Notification of Potential Part 21 on Defect in E7000 Relays
ML070680288
Person / Time
Site: Millstone, Peach Bottom, Perry, Indian Point, Oyster Creek, Watts Bar, Braidwood, Prairie Island, Limerick, North Anna, Vogtle, Farley, San Onofre, FitzPatrick  
Issue date: 03/07/2007
From: Villegas R
Tyco Electronics Corp
To: Caruso J, Vincent Gaddy, Hopper G, Steven Orth, Tabatabai-Yazdi O
Office of Nuclear Reactor Regulation, NRC Region 1, NRC/RGN-II, NRC/RGN-III, NRC Region 4
References
43218
Download: ML070680288 (5)


Text

0310 71200 7 U.S. Nuclear Regulatory Commission Operations Center Event Report P'ake I General Information or Other (PAR)

Event#

43218 Rep Org: TYCO ELECTRONICS Notification Date / Time: 03/07/2007 09:30 (EST)

Supplier: TYCO ELECTRONICS Event Date / Time: 03/05/2007 (EST)

Last Modification: 03/07/2007 Region:

1 Docket #:

City:

FIARVIEW Agreement State: Yes County:

License #:

State: NC NRC Notified by: ROBERT VILLEGAS Notifications: JOHN CARUSO RI HQ Ops Officer: MARK ABRAMOVITZ GEORGE HOPPER R2 Emergency Class: NON EMERGENCY STEVE ORTH R3 10 CFR Section:

VINCENT GADDY R4 21.21 UNSPECIFIED PARAGRAPH OMID TABATAI(E-MAIL)

NRR POTENTIAL DEFECT IN E7000 RELAYS "Notification of limited E7000 relay recall (CII-010).

"During our normal assembly processing of nuclear E7000 relays, Tyco Electronics experienced an issue with a component. A spring in the base assembly broke during the calibration process. An analysis of the spring revealed non-conforming heat treatment causing the spring to become brittle. Further investigation revealed that this condition was limited to one specific lot of springs."

The cause of the defect was determined to be stress corrosion cracking (SCC). Testing of other springs in this lot

-did not identify additional defective springs. Tyco's inspection process has been changed to better detect SCC.

The defective springs have been purged from inventory and customers notified.

Plant affected by this recall are:

Braidwood Farley Fitzpatrick Indian Point 3 Limerick Millstone North Anna Oyster Creek Peach Bottom Perry Prairie Island j- ~tq

03/07/2007 U.S. Nuclear Regulatory Commission Operations Center Event Report Pa~ze2 General Information or Other (PAR)

San Onofre Susquehana Vogtle Watts Bar Event#

43218 Other agencies/organizations:

Delphi Controls Engine Systems Inc Entergy Oswego Warehousing Ergy Tech GE Nuclear Energy Progress Energy Carolinas Trentec Inc - Curtiss-Wright Flow Control Group

I~

.~

-1

.u LIUI-L.YUU r2_1týULI1*_Ub LJu1U~

Lg UU1/0OU3 Robert Villegas, Sr. Quality Systems Ty*'rco Electron[*ics Engineer & Nuclear Quality Auditor Tyco Electronics Global Aerospace and Defense - Cl1 Relays Asheville Operations 1396 Charlotte Highway Fairview, NC 28730 Telephone: 828-338-1017 Date:

5 March 2007 Fax: 828-338-1101 To:

Operation Center United States Nuclear Regulatory Commission (NRC)

Fax: (301)816-5151

Subject:

Tyco Electronics - Part 21 Transfer of Information CII-010 This letter is written in response to a NRC staff informal request for information regarding a Tyco Electronics 10CFR21 Evaluation, originally issued 16 November 2006; "Notification of Limited E7000 Relay Recall (CII-010).

During our normal assembly processing of nuclear E7000 relays, Tyco Electronics experienced an issue with a component. A spring in the base assembly broke during the calibration process. An analysis of the spring revealed non-conforming heat treatment causing the spring to become brittle. Further investigation revealed that this condition was limited to one specific lot of springs.

This follow-up final report serves to document our further evaluation and the corrective action taken on this issue:

1.. Microstructure analysis of the broken spring revealed that the failure was caused by stress-corrosion cracking (SCC) not heat treatment. Testing of multiple samples of other springs from this lot failed to produce any other.

spring with SCC.

2. Testing of relays returned from customers based on this limited recall revealed that all relays and springs were functioning as required. No evidence of SCC was found.
3. For the corrective action, Tyco purged the specific lot of springs with the SSC condition in the inventory and "work in process". As a further preventive action, Tyco's receiving inspection has been changed to better detect if SCC is present in a specific lot. The inspection and manufacturing process in place at the time the broken spring was detected should have prevented any defective spring from being used in a relay that was shipped to a customer.

