ML20202H774

From kanterella
Revision as of 07:22, 13 January 2021 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Rev 16 to AR-304, ESD Annunciator Response
ML20202H774
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 12/04/1997
From:
FLORIDA POWER CORP.
To:
References
AR-304, NUDOCS 9712100359
Download: ML20202H774 (60)


Text

- - - - . - - - .. .. .. . . - - . .. . . - .-. .. .~ . - - . . -

Document Transmittal #: 78538 Date: 12/4/97 Tc: NRC (DC DESK) MAC: N/A Destination: .

Description:

Copy Copy Totals Document: Revision: Comment: # INFO CNTL MSTR 4

AR0304 16 24 1 0 0 I

b j instructions to the Addressee:

Please verify the document (s) received agrees with the above information.

Operations department must attach old document (s) or portions of document (s) superseded by the above to this transmittal.

The signature indicates acknowledgment of receipt of the above document (s) and that documents have

- been updated. Retum signed and dated transmittal to Document Control within 15 working days of transmittal date to mail code:

NA1C Florida Power Corporaten

~~ c--i c Crystal Ruer Energy Complex l!illH, .lgl:,ll,lyg.lll "i , ,

15760 W. Power Line St .-

-1hyO$] Crystal River, FL 344284708

. Signature of Addressee: Date:

~

9712100359 971204-P F,DR - ADOCK 05000302

-PDR

4 4

Rev. 16 O . Effective Date }2*N' NFORMATION u ONLY _a l

1 ANNUNCIATOR RESPONSE AR-304 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 ESD ANNUNCIATOR RESPONSE I

e i

APPROVED BY: Interpretation Contact

~ AisnEv 0 ft /Wff

(SICNATURE ON FILE)

DATE: I~Z-[5!97

! INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support t .. _ _ _ _

.J

- - . - _.=. .- - _ _ . . - - - .._- - - - .-_- - - _ . - _ - - - - . .-.

4 s

o '

. 1

, TABLE OF CONTENTS l SECTION PAGE

1. 0 PUfEQ5E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.0 REFERENCES

1 2.1 IIELEMENTING _ REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.2 DEYELQPflENTAL REFERENCES............................................ 1

. LD_ PERSONNEL.ItGQCTRINATION................................................ 1 L9.INSTBDCTIONS............................................................ 1 5.0 FOLLOW-UP ACTIONS....................................................... 1 ENCLOSURES 1 Annunciator Response............................................... 2 O

i AR-304 Rev. 16 Page i

_. .J

1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the ES (B)-JH1 Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the E3 (B)-JH1 Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the ES(B)-JH1 Lampbox.

L.0 REFERENCES 2.1 IMELEMENIIN(LREf18ENCES 2.1.1 E0P, Emergency Operating Procedure 2.1.2 OP-404, Decay Heat Removal System 2.1.3 OP-703, Plant Distribution System 2.1.4 AP-880, Fire Protection O 2.2 DEVELQEMENIAL_REEERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 310 PERSONNEL._INQQCTRINATIQN 3.1 The Annunciator System is powered from VBDP-5 Breaker 28.

LD JNSIBUCT10NS 4.1 Respond to alarms on the ES(B)-JH1 Lampbox as indicated on Enclosure 1, Annunciator Response.

5.0 EQLLQEUf_ACIIONS None-AR-304 Rev. 16 Page 1 J

~

' fACLOSURE 1 (Page 1 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-01-01 D-01-01 I I HPl l l ES B l l ACTUATION I I l l EVENT POINT 0923 INDICATED CONDITION:

o HPI ACTUATION "B" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS PRESSURE <1500 PSIG o RCS PRESSURE <500 PSIG o RB PRESSURE >4 PSIG o MANUAL ACTUATION OF HPI o ES STATUS LIGHTS FOR AFFECTED CHANNELS CHANGE STATE OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

THIS ALARM INDICATES HPI HAS ACTUATED, OR SHOULD HAVE ACTUATED BY EITHER 2 OUT.OF 3 HPI BI-STABLES TRIPPED OR BY THE CASCADE ACTUATION FROM LPI OR 4 PSIG REACTOR BUILDING PRESSURE. UPON RECEIPT OF THIS ALARM ES WOULD BLOCK LOAD.

