Rev 14 to Annunciator Response Procedure AR-402, PSA G Annunciator Response
ML20086G219
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 11/15/1991
From: Marshall W
FLORIDA POWER CORP.
To:
References
AR-402, NUDOCS 9112040271
Download: ML20086G219 (12)


Text

. .

4 DOCUMENT TRANSMllTAL FORM 62211 FOR DOCUMENTS TRANSMITTED 10 DC DESK (NRC)*

i I DATE 15 NOV 1991 l D A T CH: 100 l

l DOCUMENT NUMBER SHEET NUMBER REVISION NUMDER COPY NUMBER l'

AR 402 14 24 INSTRUCTIONS TO THE ADDRESSEE COMPLETE EACH OF THE INSTRUCTIONS BELOW WHICH ARE T1ARKED WITH AN " X "

l

_ X_ (1) VERIFY THE DOCUMENTS RECEIVED AGREE WI TH THE ADUVE DESCRIPTION

_X_ (2) INCORPORATE T HE TR ANSMITTED DCCUMENTS INTO YOUR FILES

_X_ (3 ) -_ DESTROY DOCUMENTS OR PORTI DAS OF DOCUMENTS SUPERSEDED IJY TPE ADOVE

_X_ (4) SIGN AND DATE IN THE SPACES BELOW INDI C ATI NG THAT YOU COMPLETED THESE INST RUCT I ONS.

(5) SIGN BELOW INDICATING THAT YOU HAVE RE AD AND UNDERSTOOD THE CHANGES AS I DE NTI F I ED -

_X_ (6) RETURN TO DOCUMENT CONTROL, CRYSTAL RIVER UNIT 3, MACit NAIC _

NR2A SAIC FLORIDA POWER CORP , P . O. DOX 219

- CRY AL RIVEH FLA.. 32623 SIGNATURE OF ADDRESSEE DATE INDEPENDENT VER I F IC A T ION _ DATE _ (OPS) n 'y I 91120402'71 911115 l I

ADOCK 03000302 PDR .i F FDR j

1 l

,x Rev. 14 11/14/91 1

Effective Date // Sh/ 1 m=ct-m=wwv.w-tuwmumvranru; DOCUfAOGt l'OCIiCll *J {-

N P O R M ATION OtJL / 6 C. R IJuc! car J l (3,mewweas-- weaucwanax.ua !.

ANNUNCIATOR RESPONSE AR-402 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 3

(J PSA G AA'NUNCIATOR RESPONSE THIS PROCEDURE ADDRESSES SAFETY RELATED COMPONENTS l

l-1 APPROVED BY: erpret t, ion Contact f it ldtt(4/gw.z.

DATE: /_ h/

l INTERPRETATION CONTACT: Nuclear Operations

! Superintendent

. _ . _ - - . . _ - . . _ _ , . _ _ . _ . - . . _ . - . - _ . . . - - _ . . _ . _ . - ~ . . . . _ . - _ _. . . . .

1 V

TABLE OF' CONTENTS -

SECTION. PJ_GJ 1.0 PURPOSE .-. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 REFERENCE 1 .-.,...................., ., 1 -.

-2.1: INPLENENTING REFERENCES . . . . . . . . . . . . . . . . I 2.2- DEVELOPMENTAL REFERENCES ..,...... ,...,, 1 3.0 . PERSONNEL INDOCTRINATION .............-....... 1 4.0' INSTRUCTIONS .......................... 1-5.0 FOLLOW-UP ACTIONS . . . . , , . . . . . . . . . , . . . . . . . 1 ENCLOSURE 1 Annunciator Response . . . . . . . . . . . . . . . . . . . . . . . 2

\

k d

A AR-402 Rev. 14 Page.i 1

l p 1.0 PURP0]ig

%) 1 I

1.1 Establish a reference document for each Annunciator Window on the i PSA-Y Lampbox. l 1.2 Establish operator actions for valid Annunciator alarms on the PSA-Y Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the PSA-Y Lampbox.