Based on our evaluation this issue is expected to have a low potential to produce a significant safety concern.

However, Tyco Electronics does not have sufficient information to perform an evaluation for unspecified applications. There r customers having received the recall notification should return affected relays for inspection and r, or,. Base on the corrective action taken, no further action is required. Tyco considers this matter resov If you havy any*u*e ins on this condition of the evaluation and corrective action, please contact me at the number 03/07/2007 WED 09:23

[TX/RX NO 6640]

Z 001

11- -. 1-1111, 1-

ýýu

-L-LV-L LYuu r-Lt--L;L1-U11-LUz3 L*j UUZ/IUU3 Attachment I Customers Notified by Tyco Electronics regarding this condition.

CUSTOMER Alabama Power Co.

Amergen Energy Co. LLC Delphi Controls Dominion Nuclear Dominion Virginia Power Edison Material Supply Engine Systems Inc Entergy Nuclear Entergy Nuclear Operation Entergy Nuclear Ergy Tech Exelon Nuclear Div Exelon Generation Company Exelon First Energy Corp.

GE Nuclear Energy Georgia Power Company Pennsylvania Power & Light Prairie Island Nuclear Generating Station Progress Energy Carolinas, Inc.

Tennessee Valley Trentec, Inc LOCA TION/PLANT AFFECTA Farley Nuclear Plant Oyster Creek Generating Station Millstone Nuclear power Station North Anna Power Station San Onofre Nuclear Gen. St.

Indian Point 3 James A. Fizpatrick LLC Oswego Warehousing Limerick Generating Station Braidwood Warehouse Peach Bottom Atomic Power Station Perry Nuclear Plant Vogtle Elect. Genr Plant/Nuc OPS Warehouse Susquehana SES Watts Bar Nuclear Plant Curtiss-Wright Flow Control Group FD RELAYS 4

1 5

1 1

1 3

4 21 3

I 2

1 5

1

.5 8

8 2

2 5

66 TOTAL 2

03/07/2007 WED 09:23

[TX/RX NO 6640)

Z 002

-ju

ýýVý

ýJýu Li*l UV.)/

UU0 Transfer of Information per Part 21.21 (b)

(i) Name and address of the individual providing the information:

Robert Villegas, Quality System Engineer, Tyco Electronics - CII of the Global Aerospace and Defense Division, 1396 Charlotte Highway, Fairview, NC USA 28730.

(ii) Identification of the facility, the activity, or the basic component supplied for such facility or such activity that contains a deviation or failure to comply; Item supplied are E7000 relays with serial numbers beginning with 0523 through 0528. Certificates of Conformance stating exact relay description and serial numbers were sent to affected customers with November 16, 2006 notification.

Tyco sold this safety-related item for specified and unspecified applications. The customers for which Tyco had insufficient information to complete the Part 21 evaluation are listed in Attachment 1.

(ill) Identification of the firm constructing the facility or supplying the basic component that contains a deviation or a failure to comply:

Tyco Electronics, 1396 Charlotte Highway, Fairview NC, USA 28730 (iv) Nature of the defect or safety hazard that could be created by such a deviation or failure to comply:

If a spring is affected by SCC, the spring could break or fail to maintain appropriate pressure on the contact arm thereby preventing the relay from changing state when activated.

(v) The date on which the information of such a deviation or failure to comply was obtained" Tyco Electronics made the determination of the existence of this condition in November 2006. Notice of Limited E7000 Relay Recall was issued to the customers we issued on 16 November 2006.

(vi) In case of a basic component, which contains a deviation or failure to comply, the locations of all such components in use or being supplied?

Customers that purchased affected safety-related items from Tyco Electronics for unspecified applications are identified in Attachment 1.

(vii) The corrective action which has been, is being, or will be taken; the name of the individual or organization responsible for the action; and the length of time that has been or will be taken to complete the action (note, these are actions specifically associated with the identified deviation or failure to comply:

Tyco purged the specific lot of springs with the SCC condition in its inventory and "work in process". The sampling plan for receipt inspection has been increased to enhance our ability to detect SCC in future lots of springs.

(vii) Any advice related to the deviation or failure to comply about the facility, activity, or basic component that has been, is being given to purchasers or licensees:

Based on our evaluation this issue is expected to have a low potential to produce a significant safety concern.

However, Tyco Electronics does not have sufficient information to perform an evaluation for unspecified applications. Therefore customers having received the recall notification should return affected relays for inspection and rework.