REFERENCES:

DRAWING 208-028 SHEET ESB-31 SENSING ELEMENT: 63-ZIA/RC-1,RC-2,/RC-3. ES ACTUATION RELAYS u

l. AR-304 Rev. 16 Page 2

ENCLOSURE 1 (Page 2 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-01-02 0-01-02 i

LOAD SEQUENCE BLOCK 2 ACTUATION B i

EVENT POINT 1023 INDICATED CONDITION:

o LOADING SEQUENCE BLOCK 2 ACTUATION "B" r

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES CHANNEL STATUS INDICATION O o LOSS OF POWER TO AN ES ACTUATION CHANNEL CABINET o FAILURE OF AN ES CHANNEL SENSING ELEMENT o ES CHANNEL TESTING IN PROGRESS OPERATOR .CTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

HPI HAS ACTUATED EITHER BY 2 OUT OF 3 HPI BI-STABLES TRIPPED OR BY THE CASCADE ACTUATION FROM LPI OR 4# RB PRESSURE AND ES EQUIPMENT STARTS 08 ONLY ONE OF THE HPI ACTUATION RELAYS HAS ACTUATED, AN ES CABINET HAS LOST PO*'ER OR A SENSING ELEMENT HAS FAILED AND ES EQUIPMENT IS NOT STARTING l

REFERENCES:

DRAWING 208-028 SHEET ESB-25 ,

l SENSING ELEMENT: 62XI/RC-1, RC-2,-RC-3. ES ACTUATION RELAYS AR-304 Rev. 16 Page 3 1

ENCLOSURE 1 .

(Page 3 of SG) l ESD ANNUNCIATOR RESPONSE ESD-J H1-01-03 0-01-03 i t

LOAD SEQUENCE BLOCK 3 ACTUATION B t

EVENT POINT 1025 INDICATED CONDITION:

o LOADING SEQUENCE BLOCK 3 ACTUATION "B" REDUNDANT INDICATION WHICH WILL VERIFY AL ARM:

o ES CHANNEL STATUS INDICATION O o LOSS OF POWER TO AN ES ACTUATION CHANNFL CABINET o FAILURE OF AN ES CHANNEL SENSING ELEMENT o ES CHANNEL TESTING IN PROGRESS OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO EOP DISCUSSION:

l HPI HAS ACTUATED EITHER BY 2 OUT OF 3 HPI BI-STABLES TRIPPED OR BY THE

! CASCADE ACTUATION FROM LPI OR 4# RB PRESSURE AND ES EQUIPMENT STARTS 08 ONLY ONE OF THE HPI ACTUATION RELAYS HAS ACTUATED, AN ES CABINET HAS LOST POWER OR A SENSING ELEMENT HAS FAILED AND ES EQUIPMENT IS NOT STARTING

REFERENCES:

DRAWING 208-028 SHEET ESB-25 SENSING ELEMENT: 62X2B/RC-1. RC-2, RC-3 ES ACTUATION RELAY

-(O.wl -

AR-304 Rev. 16 Page 4 m, , ..,-- -r .,..4r - . . , , ~ , - - - -

. - - - - - - - ~ _ - - - . _ - . . - . - - . . - - . - - . . _ - . - - . - . - _ _ - - - . - - . .

ENCLOSURE 1 (Page 4 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-01-04 D-01-04 LOAD SEQUENCE BLOCK 4 ACTUATION B EVENT POINT 1026 INDICATED CONDITION:

o LOADING SEQUENCE BLOCK 4 ACTUATION "B" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o ES CHANNEL STATUS INDICATION o LOSS OF POWER TO AN ES ACTUATION CHANNEL CABINET o FAILURE OF AN ES CHANNEL SENSING ELEMENT o ES CHANNEL TESTING IN PROGRESS OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

HPI HAS ACTUATED EITHER BY 2 OUT OF 3 HPI BI-STABLES TRIPPED OR BY THE CASCADE ACTUATION FROM LPI OR 4# RB PRESSUPE AND ES EQUIPMENT STARTS 08 ONLY ONE OF THE HPI ACTUATION RELAYS HAS ACTUATED, AN ES CABINET HAS LOST POWER OR A SENSING ELEMENT HAS FAILED AND ES EQUIPMENT IS NOT STARTING TO RESET A BLOCK 4 ACTUATION THE HPI SEAL-IN RESET PUSH-BUTTON MUST BE DEPRESSED.

