLEARPOWERCOLTD 2627660

+/-(1%URL+1%span)

HP80805675/CPB 1154DH5RAN0152 0543376 6May11 YANGJIANGNUCLEARPOWERCOLTD

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80806389/CPB 1154DH5RAN0150 0544030 14Oct11 QINSHANIINUCLEARPLANT 2685254

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80806389/CPB 1154DH5RAN0150 0544031 14Oct11 QINSHANIINUCLEARPLANT 2685254

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

HP80806389/CPB 1154DH4RAN0149 0544033 14Oct11 QINSHANIINUCLEARPLANT 2685254

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 2673688

+/-(1%URL+1%span)

HP80806213/CPB 1154DH5RAN0141 0542999 25Mar11 LINGAONUCLEARPLANT HP80806213/CPB 1154DH6RAN0141 0542971 25Mar11 LINGAONUCLEARPLANT 2673688

+/-(1%URL+1%span)

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

REVISED

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

HP80800661/CPB 1154DH5RAN0152 0540578 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

HP80800661/CPB 1154DH5RAN0152 0540930 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

HP80800661/CPB 1154DH5RAN0152 0540577 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

HP80800661/CPB 1154DH5RAN0152 0540929 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80800661/CPB 1154DH5RAN0152 0540574 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80800661/CPB 1154DH6RAN0152 0540906 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800661/CPB 1154DH4RAN0152 0541079 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800661/CPB 1154DH4RAN0152 0541076 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800661/CPB 1154DH5RAN0152 0540579 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800661/CPB 1154DH4RAN0152 0540833 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800661/CPB 1154DH4RAN0152 0540834 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800661/CPB 1154DH4RAN0152 0540835 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800661/CPB 1154DH4RAN0152 0541078 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800661/CPB 1154DH5RAN0152 0540576 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800661/CPB 1154DH5RAN0152 0540928 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800661/CPB 1154DH6RAN0152 0540907 8Apr10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800661/CPB 1154SH9RAN0170 0542159 2Dec10 HONGYANHENUCLEARPOWERSTATION 2316472

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A HP80800662/CPB 1154DH5RAN0152 0542446 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span)

HP80800662/CPB 1154DH5RAN0152 0542447 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span)

HP80800662/CPB 1154DH6RAN0152 0542395 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

HP80800662/CPB 1154DH5RAN0152 0542393 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

HP80800662/CPB 1154DH5RAN0152 0542443 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80800662/CPB 1154DH4RAN0152 0542551 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80800662/CPB 1154DH5RAN0152 0542444 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

HP80800662/CPB 1154DH4RAN0152 0542553 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

HP80800662/CPB 1154DH5RAN0152 0542394 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80800662/CPB 1154DH5RAN0152 0542392 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80800662/CPB 1154DH5RAN0152 0542445 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

HP80800662/CPB 1154DH4RAN0152 0542549 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80800662/CPB 1154DH4RAN0152 0542554 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

HP80800662/CPB 1154DH5RAN0152 0542442 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

HP80800662/CPB 1154DH6RAN0152 0542396 29Dec10 HONGYANHENUCLEARPOWERSTATION 2316473

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

HP80800667/CPB 1154DH5RAN0152 0541476 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span)

HP80800667/CPB 1154DH5RAN0152 0541477 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

HP80800667/CPB 1154DH5RAN0152 0541475 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span)

HP80800667/CPB 1154DH5RAN0152 0541367 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

HP80800667/CPB 1154DH6RAN0152 0541311 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80800667/CPB 1154DH4RAN0152 0541517 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 EMERSONPROCESSMANAGEMENTCHINALTD

HP80800667/CPB 1154SH9RAN0170 0542387 28Dec10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A HP80800667/CPB 1154DH5RAN0152 0541369 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

HP80800667/CPB 1154DH5RAN0152 0541366 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

HP80800667/CPB 1154DH4RAN0152 0541519 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

HP80800667/CPB 1154DH4RAN0152 0541494 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800667/CPB 1154DH4RAN0152 0541520 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800667/CPB 1154DH5RAN0152 0541368 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800667/CPB 1154DH5RAN0152 0541370 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

HP80800667/CPB 1154DH4RAN0152 0541496 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800667/CPB 1154DH4RAN0152 0541521 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800667/CPB 1154DH4RAN0152 0541495 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800667/CPB 1154DH4RAN0152 0541522 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316374

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

HP80800670/CPB 1154DH5RAN0152 0541461 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316470

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

HP80800670/CPB 1154DH6RAN0152 0541463 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316470

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

HP80800670/CPB 1154SH9RAN0170 0542042 28Dec10 FUJIANNINGDENUCLEARPOWERSTATION 2316470

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A HP80800670/CPB 1154DH6RAN0152 0541462 15Jul10 FUJIANNINGDENUCLEARPOWERSTATION 2316470

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

OP50021648/CNE 1154DH5RAN0141 0536354 27Jun08 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

OP50021648/CNE 1154DH5RAN0141 0537413 16Jan09 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

OP50021648/CNE 1154SH9RAN0143 0536313 27Jun08 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A OP50021648/CNE 1154DH5RAN0141 0538354 16Jan09 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

OP50021648/CNE 1154DH5RAN0141 0538355 16Jan09 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

OP50021648/CNE 1154DH5RAN0141 0538358 16Jan09 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

OP50021648/CNE 1154DH5RAN0141 0538359 16Jan09 DAYABAYNUCLEARPOWERCOMPLEX 2041726

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

OP82010800/CPB 1154DH5RAN0150 0538971 21Aug09 QINSHANIINUCLEARPLANT 2263492

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

OP82010800/CPB 1154DH5RAN0150 0538969 21Aug09 QINSHANIINUCLEARPLANT 2263492

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

OP82010800/CPB 1154DH4RAN0149 0538976 21Aug09 QINSHANIINUCLEARPLANT 2263492

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

OP82010801/CPB 1154DH5RAN0150 0540140 28May10 QINSHANIINUCLEARPLANT 2264295

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

OP82010801/CPB 1154DH5RAN0150 0540139 28May10 QINSHANIINUCLEARPLANT 2264295

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

OP82010801/CPB 1154DH5RAN0150 0540141 28May10 QINSHANIINUCLEARPLANT 2264295

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

OP82010801/CPB 1154DH5RAN0150 0540138 28May10 QINSHANIINUCLEARPLANT 2264295

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

66452/DA 1154HH5RBN0155 538310 2Jan09 ANGRA1SGRPROJECT 2234654

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 66452/DA 1154HH5RBN0155 0538321 2Jan09 ANGRA1SGRPROJECT 2234654

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 EMERSONPROCESSMANAGEMENTLTDA

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

34992357 1154SH9RA 0526794 22Dec03 C.N.VANDELLOSII 1263769

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 EMERSONPROCESSMANAGEMENTSERVICIOSSL

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

UPDATE 34998023 1154SH9RB 0531668 16Mar06 C.N.ALMARAZ 1597947

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 35002753 1154HH5RA 0534887 14Jun07 C.N.NUCLEARASCO 1868149

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 35002753 1154HH5RA 0534889 14Jun07 C.N.NUCLEARASCO 1868149

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 35009158 1154DH4RBN0026 0538882 23Mar09 ASCOVANDELLOS 2250235

+/-5.50inH2O

+/-(5.50inH2O+0.25%span)

N/A 35009158 1154DH4RBN0026 0538885 23Mar09 ASCOVANDELLOS 2250235

+/-5.50inH2O

+/-(5.50inH2O+0.25%span)

N/A 35009461 1154HH5RB 0539118 22May09 C.N.NUCLEARASCO 2265654

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 35009524 1154DH5RA 0538716 26Feb09 VANDELLOSII 2265652

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 35010360 1154SH9RB 0539544 24Jul09 C.N.NUCLEARASCO 2316084

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 35012289 1154SH9RB 0540848 18Feb10 C.N.ALMARAZ 2443627

+/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A 35014500 1154SH9RA 0542724 3Feb11 ASCOVANDELLOS 2587905

+/-(2%URL+0.5%span)

+/-(2%URL+0.5%span)

N/A DELETED 35014500 1154SH9RA 0542726 3Feb11 ASCOVANDELLOS 2587905

+/-(2%URL+0.5%span)

+/-(2%URL+0.5%span)

N/A DELETED 35014500 1154SH9RA 0542727 3Feb11 ASCOVANDELLOS 2587905

+/-(2%URL+0.5%span)

+/-(2%URL+0.5%span)

N/A DELETED 35014500 1154SH9RA 0542728 3Feb11 ASCOVANDELLOS 2587905

+/-(2%URL+0.5%span)

+/-(2%URL+0.5%span)

N/A DELETED 35014500 1154SH9RA 0542729 3Feb11 ASCOVANDELLOS 2587905

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A ADDED

+/-(2%URL+1.25%span)

N/A CHANGED

+/-(2%URL+1.5%span)

N/A

+/-(2%URL+1.5%span)

N/A CHANGED

+/-(2%URL+1.25%span)

N/A 35014658 1154SH9RBN0060 0541936 12Nov10 ASCOVANDELLOSII 2595531

+/-(3%URL+1%span)

+/-(3%URL+6.5%span)

N/A 35014658 1154SH9RBN0060 0541937 12Nov10 ASCOVANDELLOSII 2595531

+/-(3%URL+1%span)

+/-(3%URL+3.75%span)

N/A 35014658 1154SH9RBN0060 0541938 12Nov10 ASCOVANDELLOSII 2595531

+/-(3%URL+1%span)

+/-(3%URL+4.5%span)

N/A 35014658 1154HH5RB 0541939 12Nov10 ASCOVANDELLOSII 2595531

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 35014658 1154HH5RB 0541940 12Nov10 ASCOVANDELLOSII 2595531

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(3%URL+1.25%span)

N/A DUPLICATES/N DELETED

+/-(3%URL+6.5%span)

N/A

+/-(3%URL+1.25%span)

N/A DUPLICATES/N DELETED

+/-(3%URL+5.75%span)

N/A 2595531

+/-(3%URL+1%span) 35014658 1154SH9RAN0060 0543796 14Jun11 ASCOVANDELLOSII

+/-(2%URL+0.5%span) 35014658 1154SH9RAN0060 0543795 14Jun11 ASCOVANDELLOSII 2595531

+/-(3%URL+1%span)

APPENDIXA:10CFRPART21NOTIFICATIONREVISED20MARCH2012 EMERSONPROCESSMANAGEMENTSL 35014500 1154SH9RA 0542730 9Feb11 ASCOVANDELLOS 2587905

+/-(2%URL+0.5%span) 35014500 1154SH9RA 0543246 25Mar11 ASCOVANDELLOS 2587905 REVISED

+/-(3%URL+1.25%span)

N/A DUPLICATES/N DELETED

+/-(3%URL+5.75%span)

N/A

+/-(3%URL+2.25%span)

N/A DUPLICATES/N DELETED

+/-(3%URL+2.75%span)

N/A

+/-(3%URL+1.5%span)

N/A DUPLICATES/N DELETED

+/-(3%URL+4.5%span)

N/A

+/-(5.50inH2O+1.75%span)

N/A CHANGED

+/-(5.50inH2O+0.5%span)

N/A

+/-(5.50inH2O+1.75%span)

N/A CHANGED

+/-(5.50inH2O+0.5%span)

N/A

+/-(5.50inH2O+2%span)

N/A CHANGED

+/-(5.50inH2O+0.25%span)

