Instrument & Test Procedure S01-II-1.74, Auxiliary Feedwater Sys,Refueling Interval
ML14135A284
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 06/12/1981
From: Brunet R, Curran J
SOUTHERN CALIFORNIA EDISON CO.
To:
Shared Package
ML13317A779 List:
References
SO1-II-1.74, TAC-44652, NUDOCS 8112160400
Download: ML14135A284 (54)


Text

ENCODE BEO2BC SAN ONQFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74

.UNIT 1 JUN 1 0 1981 REVISION 0 Page 1 AUXILIARY FEEDWATER SYSTEM EIVED JUN 1 2 1981 (REFUELING INTERVAL) 1.0 OBJECTIVE 1.1 To provide instructions for calibration of the Auxiliary Feedwater System.

2.0 REFERENCES

2.1 Piping and Instrument diagram 2.2 Applicable wiring, elementary and/or logic diagrams 2.3 Drawings A51875-0, 451874-0, 451876-0, 451776-0, 451775-0, 235863-0, 235862-0, 451869-0, and 451791-0 3.0 PREREQUISITES 3.1 The Watch Engineer's approval is required prior to starting work.

3.2 Equipment clearance(s) or permission, as applicable, must be obtained from the Control Operator before beginning work.

3.3 An approved equipment outage request (OD-16) if required, is on file in the control room.

3.4 Measuring and test equipment to be used for this calibration shall have a current calibration history and have an accuracy equal to or better than the allowable accuracy of the device to be calibrated.

3.5 Check the applicable radiation and contamination survey information BEFORE entering job area.

Use this survey information to assist in maintaining your exposure ALARA.

3.6 Measuring and Test Equipment 3.6.1 Variable pressure sources 3.6.2 Digital multimeter 3.6.3 Foxboro calibrator 2AT-CAL 3.6.4 Foxboro module extendes board 3.6.5 Variable voltage source 3.6.6 Variable level simulator 3.6.7 Substitution must be approved by the responsible 8W 21 2

o 11%&

Instrument Foreman

ENCODE BEO?BC SAN OKOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 NIT 1 JUN 1 0 1981 REVISION 0 Page 2 4.0 PRECAUTIONS 4.1 In the event any unanticipated conditions occur during calibration, the technician shall immediately notify the control operator.

4.?

Receiving approval to calibrate does not in any way obviate the responsibility of the technician to determine for himself that it is prudent and safe to begin work.

4.3 Verify that the instrument number, manufacture's item number, type and manufacture as delineated on the instrument calibration data card is in agreement with the device name plate data.

4.A In the event that calibration data does not meet the acceptance criteria, the device shall be identified as nonconforming and the instrument foreman shall be notified immediately.

Under no circumstances shall a nonconforming device be returned to service.

5.0 CHECK-OFF LIST S.1 None

"-"6.0 PROCEDURE 6.1 The acceptance limits for devices calibrated in procedure are included as part of the instructions.

NOTE:

Enter the test data base i.e. voltage, pressure, level and mA values for all test included in this procedure at each point marked with an asterisk (*).

6.2 PT-2010 6.2.1 Disconnect input and output wiring from PT-2010 6.?.?

Connect a variable pressure or vacuum source to___

pressure input connection of PT-2010 6.2.3 Apply an input pressure of 30" Hg Vaccuum 6.2.4 Verify an output signal of 4.0 mA + 0.5% of span 6.2.5 Apply an input pressure of 30.0 PSI acun 6.2.6 Verify an output signal of 20.0 mA + 0.5% of span 6.2.7 Repeat steps 6.2.3 through 6.2.6 until all indicators are correct without further adjustment.

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE $01-11-1.74 UNIT 1' JUN 1 0 1981 REVISION 0 Page 3 6.0 PROCEDURE (continued) 6.2 (continued) 6.2.8 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT OUTPUT mA UP DOWN UP DOWN 30" Hg Vac 4.00 15" Hg Vac 8.00 0.0 PSI 12.00 15.0 PSI 16.00 30.0 PSI 20.00 6.2.9 Disconnect input and output wiring from PYV-2010 6.2.10 Apply an input signal of 4.0 mA 6.2.11 Verify an ouput signal of 0.00 Vdc + 0.5% of span 6.2.12 Apply an input signal of 20.0 mA 6.?.13 Verify an output signal of 10.0 Vdc + 0.5% of span 6.2.14 Repeat steps 6.2.10 through 6.2.13 until all indi cations are correct without further adjustment 6.2.15 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT IMPUT mA OUTPUT Vdc UP DOWN UP DOWNJ 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.0

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-I-1.74

  • UNIT 1' JUN 1 0 1381 REVISION 0 Page 4 6.0 PROCEDURE (continued) 6.2 (continued) 6.2.16 Disconnect the input and output wiring from PYB-2010 6.2.17 Apply an input of *.

Vdc 6.2.18 Verify bistable PYB-2010 actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP 6.2.19 Install module into an extender cord (PYT-?OlO) 6.2.20 Connect multimeter to TP-8 and corn, verify an output signal of 10.0 Vdc + 10.0 mV 6.2.21 Connect MUltineter to TP-lR and cor., verify an output signal of 333.0 mV + 1.0 mV 6.2.22 Connect multimeter to TP-19 and cor., verify an output signal of 167.0 mV + 1 mV 6.2.23 Disconnect input and output wiring from PI-2010A 6.2.24 Connect a variable input signal source 6.2.25 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0%, of span 6.2.26 Verify a zero indication + 1.0% of span 6.2.27 Apply an input signal of 10.0 Vdc for a full scale reading 6.2.2P Verify a full scale indication + 1.0% of scale 6.2.29 Repeat steps 6.2.25 through 6.2.27 until all indi cations are correct without further adjustment

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-11-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 5 6.0 PROCEDURE (continued) 6.?

(continued) 6.2.30 Perform a five point calibration verifying each point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN 0.00 30" Hg Vac 2.50 7.20" Hg Vac 5.00 7.50 PSIC 7.50 18.82 PSIC 10.00 30.00 PSIC 6.3 PT-3010 6.3.1 Disconnect input and output wiring from PT-3010 6.3.2 Connect a variable pressure or vacuum source to pres sure input connection of PT-3010 6.3.3 Apply an input pressure of 30" Hg Vacuum 6.3.4 Verify an output signal of 4.0 mA + 0.5% of span 6.3.5 Apply an input pressure of 30.0 PSI 6.3.6 Verify an output signal of 20.0 mA + 0.5% of span 6.3.7 Repeat steps 6.3.3 through 6.3.6 until all indi cations are correct without further adjustment 6.3.8 Perform a five point calibration verifying each point is within 0.%

of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT I NP UT OUTPUT mA UP DOWN UP DOWN t30" Hg Vac 4.00 15" Hg Vac 8.00 0.0 PSI 12.00 15.0 PSI 16.00 30.0 PSI 20.00