! REFERENCES. DRAWING 208-028 SHEET ESB-25 SENSING ELEMENT: 62X3/RC-1, RC-2, RC-3 ES ACTUATION RELAYS 1O AR-304 Rev. 16 Page 5

_ _ ~ - . . . _ - - . _ _ . -

., l ENCLOSURE 1 (Page 5 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-01-05 D-01-05 LOAD SEQUENCE BLOCK 5 3

ACTUATION 8 i EVENT POINT 0853 INDICATED CONDITION:

, o LOADING SEQUENCE BLOCK 5 ACTUATION "B" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES CHANNEL STATUS INDICATION ~

o LOSS OF POWER TO AN ES ACTUATION CHANNEL CABINET o FAILURE OF AN ES CHANNEL SENSING ELEMENT O o ES CHANNEL TESTING IN PROGRESS OPERATOR AGIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

HPI HAS ACTUATED EITHER BY 2 OUT OF 3 HPI BI-STABLES TRIPPED OR BY THE CASCADE ACTUATION FROM LPI OR 4# RB PRESSURE AND ES EQUIPMENT STARTS 08 ONLY ONE OF THE HPI ACTUATION RELAYS HAS ACTUATED, AN ES CABINET HAS LOST

, POWER OR A SENSING ELEMENT HAS FAILED AND ES EQUIPMENT IS NOT STARTING

REFERENCES:

DRAWING 208-028 SHEET ESB-25 SENSING ELEMENT: 62X4/RC1, 62X4/RC2, 62X4/RC3 O

AR-304 Rev. 16 Page 6

ENCLOSURE 1 (Page 6 of 56)

ESO ANNUNCIATOR RESPONSE ESD-JH1-01-06 D-01-06 i

I I l l I LOAD SEQUENCE I I BLOCK 6 l ACTUATION B W-l 1

EVENT POINT 1019  !

INDICATED CONDITION:

o LOADING SEQUENCE BLOCK 6 ACTUATION "B" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES CHANNEL STATUS INDICATION O o LOSS OF POWER TO AN ES ACTUATION CHANNEL CABINET o FAILURE OF AN ES CHANNEL SENSING ELEMENT o ES CHANNEL TESTING IN PROGRESS OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO EOP i DISCUSSION:

HPI HAS ACTUATED EITHER BY 2 OUT OF 3 HPI BI-STABLES TRIPPED OR BY THE CASCADE ACTUATION FROM LPI OR 4# RB PRESSURE AND ES EQUIPMENT STARTS OB ONLY ONE OF THE HPI ACTUATION RELAYS HAS ACTUATED, AN ES CABINET HAS LOST POWER OR A SENSING ELEMENT HAS FAILED AND ES EQUIPN.i4T IS NOT STARTING TO RESET A BLOCK 6 ACTUATION THE HPI SEAL-IN RESET PUSH-BUTTON MUST BE DEPRESSED.

REFERENCES:

DRAWING 208-028 SHEET ESB-25 SENSING ELEMENT: 62X5 ES ACTUATION RELAY f)

'% )

AR-304 Rev. 16 Page 7 1 11 . - _ _ _._ _ - _ . . . _ . _ - - _ - . _ . _ , , . _ _ . __ _

- . _ . . - _ . _ - - - - . - - . - - .-. ... - . - - - -_.- . . - =. - .- .

P

', t ENCLOSURE 1 (Page 7 of $6)

ESD ANNUNCIATOR RESPONSE ESD-J H.l-0?-01 D-02-01 DIVERSE I l CONTAINMENT l l 180LATION 8 I I I I ,

EVENT POINT 1114 INDICATED CONDITION:

o PARTIAL CONTAINMENT ISOLATION "B" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

! o AUTOMATIC ACTUATION HPI "B" l 5 i

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

Txl , ALARM INDICATES A PARTIAL CONTAINMENT ISOLATION HAS OCCURRED.

THE FOLLOWING VALVES SHOULD CLOSE:

i

. LRV-71 LRV-73 CAV-2 CAV-6 CAV-7 CAV-431 CFV-25 CFV-26 CFV-27 CFV-28 CFV-29 CFV-42 MUV-49 MSV-130 MSV-148 WDV-4 WDV-61 WDV-62 WDV-405 DWV-160 MUV-27

REFERENCES:

DRAWING 208-028 SHEET ESB-55 i

SENSING ELEMENT: 63Z-48 ES ACTUATION RELAY t_

AR-304 Rev. 16 Page 8

. - . - . _ _ - . ._- _--- . - . - - . . . - . . . . - . ~ . .

f

. 1 ENCLOSURE 1 (Page 8 of 56)

{

ESO ANNUNCIATOR RESPONSE ESD-JH1-02-02 l D-02-02 i

HPl B FLOW HIGH/ LOW 8

EVENT POINT 1069 INDICATED CONDITION:

o LOOP B1 HPI FLOW IS >263 GPM AS SENSED BY MU-23-FS1

  • REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HPI WIDE RANCE FLOW METER, MU-23-FIl O .