N/A

+/-(5.50inH2O+1.25%span)

N/A CHANGED

+/-(5.50inH2O+0.75%span)

N/A 35017804 1154DH4RBN0026 0545060 28Oct11 C.N.ALMARAZ 3132994

+/-5.50inH2O

+/-(5.50inH2O+0.25%span)

N/A 2639947

+/-5.50inH2O 35015497 1154DH4RBN0026 0543049 21Mar11 C.N.NUCLEARASCO 2655972

+/-5.50inH2O 35015273 1154DH4RBN0026 0542693 16Feb11 C.N.ALMARAZ 2639947

+/-5.50inH2O 35015273 1154DH4RBN0026 0542688 16Feb11 C.N.ALMARAZ 2639947

+/-5.50inH2O 35015273 1154DH4RBN0026 0542685 16Feb11 C.N.ALMARAZ 2595531

+/-(3%URL+1%span) 35014658 1154SH9RAN0060 0543799 14Jun11 ASCOVANDELLOSII 2595531

+/-(3%URL+1%span) 35014658 1154SH9RAN0060 0543798 14Jun11 ASCOVANDELLOSII 35014658 1154SH9RAN0060 0543797 14Jun11 ASCOVANDELLOSII 2595531

+/-(3%URL+1%span)

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

REVISED

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

10128836 1154SH9RCN0012 0533025 23Aug06 WATERFORD3NUCLEAR 1739327

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 10128836 1154SH9RCN0012 0533020 23Aug06 WATERFORD3NUCLEAR 1739327

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 10166776 1154SH9RCN0012 0535675 18Dec07 WATERFORD3NUCLEAR 1982772

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 10166776 1154SH9RCN0012 0535671 18Dec07 WATERFORD3NUCLEAR 1982772

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 10166776 1154SH9RCN0012 0535674 18Dec07 WATERFORD3NUCLEAR 1982772

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 ENTERGYCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00076959REL00161REV001 1154SH9RA 0536113 9Jan08 BRAIDWOODWAREHOUSE 2003982 +/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A 00076959REV001REL00136 1154DH4RB 0535039 17Jul07 LASALLEWAREHOUSE 1911938 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 00076959REV002REL00249 1154HH5RB 0539134 20May09 BRAIDWOODWAREHOUSE 2336680 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00076959REV002REL00249 1154HH5RB 0539135 20May09 BRAIDWOODWAREHOUSE 2336680 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00423255REV003 1154SH9RA 0535258 13Aug07 BRAIDWOODWAREHOUSE 1931470 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 EXELONGENERATIONCOLLC

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

45168981 1154SH9RBN0037 0531685 8Mar06 DAVISBESSEPLANT 1596217

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 45168981 1154SH9RBN0037 0531686 6Mar06 DAVISBESSEPLANT 1596217

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 45168981 1154SH9RBN0037 0531683 6Mar06 DAVISBESSEPLANT 1596217

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 45168981 1154SH9RBN0037 0531684 6Mar06 DAVISBESSEPLANT 1596217

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 45341123 1154SH9RBN0037 0541531 21Jun10 DAVISBESSEPLANT 2568616

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 FIRSTENERGYCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

R200101710 1154SH9RBN0105 0520377 17Jan01 UNSPECIFIED 783157

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 FISHERROSEMOUNTKOREALTD

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

38777 1154DH4RBN0026 0511448 6May96 UNSPECIFIED

+/-5.50inH2O

+/-(5.50inH2O+2%span)

N/A 38777 1154DH4RBN0026 0511447 6May96 UNSPECIFIED

+/-5.50inH2O

+/-(5.50inH2O+2%span)

N/A 38777 1154DH4RBN0026 0511446 6May96 UNSPECIFIED

+/-5.50inH2O

+/-(5.50inH2O+1.25%span)

N/A 40855 1154DH5RB 0513081 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 40855 1154DH5RB 0513080 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 40855 1154DH5RB 0513077 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 40855 1154DH5RB 0513070 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 40855 1154DH5RB 0513071 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 40855 1154DH5RB 0513072 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 40855 1154DH5RB 0513074 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 40855 1154DH5RB 0513076 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 40855 1154DH5RB 0513078 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 40855 1154DH5RB 0513069 28Feb97 UNSPECIFIED 108687

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 FISHERROSEMOUNTSA

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00061111 1154SH9RA 0524644 18Dec02 STLUCIESTORES 1103051

+/-(2%URL+0.5%span)

+/-(2%URL+3%span)

N/A 00061111 1154SH9RA 0524641 18Dec02 STLUCIESTORES 1103051

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 00061111 1154SH9RA 0524640 18Dec02 STLUCIESTORES 1103051

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 00061111 1154SH9RA 0524642 18Dec02 STLUCIESTORES 1103051

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 00063186 1154HH6RA 0525149 4Mar03 STLUCIESTORES 1140143

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 00063186 1154HH6RA 0525148 4Mar03 STLUCIESTORES 1140143

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00063186 1154HH6RA 0525153 4Mar03 STLUCIESTORES 1140143

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00063186 1154HH6RA 0525152 4Mar03 STLUCIESTORES 1140143

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 00090532REV002 1154SH9RA 0532047 20Apr06 STLUCIESTORES 1646676

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 FLORIDAPOWERANDLIGHTCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00062611 1154HH6RA 0523480 7Jun02 CRYSTALRIVERUNIT3 1010811 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

F340342D 1154DH6RAN0037 0513495 5May97 CRYSTALRIVERUNIT3 149618

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

F340342D 1154DH6RAN0037 0513496 5May97 CRYSTALRIVERUNIT3 149618

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

F741538D 1154HH5RAN0018 0512912 11Dec96 UNSPECIFIED

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

F741538D 1154HH5RAN0018 0512907 11Dec96 UNSPECIFIED

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 FLORIDAPOWERCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

7045892 1154DH5RH 0519803 8Aug00 VOGTLEELECTRICGENERATINGPLANT 726160

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7070664 1154DH5RH 0532193 11May06 VOGTLEELECTRICGENERATINGPLANT 1671752 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 7070664 1154DH5RH 0532192 11May06 VOGTLEELECTRICGENERATINGPLANT 1671752 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7071636 1154DH5RH 0532626 6Jul06 VOGTLEELECTRICGENERATINGPLANT 1703718 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7071636 1154DH5RH 0532628 6Jul06 VOGTLEELECTRICGENERATINGPLANT 1703718 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7071636 1154DH5RH 0532627 6Jul06 VOGTLEELECTRICGENERATINGPLANT 1703718 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 7071835 1154HH5RH 0532630 9Jul06 VOGTLEELECTRICGENERATINGPLANT 1710522 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7075037 1154SH9RH 0534414 12Apr07 VOGTLEELECTRICGENERATINGPLANT 1821700 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 7075037 1154SH9RH 0534578 24Apr07 VOGTLEELECTRICGENERATINGPLANT 1821700 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 7077388 1154DH5RH 0534935 11Jun07 VOGTLEELECTRICGENERATINGPLANT 1901678 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7077388 1154DH5RH 0534933 11Jun07 VOGTLEELECTRICGENERATINGPLANT 1901678 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7077388 1154DH5RH 0534934 11Jun07 VOGTLEELECTRICGENERATINGPLANT 1901678 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7079738 1154DH5RH 0536006 3Dec07 VOGTLEELECTRICGENERATINGPLANT 1998930 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7079738 1154DH5RH 0536005 3Dec07 VOGTLEELECTRICGENERATINGPLANT 1998930 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7081445 1154DH5RH 0536414 14Mar08 VOGTLEELECTRICGENERATINGPLANT 2072553 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7082019 1154DH6RH 0536532 7Apr08 VOGTLEELECTRICGENERATINGPLANT 2093541 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7082294 1154HH4RH 0536844 3Jun08 VOGTLEELECTRICGENERATINGPLANT 2100638 +/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 7088427 1154DH5RH 0539770 26Aug09 VOGTLEELECTRICGENERATINGPLANT 2373688 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 7088427 1154DH5RH 0539775 26Aug09 VOGTLEELECTRICGENERATINGPLANT 2373688 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 7088427 1154DH5RH 0539768 26Aug09 VOGTLEELECTRICGENERATINGPLANT 2373688 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 7088427 1154DH5RH 0539776 26Aug09 VOGTLEELECTRICGENERATINGPLANT 2373688 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 7088427 1154DH5RH 0539774 26Aug09 VOGTLEELECTRICGENERATINGPLANT 2373688 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7093513 1154DH6RH 0541719 4Oct10 VOGTLEELECTRICGENERATINGPLANT 2586524 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 70305480000 1154DH5RH 0513857 5Sep97 VOGTLEELECTRICGENERATINGPLANT 195256

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 7070103/001 1154DH6RH 0532261 23May06 VOGTLEELECTRICGENERATINGPLANT 1657352 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7074261/001 1154SH9RH 0534223 27Feb07 VOGTLEELECTRICGENERATINGPLANT 1822538 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 7079010/001 1154DH5RH 0535512 4Sep07 VOGTLEELECTRICGENERATINGPLANT 1968476 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 7079010/001 1154DH5RH 0535511 4Sep07 VOGTLEELECTRICGENERATINGPLANT 1968476 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 7079010/001 1154DH5RH 0535500 4Sep07 VOGTLEELECTRICGENERATINGPLANT 1968476 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 7079010/001 1154DH5RH 0535506 4Sep07 VOGTLEELECTRICGENERATINGPLANT 1968476 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 7079010/001 1154DH5RH 0535497 4Sep07 VOGTLEELECTRICGENERATINGPLANT 1968476 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 7079010/001 1154DH5RH 0535508 4Sep07 VOGTLEELECTRICGENERATINGPLANT 1968476 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 GEORGIAPOWERCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

01531021REV002 1154SH9RCN0156 0538691 4Mar09 COOKNUCLEARPLANT 2258323 +/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 01531021REV002 1154HH5RAN0156 0538700 4Mar09 COOKNUCLEARPLANT 2258323 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 01531021REV002 1154SH9RCN0156 0538696 4Mar09 COOKNUCLEARPLANT 2258323 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 INDIANAMICHIGANPOWERCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

0H962Y461300 1154DH5RB 0513020 27Mar97 UNSPECIFIED 108610

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

C00NYG4C040561 1154SH9RB 0520775 5Apr01 UNSPECIFIED 806985

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A OH962Y364600 1154SH9RB 0513542 20Jun97 UNSPECIFIED 143776

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A OH962Y364600 1154SH9RB 0513541 20Jun97 UNSPECIFIED 143776

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A OH972K100100 1154HH5RB 0514959 2Jun98 UNSPECIFIED 303530

+/-(1%URL+1%span)

+/-(1%URL+6.25%span)

+/-(2%URL+5.25%span)

OH992KA01500 1154SH9RBN0110 0518414 7Oct99 UNSPECIFIED 547210

+/-(3%URL+1%span)

+/-(3%URL+8%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 KOREAELECTRICPOWERCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

UPDATE B05J230A00 1154DH6RA 0538216 24May10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

B05J230A00 1154DH6RA 0541638 1Nov10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

B05J230A00 1154DH6RA 0541639 1Nov10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

B05J230A00 1154DH6RA 0541640 1Nov10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

B05J230A00 1154DH6RA 0541641 1Nov10 SHINWOLSONG1&2 1890467 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

B05J230A00 1154DH4RA 0541644 1Nov10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

B05J230A00 1154DH4RA 0541646 1Nov10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