2.0 REFERENCfd 2.1 IMPLEMENTING REFfaENCES 2.1.1 OP-404, Decay Heat Removal System l

2.1.2 - AP-360, Loss of Decay Heat Removal 2.1.3 AP-470, Loss _of Instrument Air 2.1.4 AP-380, Engineered Safeguards System Actuation 2.2 DEVELOPMENTAL REFERENCES 1

2.2.1 INP0 90-021, Good Practice OP-21 , Alarm Response Procedures 2.2.2 -Annunciator Window Engraving Drawing E-224-048 l 3.0 PERSONNEL INDOCTRINATION i 3.1 The Annunciator System is powered from VBOP 5 Breaker 28.

l 4.0 INSTRUCTIONS l

4.1 Respond to alarms on the PSA-Y Lampbox as indicated on Enclosure 1, Annunciator Response.

5.0 FOLLOW-UP ACTIONS

/*\

'O None l

AR-402 Rev. 14 Page 1

c EWCLOSUeE 1 (page 1 mf 8)

VERTICAL COLUMN 1 AukUkCIATOR PAWEL G ANNUNCIATOR PANEL LOCATION PSA-Y SETPo!NT SEhStaG

1. INDICATED CONDITION 1. AUTO ACTION WINDOW TITLE ELEMENT
2. CONTROL ROOM INDICATION WHICH VERIFf OR 2. OPERATOR ACTION - VALID ALARM NUMBER &

PikPOINT TROUBLE LOCATION STAit0N 1. a) Station ai- header press 1 85 PSIG. 1. a) N one . SA-13-PS

2. a) Start standby air compressor. 2 85 PSIG AIR PRESS b) IAV-30 closed at i 80 PSIG. b) Motify Nuclear Aux Operator. 1 80 PSIG IA-3-PS LOW 2. a) Check station air press.

c) May indicate targe system rupture with 2 compressors running.

G-1-1

1. a) None (Standby compressors starts i 105 IA/SA COMP 1 a) Control switch in normat after start and PSIG).

SWITCeGEAR TRIP br k . cpen.

2. a) Check brk position. 2. a) Notify Nuclear Aus Operator.

b) Start standby air compresser.

G-1-2 l IA/SA COMP 1. a) Air compressor brk closed with control 1. a) None.

2. a) Notify Nuclear Aux Operator. SWITCHGEAR AUTO START switch in normal after stop.

l

2. a) Check brk position.

l G-1-3 --"

G-1-4 1 1

G-1-5

1. a) WDP-8 trips when levet i 81.6a 108 in. WD-23-LS1 RC CRAIN TAkK 1. a) Level i 108 in. 2. a) [F high level, THEh pump down tank. 80.5 in.

LEVEL b) tevel 1 80.5 in. b) {F tow level, THEN restore to > 95 in.

HIGM/ LOW 2. a) None, G-1-6 _.____ _

s. ..____._______ _________

G-1 7 '----- ~ ~ - - - - - - - - - - --

1. a) None.

EC 1. a) Vessel Levet i 129' Elevation 2. a) Verify levet locatty in RB 129' Elev INVEkTO9Y 2. a) Control board vesset tevet indication b) Refer to OP-404 and/or AP-360 LOW G-1-8 - .

I

.___L.

Rev. 14 Page 2 AR-402

4 .

ENCLOSURE 1 (Pi9e 2,of 8)

G VERTICAL COLUMN 2 PSA-Y ANNUNCIATOR PAkEL ANNUNCIATOR PANEL LOCATION SETPO?NT SENSING

1. IkDICATED CONDITION 1. AUTO ACTION ELEMENT WINDOW TITLE 2. OPERATOR ACTION - VALID ALARM
2. CONTROL ROOM INDICATION WHICH VERIFT OR NUMBER &

PINPOINT TROUBLE LOCATION

1. a) De-energizes I ADR-2 INSTRUMENT 1. a) System pressure 1 85 PSIG. 2. a) Start standby air compressor. 1 85 PS!G IA-18-PS I AIR PRESS 2. a) Pressure indicates 1 85 PSIG. b) Refer to AP-470 (LotA)

LOW G-2-1 -

t 1. a) None (Trip at 1 400*F.) 1 375'r SA-12-TS IA/SA COMP 1. a) Air temp before the after cooter 1 375'F. 1 375'T IA-17-TS b) Air temp after the cooler 1 120*F. 2. a) Notify Nuclear Aux Operator.

DISCH TEMP b) Start standby compressor. 3 375*F SA-11-TS HIGH 2. a) None. 1 375'F IA-16-TS 1 120*F SA-6-TS 1 120*F IA-7-TS 1 120*F SA-5-TS 1 120*F IA-6-TS G 2-2

1. a) Mot or t rip.