ENCODE BEO2BC SAN ONQFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74

  • NIT 1 JUN 1 0 1981 REVISION 0 Page 6 6.0 PROCEDURE (continued) 6.3 (continued) 6.3.9 Disconnect input and output wiring from PYV-3010 6.3.10 Apply an input signal of 4.0 mA 6.3.11 Verify an ouput signal of 0.00 Vdc + 0.5% of span 6.3.12 Apply an input signal of 20.0 mA 6.3.13 Verify an output signal of 10.0 Vdc + 0.5% of span 6.3.14 Repeat steps 6.3.10 through 6.3.13 until all indi cations are correct without further adjustment 6.3.15 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.3.16 Disconnect the input and output wiring from PYB-3010 6.3.17 Apply an input of
  • Vdc 6.3.18 Verify bistable PYB-3010 actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-11-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 7 6.0 PROCEDURE (continued) 6.3 (continued) 6.3.19 Install module into an extender card (PYT-3010) 6.3.20 Connect multimeter to TP-8 and corn, verify an output signal of 10.0 Vdc + 10.0 mV 6.3.21 Connect multireter to TP-18 and cor., verify an output signal of 333.0 my + 1.0 rnV 6.3.22 Connect multimeter to TP-19 and cor., verify an output signal of 167.0 my + 1.0 mV 6.3.23 Disconnect input and output wiring from PI-3010A 6.3.24 Connect a variable input signal source 6.3.25 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.3.26 Verify a zero indication + 1.0% of span 6.3.27 Apply an input signal of 10.0 Vdc for a full scale reading 6.3.28 Verify a full scale indication + 1.0% of scale 6.3.29 Repeat steps 6.3.25 through 6.3.28 until all indi cations are correct without further adjustment 6.3.30 Perform a five point calibration verifying each o point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION LIP DOWN UP D OW N 0.00 30" Hg Vac 2.50 7.20" Hq Vac 5.00 7.50 P1 m

7.50 nP.82 Pawo 10.00 30.00 Pall Sedn

ENCODE BEU2BC SAN ONQFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 UNIT 1 JUN" 1 0 191 REVISION 0 Page 8 6.0 PROCEDURE (continued) 6.4 PT-2011 6.4.1 Disconnect input and output wiring from PT-2011 6.4.2 Connect a variable pressure source to pressure input connection of PT-2011 6.4.3 Apply an input pressure of 200 PSI 6.4.4 Verify an output signal of 4.0 mA + 0.5% of.span 6.4.5 Apply an input pressure of 2000 PSI 6.4.6 Verify an output signal of 20.0 mA + 0.5% of span 6.4.7 Repeat steps 6.4.3 through 6.4.6 until all indi cations are correct without further adjustment 6.4.8 Perform a five point calibration verifying each point is within 0.%

of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT OUTPUT nA UP DOWN UP DOWN 200 4.0 500 P.0 1000 12.0 1500 16.0 2000 20.0 6.4.9 Disconnect input and output wiring from PYV-2011 6.4.10 Apply an input signal of 4.0 mA 6.0.11 Verify an ouput signal of 0.00 Vdc + 0.5% of span 6.4.12 Apply an input signal of 20.0 mA 6.4.13 Verify an output signal of 10.0 Vdc + 0.5% of span 6.4.14 Repeat steps 6.4.10 through 6.4.13 until all indi cations are correct without further adjustment

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-11-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 9 6.0 PROCEDURE (continued) 6.4 (continued) 6.4.15 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.4.16 Disconnect the input and output wiring from PI-2011 6.4.17 Connect a variable input signal source 6.4.18 Apply an input signal of Q1 Vdc for a zero indication

+ 1.0% of span 6.4.19 Verify a zero indication + 1.0% of span 6.4.20 Apply an input signal of 10.0 Vdc for a full scale reading.

6.4.21 Verify a full scale indication + 1.0% of scale 6.4.22 Repeat steps 6.4.18 through 6.4.21 until all indi cations are correct without further adjustment 6.4.23 Perform a five point calibration verifying each point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP OWN PSIGxlea0 0.00 0

. 2.50 5

5.00 10 7.50 15 10.00 20

ENCODE BEO2BC SAN ON9FRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sl-II-1.74 UNIT 1 JUN 1 099 REVISION 0 Page 10 6.0 PROCEDURE (continued) 6.5 PT-3011 6.5.1 Disconnect input and output wiring from PT-3011 6.5.2 Connect a variable pressure or vacuum source to pres sure input connection of PT-3011 6.5.3 Apply an input pressure of 200 PSI 6.5.4 Verify an output signal of 4.0 mA + 0.5% of span 6.5.5 Apply an input pressure of 2000 PSI 6.5.6 Verify an output signal of 20.0 mA + 0.5% of span 6.5.7 Repeat steps 6.5.3 through 6.5.6 until all indi cations are correct without further adjustment 6.5.8 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT PSI OUTPUT mA UP DOWN UP DOWN 200 4.0

.500 A.0 1000 12.0 1500 16.0 2000 20.0 6.F.O-Disconnect input and output wiring from PYV-3011 6.5.10 Apply an input signal of 4.0 mA 6.5.11 Verify an ouput signal of 0.00 Vdc + 0.5% of span 6.5.12 Apply an input signal of 20.0 mA 6.5.13 Verify an output signal of 10.0 Vdc + 0.5% of span 6.5.14 Repeat steps 6.5.10 through 6.5.13 until all indi-cations are correct without further adjustment

ENCODE BE02BC SAN ONQFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 11 6.0 PROCEDURE (continued) 6.5 (continued) 6.5.15 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.5.16 Disconnect the input and output wiring from PI-3011 6.5.17 Connect a variable input signal source 6.5.1P Apply an input signal of 0.00 Vdc for a zero indi cation + 1.0% of span 6.5.19 Verify a zero indication + 1.0% of span 6.5.20 Apply an input signal of 10.00 Vdc for a full scale reading.

6.5.21 Verify a full scale indication + 1.0% of scale 6.5.22 Repeat steps 6.5.18 through 6.5.21 until all indi cations are correct without further adjustment 6.5.23 Perfoec a five point calibration verifying each point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN PSIGxlOO 0.00 0

2.50 5

5.00 10 7.50 15 10.00 20

ENCODE BE02BC SAN ONQFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-I1-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 12 6.0 PROCEDURE (continued) 6.6 LT-2400A, 2400B and 2400C 6.6.1 Disconnect input and output Wiring from LT-2400A 6.6.2 Apply an input signal of 82.360" H20 to low side (high side vented) adjust ZERO SUPPRESSION for an output signal of 4.0 mA + 0.5% of span.

6.6.3 Apply an input signal of 44.624" H20 to low side (high side vented), Verify an output signal of 20.0 mA + 0.5% of span.

6.6.4 Repeat steps 6.6.2 through 6.6.3 until all indi cations are correct without further adjustment 6.6.5 Perform a five point calibraion verifying each point is within 0.5% of span.

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT H20 OUTPUT mA UP DOWN UP DOWN 82.360 4.00 72.926 8.00 63.492 12.00 54.058 16.00 44.624 20.00 6.6.6 Disconnect input and output wiring from LT-2400B 6.6.7 Apply an input signal of 82.360" H20 to low side (high side vented) adjust ZERO SUPPRESSION for a output signal of 4.0 mA + 0.5% of span 6.6.8 Apply an input signal of 44.624" H20 to low side (high side vented), Verify an output signal of 20.0 mA

+ 0.5% of span.

6.6.9 Repeat steps 6.6.7 through 6.6.8 until all indications are correct without further adjustment

FNCODE BEU2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 13 6.0 PROCEDURE (continued) 6.6 (continued) 6.6.10 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT H20 OUTPUT mA UP DOWN UP DOWN 82.360 4.00 72.926 8.00 63.492 12.00 54.058 16.00 Ad.6?4 20.00 6.6.11 Disconnect input and output wiring from LT-2400C 6.6.12 Apply an input signal of 82.360" H20 to low side (high side vented) adjust ZERO SUPPRESSION for a output signal of 4.0 mA + 0.5% of span 6.6.13 Apply an input signal of 44.624" H20 to low side (high side vented), Verify an output signal of 20.0 mA

+ 0.5% of span.