B05J230A00 1154DH4RA 0541649 1Nov10 WOLSONGNPPUNIT1AND2 1890467 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

C00SYGCN024011 1154HH6RB 0520884 18Apr01 UNSPECIFIED 815209

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

C01NKR4C068470 1154HH4RAN0037 0521668 6Sep01 UNSPECIFIED 883107

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

C090014131 1154SH9RBN0037 0541967 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(2%URL+0.5%span)

+/-(2%URL+4.25%span)

N/A C090014131 1154HH5RBN0158 0541975 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

C090014131 1154HH5RBN0158 0541976 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

C090014131 1154SH9RBN0158 0541977 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A C090014131 1154HH5RAN0151 0542110 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

C090014131 1154HH5RAN0151 0542111 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

C090014131 1154HH5RAN0132 0542112 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

C090014131 1154SH9RAN0132 0542113 1Dec10 KORIUNITS1,2,3&4 2606732 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A C090014134 1154SH9RBN0105 0542035 10Dec10 YONGGWANGUNITS1,2&3 2632117 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A K040066381/CREDITNO.M0677403NS00107 1154HH4RB 0527697 20May04 KORIUNIT4 1323776 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

K040066381/CREDITNO.M0677403NS00107 1154HH4RB 0527699 20May04 KORIUNIT4 1323776 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

K040117011/CREDITNO.M0677403NS00096 1154HH5RA 0527691 20May04 KORIUNIT3 1323657 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

K040117011/CREDITNO.M0677403NS00096 1154HH5RA 0527694 20May04 KORIUNIT3 1323657 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

K050551011/CREDITNO.M0677511NS00139 1154DH6RAN0132 0531089 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K050551011/CREDITNO.M0677511NS00139 1154DH6RAN0132 0531090 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

K050551011/CREDITNO.M0677511NS00139 1154DH6RAN0132 0531092 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

K050551011/CREDITNO.M0677511NS00139 1154DH6RAN0132 0531093 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K050551011/CREDITNO.M0677511NS00139 1154DH6RAN0132 0531094 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

K050551011/CREDITNO.M0677511NS00139 1154DH5RAN0132 0531095 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

K050551011/CREDITNO.M0677511NS00139 1154DH5RAN0132 0531096 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

K050551011/CREDITNO.M0677511NS00139 1154DH5RAN0132 0531097 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

K050551011/CREDITNO.M0677511NS00139 1154DH5RAN0132 0531100 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K050551011/CREDITNO.M0677511NS00139 1154DH5RAN0132 0531101 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

K050551011/CREDITNO.M0677511NS00139 1154DH5RAN0132 0531102 16Dec05 KORIUNITS3&4 1622521 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

K060238011/M0677604NS00114 1154DH5RAN0132 0533124 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

K060238011/M0677604NS00114 1154DH5RAN0132 0533126 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

K060238011/M0677604NS00114 1154DH5RAN0132 0533128 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K060238011/M0677604NS00114 1154DH5RAN0132 0533131 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

K060238011/M0677604NS00114 1154DH6RAN0132 0533132 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

K060238011/M0677604NS00114 1154DH6RAN0132 0533134 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K060238011/M0677604NS00114 1154DH5RAN0132 0533144 31Aug06 KORIUNITS3&4 1697807 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

K060734371REV01 1154SH9RBN0037 0534190 25Apr07 KORI 1840159 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A K060734371REV01 1154SH9RBN0110 0534191 25Apr07 KORI 1840159 +/-(3%URL+1%span)

+/-(3%URL+3%span)

N/A K070085011 1154DH5RAN0132 0534450 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

K070085011 1154DH5RAN0132 0534451 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

K070085011 1154DH5RAN0132 0534453 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

K070085011 1154DH5RAN0132 0534456 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

K070085011 1154DH5RAN0132 0534457 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K070085011 1154DH5RAN0132 0534458 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

APPENDIXA:10CFRPART21NOTIFICATIONREVISED20MARCH2012 KOREAHYDROANDNUCLEARPOWERCOLTD REVISED

K070085011 1154DH5RAN0132 0534459 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K070085011 1154DH5RAN0132 0534460 12Apr07 KORI 1868534 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

K070299511 1154DH6RAN0132 0535793 29Nov07 KORIUNIT3 1949332 +/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

K070299511 1154DH4RAN0132 0535893 29Nov07 KORIUNIT3 1949332 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

K080115021 1154DH5RAN0132 0536804 2Jun08 KORIUNITS3&4 2111881 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

K080115021 1154HH5RAN0132 0536806 2Jun08 KORIUNITS3&4 2111881 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K090149371 1154HH5RBN0158 0539626 6Aug09 KORIUNIT1 2355295 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

K090266041 1154HH5RAN0132 0540562 25Jan10 KORIUNIT3 2461750 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

K090414581 1154HH5RAN0132 0540862 2Mar10 KORIUNIT4 2465684 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

K090414581 1154DH5RAN0132 0540871 2Mar10 KORIUNIT4 2465684 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

K100156441 1154HH5RAN0151 0542120 22Nov10 KORIUNIT3 2599946 +/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

K100156441 1154DH4RAN0132 0542121 22Nov10 KORIUNIT3 2599946 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

K100298401 1154SH9RBN0110 0542055 24Nov10 KORIUNIT1 2599726 +/-(3%URL+1%span)

+/-(3%URL+3.75%span)

N/A K100298401 1154SH9RBN0110 0542056 24Nov10 KORIUNIT1 2599726 +/-(3%URL+1%span)

+/-(3%URL+5.75%span)

N/A NKR301M0127530 1154SH9RA 0523455 15May02 UNSPECIFIED 994792

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A NKR301M0127530 1154HH4RAN0037 0523484 15May02 UNSPECIFIED 994792

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

NKR302M0013010 1154DH4RA 0523832 28Jun02 UNSPECIFIED 1025207 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

NKR302M0013010 1154DH4RA 0523834 28Jun02 UNSPECIFIED 1025207 +/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

NKR302M0013010 1154DH4RA 0523835 28Jun02 UNSPECIFIED 1025207 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

NKR302M0013010 1154SH9RA 0523838 28Jun02 UNSPECIFIED 1025207 +/-(2%URL+0.5%span)

+/-(2%URL+2.5%span)

N/A NKR302M0155 1154HH5RA 0524800 9Jan02 KORI 1117010 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

NKR302M0155 1154HH5RA 0524801 9Jan02 KORI 1117010 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

NKR302M0155 1154HH5RA 0524802 9Jan02 KORI 1117010 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

NKR302M0155 1154DH4RA 0524804 9Jan02 KORI 1117010 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

NKR302M0155 1154DH4RA 0524805 9Jan02 KORI 1117010 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

NKR302M0155 1154SH9RA 0524896 9Jan02 KORI 1117010 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A NKR302M0155 1154SH9RA 0524897 9Jan02 KORI 1117010 +/-(2%URL+0.5%span)

+/-(2%URL+2.75%span)

N/A NUJ302M0069111/CreditNo.M06772NS00250 1154SH9RBN0060 0525355 8Apr03 ULCHIN3 1145839 +/-(3%URL+1%span)

+/-(3%URL+6.75%span)

N/A NUJ302M0069111/CreditNo.M06772NS00250 1154DH8RBN0059 0525359 8Apr03 ULCHIN3 1145839 +/-(1.5%URL+1%span)

+/-(1.5%URL+5%span)

+/-(2%URL+5%span)

NUJ502N0013020/CreditNo.M0677301NS00185 1154SH9RBN0105 0525159 7Apr03 ULCHIN5&6 1143647 +/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A NUJ502N0013020/CreditNo.M0677301NS00185 1154HH6RB 0525160 7Apr03 ULCHIN5&6 1143647 +/-(1%URL+1%span)

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

NUJ502N0013020/CreditNo.M0677301NS00185 1154DH4RB 0525161 7Apr03 ULCHIN5&6 1143647 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

NUJ502N0013020/CreditNo.M0677301NS00185 1154DH8RBN0059 0525164 7Apr03 ULCHIN5&6 1143647 +/-(1.5%URL+1%span)

+/-(1.5%URL+2.5%span)

+/-(2%URL+2.5%span)

NYG102M0142010 1154SH9RB 0524653 21Dec02 YONGGWANG 1110703 +/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A NYG102M0142010 1154SH9RB 0524654 21Dec02 YONGGWANG 1110703 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A NYG102M0142010 1154SH9RB 0524655 21Dec02 YONGGWANG 1110703 +/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A NYG102M0142010 1154DH4RB 0524660 21Dec02 YONGGWANG 1110703 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

NYG102M0142010 1154DH4RB 0524661 21Dec02 YONGGWANG 1110703 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

NYG102M0142010 1154DH4RB 0524664 21Dec02 YONGGWANG 1110703 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

NYG102M0142010 1154DH4RB 0524668 21Dec02 YONGGWANG 1110703 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

NYG301M0071040 1154DH4RB 0522848 31Jan02 UNSPECIFIED 956397

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

NYG301M0071040 1154DH4RB 0522849 31Jan02 UNSPECIFIED 956397

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

NYG301M0071040 1154SH9RB 0522852 31Jan02 UNSPECIFIED 956397

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A NYG302M0053080/CreditNo.M0677212NS00274 1154SH9RB 0525247 21Mar03 KORIUNIT2 1146563 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A NYG302M0055080/CreditNo.M0677212NS00281 1154SH9RB 0525242 24Mar03 KORIUNIT2 1146994 +/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A NYG302M0055080/CreditNo.M0677212NS00281 1154DH4RB 0525243 24Mar03 KORIUNIT2 1146994 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

NYG502M0116261 1154SH9RBN0105 0525041 25Feb03 YONGGWANG 1132765 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A S05J230A00 1154DH6RA 0536475 5Sep08 KORINPPUNIT1AND2 1890446 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

S05J230A00 1154DH6RA 0539553 9Sep09 KORINPPUNIT1AND2 1890446 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

S05J230A00 1154DH4RA 0539612 9Sep09 KORINPPUNIT1AND2 1890446 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

T08J230A00 1154DH4RA 0542324 22Dec10 SHINKORIUNITS3AND4 2401346 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

T08J230A00 1154DH4RA 0542327 22Dec10 SHINKORIUNITS3AND4 2401346 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

T08J230A00 1154DH4RA 0542331 22Dec10 SHINKORIUNITS3AND4 2401346 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527503 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527504 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527505 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

REVISED

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527506 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527507 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527510 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U03M1002H1CREDITNO.M0677402NS00107 1154HH4RB 0527511 31Mar04 ULCHIN 1311098 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

U040275481/CREDITNO.M0677407NS00153 1154HH6RB 0528402 7Oct04 ULCHINUNIT4 1385254 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U040275481/CREDITNO.M0677407NS00153 1154HH6RB 0528403 7Oct04 ULCHINUNIT4 1385254 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U040275481/CREDITNO.M0677407NS00153 1154SH9RB 0528404 7Oct04 ULCHINUNIT4 1385254 +/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A U040275481/CREDITNO.M0677407NS00153 1154DH8RBN0059 0528405 7Oct04 ULCHINUNIT4 1385254 +/-(1.5%URL+1%span)

+/-(1.5%URL+5%span)

+/-(2%URL+5%span)

U040327011/CREDITNUMBERM0677408NS00153 1154DH4RBN0132 0528355 30Sep04 ULCHINUNITS1&2 1400505 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

