LER 89-014-01:on 890506,supply Breaker to 480 Volt Essential Bus J Opened & Alternate Bus J Supply Breaker Did Not Close. Caused by Spurious Trip Due to Broken Circuit.Reset Button Returned to Normal Position & Breaker closed.W/891031 Ltr
ML19327B870
Person / Time
Site: Beaver Valley
Issue date: 10/31/1989
From: Noonan T
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LER-89-014, LER-89-14, ND3MNO:1983, NUDOCS 8911140110
Download: ML19327B870 (6)


Text

u L . 1 l

. l be "l>lp0C  !

, wennone um so3.t.ox

se-punningmet rA nonau 1 l

October 31, 1989 l ND3MNO 1983 l i

J Beaver Valley Power Station, Unit No. 2 Docket No. 50-412, License No. NPF-73 l LER 89-014-01 l United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen

.In accordance with Appendix A, Beaver Valley Technical Specifications, the following revised Licensee Event Report is submitted:

LER 89-014-01, 10 CFR 50.73.a.2.iv. " Leak Collection Ventilation Flowpath Automatic Realignment Actuation".

c%d

, T. P. loonan General Manager Nuclear Operations C) .

Attachment J23%

't 8911140110 B91031 )

DR ADOCK 05000412 PNV

I *

)

l .

l '

. October 31, 1939

. '.- ND3MN0:1983 Page two i cc Mr. William T. Russell (

Regional Administrator ,

United States Nuclear Regulatory Commission l Region 1  ;

475 Allendale Road ,

! Xing of Prussia, PA 19406 j C. A. Roteck, Ohio Edison Mr. Peter Tam, BVPS Licensing Projact Manager i United States Nuclear Regulatory Commission  ;

Washington, DC 20555 J. Beall, Nuclear Regulatory Commission, '

BVPS Senior Resident Inspector CAPCO Nuclear Projects Coordinator l Toledo Edison j INPO Recordo Center

  • Suite 1500 1100 circle 75 Parkway i Atlanta, GA 30339 s G. E. Muckle, Factory Hutual Engineering, Pittsburgh t Mr. J. N. Steinmetz, Operating Plant Projects Manager Mid Atlantic Area Westinghouse Electric Corporation Energy Systems Service Division Box 355 Pittsburgh, PA 15230 American Nuclear Insurers '

c/o Dottie Sherman, ANI Library '

The Exchange Suite 245 2','O Farmington Avenue Farmington, CT 06032 Mr. Richard Janati Department of Environmental Resources P. O. Box 2063 16th Floor, Pulton Building Harrisburg, PA 17120 Director, Safety Evaluation & Control L , Virginia Electric & Power Co.

P.O. Box 26666 One James River Plaza Richmond, VA 23261 l

l

e

,c,,,J., an o, wetis hiev6 vont co==nnio=

)

C PPR0viD OMS WO 91t091M j LICENSEE EVENT REPORT (LER) ""* ' 8 ' U " 1

. acio, v ... ni juocesi=vw.inei 'an + i Beaver Valley Power Station Unit 2 lo l6 l 0 t o l 01411 12 1 lod 0 14 1 t14 4 ..I I,cak Collection Ventilation flowpath Automatic Realignment Actuation i v e =, i.a n ... 6 n =v u m i., neou can i,, l ovnen e aciuvin .=votvio .i waNin oav viam v i a si **g l 6 y;j,'3 was t .. car i i .s! s.outimewes ovcsi t wvupiais, j N/A o1610lo10l l [ l

~ -

8 9 N/A oistoiciog l l 0l 5 0l6 8[9 0l1 l4 0l1 1l0 3l1 8] 9  !

,,,,,,,,,,, vuisai one . svuoitn oevnvau toen ni avini i Nu o, io ce n 6 <em. . .. . . .. , . . ,, n n l

l "oot a' $ n .eai.i n .*m x p n.nrn i nui

.nm a n m.nuni .o ni.nu no n.e. n.i nn .