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-13 FOR HPI THROTTLING REQUIREMENTS o THROTTLE MUV-25 AS REQUIRED

, DISCUSSION:

RUNOUT CONDITIONS FOR A MAKEUP PUMP MAY BE VERIFIED BY OBSERVING MAKE UP PUMP CURRENT INDICATION FOR FLUCTUATIONS. ALSO FLOW OSCILLATIONS MAY OCCUR DURING HIGH FLOW CONDITIONS. IF ANY OF THESE SYMPTOMS ARE EVIDENT ON OPERATING MAKE UP PUMPS CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE MAKE UP PUMP.

REFERENCES:

DRAWING 208-041 SHEET MU-047 SENSING ELEMENT: MU-23-FS1 AR-304 Rev. 16 Page 9 ,

ENCLOSURE 1 O ESD ANNUNCIATOR RESPONSE ESD .1HI-02-02 (Page 9 of 56) 0-02-02 HPl B FLOW ,

HIGH/ LOW EVENT POINT 1070 INDICATED CONDITION:

o LOOP B2 HPI FLOW IS >263 GPM AS SENSED BY MU .s-FS3 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HPI WIDE RANCE FLOW METER, MU-23-FI3 O

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-13 FOR HPI THRO 1TLING REQUIREMENTS o THROTTLE MUV-26 AS REQUIRED DISCUSSION:

RUNOUT CONDITIONS FOR A MAKEUP PUMP MAY-BE VERIFIED BY OBSERVING MAKE UP PUMP CURRENT INDICATION FOR FLUCTUATIONS. ALSO FLOW OSCILLATIONS MAY OCCUR DURING HIGH FLOW CONDITIONS. IF ANY OF THESE SYMPTOMS ARE EVIDENT ON OPERATING MAKE UP PUMPS CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE MAKE UP PUMP.

REFERENCES:

DRAWING 208-041 SHEET MU-047 SENSING ELEMENT: MU-23-FS3 O ,

AR-304 Rev. 16 Page 10

ENCLOSURE 1 (Page 10 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-02-02 D-02-02 i

~

H P! 5 FLOW HIGH/ LOW EVENT POINT 1073 INDICATED CONDITION:

o LOOF B1 HPI FLOW IS <75 GPM AS SENSED BY MU-23-FS1 COINCIDENT WITH A HPI ACTUATION SIGNAL .

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HPI LOW RANGE FLOW METER, MU-23-FI5-1 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-13 FOR HPI THROTTLING REQUIREMENTS o VERIFY PROPER MAKE UP PUMP OPERATION o ENSURE EITHER, >200 GPM TOTAL HPI FLOW PER RUNNING MAKEUP PUMP OR BOTH MAKE UP PUMP RECIRC VALVES, MUV-53 AND MUV-257 ARE OPEN OR HPI RECIRC VALVES TO RB SUMP (MUV-543, 544, 545, & 546) ARE OPEN PER AP-404, E0P-4, '

OR E0P-13 DISCUSSION:

LOW FLOW CONDITIONS FOR AN OPERATING MAKE UP PUMP CAN RESULT IN MAKE UP PUMP DAMAGE. DURING PERIODS OF LOW FLOW THE MAKE UP PUMP RECIRC VALVES MUST BE OPEN.

REFERENCES:

DRAWING 208-041 SHEET MU-047 SENSING ELEMENT: MU-23-FS1 AR-304 Rev. 16 Page 11

ENCLOSURE 1 (Page 11 of 56)

ESD ANNUNCIATOR RESPONSE lESD-JH1-02-02 0-02-02 HPl B i FLOW '