U040327011/CREDITNUMBERM0677408NS00153 1154DH4RBN0132 0528358 30Sep04 ULCHINUNITS1&2 1400505 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U040327011/CREDITNUMBERM0677408NS00153 1154DH4RBN0132 0528364 30Sep04 ULCHINUNITS1&2 1400505 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

U040711601/CREDITNO.M0677505NS00096 1154SH9RBN0132 0529881 23Jun05 ULCHINUNITS1&2 1520992 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U040711601/CREDITNO.M0677505NS00096 1154DH6RBN0132 0529895 23Jun05 ULCHINUNITS1&2 1520992 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U040711601/CREDITNO.M0677505NS00096 1154DH6RBN0132 0529896 23Jun05 ULCHINUNITS1&2 1520992 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

U040711601/CREDITNO.M0677505NS00096 1154DH5RBN0132 0529903 23Jun05 ULCHINUNITS1&2 1520992 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U040711601/CREDITNO.M0677505NS00096 1154DH5RBN0132 0529908 23Jun05 ULCHINUNITS1&2 1520992 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530461 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530462 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530463 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530468 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A U050124391/CREDITNO.M0677508NS00210 1154DH7RB 0530469 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U050124391/CREDITNO.M0677508NS00210 1154HH5RBN0132 0530486 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U050124391/CREDITNO.M0677508NS00210 1154HH5RBN0132 0530490 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

U050124391/CREDITNO.M0677508NS00210 1154HH5RBN0132 0530491 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

U050124391/CREDITNO.M0677508NS00210 1154DH6RBN0132 0530521 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

U050124391/CREDITNO.M0677508NS00210 1154DH6RBN0132 0530522 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U050124391/CREDITNO.M0677508NS00210 1154DH6RBN0132 0530524 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U050124391/CREDITNO.M0677508NS00210 1154DH6RBN0132 0530525 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

U050124391/CREDITNO.M0677508NS00210 1154DH6RBN0132 0530526 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

U050124391/CREDITNO.M0677508NS00210 1154DH6RBN0132 0530527 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U050124391/CREDITNO.M0677508NS00210 1154DH5RBN0132 0530531 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

U050124391/CREDITNO.M0677508NS00210 1154DH5RBN0132 0530532 13Oct05 ULCHINUNITS1&2 1563249 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530607 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530608 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U050124391/CREDITNO.M0677508NS00210 1154SH9RBN0132 0530610 13Oct05 ULCHINUNITS1&2 1563249 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U050696331/CREDITNO.M0677511NS00121 1154DH4RB 0531606 27Feb06 ULCHIN 1625202 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

U050696331/CREDITNO.M0677511NS00121 1154DH8RBN0059 0531607 24Apr06 ULCHIN 1625202 +/-(1.5%URL+1%span)

+/-(1.5%URL+2.25%span)

+/-(2%URL+2.25%span)

U050696331/CREDITNO.M0677511NS00121 1154SH9RBN0060 0531669 24Apr06 ULCHIN 1625202 +/-(3%URL+1%span)

+/-(3%URL+5.25%span)

N/A U050696331/CREDITNO.M0677511NS00121 1154HH5RB 0531723 24Apr06 ULCHIN 1625202 +/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

U050696331/CREDITNO.M0677511NS00121 1154DH5RB 0531724 24Apr06 ULCHIN 1625202 +/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

U060736271 1154SH9RBN0105 0534159 17May07 ULCHIN 1821584 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A U060771291/M04C3701NS00413 1154DH6RB 0534309 23Apr07 ULCHIN 1851325 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

U060771291/M04C3701NS00413 1154DH6RB 0534311 23Apr07 ULCHIN 1851325 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U060771291/M04C3701NS00413 1154HH6RB 0534312 23Apr07 ULCHIN 1851325 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

U060907301/M0677701NS00242 1154HH5RB 0534671 22Jun07 ULCHIN 1842477 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

U070797461 1154HH5RB 0537196 29Aug08 ULCHINUNIT1 2143207 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U070797461 1154HH5RB 0537197 29Aug08 ULCHINUNIT1 2143207 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U070797461 1154HH5RB 0537203 29Aug08 ULCHINUNIT1 2143207 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U070797461 1154HH5RB 0537205 29Aug08 ULCHINUNIT1 2143207 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

U070797461 1154HH5RB 0537219 29Aug08 ULCHINUNIT1 2143207 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U070960321 1154SH9RBN0105 0536866 17Jun08 ULCHINUNIT6 2077610 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A U070960321 1154SH9RBN0105 0536867 17Jun08 ULCHINUNIT6 2077610 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U080042401 1154HH6RB 0537442 24Sep08 ULCHINUNITS1&2 2180373 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U080183401 1154SH9RBN0105 0537894 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U080183401 1154SH9RBN0105 0537895 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U080183401 1154SH9RBN0105 0537896 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A REVISED

U080183401 1154SH9RBN0105 0537897 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U080183401 1154SH9RBN0105 0537898 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U080183401 1154SH9RBN0105 0537899 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U080183401 1154SH9RBN0105 0537900 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U080183401 1154SH9RBN0105 0537901 18Nov08 ULCHINUNIT5 2213153 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U080183401 1154HH5RB 0538073 18Nov08 ULCHINUNIT5 2213153 +/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

U090057611 1154HH6RB 0539588 26Aug09 ULCHINUNIT6 2359125 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

U090057611 1154HH5RB 0539621 26Aug09 ULCHINUNIT6 2359125 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U090057611 1154HH5RB 0539622 26Aug09 ULCHINUNIT6 2359125 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

U090057611 1154HH5RB 0539623 26Aug09 ULCHINUNIT6 2359125 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U090057611 1154HH5RB 0539624 26Aug09 ULCHINUNIT6 2359125 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U090057611 1154SH9RBN0060 0539757 26Aug09 ULCHINUNIT6 2359125 +/-(3%URL+1%span)

+/-(3%URL+2.25%span)

N/A U090057611 1154SH9RBN0060 0539759 26Aug09 ULCHINUNIT6 2359125 +/-(3%URL+1%span)

+/-(3%URL+2.25%span)

N/A U090057611 1154SH9RBN0060 0539760 26Aug09 ULCHINUNIT6 2359125 +/-(3%URL+1%span)

+/-(3%URL+6.75%span)

N/A U090165541 1154DH5RB 0539660 25Aug09 ULCHINUNIT2 2360574 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U090165541 1154DH5RB 0539662 25Aug09 ULCHINUNIT2 2360574 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U090165541 1154DH5RB 0539663 25Aug09 ULCHINUNIT2 2360574 +/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

U090633621 1154DH5RB 0540588 12Feb10 ULCHINUNIT1 2464304 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

U090633621 1154DH5RB 0540589 12Feb10 ULCHINUNIT1 2464304 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

U090633621 1154SH9RB 0540717 12Feb10 ULCHINUNIT1 2464304 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A U100519011 1154DH5RB 0544236 13Sep11 ULCHINUNIT2 3063275 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U100519011 1154DH5RB 0544237 13Sep11 ULCHINUNIT2 3063275 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

DUPLICATES/N

DELETED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

U110262011 1154DH5RB 0544556 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U110262011 1154DH5RB 0544629 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U110262011 1154DH5RB 0544630 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U110262011 1154DH5RB 0544631 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

U110262011 1154DH5RB 0544632 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

U110262011 1154DH5RB 0544633 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

U110262011 1154DH5RB 0544634 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

U110262011 1154DH5RB 0544635 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

U110262011 1154DH5RB 0544686 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

U110262011 1154DH5RB 0544688 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U110262011 1154DH5RB 0544690 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

U110262011 1154DH5RB 0544692 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

U110262011 1154DH5RB 0544693 16Sep11 ULCHINUNITS1&2 3078803 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

Y030554891/CREDITNO.M0677402NS00192 1154DH8RBN0059 0527417 22Mar04 UNSPECIFIED 1311311 +/-(1.5%URL+1%span)

+/-(1.5%URL+5%span)

+/-(2%URL+5%span)

Y030554891/CREDITNO.M0677402NS00192 1154DH8RBN0059 0527418 22Mar04 UNSPECIFIED 1311311 +/-(1.5%URL+1%span)

+/-(1.5%URL+3.5%span)

+/-(2%URL+3.5%span)

Y030554891/CREDITNO.M0677402NS00192 1154DH5RB 0527449 22Mar04 UNSPECIFIED 1311311 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

Y030554891/CREDITNO.M0677402NS00192 1154HH6RB 0527450 22Mar04 UNSPECIFIED 1311311 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

Y030554891/CREDITNO.M0677402NS00192 1154DH4RB 0527451 22Mar04 UNSPECIFIED 1311311 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

Y030554891/CREDITNO.M0677402NS00192 1154DH4RB 0527452 22Mar04 UNSPECIFIED 1311311 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

Y030554891/CREDITNO.M0677402NS00192 1154DH5RB 0527453 22Mar04 UNSPECIFIED 1311311 +/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

Y040083010/CREDITNO.M0677406NS00250 1154HH5RB 0527813 29Jun04 YONGGWANGUNIT1 1362819 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

Y040083010/CREDITNO.M0677406NS00250 1154HH5RB 0527816 29Jun04 YONGGWANGUNIT1 1362819 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

Y040083010/CREDITNO.M0677406NS00250 1154HH5RB 0527817 29Jun04 YONGGWANGUNIT1 1362819 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

Y040083010/CREDITNO.M0677406NS00250 1154HH5RB 0527822 29Jun04 YONGGWANGUNIT1 1362819 +/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

Y040369983/CREDITNO.M0677411NS00192 1154DH4RB 0529402 11Mar05 YONGGWANG 1445494 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

Y040369983/CREDITNO.M0677411NS00192 1154DH4RB 0529403 11Mar05 YONGGWANG 1445494 +/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

Y040689581 1154SH9RB 0530390 14Sep05 YONGGWANGUNITS1&2 1534627 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A Y040689581 1154SH9RB 0530391 14Sep05 YONGGWANGUNITS1&2 1534627 +/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A U110094501

1154DH6RB 0544519 ULCHINUNITS1&2 9Sep11 3098658

+/-(1%URL+1%span)

REVISED

Y050042601 1154SH9RB 0530307 12Sep05 YONGGWANGUNITS1&2 1560135 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A Y050042601 1154SH9RB 0530308 12Sep05 YONGGWANGUNITS1&2 1560135 +/-(2%URL+0.5%span)

+/-(2%URL+5.5%span)

N/A Y050042601 1154SH9RB 0530309 12Sep05 YONGGWANGUNITS1&2 1560135 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A Y050143011 1154HH5RB 0530359 19Sep05 YONGGWANGUNITS1&2 1560255 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

Y050143011 1154HH5RB 0530361 19Sep05 YONGGWANGUNITS1&2 1560255 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

Y050261581 1154DH8RBN0059 0531370 27Feb06 YONGGWANG 1566671 +/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span)

Y050572411 1154SH9RBN0105 0532111 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A Y050572411 1154SH9RBN0105 0532113 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A Y050572411 1154SH9RBN0105 0532115 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A Y050572411 1154SH9RBN0105 0532117 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A Y050572411 1154SH9RBN0105 0532118 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A Y050572411 1154SH9RBN0105 0532119 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A Y050572411 1154SH9RBN0105 0532120 12Jun06 YONGGWANGUNITS5&6 1650803 +/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A Y060238481/M0677609NS00228 1154DH5RB 0533847 19Dec06 YONGGWANG 1779089 +/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