'N'

~

O00 i 1 n m. inn.i u mi.ns, w u .nen..i

~

ov ui n <s , .. . ,,a n .oe.in naa

~

.o n.ninii

~

a n nen..unai l'I,' ** '"' * * # # "*

n .in ni., o n.ia ni., w n.i.n. n.,

p an.wo n.i w n.nen.oi w n nen.i LiciN4ii CONI &C1 f On TM18 te m nel

~

N1We TitPHohi NvMesh Thomas P. Noonan General Manager of Nuclear Operations 411 l2 61413 l -11 l 21518 COMrtiti op.g tihe f Oft iaCH CDeh4PQNiht f alL(phe dis (higiD iN TMt. Di,0$ f l13t

  1. ((g'I MPOnta i
Aunt $1816 v COM8'ON N1 $C 3 Casti S $'iM COMPONaNT
  • hg$C pp X QC B[Klkl Gil18 i7 Y f f 1 I i 1 1 1 111 I I I I I I I I I I evertimiuvu n,Cav neieno c4, , y, l von 1 car n..
w. um

,il t,8r.a reagier, i APff'7f D 8t$M'$3/C'% CA ffi ND l l l a n n a e t ,o , ,, i . x .. ... .. ,. , , . ,<. .. ..~,. . - , o .

On 5/6/89 at 0210 hours0.00243 days <br />0.0583 hours <br />3.472222e-4 weeks <br />7.9905e-5 months <br />, the supply breaker to the J 480 Volt Essential Bus opened. The alternate J Bus Supply Breaker did not close. This de-energized the J Bus and all components powered off the J Bus, including Non-Filtered Ventilation Exhaust radiation monitor (2RMR-RQ301). As designed, the monitor failed high when de-energized. This High Radiation signal initiated an automatic ventilation realignment, diverting the ventilation from the Non-Filtered to Filtered flowpath. Operators found no apparent cause for the breaker to trip. It was discovered that the reset button on the supply breaker was in the "out" position. Following an investigation the reset button was returned to its normal "in" position, and the supply breaker was closed. The J Bus including radiation monitor (2RMR-RQ301) was re-energized and the ventilation system was returned to its normal flowpath. After replacing with a tested spare, Maintenance sent the J Bus supply breaker to the vendor for analysis. The breaker was found to have a broken circuit run in the power shield which caused the spurious trip. All relays and circuits associated with the supply and alternate breakers were tested and verified operable. There woro no safety implications due to this event. This event was bounded by Beaver Valley UFSAR Section 6.5.3.2, " Supplementary Leak Collection and Release System".

i g, .

r-essiC foam Seta U S NUC481R Ll!U4110hv CDhtwigsspeg UCENSEE EVENT CEPORT (LER) TEXT CONTINUATION < movie ove wo s+ms sens en 8 Acststy haw 6 tia po p ei wunnega ni g , ,g , , ,,gg ,

ya "!"t@  %"ju B: aver Valley Power Station Unit 2

, , , , _ _ n7 van u s, . e u. .es mc s mm nn Descriotion of Event On 5/6/89 at 0210 hours, the J 480 volt Essential Bus Normal Supply Breaker (BKR 2J2B) opened. The J Bus alternate supply breaker (cross tie breaker frcm the X 480 Volt Essential Bus) did not close. This de-energized the J Bus and all its loads, including the Leak Collection Ventilation radiation monitor (2RMR-RQ301). (2RMR-RQ301) monitors the Non-Filtered Ventilation Exhaust flowpath. When (2RMR-RQ301) was de-energized, it initiated a High Radiation signal, as designed. This signal automatically caused the Non-Filtered Ventilation flow to divert to the Filtered Ventilation Flowpath. This was done by automatically opening the Non-Filtered to Filtered flowpath supply dampers (2HVS* MOD 202A&B), closing the Non-Filtered flowpath exhaust dampers (2HVS* MOD 201A&B) and stopping the Non-Filtered flovpath exhaust fan (2HVS-FN263A). Operators verified all automatic actions. The ventilation realignment was not immediately identified as hn ESP Component Actuation. A later review determined that the event was an ESF Component Actuation and the NRC was notified on 5/8/89 at 1615 hours0.0187 days <br />0.449 hours <br />0.00267 weeks <br />6.145075e-4 months <br />.