6.6.14 Repeat steps 6.6.12 through 6.6.13 until all indi cations are correct without further adjustment 6.6.15 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT " H20 OUTPUT mA UP DOWN UP DOWN 82.360 4.00 72.9?6 8.00 63.492 12.00 54.OP 16.00 44.624 20.00

ENCODE BEU2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SO1-II-1.74 UNIT 1 JUN 1 0 191 REVISION 0 Page 14 6.0 PROCEDURE (continued) 6.6 (continued) 6.6.16 Disconnect input and output wiring from LYV2400A 6.6.17 Apply an input signal of 4.0 mA 6.6.18 Verify an output signal of 0.00 Vdc + 0.5% of span 6.6.19 Apply a input signal of 20.0 mA 6.6.20 Verify an output signal of 10.0 Vdc + 0.5% of span 6.6.21 Repeat steps 6.6.17 through 6.6.20 until all indi cations are correct without further adjustment 6.6.22 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.6.23 Disconnect input and output wiring from LYV-2400B 6.6.24 Apply an input signal of 4.0 mA 6.6.25 Verify an output singal of 0.00 Vdc + 0.5% of span 6.6.26 Apply an input signal of 20.0 mA 6.6.27 Verify an output signal of 10.0 Vdc + 0.5% of span 6.6.28 Repeat steps 6.6.24 through 6.6.26 until all indi cations are correct without further adjustment 6.6.29 Perform a five point calibration verifying each point is within 0.5% of span

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01 -I1-1.74 UNIT 1 '

JUN 1 0 1981 REVISION 0 Page 15 6.0 PROCEDURE (continued) 6.6 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.6.30 Disconnect input and output wiring from LYV-2400C 6.6.31 Apply an input signal of 4.0 mA 6.6.32 Verify an output signal of 0.00 Vdc + 0.5% of span 6.6.33 Apply an input signal of 20.0 mA 6.6.34 Verify an output signal of 10.0 Vdc + 0.5% of span 6.6.35 Repeat steps 6.6.31 through 6.6.34 until all indications are correct without further adjustment 6.6.36 Perform a five point calibration verifying each point is within 0.5% of span.

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 1 6.0_________________

_________________________ 1_________________

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-II-1.74 UNIT 1 JUN 1 0 1901 REVISION 0 Page 16 6.0 PROCEDURE (continued) 6.6 (continued) 6.6.37 Disconnect the input and output wiring from LYB-2400A 6.6.38 Apply an input of

  • Vdc Verify Bistable LYB-2400A actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP 6.6.39 Disconnect the input and output wiring from LYB-2400B 6.6.40 Apply an input of
  • Vdc Verify Bistable LYB-2400B actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPIniT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SOl-II-1.7 4 UNIT 1 '

JUN 1 0 1981 PEVISION 0 Page 17 6.0 PROCEDURE (continued) 6.6 (continued) 6.6.41 Disconnect the input and output wiring from LYB-2400C 6.6.42 Apply an input of

  • Vdc Verify Bistable LYB-2400C actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP 6.6.43 Disconnect input and output wiring from LI-2400A 6.6.44 Connect a variable input signal source 6.6.45 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.6.46 Verify a zero indication + 1.0% of span 6.6.47 Apply an input signal of 10.0 Vdc for a full scale reading 6.6.48 Verify a full scale indication + 1.0% of scale 6.6.49 Repeat steps 6.6.45 through 6.6.48 until all indi cations are correct without further adjustment 6.6.50 Perform a five point calibration verifying each point is within 1.0% of full span.

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-I1-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 18 6.0 PROCEDURE (continued) 6.6 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN LEVEL FEET 0.00 235 2.50 245 5.00 255 7.50 265 10.00 275 6.6.51 Disconnect input and output wiring from LI-2400B 6.6.52 Connect a variable input signal source 6.6.53 Apply an input signal of 0.0 Vdc for a zero idi cation + 1.0% of span 6.6.54 Verify a zero indication + 1.0% of span 6.6.55 Apply an input signal of 10.0 Vdc for a full scale reading 6.6.56 Verify a full scale indication + 1.0% of scale.

6.6.57 Repeat steps 6.6.53 through 6.6.56 until all indi cations are correct without further adjustment 6.6.58 Perform a five point calibration verifying each point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN LEVEL FEET 0.00 235 2.50 245 5.00 255 7.50 265 10.00 275

ENCODE BE2BC SAN ONWfRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SOl-11-1.74

  • UNIT 1 JUN 1 0 OT REVISION 0 Page 19 6.0 PROCEDURE (continued) 6.6 (continued) 6.6.59 Disconnect input and output wiring from LI-2400C 6.6.60 Connect a variable input signal source 6.6.61 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.6.62 Verify a zero indication + 1.0% of span 6.6.63 Apply an input signal of 10.0 Vdc for a full scale reading 6.6.64 Verify a full scale indication + 1.0% of scale 6.6.65 Repeat steps 6.6.61 through 6.6.64 until all indi cations are correct without further adjustment 6.6.66 Perform a five point calibration verifying each point is within a 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN LEVEL FEET 0.00 235 2.50 245 5.00 255 7.50 265 10.00 275 6.7 LT-3400A, 3400B & 3400C 6.7.1 Disconnect input and output wiring from LT-3400A 6.7.2 Apply an input signal of 82.360" H20 to low side (high side vented) adjust ZERO SUPPRESSION for an output signal of 4.0 mA + 0.5% of span 6.7.3 Apply an input signal of 44.624" H20 to low side (high side vented), Verify an output signal of 20.0 mA + 0.5% of span

ENCODE BEU2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-11-1.74 UNIT 1 JUN 1 0 8i8 REVISION 0 Page 20 6.0 PROCEDURE (continued) 6.7 (continued) 6.7.4 Repeat steps 6.7.2 through 6.7.3 until all indi cations are correct without further adjustment 6.7.5 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT H20 OUTPUT mA UP DOWN UP DOWN 82.360 4.00 72.926 8.00 63.492 12.00 54.058 16.00 44.624 20.00 67.6 Disconnect input and output wiring from LT-3400B 6.7.7 Apply an input signal of 82.360" HyO to low side (high side vented) adjust ZERO SUPPRESSION for an verify an output signal of 4.0 mA + 0.5% of span 6.7.8 Apply an input signal of 44.624" H20 to low side (high side vented), verify an output signal of 20.0 mA + 0.5% of span 6.7.9 Repeat steps 6.7.6 through 6.7.7 untill all indi cations are correct without further adjustment 6.7.10 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT H20 OUTPUT mA UP DOWN UP DOWN 82.360 4.00 72.926 8.00 63.492 12.00 54.058 16.00 44.624 20.00

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 UNIT 1 'JUN 101981 REVISION 0 Page 21 6.0 PROCEDURE (continued) 6.7 (continued 6.7.11 Disconnect input and output wiring from LT-3400C 6.7.12 Apply an input signal of 82.360" H20 to low side (high side vented) adjust ZERO SUPPRESSION for an output signal of 4.0 mA + 0.5% of span 6.7.13 Apply an input signal of 44.624" H20 to low side (high side vented), verify an output signal of 20.0 mA + 0.5% of span 6.7.14 Repeat steps 6.7.10 through 6.7.11 untill all indi cations are correct without further adjustment 6.7.15 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT H20 OUTPUT mA UP DOWN UP DOWN 82.360 4.00 72.926 8.00 63.492 12.00 54.058 16.00 44.624 20.00 6.7.16 Disconnect input and output wiring from LYV-3400A 6.7.17 Apply an input signal of 4.0 mA 6.7.18 Verify an output signal of 0.00 Vdc + 0.5% of span 6.7.19 Apply an input signal of 20.0 mA 6.7.20 Verify an output signal of 10.0 Vdc + 0.5% of span 6.7.21 Repeat steps 6.7.15 through 6.7.18 until all indi cations are correct without further adjustment 6.7.22 Perform a five point calibration verifying each point is within 0.5% of span