Y060238481/M0677609NS00228 1154DH5RB 0533850 19Dec06 YONGGWANG 1779089 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

Y060479501/M0677612NS00057 1154DH5RB 0534323 25Apr07 YONGGWANG 1828882 +/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span)

Y070299451 1154DH8RBN0059 0536115 18Jan08 YONGGWANGUNIT5 1993245 +/-(1.5%URL+1%span)

+/-(1.5%URL+3.25%span)

+/-(2%URL+3.25%span)

Y070299451 1154DH8RBN0059 0536116 18Jan08 YONGGWANGUNIT5 1993245 +/-(1.5%URL+1%span)

+/-(1.5%URL+3.5%span)

+/-(2%URL+3.5%span)

Y070299451 1154DH8RBN0059 0536121 18Jan08 YONGGWANGUNIT5 1993245 +/-(1.5%URL+1%span)

+/-(1.5%URL+3%span)

+/-(2%URL+3%span)

Y070299451 1154DH8RBN0059 0536122 18Jan08 YONGGWANGUNIT5 1993245 +/-(1.5%URL+1%span)

+/-(1.5%URL+3.5%span)

+/-(2%URL+3.5%span)

Y070491511 1154HH6RB 0536552 13May08 YONGGWANGUNIT4 2076220 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

Y070491511 1154HH6RB 0536553 13May08 YONGGWANGUNIT4 2076220 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

Y080003531 1154DH8RBN0059 0537317 10Sep08 YONGGWANGUNIT6 2157958 +/-(1.5%URL+1%span)

+/-(1.5%URL+2%span)

+/-(2%URL+2%span)

Y080003531 1154DH8RBN0059 0537318 10Sep08 YONGGWANGUNIT6 2157958 +/-(1.5%URL+1%span)

+/-(1.5%URL+4.5%span)

+/-(2%URL+4.5%span)

Y090528481 1154SH9RB 0540846 23Feb10 YONGGWANGUNIT2 2465840 +/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A Y090528481 1154SH9RB 0540847 23Feb10 YONGGWANGUNIT2 2465840 +/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A Y110304566 1154HH5RB 0545288 23Nov11 YONGGWANGUNIT5 3177117 +/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

Y110304566 1154HH5RB 0545289 23Nov11 YONGGWANGUNIT5 3177117 +/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

REVISED

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

954476 1154DH4RCN0011 0512657 30Oct96 UNSPECIFIED

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 02084603 1154SH9RCN0011 0517222 10Mar99 MILLSTONENUCLEARPWRSTATION 487324

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 NORTHEASTNUCLEARENERGYCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00078670 1154DH8RCN0121 0522202 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 00078670 1154DH8RCN0121 0522203 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 00078670 1154DH8RCN0121 0522204 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 00078670 1154DH8RCN0121 0522207 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 00078670 1154DH8RCN0121 0522210 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 00078670 1154DH8RCN0121 0521407 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 00078670 1154DH8RCN0121 0521391 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0521396 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522213 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522214 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0521394 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522084 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522086 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522110 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522200 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522201 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522205 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522206 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522215 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522217 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00078670 1154DH8RCN0121 0522109 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0522211 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0522085 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0522219 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0521406 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0522208 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0522209 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00078670 1154DH8RCN0121 0522216 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00078670 1154DH8RCN0121 0522108 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00078670 1154DH8RCN0121 0522083 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00078670 1154DH8RCN0121 0522087 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00078670 1154DH8RCN0121 0521397 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 ONTARIOPOWERGENERATIONINC

00078670 1154DH8RCN0121 0522089 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00078670 1154DH8RCN0121 0522107 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00078670 1154DH8RCN0121 0522112 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00078670 1154DH8RCN0121 0522220 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00078670 1154DH8RCN0121 0521389 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00078670 1154DH8RCN0121 0521404 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 00078670 1154DH8RCN0121 0522113 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 00078670 1154DH8RCN0121 0521403 1Nov01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 00078670 1154DH8RCN0121 0522111 27Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 00078670 1154DH8RCN0121 0521386 26Sep01 PICKERINGNUCLEAR 846407

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

P.O.00119129 1154DH8RCN0121 0526311 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

P.O.00119129 1154DH8RCN0121 0526314 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

P.O.00119129 1154DH8RCN0121 0526320 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

P.O.00119129 1154DH8RCN0121 0526307 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

P.O.00119129 1154DH8RCN0121 0526304 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

P.O.00119129 1154DH8RCN0121 0526309 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

P.O.00119129 1154DH8RCN0121 0526313 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

P.O.00119129 1154DH8RCN0121 0526315 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

P.O.00119129 1154DH8RCN0121 0526317 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

P.O.00119129 1154DH8RCN0121 0526319 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

P.O.00119129 1154DH8RCN0121 0526308 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

P.O.00119129 1154DH8RCN0121 0526316 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

P.O.00119129 1154DH8RCN0121 0526305 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

P.O.00119129 1154DH8RCN0121 0526306 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

P.O.00119129 1154DH8RCN0121 0526318 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

P.O.00119129 1154DH8RCN0121 0526312 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

P.O.00119129 1154DH8RCN0121 0526303 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

P.O.00119129 1154DH8RCN0121 0526310 11Sep03 PICKERINGNUCLEAR 1220757

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

129114 1154SH9RC 0532412 19Jun06 DIABLOCANYONNPP 1694999

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 130124 1154DH5RC 0533270 18Sep06 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 130124 1154DH5RC 0534176 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 130124 1154DH5RC 0534178 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 130124 1154DH5RC 0534180 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 130124 1154DH5RC 0532692 7Jul06 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 130124 1154DH5RC 0533271 18Sep06 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 130124 1154DH5RC 0534175 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 130124 1154DH5RC 0533268 18Sep06 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 130124 1154DH5RC 0533269 18Sep06 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 130124 1154DH5RC 0534173 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 130124 1154DH5RC 0534174 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 130124 1154DH5RC 0534181 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 130124 1154DH5RC 0533273 18Sep06 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 130124 1154DH5RC 0534170 12Mar07 DIABLOCANYONNPP 1732406

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 3500892008 1154DH5RC 0543822 12May11 DIABLOCANYONNPP 3052849

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 PACIFICGASANDELECTRICCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00257132 1154HH5RAN0018 0532124 8May06 CRYSTALRIVERUNIT3 1656652

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00498092 1154HH5RAN0018 0541355 18Jun10 CRYSTALRIVERUNIT3 2537331

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00382610REV1 1154HH5RAN0018 0537145 16Jul08 CRYSTALRIVERUNIT3 2147591

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 PROGRESSENERGYFLORIDAINC

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

4500158649 1154SH9RA 0524108 27Aug02 SALEM/HOPECREEK 1056075

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500158649 1154SH9RA 0524106 27Aug02 SALEM/HOPECREEK 1056075

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500158649 1154SH9RA 0524107 27Aug02 SALEM/HOPECREEK 1056075

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500226996 1154HH5RHN0133 0527159 25Feb04 SALEM/HOPECREEK 1299544

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span) 4500226996 1154HH4RHN0132 0527183 25Feb04 SALEM/HOPECREEK 1299544

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500226996 1154HH4RHN0132 0527184 25Feb04 SALEM/HOPECREEK 1299544

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500226996 1154HH4RHN0132 0527180 25Feb04 SALEM/HOPECREEK 1299544

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500226996 1154HH4RHN0132 0527179 25Feb04 SALEM/HOPECREEK 1299544

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500272877 1154HH5RHN0133 0529115 27Jan05 SALEM/HOPECREEK 1441744

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500274724 1154HH4RHN0132 0529126 31Jan05 SALEM/HOPECREEK 1446829

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500307906 1154HH5RHN0133 0530246 9Aug05 SALEM/HOPECREEK 1561710

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500307906 1154HH5RHN0133 0530248 9Aug05 SALEM/HOPECREEK 1561710

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500364148 1154HH5RHN0132 0533546 7Nov06 SALEM/HOPECREEK 1764905

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500364148 1154HH5RHN0132 0533547 7Nov06 SALEM/HOPECREEK 1764905

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500515472 1154HH5RHN0132 0539361 29Jun09 SALEM/HOPECREEK 2334989

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500642438 1154HH5RHN0132 0544849 28 S 11 SALEM/HOPE CREEK 3115784 (1%URL 1%

)

(1%URL 4%

)

(2%URL 3%

)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 PUBLICSERVICEELECTRICANDGAS/PSEGNUCLEARLLC 4500642438 1154HH5RHN0132 0544849 28Sep11 SALEM/HOPECREEK 3115784

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span) 4500671134 1154SH9RAN0132 0545629 15Feb12 SALEM/HOPECREEK 3230752

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

0508864

+/-(2%URL+3.25%span) 0508863

+/-(2%URL+2.5%span) 4500280588 1154DH8RAN0094 0541470 28Jun10 SANONOFRENUCLEARWHSE 2558542 +/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

APPENDIXA:10CFRPART21NOTIFICATIONREVISED28MARCH2012 SOUTHERNCALIFORNIAEDISONCO 6V27400201 1154SH9RA 27Jan95 UNSPECIFIED

+/-(2%URL+0.5%span)

N/A REVISED

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

129109 1154SH9RB 0541578 27Jul10 STEXASPROJECTEGS 2566298

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 STPNUCLEAROPERATINGCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

00000151REL00324 1154DH5RC 0540003 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+4.5%span)

+/-(2%URL+3.5%span) 00000151REL00324 1154DH5RC 0539953 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 00000151REL00324 1154DH5RC 0540006 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 00000151REL00324 1154DH5RC 0539954 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 00000151REL00324 1154HH5RC 0539843 14Sep09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 00000151REL00324 1154DH5RC 0540009 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 00000151REL00324 1154DH5RC 0540001 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 00000151REL00324 1154DH5RC 0539961 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 00000151REL00324 1154DH5RC 0540000 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 00000151REL00324 1154DH5RC 0540002 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 00000151REL00324 1154DH5RC 0539960 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00000151REL00324 1154DH5RC 0540007 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 00000151REL00324 1154DH5RC 0539952 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00000151REL00324 1154DH5RC 0539963 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00000151REL00324 1154DH5RC 0539955 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00000151REL00324 1154DH5RC 0539957 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 00000151REL00324 1154DH5RC 0539958 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154HH5RC 0539829 14Sep09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154HH5RC 0539830 14Sep09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154HH5RC 0539844 14Sep09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154HH5RC 0539831 14Sep09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154DH5RC 0539949 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154DH5RC 0539999 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 00000151REL00324 1154DH5RC 0540004 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 00000151REL00324 1154HH5RC 0539819 14Sep09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 00000151REL00324 1154DH6RC 0539946 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 00000151REL00324 1154DH4RC 0539964 29Oct09 TVAWATTSBARUNIT2

2384837

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 TENNESSEEVALLEYAUTHORITY

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDERNUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

B0079178068REV1 1154DH5RC 0531930 28Mar06 COMANCHEPEAKSES 1591158

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

B0079178068REV1 1154DH5RC 0531932 28Mar06 COMANCHEPEAKSES 1591158

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

S05452076D2 1154DH6RC 0535262 3Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+6%span)

+/-(2%URL+5%span)

S05452076D2 1154DH6RC 0535268 3Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+5.25%span)

+/-(2%URL+4.25%span)

S05452076D2 1154DH6RC 0535261 11Sep07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

S05452076D2 1154DH6RC 0535260 3Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