HIGH/ LOW EVENT POINT 1074 INDICATED CONDITION:

o LOOP 82 HPI FLOW IS <75 GPM AS SENSED BY MU-23-FS3 COINCIDENT WITH A HPI ACTUATION SIGNAL REDUNDANT INDICA

  • ION WHICH WILL VERIFY ALARM:

o HPI LOW RANCE FLOW METER, MU-23-FI7-1 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-13 FOR HPI THROTTLING REQUIREMENTS o VERIFY PROPER MAKE UP PUMP OPERATION o ENSURE EITHER, >200 CPM TOTAL HPI FLOW PER RUNNING MAKEUP PUMP OR BOTH MAKE UP PUMP RECIRC VALVES, NUV-53 AND MVV-257 ARE OPEN OR HPI RECIRC VALVES TO RB SUMP (MUV-543, 544, 545, & 546) ARE OPEN PER AP-404, EOP-4, OR E0P-13 DISCUSSION:

LOW FLOW CONDITIONS FOR AN OPERATING MAKE UP PUMP CAN RESULT IN MAKE UP PUMP DAMAGE. DURING PERIODS OF LOW FLOW THE MAKE UP PUMP RECIRC VALVES MUST BE OPEN.

REFERENCES:

DRAWING 208-041 SHEET MU-047 SENSING ELEMENT: MU-23-FS3 O

AR-304 Rev. 16 Page 12

ENCLOSURE 1 (Page 12 of 56)

(])

N__

D-02-03 ESD ANNUNCIATOR RESPONSE ESD-JH1-02-03 LPI (DHV-6)

OPEN EVENT POINT 0218 INDICATED CONDITION:

o DHV-6 NOT FULL CLOSED AND RCS PRESSURE >200 PSIG AS SENSED BY RC-3A-PS4 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

g o DHV-6 INDICATION t o RCS PRESSURE INDICATION

(

OPERATOR ACTIONS FOR A VALID ALARM:  : ,

o REFER TO E0P-08 IF ON LPI.

o 'F ON DECAY HEAT REMOVAL THEN ENSURE PROPER DH FLOW PATH.

o REFER TO OP-404 FOR MINIMUM FLOW LIMITATIONS. .

DISCUSSION:

1HIS ALARM MAY INDICATE THE ACI SETPOINT IS BEING APPROACHED (ABOUT 250#)

IF THIS IS OCCURRING THEN THE OPERATOR SHOULD REDUCE RCS PRESSURE.

CARE Sr.0ULD BE TAKEN AS TO NOT OVERPRESSURIZE THE DECAY HEAT SYSTEM.

WHILE ON LPI THIS ALARM WOULD INDICATE A LOW FLOW CONDITION ON THE OPERATING DECAY HEAT PUMP.

FERENCES: DRAWING 208-021 SHEET DH-06 SENSING ELEMENT: RC-3A-PS4 ANL 33 AC (CLOSED LIMIT SWITCH FOR DHV-6)

G AR-304 Rev. 16 Page 13

l .

ENCLOSURE 1 (Page 13 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-02-04 D-02-04 LPIB FLOW HIGHILOW EVENT POINT 0228 INDICATED CONDITION: }

o DHP-1A FLOW >3750 GPM AS SENSED BY DH-1-FS2 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DECAY HEAT FLOW INDICATOR, DH-1-FI-2 INDICATES HIGH FLOW OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-404 FOR MAXIMUM DECAY HEAT FLOW LIMITATIONS o VERIFY PROPER OPERATION OF DHV-111. "B" DECAY HEAT CONTROL VALVE.

o REDUCE FLOW BY EITHER THROTTLING DHV-111 OR DHV-6, CLOSED.

DISCUSSI(N:

THIS ALARM MAY INDICATE THE DECAY HEAT PUMP IS EXCEEDING ITS MAXIMUM FLOW.

IF THIS OCCURS PUMP DAMAGE MAY RESULT FROM CAVITATION INDUCED BY PUMP RUNOUT. IF INDICATIONS OF CAVITATION EXIST THEN CONSIDERATION SHOULD BE GIVEN TO SECURING THE DECAY HEAT PUMP.