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SO1-II-1.74 U NIT 1 JuN 1 GC REVISION 0 Page 22 6.0 PROCEDURE (continued) 6.7 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.7.23 Disconnect input and output wiring from LYV-3400B 6.7.24 Apply an input signal of 4.0 mA 6.7.25 Verify an output signal of 0.00 Vdc + 0.5% of span 6.7.26 Apply an input signal of 20.0 mA 6.7.27 Verify an output signal of 10.0 Vdc + 0.5% of span 6.7.28 Repeat steps 6.7.22 through 6.7.25 until all indi cations are correct without further adjustment 6.7.29 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.7.30 Disconnect input and output wiring from LYV-3400C

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sol-11-1.74 UNIT 1 '

JUN 1 0 1981 REVISION 0 Page 23 6.0 PROCEDURE (continued) 6.7 (continued) 6.7.31 Apply an input signal of 4.0 mA 6.7.32 Verify an output signal of 0.00 Vdc + 0.5% of span 6.7.33 Apply an input signal of 20.0 mA 6.7.34 Verify an output signal of 10.0 Vdc + 0.5% of span 6.7.35 Repeat steps 6.7.29 through 6.7.32 until all indi cations are correct without further adjustment 6.7.36 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIF SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.7.37 Disconnect the input and output wiring from LYB-3400A 6.7.38 Apply an input of

  • Vdc Verify Bistable LYB-3400A actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK LIP SETPOINT LOCK UP SFTPOINT LOCK UP

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 NIT 1 JUN U

Q I REVISION 0 Page 24 6.0 PROCEDURE (continued) 6.7 (continued) 6.7.39 Disconnect the input and output wiring from LYB-3400B 6.7.40 Apply an input of

  • Vdc Verify Bistable LYB-3400B actuates SPECIFIED SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP 6.7.41 Disconnect the input and output wiring from LYB-3400C 6.7.42 Apply an input of
  • Vdc Verify Bistable LYB-3400C actuates SPECIFIEP SPECIFIED FOUND FOUND LEFT LEFT SETPOINT LOCK UP SETPOINT LOCK UP SETPOINT LOCK UP

ENCODE BEU2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sol1-II1.74

  • NIT 1 JUN 1 0 1981 REVISION 0 Page 25 6.0 PROCEDURE (continued) 6.7 (continued) 6.7.43 Disconnect input and output wiring from LI-3400A 6.7.44 Connect a variable input signal source 6.7.45 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.7.46 Verify a zero indication + 1.0% of span 6.7.47 Apply an input signal of 10.0 Vdc for a full scale reading 6.7.40 Verify a full scale indication + 1.0% of scale 6.7.49 Repeat steps 6.7.43 through 6.7.46 until all indi cations are correct without further adjustment 6.7.50 Perform a five point calibration verifying each point is within a 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN LEVEL FEET 0.00 235 2.50 245 5.00 255 7.50 265 10.00 275 6.7.51 Disconnect input and output wiring from LI-3400B 6.7.52 Connect a variable input signal source 6.7.53 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.7.54 Verify a zero indication + 1.0% of span 6.7.55 Apply an input signal of 10.0 Vdc for a full scale reading

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-I-1.74 O

UNIT 1 JUN 10 REVISION 0 Page 26 6.0 PROCEDURE (continued) 6.7 (continued) 6.7.56 Verify a full scale indication + 1.0% of scale 6.7.57 Repeat steps 6.7.53 through 6.7.56 until all indi cations are correct without further adjustment 6.7.58 Perform a five point calibration verifying each point is within a 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc INDICATION UP DOWN UP DOWN LEVEL FEET 0.00 235 2.50 245 5.00 255 7.50 265 10.00 275 6.7.59 Disconnect input and output wiring from LI-3400C 6.7.60 Connect a variable input signal source 6.7.61 Apply an input siginal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.7.62 Verify a zero indication + 1.0% of span 6.7.63 Apply an input signal of 10.0 Vdc for a full scale reading 6.7.64 Verify a full scale indication + 1.0% of scale 6.7.65 Repeat steps 6.7.61 through 6.7.64 until all indi cations are correct without further adjustment 6.7.66 Perform a five point calibration verifying each point is within a 1.0% of full span

ENCODE BEU2BC SAN ONOFRENUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74

  • IT 1 JUN 1 0 1981 REVISION 0 Page 27 6.0 PROCEDURE (continued) 6.7 (continued)

UN ASLEFTAS LEFT SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT DOWN INPUT Vdc INDICATION UP DOWN UP DOWN LEVEL FEET 0.00 235 2.50 245 5.00 255 7.50 265 10.00 275 6.8 HC-2300, 2301, 3300 and 3301 6.8.1 Place HC-2300 in the manual position 6.8.2 Set A/M station to 0%, verify FYI-2300 indicates 0.0 Vdc 6.8.3 Set A/M station to 100% verify FYI-2300 indicates 10.0 Vdc 6.8.4 Place HC-2301 in the manual position 6.8.5 Set A/M station to 0%, verify FYI-2301 indicates 0.0 Vdc 6.8.6 Set A/M station to 100% verify FYI-2301 indicates 10.0 Vdc 6.8.7 Place KC-3300 in the manual position 6.8.8 Set A/M station to 0%, verify FYI-3300 indicates 0.0 Vdc 6.8.9 Set A/M station to 100% verify FYI-3300 indicates 10.0 Vdc 6.8.10 Place HC-3301 in the manual position 6.8.11 Set A/M station to 0%, verify FYI-3301 indicates 0.0 Vdc

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-11-1.74 UNIT 1 JUN 1 0 196i REVISION 0 Page 28 6.0 PROCEDURE (continued) 6.8 (continued) 6.8.12 Set A/M station to 100% verify FYI-3301 indicates 10.0 Vdc 6.8.13 Disconnect input and output wiring from FYI-2300 6.8.14 Apply an input signal of 0.0 Vdc 6.8.15 Verify an output signal of 10.00 + 0.50 mA 6.8.16 Apply an input signal of 10.00 Vdc 6.8.17 Verify an output signal of 20.00 + 0.50 mA 6.8.18 Repeat steps 6.8.14 through 6.8.17 until all indi cations are correct without further adjustment 6.8.19 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.0 10.0 2.5 12.5 5.0 15.0 7.5 17.5 10.0 20.0 6.8.20 Disconnect input and output wiring from FYI-2301 6.8.21 Apply an input signal of 0.0 Vdc 6.8.22 Verify an; output signal of 10.00 + 0.50 mA 6.8.23 Apply an input signal of 10.00 Vdc 6.8.24 Verify an output signal of 20.00 + 0.50 mA 6.8.25 Repeat steps 6.8.21 through 6.8.24 until all indi cations are correct without further adjustment

ENCODE BEO2BC SAN ONOFRE NUQLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SO-1I-1.74

.0 UNIT 1 JN 0 198i REVISION 0 Page 29 6.0 PROCEDURE (continued) 6.8 (continued) 6.8.26 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.0 10.0 2.5 12.5 5.0 15.0 7.5 17.5 10.0 20.0 6.8.27 Disconnect input and output wiring from FYI-3300

(

6.8.28 Apply an input signal of 0.0 Vdc 6.8.29 Verify an output signal of 10.00 + 0.50 mA 6.8.30 Apply an input signal of 10.00 Vdc 6.8.31 Verify an output signal of 20.00 + 0.50 mA 6.8.32 Repeat steps 6.8.28 through 6.8.31 until all indi cations are correct without further adjustment 6.8.33 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.0 10.0 2.5 12.5 5.0 15.0 7.5 17.5 10.0 20.0

ENCODE BE02BC SNNONOFRE RUCL.