As designed, the alternate supply breaker should close following an undervoltage trip of the normal supply breaker and stay open following an overcurrent trip. Operators removed all loads supplied by the J Bus and performed an investigation. After finding no conditions which would have caused the breaker to trip an attempt was made to manually close the J Bus Supply Breaker; however, the breaker would not close. Operators then closed the ,

alternate supply (tie) breaker. After the alternate breaker was closed it was noticed that the reset button on the J Bus Supply Breaker was in the "out" position. This is designed to occur when an overcurrent condition exists and is a mechanical interlock to prevent the breaker from being closed. Following the return of the reset button to its normal "in" position, the operators were able to close the supply breaker. The alternate breaker was then returned to its normal open position. The radiation monitor, the j 480 VAC J Bus, and the ventilation system were returned to their normal arrangement.

I 1

, on, an .s.. am im .--s t

y

=c e . ma vs woeusa m utaca,couw w o

s LICENSEE EVENT CEPORT (LER) TEXT CONTINUATION amovio ous wo mo-ma swa mm 8 adulv samt sti oockti wou6th to gg , wpygg , g, ,ggg g vi.a "t'a ;r My 11 caver Valley Power Station Unit 2 M

mm .. oc % .= uon 01 Cause of Event It has been concluded the event occurred due to a spurious trip of the J Bus Supply Breaker caused by a broken circuit run in the breaker's power shield. Following the event Maintenance removed the J Bus Supply Breaker, replaced it with a tested spare, and sent the breaker to the vendor for analysis. All relays associated with the supply and alternate supply breaker were calibrated and checked and all associated circuits were meggered, tested with an input current, and verified operable. Vendor testing of the breaker determined that the short time tripping function would intermittently trip above it's time curve, causing the breaker to trip erratically. The power shield was then sent to the vendor relay factory for analysis and repair. Innpection of the power shield revealed a broken circuit, near a resistor, which made intermittent contact. When contact was broken, the short time tripping function would activate and cause the breaker to trip. It is concluded that the broken circuit in the power shield cauced the spurious trip of the breaker, and that the broken circuit run was most likely weak or damaged originally.

The alternate supply breaker stayed open ao designed, as there was no supply undervoltage condition upstream of the J Bus Supply Breaker. The reset button on the supply breaker opened as a result of the faulty condition in the breaker. All relay and circuit tests verified that no overcurrent condition had existed in the bus and that no undervoltage condition existed upstream of the J Bus Supply Breaker.

Corrective Action After the reset button on the J Bus supply Breaker was returned to its normal "in" position, the breaker was closed and the alternate supply breaker was opened. The radiation monitor was reset and the ventilation system was realigned to its normal arrangement.

An extensive investigation was conducted which included sending the supply breaker to the vendor for analysis. The breaker was found to have a defective circuit in the power shield which caused it to trip spuriously. All other components were verified to have functioned properly. Following the replacement of the supply breaker with a spare, no system abnormalities have occurred.

Presently no further action is planned. l l g w2c somu ma 'v.s. ac. ine-sa"uteM"U C S3)

I e ,b p.. v s westa c e:vatoav ec==imoh i

. LICENSEE EVENT REPORT (LER) TEXT CONTINUATION emono ove =o neo-c*

inals e um )

, ACILIT V is&Istt 04 DOCD,41 WM6t h th ,&GE 12 Llh WQM$lk 16) naa " O'M." Mlit l M aver Valley Power Station Unit 2 0 l6 l0 l0 l0 l4 l1 l 2 Bl 9 -

Ol1l4 -

O ll _ O l4 0' O l4 YLKT (J fuere apete 4 geprod. ese pesHew 44C Arun JEM U Uh Previous Similar Events There have been four previous events when the J Bus was de-energized, causing radiation monitor (2RMR-RQ301) to fail high resulting in similar ESF actuations. Three of the previous occurrences were initiated by other unrelated events as follows:

Personnel Error (LER 87-013-00)

Improper clearance (LER 88-00,1-00)

Electrical overload (LER 88-005-00) i The last occurrence (LER 89-007-00) was a similar event involving a spurious trip of the J Bus Supply Breaker.

Safety Evaluation There were no safety concerns due to this event. The radiation monitor initiated a High Radiation signal when de-energized, as designed. The Non-Filtered Ventilation Flowpath was diverted to the Filtered Ventilation Flowpath in response to the High -

Radiation signal. The above actions were conservative and did not adversely affect any safety related systems. This event wac bounded by Beaver Valley Unit 2 UFSAR Section 6.5.3.2.,

" Supplementary Leak Collection and Release System".

e ggg g g O[.ie ( I 'I lNbb' OY % k'U b