S05452076D2 1154DH6RC 0535263 13Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

S05452076D2 1154DH6RC 0535267 3Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

S05452076D2 1154DH6RC 0535265 13Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

S05452076D2 1154DH6RC 0535266 3Aug07 COMANCHEPEAKSES 1952523

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 TXUELECTRICANDGAS/LUMINANTGENERATIONCO

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

UPDATE 9084056 1154SH9RBN0105 0512506 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+2.75%span)

N/A 9084056 1154SH9RBN0105 0512518 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A 9084056 1154SH9RBN0105 0512515 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 9084056 1154SH9RBN0105 0512519 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 9084056 1154SH9RBN0105 0512516 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9084056 1154SH9RBN0105 0512520 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9084056 1154SH9RBN0105 0512753 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9084056 1154SH9RBN0105 0512507 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 9084056 1154SH9RBN0105 0512752 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 9084056 1154SH9RBN0105 0512528 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9084056 1154SH9RBN0105 0512514 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9084056 1154SH9RBN0105 0512513 12Dec96 YONGGWANG3&4

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9200056 1154SH9RBN0105 0510763 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510762 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510761 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510760 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510759 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510758 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510757 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510756 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510755 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510754 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510749 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510748 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510747 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510746 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510732 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510731 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510696 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0105 0510695 15Jul96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 9200056 1154SH9RBN0060 0512118 25Sep96 ULCHIN3&4

+/-(3%URL+1%span)

+/-(3%URL+8%span)

N/A 9200056 1154SH9RBN0060 0512117 25Sep96 ULCHIN3&4

+/-(3%URL+1%span)

+/-(3%URL+8%span)

N/A 9200056 1154DH8RBN0059 0512108 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9200056 1154DH8RBN0059 0512105 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9200056 1154DH8RBN0059 0512104 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9200056 1154DH8RBN0059 0512103 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9200056 1154DH8RBN0059 0512102 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9200056 1154SH9RBN0105 0512198 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A 9200056 1154SH9RBN0105 0512195 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A 9200056 1154SH9RBN0105 0512196 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 9200056 1154SH9RBN0105 0512199 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A APPENDIXA:10CFRPART21NOTIFICATIONREVISED20MARCH2012 WESTINGHOUSEELECTRICCOLLC REVISED

9200056 1154SH9RBN0105 0512197 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 9200056 1154DH5RB 0512110 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 9200056 1154DH8RBN0059 0512109 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.25%span)

+/-(2%URL+2.25%span) 9200056 1154SH9RBN0105 0512283 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 9200056 1154DH5RB 0512111 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 9200056 1154SH9RBN0105 0512235 25Sep96 ULCHIN3&4

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 9200056 1154HH6RB 0512148 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 9200056 1154DH4RB 0512303 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9200056 1154DH5RB 0512365 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 9200056 1154DH4RB 0512305 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9200056 1154HH5RB 0512368 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9200056 1154DH4RB 0512306 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9200056 1154DH4RB 0512304 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9200056 1154DH4RB 0512302 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9200056 1154DH8RBN0059 0512107 25Sep96 ULCHIN3&4

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.5%span)

+/-(2%URL+1.5%span) 9200056 1154DH5RB 0512366 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9200056 1154DH4RB 0512308 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9200056 1154DH5RB 0512361 25Sep96 ULCHIN3&4

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9500056 1154SH9RBN0060 0514651 18Sep98 YONGGWANG5&6 192629

+/-(3%URL+1%span)

+/-(3%URL+8%span)

N/A 9500056 1154DH5RB 0515304 18Sep98 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+6.75%span)

+/-(2%URL+5.75%span) 9500056 1154DH8RBN0059 0516639 11May99 YONGGWANG5&6 192629

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9500056 1154DH8RBN0059 0516640 11May99 YONGGWANG5&6 192629

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9500056 1154DH4RB 0516629 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 9500056 1154HH6RB 0516594 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 9500056 1154HH6RB 0515296 18Sep98 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 9500056 1154HH6RB 0515295 18Sep98 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 9500056 1154HH6RB 0515297 18Sep98 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 9500056 1154DH8RBN0059 0516638 11May99 YONGGWANG5&6 192629

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 9500056 1154SH9RBN0105 0514659 18Sep98 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 9500056 1154HH6RB 0516593 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 9500056 1154SH9RBN0060 0514650 18Sep98 YONGGWANG5&6 192629

+/-(3%URL+1%span)

+/-(3%URL+2.75%span)

N/A 9500056 1154SH9RBN0105 0514660 18Sep98 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9500056 1154DH5RB 0516602 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 9500056 1154DH8RBN0059 0516641 11May99 YONGGWANG5&6 192629

+/-(1.5%URL+1%span)

+/-(1.5%URL+2%span)

+/-(2%URL+2%span) 9500056 1154DH8RBN0059 0516642 11May99 YONGGWANG5&6 192629

+/-(1.5%URL+1%span)

+/-(1.5%URL+2%span)

+/-(2%URL+2%span) 9500056 1154HH6RB 0516595 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 9500056 1154DH5RB 0516599 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 9500056 1154DH4RB 0516631 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 9500056 1154SH9RBN0105 0516815 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 9500056 1154SH9RBN0105 0514656 18Sep98 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154SH9RBN0105 0514658 18Sep98 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154SH9RBN0105 0514661 18Sep98 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154SH9RBN0105 0516804 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154SH9RBN0105 0514672 18Sep98 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154HH6RB 0516591 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9500056 1154SH9RBN0105 0516812 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154DH4RB 0516630 11May99 YONGGWANG5&6 192629

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9500056 1154SH9RBN0105 0516801 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A REVISED

9500056 1154SH9RBN0105 0516802 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154SH9RBN0105 0516805 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9500056 1154SH9RBN0105 0516819 11May99 YONGGWANG5&6 192629

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9600056 1154DH5RB 0519336 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+6.75%span)

+/-(2%URL+5.75%span) 9600056 1154DH8RBN0059 0520124 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9600056 1154DH8RBN0059 0520125 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9600056 1154DH8RBN0059 0520126 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9600056 1154DH8RBN0059 0520127 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9600056 1154DH8RBN0059 0520129 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9600056 1154DH8RBN0059 0520131 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+5.25%span)

+/-(2%URL+5.25%span) 9600056 1154SH9RBN0105 0519372 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+3.5%span)

N/A 9600056 1154SH9RBN0105 0519374 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+3%span)

N/A 9600056 1154SH9RBN0105 0519373 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+3%span)

N/A 9600056 1154SH9RBN0105 0519328 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2.5%span)

N/A 9600056 1154SH9RBN0105 0520150 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2.5%span)

N/A 9600056 1154SH9RBN0105 0519370 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A 9600056 1154DH8RBN0059 0519470 25Sep00 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+3.5%span)

+/-(2%URL+3.5%span) 9600056 1154SH9RBN0105 0519326 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A 9600056 1154SH9RBN0105 0519325 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A 9600056 1154SH9RBN0105 0520173 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A 9600056 1154HH6RB 0519408 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 9600056 1154SH9RBN0105 0520151 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+2%span)

N/A 9600056 1154HH6RB 0519412 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 9600056 1154HH6RB 0519407 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 9600056 1154SH9RBN0105 0520148 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 9600056 1154DH8RBN0059 0519468 25Sep00 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 9600056 1154SH9RBN0105 0519369 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9600056 1154SH9RBN0105 0519371 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9600056 1154SH9RBN0105 0520149 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9600056 1154SH9RBN0105 0520152 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9600056 1154SH9RBN0060 0519391 25Sep00 ULCHIN5&6 586278

+/-(3%URL+1%span)

+/-(3%URL+2.75%span)

N/A 9600056 1154HH6RB 0520280 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 9600056 1154SH9RBN0105 0520103 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 9600056 1154DH8RBN0059 0519473 25Sep00 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.5%span)

+/-(2%URL+2.5%span) 9600056 1154SH9RBN0105 0520153 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 9600056 1154SH9RBN0060 0519392 25Sep00 ULCHIN5&6 586278

+/-(3%URL+1%span)

+/-(3%URL+2.25%span)

N/A 9600056 1154DH5RB 0520269 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 9600056 1154HH6RB 0520284 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 9600056 1154DH8RBN0059 0520128 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.75%span)

+/-(2%URL+1.75%span) 9600056 1154SH9RBN0105 0520106 21Mar01 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9600056 1154DH8RBN0059 0519472 25Sep00 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.5%span)

+/-(2%URL+1.5%span) 9600056 1154DH8RBN0059 0520130 21Mar01 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.5%span)

+/-(2%URL+1.5%span) 9600056 1154DH4RB 0520308 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9600056 1154HH6RB 0519409 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9600056 1154HH6RB 0519414 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9600056 1154DH5RB 0519444 25Sep00 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9600056 1154HH6RB 0520283 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 9600056 1154SH9RBN0105 0519375 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A REVISED

9600056 1154SH9RBN0105 0519376 25Sep00 ULCHIN5&6 586278

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 9600056 1154DH8RBN0059 0519471 25Sep00 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.25%span)

+/-(2%URL+1.25%span) 9600056 1154SH9RBN0060 0520109 21Mar01 ULCHIN5&6 586278

+/-(3%URL+1%span)

+/-(3%URL+1.25%span)

N/A 9600056 1154DH8RBN0059 0519469 25Sep00 ULCHIN5&6 586278

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.25%span)

+/-(2%URL+1.25%span) 9600056 1154DH4RB 0520309 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 9600056 1154SH9RBN0060 0520108 21Mar01 ULCHIN5&6 586278

+/-(3%URL+1%span)

+/-(3%URL+1.25%span)

N/A 9600056 1154HH6RB 0520279 21Mar01 ULCHIN5&6 586278

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154SH9RBN0105 0534958 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+3.25%span)

N/A 4500110224 1154SH9RBN0060 0534209 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(3%URL+1%span)

+/-(3%URL+6.5%span)

N/A 4500110224 1154SH9RBN0060 0534208 15Apr08 SHINKORI/SHINWOLSONG1&2 1494839

+/-(3%URL+1%span)

+/-(3%URL+6.25%span)

N/A 4500110224 1154SH9RBN0060 0530768 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(3%URL+1%span)

+/-(3%URL+6%span)

N/A 4500110224 1154SH9RBN0060 0533665 15Apr08 SHINKORI/SHINWOLSONG1&2 1494839

+/-(3%URL+1%span)

+/-(3%URL+6%span)

N/A 4500110224 1154HH6RB 0533970 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+5%span)

+/-(2%URL+4%span) 4500110224 1154SH9RBN0060 0533666 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(3%URL+1%span)

+/-(3%URL+5.25%span)

N/A 4500110224 1154SH9RBN0105 0533213 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+3%span)

N/A 4500110224 1154SH9RBN0060 0530767 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(3%URL+1%span)

+/-(3%URL+4.5%span)

N/A 4500110224 1154DH8RBN0059 0530345 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+4%span)

+/-(2%URL+4%span) 4500110224 1154HH6RB 0534987 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span) 4500110224 1154HH6RB 0534985 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span) 4500110224 1154HH6RB 0534989 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span) 4500110224 1154HH6RB 0533965 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span) 4500110224 1154DH8RBN0059 0533608 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+3.75%span)

+/-(2%URL+3.75%span) 4500110224 1154DH8RBN0059 0534994 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+3.75%span)

+/-(2%URL+3.75%span) 4500110224 1154HH6RB 0534983 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH5RB 0535025 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.75%span)