1 G ATING STATION INSTRUMENT & TEST PROCEDURE SO-IIlge740 UNIT 1 REVISION 0Pae3 6.0 PROCEDURE (continued) 6.8 (continued) 6.8.34 Disconnect input and output wiring from FYI-3301 6.8.35 Apply an input signal of 0.0 Vdc 6.8.36 Verify an output signal of 10.00 + 0.50 mA 6.8.37 Apply an input signal of 10.00 Vdc 6.8.38 Verify an output signal of 20.00 + 0.50 mA 6.8.39 Repeat steps 6.8.35 through 6.8.38 until all indi-cations are correct without further adjustment 6.8.40 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT I AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.0 10.0 2.5 12.5 5.0 15.0 7.5 17.5 10.0 20.0 6.9

FTL, 3453, 3454 and 3455 FTH, 3453, 3454 and 3455 6.9.1 Disconnect input and output wiring from FTL-3453 6.9.2 Apply an input pressure of 0.0" H20 6.9.3 Verify an output signal of 4.0 mA + 0.5% of span 6.9.4 Apply an input pressure of 33.5" H20 6.9.5 Verify an output signal of 20.0 mA + 0.5% of span

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 S NIT 1 JUN 1 0 1961 REVISION 0 Page 31 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.6 Repeat steps 6.9.2 through 6.9.5 until all indi cations are correct without further adjustment 6.9,.7 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT" H20 OUTPUT" H20 UP DOWN UP DOWN 0.0 4.0 8.375 8.0 16.75 12.0 25.125 16.0 33.5 20.0 6.9.8 Disconnect input and output wiring from FTH-3453 6.9.9 Apply an input pressure of 0.0" H20 6.9D10 Verify an output signal of 4.0 mA + 0.5% of spanFTH 6.9.11 Apply an input pressure of 300.0" H20 6.9.12 Verify an output signal of 20.0 mA + 0.5% of span 6.9.13 Repeat steps 6.9.9 through 6.9.12 until all indi cations are correct without further adjustment 6.9.14 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT" H20 OUTPUT" H20 UP DOWN UP DOWN 0.0 4.0 75.0 8.0 150.0 12.0 225.0 16.0 300.0 20.0

ENCODE BEO2BC SAN ONOFRE NUCLEAR;GE ERATING STATION INSTRUMENT-& TEST PROCEDURE 501-11-1.74 UNIT 1 UN 1.

1981 REVISION 0 Page 32 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.15 Disconnect input and output wiring from FTL-3454 6.9.16 Apply an input pressure of 0.0" H20 6.9.17 Verify an output signal of 4.0 mA + 0.5% of span 6.9.18 Apply an input pressure of 33.5" H20 6.9.19 Verify an output signal of 20.0 mA + 0.5% of span 6.9.20 Repeat steps 6.9.16 through 6.9.19 until all indi cations are correct without further adjustment 6.9.21 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT" H20 OUTPUT" H20 UP DOWN UP DOWN 0.0 4.0 8.375 8.0 16.75 12.0 25.125 16.0 33.5 20.0 6.9.22 Disconnect input and output wiring from FTH-3454 6.9.23 Apply an input pressure of 0.0" H20 6.9.24 Verify an output signal of 4.0 mA + 0.5% of span 6.9.25 Apply an input pressure of 300.0" H20 6.9.26 Verify an output signal of.20.0 mA + 0.5% of span 6.9.27 Repeat steps 6.9.23 through 6.9.26 until all indi cations are correct without further adjustment

ENCODE BEU2BC SAN ONOFRE NUCLEAR QENERATING STATION INSTRUMENT & TEST PROCEDURE 501-11-1.74

  • UNIT 1

JUN 1 0 B' REVISION 0 Page 33 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.28 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT

.AS LEFT INPUT" H20 OUTPUT" H20 UP DOWN UP DOWN 0.0 4.0 75.0 8.0 150.0 12.0 225.0 16.0 300.0 20.0 6.9.29 Disconnect input and output wiring from FTL-3455 6.9.30 Apply an input pressure of 0.0" H20 6.9.31 Verify an output signal of 4.0 mA + 0.5% of span 6.9.32 Apply an input pressure of 33.5" H20 6.9.33 Verify an output signal of 20.0 mA + 0.5% of span 6.9.34 Repeat steps 6.9.30 through 6.9.33 until all indi cations are correct without further adjustment 6.9.35 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT" H20 OUTPUT" H20 UP DOWN UP DOWN 0.0 4.0 8.375 8.0 16.75 12.0 25.125 16.0 S

20.0

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sol-11-1.74 NIT 1 JUN 1 0 1981 REVISION 0 Page 34 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.36 Disconnect input and output wiring from FTH-3455 6.9.37 Apply an input pressure of 0.0" H20 6.9.38 Verify an output signal of 4.0 mA + 0.5% of span 6.9.39 Apply an input pressure of 300.0" H20 6.9.40 Verify an output signal of 20.0 mA + 0.5% of span 6.9.41 Repeat steps 6.9.37 through 6.9.40 until all indi cations are correct without further adjustment 6.9.42 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT" H?0 OUTPUT" H20 UP DOWN UP DOWN 0.0 4.0 75.0 8.0 150.0 12.0 225.0 16.0 300.0 20.0 6.9.43 Disconnect input and output wiring from FYV-3453A 6.9.44 Apply an input signal of 4.0 mA 6.9.45 Verify an output signal of 0.00 Vdc + 0.5% of span 6.9.46 Apply an input signal of 20.0 mA 6.9.47 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.48 Repeat steps 6.9.44 through 6.9.47 until all indi cations are correct without further adjustment 6.9.49 Perform a five point calibration verifying each point is within 0.5% of span

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SO-11-1.74

.UNIT 1

JUN 1 0 1981 REVISION 0 Page 35 6.0 PROCEDURE (continued) 6.9 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT

-AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.9.50 Disconnect input and output wiring from FYV-3453B 6.9.51 Apply an input signal of 4.0 mA 6.9.52 Verify an output signal of 0.00 Vdc + 0.5% of span 6.9.53 Apply an input signal of 20.0 mA 6.9.54 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.55 Repeat steps 6.9.51 through 6.9.54 until all indi cations are correct without further adjustment 6.9.56 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.9.57 Disconnect input and output wiring from FYV-3454A 6.9.58 Apply an input signal of 4.0 mA 6.9.59 Verify an output signal of 0.00 Vdc + 0.5% of span 6.9.60 Apply an input signal of 20.0 mA

ENCODE BEO2BC SAN ONOFRE NUCLEARIGENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-.74

  • NIT 1 J*;r.;0 1u_;

REVISION 0 Page 36 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.61 Verify an output signal of 10.0 Vdc + 0.5% of span, 6.9.62.