REFERENCES:

DRAWING 208-021 SHEET DH-24 SENSING ELEMENT: DH-1-FS2 AR-304 Rev. 16 Page 14

l ENCLOS'JRE 1 O (Page 14 of 56)

(v)

ESD ANNUNCIATOR RESP 0,4SE ESD-JH1-02-04 D-02-04 L Pl B

~' ~'

FLOW HIGH/ LOW t ._ _

EVENT POINT 0230 INDICATED CONDITION:

o DHP-1B FLOW <2800 GPM AS SENSED BY DH-1-FS2 FOR >5 SEC COINCIDENT WITH LPI ACTUATION "B" REDUNDANT -991 CATION WHICH WIIL VERIFY ALARM:

o DECAY HEAT FLOW INDICATOR, DH-1-FI2 INDICATES LOW FLOW V

OPERATOR ACTIO!45 FOR A VALID ALARM:

o RcFER TO EOP o \tlIFY PROPER OPERATION OF DHP-1B o L.tIFY PROPER OPERATION OF DHV-111, "B" DECAY HEAT CONTROL VALVE.

o INCREASE FLOW BY EITHER THROTTLING DHV-111 OR DHV-6, OPEN.

DISCUSSION:

REFERENCES:

DRAWING 208-021 SHEET DH-24 SENSING ELEMENT: DH-1-FS2 im AR-304 Rev. 16 Page 15

l l

EELQSEL1 (Page 15 of 56)

(}

ESD ANNUNCIATOR RESPONSE ESD-JH1-02-05 D-02-05 I

ES B ACTUATION NOT BYPASSED EVENT POINT 0930 INDICATED CONDITION:

o RCS PRESSURE <1640 PSIG AND HPI NOT BYPASSED o RCS PRESSURE <750 PSIG AND LPI NOT BYPASSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS PRESSURE INDICATION

! o ES STATUS LIGHTS INDICATE ES NOT BYPASSED OPERATOR ACTIONS FOR A VALID ALARM:

o IF DIRECTED BY AN APPROVED PROCEDURE AND WITH THE CONCURRENCE OF THE NSS/ANSS, THEN BYPASS HPI AND/OR LPI AS REQUIRED.

DISCUSSION:

THIS ALARM INDICATES THE ES SYSTEMS ARE STILL ABLE TO ACTUATE AND RCS PRESSURE IS DECREASING. IF THIS CONDITION OCCURS DURING A NORMAL PLANT C00LDOWN THEN ES MUST BE BYPASSED IN ORDER TO PREVENT INADVERTENT ACTUATION. IF, HOWEVER A PLANT TRANSIENT IS IN PROGRESS THIS ALARM INFORMS THE OPERATOR THAT ES ACTUATION IS IMMINENT.

REFERENCES:

DRAWING 208-028 SHEET ESAB-06 SENSING ELEMENT: 62-B ES ACTUATION RELAY AR-304 Rev. 16 Page 16

4 l .

ENCLOSURE 1

(,,} (Page 16 of 56)

'%J ESD ANNUNCIATOR RESPONSE ESD-JH1-02-06 D-02-06 ES B ACTUATION NOT RESET EVENT POINT 0928 INDICATED CONDITION:

o RCS PRESSURE >1640 PSIG AND HPI NOT RESET o RCS PRESSURE >750 PSIG AND LPI NOT RESET REDUNDANT INDICATION WHICil WILL VERIFY ALARM:

o RCS PRESSURE INDICATION ln 5 o ES STATUS LIGHTS INDICATE ES NOT RESET

%.)

OPERATOR ACTIONS FOR A VALID ALARM:

o IF DIRECTED BY AN APPROVED PROCEDURE AND WITH THE CONCURRENCE OF THE NSS/ANSS, THEN RESET HPI AND/0R LPI AS REQUIRED.

DISCUSSION:

THIS ALARM INDICATES THE ES SYSTEMS ARE STILL BYPASSED AND RCS PRESSURE IS INCREASING. IF HPI/LPI RC PRESSURE BI-STABLES ARE NOT RESET PRIOR TO EXCEEDING 1750 PSIG (HPI) OR 900 PSIG (LPI), HPI AND LPI WILL ACTUATE WHEN THE ACTUATION CIRCUIT BYPASS BI-STABLE AUTOMATICALLY RESETS AND REMOVES THE CHANNEL FROM BYPASS.

FERENCES: DRAWING 208-028 SHEET ESAB-06 SENSING ELEMENT: RC-3A-PSS, RC-3A-PS6 p

/

l AR-304 Rev. 16 Page 17 l 1 - -- - --- - - - - - - - - - - - - - - - - - - - - - - _ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - --------- -__

l .