+/-(2%URL+2.75%span) 4500110224 1154HH6RB 0533967 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 4500110224 1154HH6RB 0533969 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 4500110224 1154DH5RB 0533979 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 4500110224 1154HH6RB 0534988 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 4500110224 1154DH5RB 0533973 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 4500110224 1154HH6RB 0533968 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 4500110224 1154DH8RBN0059 0530348 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+3%span)

+/-(2%URL+3%span) 4500110224 1154DH5RB 0533676 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span) 4500110224 1154HH6RB 0530666 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 4500110224 1154HH6RB 0533659 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 4500110224 1154SH9RBN0105 0533215 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 4500110224 1154HH5RB 0533668 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 4500110224 1154DH8RBN0059 0530341 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH8RBN0059 0530342 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH8RBN0059 0530344 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH8RBN0059 0530346 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH8RBN0059 0530347 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH8RBN0059 0533610 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154DH8RBN0059 0533614 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154HH6RB 0533966 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 4500110224 1154DH8RBN0059 0534995 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span) 4500110224 1154SH9RBN0105 0533576 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 4500110224 1154DH8RBN0059 0534996 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span)

REVISED

4500110224 1154SH9RBN0105 0531380 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 4500110224 1154SH9RBN0105 0533585 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 4500110224 1154SH9RBN0105 0534920 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.75%span)

N/A 4500110224 1154HH6RB 0533658 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 4500110224 1154DH5RB 0533674 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 4500110224 1154DH5RB 0533980 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 4500110224 1154DH5RB 0530679 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span) 4500110224 1154SH9RBN0105 0531392 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500110224 1154SH9RBN0105 0533214 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500110224 1154SH9RBN0105 0533588 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500110224 1154SH9RBN0060 0533592 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(3%URL+1%span)

+/-(3%URL+2.75%span)

N/A 4500110224 1154DH8RBN0059 0533611 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.5%span)

+/-(2%URL+2.5%span) 4500110224 1154DH8RBN0059 0533619 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.5%span)

+/-(2%URL+2.5%span) 4500110224 1154SH9RBN0105 0534941 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500110224 1154SH9RBN0105 0534959 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500110224 1154SH9RBN0105 0535000 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.5%span)

N/A 4500110224 1154DH8RBN0059 0533615 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.5%span)

+/-(2%URL+2.5%span) 4500110224 1154DH8RBN0059 0533617 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.5%span)

+/-(2%URL+2.5%span) 4500110224 1154HH6RB 0533660 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 4500110224 1154DH8RBN0059 0533618 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.25%span)

+/-(2%URL+2.25%span) 4500110224 1154DH8RBN0059 0533620 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.25%span)

+/-(2%URL+2.25%span) 4500110224 1154DH8RBN0059 0534990 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.25%span)

+/-(2%URL+2.25%span) 4500110224 1154DH8RBN0059 0534997 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2.25%span)

+/-(2%URL+2.25%span) 4500110224 1154SH9RBN0105 0531389 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 4500110224 1154SH9RBN0105 0533606 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 4500110224 1154DH4RB 0533930 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 4500110224 1154DH5RB 0533977 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154HH6RB 0530667 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154HH6RB 0530673 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154SH9RBN0105 0534955 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 4500110224 1154SH9RBN0105 0534957 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A 4500110224 1154DH5RB 0535036 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154HH5RB 0533591 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154DH5RB 0535027 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154HH5RB 0535312 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500110224 1154SH9RBN0105 0531387 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154SH9RBN0105 0533296 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154SH9RBN0105 0533949 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154HH6RB 0533971 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span) 4500110224 1154SH9RBN0105 533300 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154SH9RBN0105 0533882 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154DH8RBN0059 0533607 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2%span)

+/-(2%URL+2%span) 4500110224 1154DH8RBN0059 0534993 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+2%span)

+/-(2%URL+2%span) 4500110224 1154SH9RBN0105 0534921 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154SH9RBN0105 0534924 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154SH9RBN0105 0534956 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+1%span)

N/A 4500110224 1154DH8RBN0059 0530343 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.75%span)

+/-(2%URL+1.75%span) 4500110224 1154HH6RB 0533661 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

REVISED

4500110224 1154HH6RB 0534986 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500110224 1154HH6RB 0533972 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500110224 1154DH8RBN0059 0533609 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.75%span)

+/-(2%URL+1.75%span) 4500110224 1154DH8RBN0059 0533613 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.75%span)

+/-(2%URL+1.75%span) 4500110224 1154HH6RB 0533657 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500110224 1154DH5RB 0533678 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500110224 1154DH5RB 0533984 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500110224 1154DH5RB 0535030 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span) 4500110224 1154DH4RB 0535475 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154SH9RBN0105 0531388 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533299 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533946 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0534940 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154DH4RB 0533581 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154SH9RBN0060 0533593 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(3%URL+1%span)

+/-(3%URL+1.75%span)

N/A 4500110224 1154SH9RBN0105 0533307 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533309 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0531395 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533604 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154DH4RB 0533577 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154DH4RB 0533929 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154DH4RB 0533934 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154HH6RB 0533663 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH5RB 0530683 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH5RB 0533677 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH5RB 0533981 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH8RBN0059 0534991 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1.5%URL+1%span)

+/-(1.5%URL+1.5%span)

+/-(2%URL+1.5%span) 4500110224 1154DH5RB 0535026 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH5RB 0535028 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH5RB 0535032 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH5RB 0535033 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154DH4RB 0535470 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154DH4RB 0535474 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154DH4RB 0533583 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154DH5RB 0530674 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154SH9RBN0105 0534999 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154DH5RB 0530680 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500110224 1154SH9RBN0105 0531379 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0531382 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533587 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0534939 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154HH5RB 0530686 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154SH9RBN0105 0533216 24Apr07 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533586 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154DH4RB 0535473 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 4500110224 1154SH9RBN0105 0531397 26Apr06 SHINKORI/SHINWOLSONG1&2 1494839

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154SH9RBN0105 0533945 23Mar07 SHINKORI/SHINWOLSONG1&2 1563340

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500110224 1154DH4RB 0535477 15Apr08 SHINKORI/SHINWOLSONG1&2 1563340

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

REVISED

4500212945 1154HH6RB 0533941 19Jan07 UNSPECIFIED 1803901

+/-(1%URL+1%span)

+/-(1%URL+5.25%span)

+/-(2%URL+4.25%span)

+/-(1%URL+5.25%span)

+/-(2%URL+4.25%span)

CHANGED

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span)

+/-(1%URL+4%span)

+/-(2%URL+3%span)

CHANGED

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

+/-(2%URL+2.25%span)

N/A CHANGED

+/-(2%URL+0.75%span)

N/A

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

CHANGED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(1%URL+3.25%span)

+/-(2%URL+2.25%span)

CHANGED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(3%URL+3.25%span)

N/A CHANGED

+/-(3%URL+2%span)

N/A

+/-(1%URL+3%span)

+/-(2%URL+2%span)

CHANGED

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

+/-(2%URL+1.75%span)

N/A CHANGED

+/-(2%URL+1%span)

N/A

+/-(2%URL+1.75%span)

N/A CHANGED

+/-(2%URL+1%span)

N/A

+/-(3%URL+3%span)

N/A CHANGED

+/-(3%URL+2.25%span)

N/A

+/-(1%URL+3%span)

+/-(2%URL+2%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED 2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540701 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540855 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154HH5RB 0540707 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540635 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540703 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154SH9RBN0060 0540376 2Feb11 SHINKORI3

2300433

+/-(3%URL+1%span) 4500294551 1154SH9RBN0105 0540395 2Feb11 SHINKORI3

4500294551 1154HH6RB 0540844 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154SH9RBN0105 0540687 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154HH6RB 0540860 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154DH5RB 0540857 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154SH9RBN0105 0540686 2Feb11 SHINKORI3

4500294551 1154HH6RB 0540858 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154HH6RB 0540843 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 2300433

+/-(1%URL+1%span) 4500294551 1154SH9RBN0060 0540375 2Feb11 SHINKORI3

2300433

+/-(3%URL+1%span)

REVISED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500294551 1154DH5RB 0540629 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 4500294551 1154DH5RB 0540631 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 4500294551 1154DH5RB 0540633 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 4500294551 1154HH5RB 0540706 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(2%URL+1.25%span)

N/A CHANGED

+/-(2%URL+1.5%span)

N/A

+/-(2%URL+1.25%span)

N/A CHANGED

+/-(2%URL+1.5%span)

N/A

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

CHANGED

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

+/-(1.5%URL+2%span)

+/-(2%URL+2%span)

CHANGED

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span)

+/-(2%URL+1.25%span)

N/A CHANGED

+/-(2%URL+1.75%span)

N/A

+/-(1.5%URL+2%span)

+/-(2%URL+2%span)

CHANGED 2Feb11

+/-(1.5%URL+2.75%span)

+/-(2%URL+2.75%span)

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span)

CHANGED

+/-(1%URL+3%span)

+/-(2%URL+2%span)

+/-(1%URL+2%span)

+/-(2%URL+1%span)

CHANGED

+/-(1%URL+3%span)

+/-(2%URL+2%span) 2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540632 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540854 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154DH8RBN0059 0540377 SHINKORI3

2300433

+/-(1.5%URL+1%span) 4500294551 1154SH9RBN0105 0540688 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH8RBN0059 0540380 2Feb11 SHINKORI3

2300433

+/-(1.5%URL+1%span) 4500294551 1154DH5RB 0540509 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154HH6RB 0540842 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540856 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154SH9RBN0105 0540553 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154SH9RBN0105 0540552 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540704 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154HH6RB 0540861 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540508 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540628 2Feb11 SHINKORI3

4500294551 1154HH6RB 0540859 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span)

REVISED

+/-(2%URL+1%span)

N/A CHANGED

+/-(2%URL+2%span)

N/A

+/-(1%URL+1.75%span)

+/-(2%URL+0.75%span)

CHANGED

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span) 4500294551 1154HH5RB 0540705 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span)

+/-(1%URL+3.5%span)

+/-(2%URL+2.5%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span)

CHANGED

+/-(1%URL+4.25%span)

+/-(2%URL+3.25%span)

+/-(1%URL+2.75%span)

+/-(2%URL+1.75%span)

CHANGED

+/-(1%URL+2.25%span)

+/-(2%URL+1.25%span) 4500389398 1154DH8RBN0059 0544261 28Sep11 SHINKORI1&2

3085973

+/-(1.5%URL+1%span)

+/-(1.5%URL+4.5%span)

+/-(2%URL+4.5%span) 4500389398 1154DH8RBN0059 0544270 28Sep11 SHINWOLSONG1&2 3090141

+/-(1.5%URL+1%span)

+/-(1.5%URL+3.25%span)

+/-(2%URL+3.25%span) 4500389398 1154DH5RB 0544306 28Sep11 SHINKORI1&2

3085973

+/-(1%URL+1%span)

+/-(1%URL+3%span)

+/-(2%URL+2%span) 4500389398 1154HH6RB 0544324 28Sep11 SHINKORI1&2

3085973

+/-(1%URL+1%span)

+/-(1%URL+2.5%span)

+/-(2%URL+1.5%span) 4500389398 1154SH9RBN0105 0544680 28Sep11 SHINWOLSONG1&2 3090141

+/-(2%URL+0.5%span)

+/-(2%URL+0.75%span)

N/A 4500389398 1154DH5RB 0544305 28Sep11 SHINWOLSONG1&2 3090141

+/-(1%URL+1%span)

+/-(1%URL+1.5%span)

+/-(2%URL+0.5%span) 4500389398 1154DH4RB 0544281 28Sep11 SHINKORI1&2

3085973

+/-(1%URL+1%span)

+/-(1%URL+1.25%span)

+/-(2%URL+0.25%span) 2300433

+/-(1%URL+1%span) 4500385592 1154HH5RB 0543715 17Jun11 UNSPECIFIED 3065873

+/-(1%URL+1%span) 4500294551 1154DH5RB 0540507 2Feb11 SHINKORI3

2300433

+/-(2%URL+0.5%span) 4500294551 1154DH5RB 0540634 2Feb11 SHINKORI3

2300433

+/-(1%URL+1%span) 4500294551 1154SH9RBN0105 0540689 2Feb11 SHINKORI3

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

REVISED

PURCHASE

ORDER

NUMBER MODEL

NUMBER SERIAL

NUMBER SHIPDATE SITE RNII

SALES

ORDER ORIGNAL SPECIFICATION REVISED

SPECIFICATION REVISED

SPECIFICATIONFOR

NONZEROBASED

CALIBRATIONS*

0710983/2 1154SH9RA 0520706 14Mar01 WOLFCREEKNUCLEAR 799823

+/-(2%URL+0.5%span)

+/-(2%URL+1.25%span)

N/A APPENDIXA:10CFRPART21NOTIFICATION02MARCH2012 WOLFCREEKNUCLEAROPERATINGCORP

  • REFERTOROSEMOUNTNUCLEARINSTRUMENTS,INC.PART21NOTIFICATIONDATEDFEBRUARY23,2012.