Repeat steps 6.9.58 through 6.9.61 until all indi cations are correct without further adjustment 6.9.63 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 A.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.9.64 Disconnect input and output wiring from FYV-3454B 6.9.65 Apply an input signal of 4.0 mA 6.9.66 Verify an output signal of 0.00 Vdc + 0.5% of span 6.9.67 Apply an input signal of 20.0 mA 6.9.68 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.69 Repeat steps 6.9.65 through 6.9.68 until all indi cations are correct without further adjustment 6.9.70 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-I-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 37 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.71 Disconnect input and output wiring from FYV-3455A 6.9.72 Apply an input signal of 4.0 mA 6.9.73 Verify an output signal of 0.00 Vdc + 0.5% of span 6.9.74 Apply an input signal of 20.0 mA 6.9.75 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.76 Repeat steps 6.9.72 through 6.9.75 until all indi cations are correct without further adjustment 6.9.77 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT nA OUTPUT Vdc UP DOWN UP DOWN 4.00 0.00 8.00 2.50 12.00 5.00 16.00 7.50 20.00 10.00 6.9.78 Disconnect input and output wiring from FYV-3455B 6.9.79 Apply an input signal of 4.0 mA 6.9.80 Verify an output signal of 0.00 Vdc + 0.5% of span 6.9.81 Apply an input signal of 20.0 mA 6.9.82 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.83 Repeat steps 6.9.79 through 6.9.82 until all indi cations are correct without further adjustment 6.9.84 Perform a five point calibration verifying each point is within 0.5% of span

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 O UNIT 1 JUN4 0 19R1 REVISION 0 Page 38 6.0 PROCEDURE (continued) 6.9 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT mA OUTPUT Vdc UP DOWN UP DOWN 4.0 0.00 8.0 2.50 12.0 5.00 16.0 7.50 20.0 10.00 6.9.85 Disconnect input and output wiring from FYQ-3453A 6.9.86 Apply an input sional of 0.100 Vdc 6.9.87 Verify an output signal of 1.00 Vdc + 0.5% of span 6.9.88 Apply an input signal of 10.0 Vdc 6.9.89 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.90 Repeat steps 6.9.86 through 6.9.89 until all indi cations are correct without further adjustment 6.9.91 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP DOWN UP DOWN 0.100 1.00 0.62F 2.50 2.500 5.00 5.62F 7.50 10.000 10.00 6.9.92 Disconnect input and output wiring from FYQ-3453B 6.9.93 Apply an input signal of 0.100 Vdc 6.9.94 Verify an output signal of 1.00 Vdc + 0.5% of span 6.9.95 Apply an input signal of 10.0 Vdc

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-11-1.74 UNIT 1 U

m0 REVISION 0 Page 39 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.96 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.97 Repeat steps 6.9.92 through 6.9.95 until all indi cations are correct without further adjustment 6.9.98 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP DOWN UP DOWN 0.100 1.00 0.625 2.50 2.500 5.00 5.625 7.50 10.000 10.00 6.9.99 Disconnect input and output wiring from FYQ-3454A 6.9.100 Apply an input signal of 0.100 Vdc 6.9.101 Verify an output signal of 1.00 Vdc + 0.5% of span 6.9.102 Apply an input signal of 10.0 Vdc 6.9.103 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.104 Repeat steps 6.9.100 through 6.9.103 until all indi cations are correct without further adjustment 6.9.105 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP DOWN UP DOWN 0.100 1.00 0.625 2.50 2.500 5.00 5.625 7.50 10.000 10.00

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S0l-II-1.74 NIT 1 JUN 1 0 1981 REVISION 0 Page 40 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.106 Disconnect input and output wiring from FYQ-3454B 6.9.107 Apply an input signal of 0.100 Vdc 6.9.108 Verify an output signal of 1.00 Vdc + 0.5% of span 6.9.109 Apply an input signal of 10.0 Vdc 6.9.110 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.111 Repeat steps 6.9.107 through 6.9.110 until all indi cations are correct without further adjustment 6.9.112 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP DOWN UP DOWN 0.100 1.00 0.625 2.50 2.500 5.00 5.625 7.50 10.000 10.00 6.9.113 Disconnect input and output wiring from FYQ-3455A 6.9.114 Apply an input signal of 0.100 Vdc 6.9.115 Verify an output signal of 1.00 Vdc + 0.5% of span 6.9.116 Apply an input signal of 10.0 Vdc 6.9.117 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.118 Repeat steps 6.9.114 through 6.9.117 until all indi cations are correct without further adjustment 6.9.119 Perform a five point calibration verifying each point is within 0.5% of span

SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SOl-11-1.74

, IT 1 JUJN l1.901 REVISION 0Pae4 6.0 PROCEDURE (continued) 6.9 (continued)

S LEFT SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP DOWN UP DOWN 0.100 1.00 0.625 2.50 2.500 5.00 5.625 7.50 10.000 10.00 6.9.120 Disconnect input and output wiring from FYQ-3455B 6.9.121 Apply an input signal of 0.100 Vdc 6.9.122 Verify an output signal of 1.00 Vdc + 0.5% of span 6.9.123 Apply an input signal of 10.0 Vdc 6.9.124 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.125 Repeat steps 6.9e121 through 6.9.124 until all indi cations are correct without further adjustment 6.9.126 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP DOWN UP DOWN 0.100 1.00 0.625 2.50 2.500 5.00 5.625 7.50 10.000 10.00 6.9.127 Disconnect input and output wiring from FYA-345 3 6.9.128 Apply a 7.0 Vdc input signal to inputs A & B 6.9.129 Apply a 3.0 Vdc input signal to inputs C & D

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sl-11-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 42 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.130 Verify an output signal of 7.0 Vdc 6.9.131 Apply a 7.0 Vdc input signal to inputs C & D 6.9.132 Apply a 3.0 Vdc input signal to inputs A & B 6.9.133 Verify an output signal of 7.0 Vdc 6.0.134 Apply a 7.0 Vdc input signal to inputs A & C 6.9.135 Apply a 3.0 Vdc input signal to inputs B & D 6.9.136 Verify an output signal of 7.0 Vdc 6.9.137 Apply a 7.0 Vdc input signal to inputs A & D 6.9.138 Apply a 3.0 Vdc input signal to inputs B & C 6.9.139 Verify an output signal of 7.0 Vdc 6.9.140 Apply 7.0 Vdc input signal to inputs B & C 6.9.141 Apply a 3.0 Vdc input signal to inputs A & D 6.9.142 Verify an output signal of 7.0 Vdc 6.9.143 Apply a 7.0 Vdc input signal to inputs B & D 6.9.144 Apply a 3.0 Vdc input signal to inputs A & C 6.9.145 Verify an output signal of 7.0 Vdc 6.9.146 Disconnect input and output wiring from FYA-3454 6.9.147 Apply a 7.0 Vdc input signal to inputs A & B 6.9.148 Apply a 3.0 Vdc input signal to inputs C & D 6.9.149 Verify an output signal of 7.0 Vdc 6.9.lFO Apply a 7.0 Vdc input signal to inputs C & D 6.9.1 51 Apply a 3.0 Vdc input signal to inputs A & B 6.9.152 Verify an output signal of 7.0 Vdc 6.9.1 53 Apply a 7.0 Vdc input signal to inputs A & C