ENCLOSURE 1 (Page 17 of $6)

ESD ANNUNCIATOR RESPONSE ESD-JH1-03-01 0-03-01 p

l l ES B l l ACTUATION I I I I EVENT POINT 0924 INDICATED CONDITION:

o RCS PRESSURE IS <500 PSIG o REACTOR BUILDING PRESSURE >4 PSIG o MANUAL ACTUATION OF LPI "B" -

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS PRESSURE INDICATION o RB PRESSURE INDICATION o ES STATUS LIGHTS FOR AFFECTED CHA NELS CHANGE STATE OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

THIS ALARM INDICATES LPI HAS A.CTUATED OR SHOULD HAVE ACTUATED BY EITHER 2 OUT OF 3 LPI BI-STABLES TRIPPED OR BY THE CASCADE ACTUATION FROM 4 PSIG REACTOR BUILDING PRESSURE OR THAT A MANUAL LPI ACTUATION HAS OCCURRED.

REFERENCES:

DRAWING 208-028 SHEET ESB-42 SENSING ELEMENT: 63Z3 ES ACTUATION RELAY i

l AR-304 Rev. 16 Page 18

l i

ENCLOSURE 1 O

V (Page 18 of 56)

ESD ANNUNCIATOR RESPONSE ESD-3H1-03-02 D-03-02 DH PUMP B TRIP EVENT POINT 0220 INDICATED CONDITION:

o DHP-1B BREAKER IS OPEN WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN INDICATOR LIGHT IS ON WITH A RED FLAG ON DHP-1B CONTROL STATION t, o AMBER ES STATUS LIGHT FOR DHP-1B OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P-11, LOSS OF DECAY HEAT REMOVAL o PLACE "A" DECAY HEAT TRAIN IN SERVICE PER OP-404 o INVESTIGATE CAUSE OF PUMP TRIP DISCUSSION:

IF CAUSE OF PUMP TRIP IS NOT APPARENT CARE SHOULD BE EXERCISED IN STARTING DHP-1A PUMP. SUCTION AND DISCHARGE FLOW PATHS SHOULD BE VERIFIED PRIOR TO ALTERNATE DECAY HEAT TR/IN STARTUP.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-021 SHEET ESB-42 SENSING ELEMENT: DHP-1B CONTROL SWITCH CONTACTS CS/SC AND CS/0 i

AR-304 Rev. 16 Page 19

ENCLOSURE 1

/^)

LJ (Page 19 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-03-03 D-03-03 DH PUMP B MOTOR OVERLOAD EVENT POINT 0224 INDICATED CONDITION:

o DHP-1B MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

p o DHP-18 HIGH MOTOR AMPS g o DHP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o REDUCE DHP "; LOAD BY THROTTLING DHV-111 OR DHV-6 o IF LOAD REMAINS HIGH ON DHP-1B CONSIDER ALTERNATING DECAY HEAT TRAINS PER OP-404 o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DIFCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED.

INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE 6REAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-021 SHEET DH-02 SENSING ELEMENT: DHP-1B OVERCURRENT DEVICES (51 IOC OR 51 TOC)

)

%/

AR-304 Rev. 16 Page 20

l

  • ENCLOSURE 1 (Page 20 of 56)

! ESD ANNUNCIATOR RESPONSE ESD-]H1-03-04 D-03-04 DH PUMP B OUT OF SERVICE EVENT POINT 0222 INDICATED CONDITION:

o DHP-1B BREAKER IS RACKED OUT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON CONTROL STATION O o NO ES STATUS INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT DISCUSSION:

ADDRESS TS REQUIREMENTS CONCERNING THIS CONDITION

REFERENCES:

ORAWINC 208-021 SHEET DH-02 SENSING ELEMENT: DHP-1B BREAKER RELAY (52 H)

O AR-304 Rev. 16 Page 21

s.

l ENCLOSURE 1 (Page 21 of 56)

ESD ANNUNCIATOR RESPONSE ESD-]H1-03-04 D-03-04 DH PUMP B OUT OF SERVICE EVENT POINT 0243 INDICATED CONDITION:

o DHP-1B BREAKER HAS NO DC CONTROL POWER.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON DHP-1B CONTROL STATION O o ES STATUS LIGHTS INDICATE BREAKER POSITION OFERATOR ACTIONS FOR A VALID ALARM:

o VERIFY CLOSED DPDP-SB SWITCH 10 o VERIFY DC KNIFE SWITCH FOR DHP-1B IS CLOSED DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-021 SHEET DH-02 SENSING ELEMENT: DHP-1B BREAKER RELAY (27C)