Appendix B: Part 21 Notification dated February 23, 2012 (revised April 2, 2012)

Page 1 of 7 Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 USA Tel 1 (952) 949-5210 Fax 1 (952) 949-5201 www.RosemountNuclear.com 2 April 2012 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk Re: Revision to 23 FEBRUARY 2012 Notification under 10 CFR Part 21 on certain Rosemount Model 1154 Series H Pressure Transmitters with nonzero based calibrations Note: This revision only affects Section 4.0 of the 23 February 2012 notification letter.

The pressure values listed in Section 4.0 at 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and 56 hours6.481481e-4 days <br />0.0156 hours <br />9.259259e-5 weeks <br />2.1308e-5 months <br /> have been corrected.

No other changes have been made.

Following is the 23 FEBRUARY 2012 notification letter in its entirety with the above specific updates incorporated:

Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that certain Model 1154 Series H pressure transmitters may not perform within the published steam pressure/temperature accuracy specification.

Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.

The potentially affected Model 1154 Series H pressure transmitters were shipped from RNII beginning in 1988. Model 1154 pressure transmitters (versus Model 1154 Series H) are not affected by this notification.

1.0 Name and address of the individual providing the information:

Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 2.0 Identification of items supplied:

All Model 1154 Series H range code 4-8 pressure transmitters shipped since the initial release in 1988 are potentially affected. Model 1154 Series H range code 9 pressure transmitters are not affected, nor are Model 1154 (versus Model 1154 Series H) transmitters.

Page 2 of 7 More detailed information can be found in the enclosed appendices.

x Appendix A lists 1154 model code combinations x

Appendix B lists N-options Specials with Specific Steam Pressure/Temperature Accuracy Specifications x

Appendix C lists U.S. domestic customers to which Rosemount Nuclear Instruments, Inc. has shipped one or more 1154 Series H range code 4-8 pressure transmitters 3.0 Identification of items supplied:

Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:

During the course of qualification testing to replace certaindiodes identified for obsolescence, RNII has determined that Model 1154 Series H range code 4-8 pressure transmitters with a significantly elevated or suppressed 4 mA point may not meet the published steam pressure/temperature accuracy specification.

The out of tolerance condition observed during steam pressure/temperature qualification testing is not related to the replacement diode changes. It is an inherent performance characteristic related to large zero elevation or suppression.

The steam pressure/temperature accuracy specification will be revised to account for nonzero based calibrations with a significantly elevated or suppressed 4 mA point.

Currently, the Model 1154 Series H steam pressure/temperature specification establishes an expected accuracy as follows:

Accuracy within +/- (1.0% of upper range limit + 1.0% of span) for range codes 4-8; +/- (2.0% of upper range limit + 0.5% of span) for range code 9 during and after sequential exposure to steam at the following temperatures and pressures, concurrent with chemical spray for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

420°F (215.6°C), 85 psig for 3 minutes 350°F (176.6°C), 85 psig for 7 minutes 320°F (160°C), 85 75 psig for 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 265°F (129.4°C), 85 24 psig for 56 hours6.481481e-4 days <br />0.0156 hours <br />9.259259e-5 weeks <br />2.1308e-5 months <br /> The Model 1154 Series H steam pressure/temperature accuracy specification will be revised to envelop the observed steam pressure/temperature qualification test data as follows:

Accuracy within +/- (1.0% of upper range limit + 1.0% of span)* for range codes 4-8; +/- (2.0% of upper range limit + 0.5% of span) for range code 9 during and after sequential exposure to steam at the following temperatures and pressures, concurrent with chemical spray for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Page 3 of 7 420°F (215.6°C), 85 psig for 3 minutes 350°F (176.6°C), 85 psig for 7 minutes 320°F (160°C), 85 75 psig for 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 265°F (129.4°C), 85 24 psig for 56 hours6.481481e-4 days <br />0.0156 hours <br />9.259259e-5 weeks <br />2.1308e-5 months <br />

  • For range codes 4-8, if pressure at the 4mA point (applied to either the high or low side of the transmitter) is greater than 50% of the upper range limit, the accuracy specification is +/- 2% of upper range limit.

This revised specification supersedes the published steam pressure/temperature accuracy specification for all Model 1154 Series H pressure transmitters affected by this notification.

The 1154 Series H range code 9 pressure transmitters have a steam pressure/temperature accuracy specification that already envelopes the observed steam pressure/temperature qualification test data and are not affected by this notification.

Model 1154 Series H pressure transmitters ordered with N-option specials which include specific steam pressure/temperature accuracy specifications may also be affected. See Appendix B for details.

On February 16, 2012, it was concluded that a substantial safety hazard may exist.

Rosemount Nuclear Instruments, Inc. does not have sufficient information to determine the potential safety impact in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased affected 1154 Series H pressure transmitters.

5.0 The corrective action which is taken, the name of the individual or organization responsible for that action, and the length of time taken to complete that action:

(a) Update Model 1154 Series H Qualification Report D8700096 to include the revised steam pressure/temperature specification for pressure transmitters impacted by this notification as noted in Section 4.0.

(b) Update the Model 1154 Series H Product Data Sheet 00813-0100-4631 and Product Manual 00809-0100-4631 to include the revised steam pressure/temperature specification for pressure transmitters impacted by this notification as noted in Section 4.0.

(c) Update the N0059 Specification Drawing 01154-2704 to include the revised steam pressure/temperature specification for pressure transmitters impacted by this notification as noted in Appendix B.

Completion: March 2012 Mr. Marc Bumgarner, VP&GM of Rosemount Nuclear Instruments, Inc. is responsible for any further action related to this issue.

6.0 Any advice related to the potential failure of the item:

Page 5 of 7 Appendix A: Model Code Combinations Potentially affected model codes begin with the following:

Base Model Description 1154DH4 1154 Series H Differential Pressure 2000 psig Static Pressure Rating 1154DH5 1154 Series H Differential Pressure 2000 psig Static Pressure Rating 1154DH6 1154 Series H Differential Pressure 2000 psig Static Pressure Rating 1154DH7 1154 Series H Differential Pressure 2000 psig Static Pressure Rating 1154DH7 1154 Series H Differential Pressure 2000 psig Static Pressure Rating 1154DH8 1154 Series H Differential Pressure 2000 psig Static Pressure Rating 1154HH4 1154 Series H Differential Pressure 3000 psig Static Pressure Rating 1154HH5 1154 Series H Differential Pressure 3000 psig Static Pressure Rating 1154HH6 1154 Series H Differential Pressure 3000 psig Static Pressure Rating 1154HH7 1154 Series H Differential Pressure 3000 psig Static Pressure Rating 1154HH7 1154 Series H Differential Pressure 3000 psig Static Pressure Rating 1154HH8 1154 Series H Differential Pressure 3000 psig Static Pressure Rating Unaffected model codes begin with the following:

Base Model Notes 1154SH9 1154 Series H Sealed Reference Pressure 1154DP 1154 Differential Pressure 2000 psig Static Pressure Rating 1154HP 1154 Differential Pressure 3000 psig Static Pressure Rating 1154GP 1154 Gage Pressure

Page 6 of 7 Appendix B: N-option Specials with Specific Steam Pressure/Temperature Accuracy Specifications N-option (RNII drawing reference)

Description Steam Pressure/Temperature Accuracy Specification Notes N0059 (01154-2704)

Defines the use of a Model 1154DH8RB with a sealed reference on the low side.

+/-(1.5%URL+1%span)

Is affected by this notification.

The revised steam pressure/temperature accuracy specification is

+/-(2% URL + 1% span) when the 4 mA point is greater than 50% of URL.

N0026 (01153-2725)

Defines the use of an 1154 Series H range code 4 pressure transmitter calibrated to a maximum working pressure of 210 in. H2O.

+/-5.50 inH2O Not affected by this notification N0079 (01153-2758)

Variant of the N0026 option with a vent/drain valve kit consisting of two threaded SST valve seats and two SST valve stems.

N0087 (01154-2712)

Variant of the N0026 option with the electronic housing rotated 180 degrees.

N0089 (01154-2714)

Variant of the N0026 option with the electronic housing rotated 90 degrees in the clockwise direction.

N0060 (01154-2705)

Defines the use of a range code 9 module for a calibration range of 0 - 4000 psi.

+/-(3%URL+1%span)

Not affected by this notification N0110 (01154-2725)

Defines the use of a range code 9 module for a calibration range of 0 - 4000 psi with adjustable damping.

+/-(3%URL+1%span)

Not affected by this notification

Page 7 of 7 Appendix C: List of Customers Domestic U.S. Customers ALABAMA POWER CO AMERICAN ELECTRIC POWER CO INC ARIZONA PUBLIC SERVICE CO/PINNACLE WEST CAPITAL BECHTEL POWER CORP CONSTELLATION ENERGY GROUP INC DOMINION NUCLEAR CONNETICUT INC/DOMINION GENERATION DUKE ENERGY CORP ECFS MCS EDISON MATERIAL SUPPLY LLC ELECTRO MECHANICS ENTERGY CORP EXELON GENERATION CO LLC FLORIDA POWER AND LIGHT CO FPL ENERGY LLC GEORGIA POWER CO NORTHERN STATES POWER - MINNESOTA DBA XCEL ENERGY PACIFIC GAS AND ELECTRIC COMPANY PROGRESS ENERGY FLORIDA INC PROGRESS ENERGY CAROLINAS INC PSEG NUCLEAR LLC SOUTH CAROLINA ELECTRIC & GAS SOUTHERN CALIFORNIA EDISON CO SOUTHERN NUCLEAR OPERATING COMPANY STP NUCLEAR OPERATING CO TENNESSEE VALLEY AUTHORITY TXU/LUMINANT GENERATION CO LLC WESTINGHOUSE ELECTRIC CO LLC