IA/SA COMP 1. a) Motor overload at 115%. 2. a) Start standby compressor. 115% SWITCHGEAR MOTOR 2. a) Brk indicates trip. 49 X OVERlCAD l

i G-2-3 G-2-4 '- --

G-2-5 --

~*

G-2-6 --"

~~

G 2-7 . _ _ ..

1. a) Grcund on annunciator system. 1. a) None.

ANNUNCIATOR 2. a) Notify Electrical Supervisor.

GROUND 2. a) None.

G-2-8 --- -_ --

Rev. 14 Page 3 AR-402 e - _ _ _ _ _

, ( <"

& l- N]*

E CtOSURE 1 (Page 3-of 8)i ANNUNCIATOR PANEL LOCATION PSA-Y ANNUNCIATOR PANEL G VERTICAL COLUMN 3 WINDOW TITLE 1. ' INDICATED CONDITION 1. AUTO ACTICW SETPolNT SEusikG Z. CONTROL ROOM INDICATION WHICH VERIFY OR 2. OPERATOR ACTION - VALID ALARM ELEMENT PINPOINT TROUBLE NUMBER &

LOCATIO4 f

l SUBC00 LING 1. a) T Margio 2 30'F and reacter tripped. 1. &) None.

MARGIN sat l LOW 2. a) RCS pressure vertus RCS Temperature. 2. a) Ref er to' AP-380 (ESA). < 30*F b) SPDS screen.

G-3-1 G-3-2 G-3-3 G-3-4 p- . 1 l G-3-5 L_ _____,

G-3-6 G-3-7

{

l G-3-8

_ _ _ _ _ _ _ _ 1 l AR-402 Rev. 14 Page 4

  • ew ,- .

w) G QJ' ENClosuet 1-(Page 4 of 8)

ANNUNCIATOR PANEL LOCATION PSA-Y ANNUNCIATOR PANEL G VERTICAL COLUMN 4 WINDOW TITLE '1. INDICATED' CONDITION 1. AUTO ACTION SETPo!NT SENSING -

2. CONTROL ROOM INDICATION WHICH VERIFY OR 2. OPERATOR ACTION - VALID ALARM ELEMENT FINPOINT TROUBLE NUMBER &

tCCATION SC PUMP a) Pump A or 8 brk open with control switch 1. a) Standby purap starts in 10 see with system l TRIP in normal'after start. press at 55 PSIG. SWITCHGEAR

2. a) Pump brk indicates open, standby pump 2. a) Place control switch for tripped pump in starts, normat after stop.

G-4-1 b) Notify Nuclear Aux Operator.

l SC PUMP 1. a) Motor overload at 115%. 1. a) Standby pump starts at 55 PSIG.

MOTOR 2. a) Breaker indicates trip. 2. a) Place control switch f or overloaded pump 115% SWITCMGEAR OVERLOAD in normal after stop.

G-4-2 SC STSTEM 1. a) High surge tank level 1 11'6". 1. a) Auto fill on low level, t 11'6" SC-68-LS l TROUBLE b) Low surge tar.k tevet i 680". b) Standby pump starts at 1 55 PSIG after 1 6'0" c) System pressure 1 50 PSIG. 10 seconds. 1 50 PSIG SC-89-PS

2. a) Check tank tevet. 2. a) If level continues to go up or down, notify G-4-3 Nuclear Aun Operator.

SC PUMP 1. a) Pump running with ccntrol switch in normal 1. a) None.

AUTO START after stop. 2. a) Notif y Nuclear Aum Operator. SWITCMGEAR

2. a) Pump brk indicates closed.

G-4-4 G-4-5 G-4-6 G-4-7 EVACUATION 1. a) Tone #1 not available. 1. a) Nona.

TONE GENERATOR b) Tone s2 not available. 2. a) Notify Electrical Supervisor.

FAILURE 2. a) None.

G-4-8 AR-402 Rev. 14 Page 5

,. ,.  : e l-

%) w t EPCLOSURE'1 l (Page 5 of 8) l ANNUNCIATOR PANEL LOCATION PSA-Y ANNUNCIATOR PANEL G VERTICAL COLUMN 5 WINDOW Y!TLE .1. INDICATED CONDITION 1. AUTO ACTION SEiP0lNT SENSING

2. CONTROL ROOM INDICATION WHICH VERIFY OR 2. OPERATOR ACil0N - VALID ALARM ELEMENT PINPO!NT TROUBLE NUMBER &

LOCATION DW FROM CR-1 1. a) High cation conductivity sodium,'sitica 1. a) DWV-346 closes.