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SO1-II-1.74 UNIT 1 JUN 10 3

REVISION 0 Page 43 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.154 Apply a 3.0 Vdc input signal to inputs B & D 6.9.155 Verify an output signal of 7.0 Vdc 6.9.156 Apply a 7.0 Vdc input signal to inputs A & D 6.9.157 Apply a 3.0 Vdc input signal to inputs B & C 6.9.158 Verify an output signal of 7.0 Vdc 6.9.159 Apply,7.0 Vdc input signal to inputs B & C 6.9.160 Apply a 3.0 Vdc input signal to inputs A & D 6.9.161 Verify an output signal of 7.0 Vdc 6.9.162 Apply a 7.0 Vdc input signal to inputs B & D 6.9.163 Apply a 3.0 Vdc input signal to inputs A & C 6.9.164 Verify an output signal of 7.0 Vdc 6.9.165 Disconnect input and output wiring from FYA-3455 6.9.166 Apply a 7.0 Vdc input signal to inputs A & B 6.9.167 Apply a 3.0 Vdc input signal to inputs C & D 6.9.168 Verify an output signal of 7.0 Vdc 6.9.169 Apply a 7.0 Vdc input signal to inputs C & D 6.9.170 Apply a 3.0 Vdc input signal to inputs A & B 6.9.171 Verify an output signal of 7.0 Vdc 6.9.172 Apply a 7.0 Vdc input signal to inputs A & C 6.9.173 Apply a 3.0 Vdc input signal to inputs B & D 6.9.174 Verify an output signal of 7.0 Vdc 6.9.175 Apply a 7.0 Vdc input signal to inputs A & D 6.9.176 Apply a 3.0 Vdc input signal to inputs B & C 6.9.177 Verify an output signal of 7.0 Vdc

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-11-1.74 UNIT 1 JUN10 REVISION 0 Page 44 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.178 Apply 7.0 Vdc input signal to inputs B & C 6.9.179 Apply a 3.0 Vdc input signal to inputs A & D 6.9.180 Verify an output signal of 7.0 Vdc 6.9.181 Apply a 7.0 Vdc input signal to inputs B & D 6.9.182 Apply a 3.0 Vdc input signal to inputs A & C 6.9.183 Verify an output signal of 7.0 Vdc 6.9.184 Disconnect input and output wiring from FYS-3453A 6.9.185 Connect a variable voltage source to "A" input con nector 6.9.186 Apply an input 6f 0.0 Vdc 6.9.187 Verify an output signal of 0.0 Vdc + 0.5% of span 6.9.188 Apply an input of 3.333 Vdc_

6.9.189 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.190 Repeat steps 6.9.186 through 6.9189 until all indi cations are correct without furterh adjustment 6.9.191 Perform a five point calibration verifying each point is withing 0.5% of span SPEC IFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP Vdc DOWN Vdc UP Vdc DOWN Vdc 0.00 0.00 0.833 2.50 1.667 5.00 2.500 7.50 3.333 10.00 6.9.192 Disconnect input and output wiring from FYS-3454 6.9.193 Connect a variable voltage source to "A" input con

-_pti nec to r

SAN ONOFE NUCLEA GFNE MENCODE BE02BC

-117 SAN ONFRE NUCLEAR GfNEI5,TING STATION INSTRUMENT & TEST PROCEDURE So1-Iag745 UNIT 1 I U REVISION 0 Page 45 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.194 Apply an input of 0.0 Vdc 6.9.195 Verify an output signal of 0.0 Vdc + 0.5% of span 6.9.196 Apply an input of 3.333 Vdc_

6.9.197 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.198 Repeat steps 6.9.194 through 6.9.197 until all indi cations are correct without furterh adjustment 6.9.199 Perform a five point calibration verifying each point is within 0.5% of span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT

. INPUT Vdc OUTPUT Vdc UP Vdc DOWN Vdc UP Vdc DOWN Vdc 0.00 0.00 0.833 2.50 1.667 5.00 2.500 7.50 3.333 10.00 6.9.200 Disconnect input and output wiring from FYS-3455 6.9.201 Connect a variable voltage source to "A" input con nector 6.9.202 Apply an input of 0.0 Vdc 6.9.203 Verify an output signal of 0.0 Vdc + 0.5% of span 6.9.204 Apply an input of 3.333 Vdc_

6.9.205 Verify an output signal of 10.0 Vdc + 0.5% of span 6.9.206 Repeat steps 6.9.202 through 6.9.205 until all indi cations are correct without furterh adjustment 6.9.207 Perform a five point calibration verifying each point is within 0.5% of span

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE 501-I1-1.74 UNIT 1 JUN 1 0 1961 REVISION 0 Page 46 6.0 PROCEDURE (continued) 6,9 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT Vdc UP Vdc DOWN Vdc UP Vdc DOWN Vdc 0.00 0.00 0.833 2.50 1.667 5.00 2.500 7.50 3.333 10.00 6.9.208 Disconnect input and output wiring from FYI-3453 6.9.209 Apply an input signal of 0.00 Vdc 6.9.210 Verify an output signal of 10.0 mA + 0.5% of span 6.9.211 Apply an input signal of 10.0 Vdc 6.9.212 Verify an output signal of 20.0 mA + 0.5% of span 6.9.213 Repeat steps 6.9.209 through 6.9.212 until all indi cations are correct without further adjustment 6.9.214 Perform a five point calibartion verifying each point SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.00 10.0 2.50 12.5 5.00 15.0 7.50 17.5 10.0 20.0 6.9.215 Disconnect input and output wiring from FYI-3454 6.9.216 Apply an input signal of 0.00 Vdc 6.9.217 Verify an output signal of 10.0 mA + 0.5% of span 6.9.218 Apply an input signal of 10.0 Vdc

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sol-II-1.74

  • NIT 1 J

UN 1,3-6 REVISION 0 Page 47 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.219 Verify an output signal of 20.0 mA + 0.5% of span 6.9.220 Repeat steps 6.9.216 through 6.9.219 until all indi cations are correct without further adjustment 6.9.221 Perform a five point calibartion verifying each point SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.00 10.0 2.50 12.5 I

5.00 15.0 7.50 17.5 10.0 20.0 6.9.222 Disconnect input and output wiring from FYI-3455 6.9.223 Apply an input signal of 0.00 Vdc 6.9.224 Verify an output signal of 10.0 mA + 0.5% of span 6.9.225 Apply an input signal of 10.0 Vdc 6.9.226 Verify an output signal of 20.0 mA + 0.5% of span 6.9.227 Repeat steps 6.9.223 through 6.9.226 until all indi cations are correct without further adjustment 6.9.228 Perform a five point calibration verifying each point SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT Vdc OUTPUT mA UP DOWN UP DOWN 0.00 10.0 2.50 12.5 5.00 15.0 7.50 17.5 10.0 20.0

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 48 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.229 Disconnect input and output wiring from FI-3453 6.9.230 Connect a variable input signal source 6.9.231 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.9.232 Verify a zero indication + 1.0% of span 6.9.233 Apply an input signal of 10.0 Vdc for a full scale reading 6.9.234 Verify a full scale indication + 1.0% of scale 6.9.235 Repeat steps 6.9.231 through 6.9.234 until all indi cations are correct without further adjustment 6.9.236 Perform a five point calibration verifying each point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT INDICATION UP DOWN UP DOWN GPM1 0.00 0

2.50 75 5.00 150 7.50 225 10.0 300 6.9.237 Disconnect input and output wiring from FI-3454 6.9.238 Connect a variable input signal source 6.9.239 Apply an input signal of 0.0 Vdc for a zero indi cation + 1.0% of span 6.9.240 Verify a zero indication + 1.0% of span S1

ENCODE BEO2BC SAN ONOFRE NUCLEAR GINERATING STATION INSTRUMENT & TEST PROCEDURE S01-II-1.74 UNIT 1 1, 1 0 1981 REVISION 0 Page 49 6.0 PROCEDURE (continued) 6.9 (continued) 6.9.241 Apply an input signal of 10.0 Vdc for a full scale reading 6.9.242 Verify a full scale indication + 1.0% of scale 6.9.243 Repeat steps 6.9.239 through 6.9.242 until all indi cations are correct without further adjustment 6.9.244 Perform a five point calibration verifying each point is within 1.0% of full span SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT INDICATION UP DOWN UP DOWN GPM 0.00 0