WTR QUALITY dissolved oxygen, or organic carbon. 2. a) Notify Chemistry. DWPL-1 IMPURE 2. a) None.

l l G-5-1 DW 1..a) WTP-6A, 6B control switch in normat after 1. a) Standby pump auto starts if cause of pump TRANSFER PP stop and brk for pump closed. stop was not low water levet. SWITCMGEAR i IROUBLE b) WTP-6A or 68 brk is open and pump controt 2. a) Notif y Electricat ' Supervisor of pump motor RD-WL switch in normal after start. problems.

c) Lcw levet in WTT-1. b) Notify Unit 112 of low levet if this is

2. a) Brk indication. reason for stop.

G 5-2 i

AUX BLOG DW 1. a) Hi tank tevet i 7.5 ft. 1. a) None.  !

SYSTEM b) Low tank levet i 3.0 ft. 2. a) Notify Assistant Nuclear Operator in 1 7.5 ft DW L S

, TROUBLE c) Aux Bldg demin water pump tow discharge press 1 80 PSIG.

Aun Bldg. 1 3.0 ft DW-15-LS b) Clean o* *wypass fitter. 1 80 PSIG DW-06-PS2 d) High DP across ff c) Secure standby pump when demin wtr demad 25 PSIG DW-09-PS .

e) 1A pump auto statt a. 100 PSIG. down to tevel of one pump. SWITCMGEAR f) 18 pump auto start at _ 100 PSIG. (DW-6 PSI)

G-5-3 2. a) Standby pump brk indicates closec.

G-5-4 G-5-5 t

G-5-6 G-5-7 >

i G-5-8 i

AR-402 Rev. 14 Page 6

t

  • .~

4, .

i

! ENCLOSU4E 1 (Page 6- of 8)

ANNUNCIAf0R PANEL LOCATION PSA-Y ANNUNCIATOR PANEL G VERTICAL COLUMN 6 l WINDOW TITLE 1. INDICATED CONDITION 1. AUTO ACTION OETPOINT SENSING

2. CONTROL ROOM INDICATION WP:CH V RIFY OR 2. OPERATOR ACTION - VALID ALARM ELEMENT
  • PINPOINT TROUBLE NUMBER &

I LOCATION BORIC ACID PP 1. a) Centrol switch in normat after start and 1. a) None. CS/SC TRIP pump brk open. 2. a) If lined up, start other pump. CS/40

2. a) Brk indicates open. b) If not, secure boration or rectrc. 428 G-6-1 BORIC ACID 1. a) Hi LVL 1 95" H 20, to tevet i 30" H20. 1.'a) None.

STOR TNK LEVEL 2. a) None. 2. a) Notify Assistant Nuclear Operator. t 95= N20 CA'11'LS HIGH/ LOW b) Have Chem / Rad sample if LVL change. 1 30* H 2O CA-13-LS G-6-2 BORIC ACID 1. a) Hi temp 1 164'F, to temp i 152*F. 1. a) None. 1 164*F CA-10-TSI STOR TNK TEMP 2. a).None. 2. a) Notify Assistant Nuclear operator. 1 152'F CA-12-TS1 HlGHfLOW G-6-3 NEAT TRACikG 1. a) Heat tracing from ES Bus A De-energized 1. a) None b) Heat tracing from ES Bus B De-energized 2. a) Uhen ES Bus A is re-energized, reset ES A DE-ENERGIZED 2. a) None. Heat tracing at'HTCP-5 (Near ES MCC 3A2)

2. b) When ES Bus B is re-energized, reset ES B .

Heat tracing at HTCp.2 (Near Aux. Building G-6-4 Elevator on 95' Levet.

GW PUMP 1. a) Condensate injection pump A or B breaker 1. a) None. CS/ST TRIP open and control switch in normal after 2. a) Notif y Nuclear Aux Operator. CS/0 start. SWITCHGEAR G-6-5 2. a) Brk indicates open.

GW 1. a) Gland seat water press 1 195 PSIG. 1. a) None.

PRESS 2. a) None. 2. a) Noti f y Nuclear Aux Operator. 1 195 PSIG GW-39-PS LOW b) Start standby pump.

G-6-6 GW TUMP 1. a) Motor overicad at 115%. 1. a) None. (Standby pump starts at i 190 PSIG). I MOTOR 2. a) Breaker indicates trip. 2. a) Noti f y Nuclear Aux Operator. 115% 49 x-OVERLOAD su1TCHGEAR G-6-7 I

GW PUMP 1. a) Condensate injection pump 1A auto start. 1. a) None.

AUTO START b) Condensate injection pump 18 auto start. 2. a) Notify Nuclear Aun Operator CS/ST

2. a) Brk indicates closed. CS/0 G-6-8 SWITCHGEAR 1

AR-402 Rev. 14 Page.7

,I .) flji  !'

)

e 18 Ef R o U

S7 O

S L e C g N a EP

(

&N GT O N NRI I EET SMBA NEMC E LUO S ENL T

N 7 I O

P T

E S

N M

U L

O C

L A

C I

T R

E Y 8 M e R

A g L a A P D

I L

A V

N O

I G T NC OA I -

T R CO -

O AT -

A OR -

L T E E UP N AO A

P R 1 2 O

T A

I C

N U

N R 4 N O 1 A

Y .

F I v R e E

V R

H -

C I

H W

N O

I T

NA

- C

I T DE Y I NL

- DI B A N U S OMO P COR OT DR E T N T L N O AOI I CRO T I T P A DN N C NOI O I CP L -

L . . - -

E 1 2 -

N A

P O R O

T A

I C

E L

I T

1 7

2 7

3 7

4 7

5 7

6 7

7 7

8 7

'4 R

A N W G G G - G G G G G U O -

N D - _.

N N -

A I W i 1 1 ll 1liI 1,tlll

r

.- g .cg ErCtOSURE 1 (Page 8 4f 8)

ANNUNCIA10R PANEL LOCATION PSA-Y ANNUNCIATOR PAhEL G VERTICAL COLUMN 8 WINDOW TITLE 1. INDICATED CONDITION 1. AUTO ACTION SETPOINT SENSING

2. CONTROL ROOM INDICATION WHIch VERIFY OR 2. OPERATOR ACTION - VALID ALARM ELEMENT P!hPOINT TRDUBLE NUMBER &

LOCATION SPENT FUEL 1. a) Hi levet 1 +.5 ft. 1. a) None. 1 + .5 ft SF-1-LS1 POOL LEVEL b) Lo level 1 -2 ft. 2. a) Notify Assistant Nuclear Operator. 1 -2 ft. SF-1-LS2 HIGH/ LOW 2. a) Check poet levet indication.

G-8 1 h0TE: Normal Water Levet = 158 ft. 6 in. E lev.

fuel TRANSFER 1. a) Hi level 1 5 ft. 1. a) None. 1 + .5 ft SF-10-LS CANAL LEVEL b) Lo tevet 1 -1 ft. 2. a) Notify Assistant Nuclear Operator. 1 -1 ft.

HIGH/ LOW 2. a) None.

G-8-2 40TE: hermal Water Levet = 158 ft. 6 in. Elev.

CASK AREA 1. a) Mi tevet +.5 ft. 1. a) None. 1 + .5 ft SF-11-LS LEVEL b) to tevet 1 -1 ft. 2. a) actify Assistant nuclear Operator. 1 -1 ft.

N!GH/LCW 2. a) kone.

G-8-3 NOTE: Normat Water Levet = 158 ft. 6 in. Elev.

SPENT FUEL 1. a) Pump brk open with remote control switch 1 a) None.

  • PUMP it normat after start. 2. a) Start standby pump if not recir pump. SF-02-04 42B TRIP 2. a) 3rk indicates open. b) Notify Assistant Nuclear Aux Operator. SF-01-03 CS/SC G-8-4 CS/O G-8-5 G-8-6 G-8-7

________1_

WASTE 1. a) Alarm on Rad =aste Disposai Panet in 1. a) Ncne.

DISPOSAL PAkEL Auxiliary Building, 95' elev., that has 2. a) Notify Assistant nuclear operator. 3 to 30 WASTE TROUBLE not been acknowledged within the timer Minutes DISPOSAL setting. PAhEL G-8-8 2. a) None.

AR-402 Rev. 14 Page 9 (LAST PAGE)

-