2.50 75 5.00 150 7.50 225 10.0 300 6.9.245 Disconnect input and output wiring from FI-3455 6.9.246 Connect a variable input signal source 6.9.247 Apply an input signal of 0.00 Vdc for a zero indi cation + 1.0% of span 6.9.248 Verify a zero indication + 1.0% of span 6.9.249 Apply an input signal of 10.000 Vdc for a full scale reading 6.9.250 Verify a full scale indication + 1.0% of scale 6.9.251 Repeat steps 6.9.247 through 6.9.250 until all indi cations are correct without further adjustment 6.9.252 Perform a five point calibration verifying each point is within 1.0% of full span

ENCODE BEu2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT A TEST PROCEDURE S0l1-II1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 50 6.0 PROCEDURE (continued) 6.9 (continued)

SPECIFIED SPECIFIED AS FOUND AS FOUND AS LEFT AS LEFT INPUT INDICATION UP DOWN UP DOWN GPM 0.00 0

2.50 75 5.00 150 7.50 225 10.0 300 6.10 Auxiliary Feedwater System Loop Verifications 6.10.1 Connect a variable pressure source to the specified transmitter monitor the input and output signals.

6.10.2 Verify that the output of each component functions correctly. (i.e. wiring, calibration, and instal lation).

6.10.3 Record all data on the appropriate data sheet or SO-16 6.10.4 Perform at a minimum, a five point verification from 0 to 150%

6.10.5 Enter the test data base i.e. Voltage, mA, flow and pressure values for all test included in this proce dure at each point marked with an asterisk (*).

6.10.6 Connect a variable pressure/vacuum source to PT-2010 apply an input signal of

  • verify "SUCTION LOW PRESSURE" annuciator alarms.

6.10.7 Verify PI-2010A indicators the correct signal 6.10.8 Connect a variable pressure/vacuum source to PT-3010 apply an input signal of

6.10.9 Verify PI-3010A indicates the correct signal 6.10.10 Connect a variable pressure source to PT-2011 apply a a signal and verify PI-2011 indicates the correct signal.

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SOl-II-1.74 UNIT 1 JUN 1 0 193i REVISION 0 Page 51 6.0 PROCEDURE (continued) 6.10 (continued) 6.10.11 Connect a variable pressure source to PT-3011 apply a and verify PI-3011 indicates the correct signal.

6.10.12 Connect a variable mA source to LYV-2400A and LYV-2400B apply an input signal of *mA verify "2 OF 3 STEAM GEN LOW LEVEL" 6.10.13 Repeat step 6.10.12 substituting LYV-2400B and 2400C and 2400A and 2400C 6.10.14 Connect a variable level simulator to LT-2400A, apply an input signal 11of *______

N 20 verify "STEAM GEN A LOW LEVEL" annunciator alarms.

6.10.15 Verify LI-2400A indicates the correct signal.

6.10.16 Connect a variable level simulator to LT-2400B apply an input signal of *_____

N 20 verify "STEAM GEN B LOW LEVEL" annunciator alarms 6.10.17 Verify LI-2400B indicates the correct signal 6.10.18 Connect a variable level simulator to LT-2400C apply an input signal of *_____

"H20 verify "STEAM GEN C LOW LEVEL" annunciator alarms 6.10.19 Verify LI-2400C indicates the correct signal 6.10.20 Connect a variable mA source to LYV-3400A and 3400A apply an input signal of *______

mA verify___

"2 OF 3 STEAM GEN.

LOW LEVEL" annunciator alarms.

6.10.21 Repeat step 6.10.20 substituting LYV-2400B and 2400C and 2400A and 2400C 6.10.22 Verify "SYSTEM ACTUATED" annunciator alarms 6.10.23 Connect a variable level simulator to LT-3400Applya apply an input signal of *___

NH20 verify "STEAM GEN A LOW LEVEL" annunciator alarms 6.10.24 Verify LI-3400A indicates the correct signal 6.10.25 Connect a variable level simualtor to LT-3400B, apply an input signal of

  • N 20 verify "STEmA GEN B LOW LEVEL" annunciator alarms 6.10.26 Verify LI-3400B indicates the correct signal.

ENCODE BEU2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE SO1-IIl742

  • IT 1 REVISION 0Pae5 6.0 PROCEDURE (continued) 6.10 (continued) 6.10.27 Connect a variable level simulator to LT-3400C, apply an input signal of *_____

"H20 verify "STEAM GEN C LOW LEVEL" annunciator alarms 6.10.28 Verify LI-3400C indicates the correct signal 6.10.29 Connect a variable pressure source to FTH-3453, apply an input signal and verify FI-3453 indicates the correct signal.

6.10.30 Connect a variable pressure source to FTL-3453, apply an input signal and verify FI-3453 indicates the correct signal.

6.10.31 Connect a variable pressure source to.FTH-3454, apply an input signal and verify FI-3454 indicates the correct signal.

6.10.32 Connect a variable pressure source to FTL-3454, apply an input signal and verify FI-3454 indicates the correct signal.

6.10.33 Connect a variable pressure source to FTH-3455, apply an input signal and verify FI-3455 indicates the correct signal.

6.10.34 Connect a variable pressure source to FTL-3455, apply an input signal and verify FI-3455 indicates the correct signal.

6.10.35 Depress HC-2300 manual push button and verify FCV-2300 operates from 0 to 100% of valve travel 6.10.36 Place HC-2300 AUTO/MAUAL station to auto.

Depress the iux. Feedwater System initiate push button HS-c400A. Verify an auto initiate signal.

6.10.37 Depress HC-2301 manual push button and verify FCV-230134ncet operates from 0 to 100% of value travel.

6.1C.3 Place HC-2301 auto/manual station to auto. Depress the Aux. Feedwate System initiate push button HS-2400B iverify an auto initiate signal.

6.10.39 Depress HC-3300 manual push button and verify FCV-3300 operates from 0 to 100% of valve travel.

ENCODE BEO2BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE Sol-11-1.74 UNIT 1 JUN 1 0 1981 REVISION 0 Page 53 6.0 PROCEDURE (continued) 6.10 (continued) 6.10.40 Place HC-3300 AUTO/MANUAL station to auto. Depress the Aux. Feedwater System initiate push button HS-3400A verify an auto initiate signal.

6.10.41 Depress HC-3301 manual push button and verify FCV-3301 operates from 0 to 100% of valve travel.

6.10.42 Place HC-3301 AUTO/MANUAL station to auto. Depress the Aux. Feedwater System initiate push button HS-3400B verify an auto intiate signal.

6.11 Return to Service 6.11.1 Request a second qualified person to verify proper operation of the Aux. Feedwater System and its associated equiment.

7.0 RECORDS 7.1 After completion this procedure shall be signed by the technician and the Instrument Foreman. The Supervisor of Nuclear Plant Instrumentation shall review and approve the recorded data.

7.2 Transfer of the data shall be made to the EDM Center after the completion of this test and filed under encode BEO2BC copies of this procedure shall be made for retention in the Instrument and Test Shop files.

7.3 Record the date test is complete DATE TECHNICIAN(S)

FOREMAN APPROVED BY DATE REMARKS

ENCODE BE02BC SAN ONOFRE NUCLEAR GENERATING STATION INSTRUMENT & TEST PROCEDURE S01-11-1.74 NIT 1 REVISION 0 Page 54 8.0 ATTACHMENTS 8.1 None R. R. BRUNET SUPERINTENDENT UNIT 1 APPROVED:

.. t CURPAN PLANT MANAGER BDW:0013B:jhm