U AR-304 Rev. 16 Page 22

- ~ . _ _ _ _ _ _ _ _ _ . _ . . - -

s ENCLOSURE 1 (Page 22 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-03-05 D-03-05' DH PUMP B SUCT TEMP HIGH EVENT POINT 0232 INDICATED CONDITION:

o DHP-1B SUCTION TEMP IS >280*F AS SENSED BY DH-6-TS2 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DHP-1B SUCTION TEMP. INDICATOR, DH-6-TI2 INDICATES HIGH O\

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER "B" DC SYSTEM OPERATION BY CHECKING DC SURGE TANK LEVEL, DC PUMP RUNNING AND DC CONTROL VALVES SETPOINT NORMAL.

o-VERIFY PROPER DC RAW WATER OPERATION BY CHECKING RWP-3B RUNNING, RWP-3B DISCHARGE PRESSURE GOOD AND DC RAW WATER TEMP NORMAL o INCREASE DC COOLING TO THE DC HEAT EXCHANGER BY INCREASING SETPOINT o Ir RCS TEMPERATURE CONTINUES TO RISE CONSIDER ALTERNATING DECAY HEAT TRAINS PER OP-404.

DISCUSSION:

THIS ALARM INDICATES A LOSS OF COOLING TO THE RCS IS OCCURRING. CORE COOLING MUST BE REGAINED AS 500N AS POSSIBLE.

REFERENCES:

DRAWING 208-021 SHEET DH-24 SENSING ELEMENT: DH-6-TS2 h

v

~

AR-304 Rev. 16 Page 23

-s ENCLOSURE 1-(Page 23 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-03-06 D-03-06 l

l DH PUMP B l FLOW j LOW Z

EVENT POINT 0226 INDICATED CONDITION:

o DHP-1B FLOW RATE <1500 GPM AS SENSED BY DH-1-FS4 WITH THE DHP-1B CONTROL HANDLE IN NORMAL AFTER START.

08 DHP-18 RUNNING AND MOTOR AMPERAGE IS BELOW THE OPERATOR ADJUSTED SETPOINT.

~

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DECAY HEAT FLOW INDIC ATOR, DH-1-FI2 INDICATES LOW FLOW D o DHP-1B CONTROL STATION AMP METER OPERATOR ACTIONS FOR A VALID ALARM:

o INCREASE DHP-1B FLOW BY THROTTLING OPEN DHV-111 OR DHV-6 o REFER TO OP-404 CONCERNING DECAY HEAT PUMP LOW FLOW OPERATION.

o READJUST DHP-1B AMP MONITOR, DH-57-IR, LOCATED INSIDE MCB ON HVC SECTION, IF NECESSARY PER OP-404 o IF DH FLOW CANNOT BE RECOVERED THEN CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DECAY HEAT TRAINS PER OP-404.

DISCUSSION-OPERATION AT LOW FLOW RATES MAY REDUCE DH PUMP LIFE, AND SHOULD BE AVOIDED.

DHP-1B AMP MONITOR CAN BE ADJUSTED TO ALARM AT SLIGHTLY LESS THAN DHP STEADY STATE OPERATION,

REFERENCES:

DRAWING 208-021 SHEET DH-02 SENSING ELEMENT: DH-1-FS4, DHP-1B CONTROL HANDLE CONTACTS AND DH-57-IR AR-304 Rev. 16 Page 24

N ENCLOSURE 1 (Page 24 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-04-02 D-04-02 d

DC PUMP B TRIP EVENT POINT 0203 INDICATED CONDITION:

o DCP-1B BREAKER OPEN AND CONTROL HANDLE IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN INDICATOR LIGHT WITH A RED FLAG ON DCP-1B CONTROL STATION OPERATOR ACTIONS FOR A VA3.ID ALARM:

o IF DH SYSTEM IS OPERATING, CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DECAY HEAT TRAINS l'ER OP-404 o INVESTIGATE DCP-1B PUMP, MOTOR, AND BREAKER DISCUSSION:

DCP-1B TRIP REMOVES COOLING FOR THE DH PUMP, BS PUMP, DC RW PUMP AND THE DC COOLED MAKE UP PUMP. ANY OF THESE PUMPS RUNNING WHEN THE DC PUMP TRIPS SHOULD BE SECURED AS 500N AS POSSIBLE. WITH THE EXCEPTION OF THE MAKE Ui PUMP WHICH SHOULD BE SWAPPED OVER TG SW COOLING, PER OP-408.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-019 SHEET DC-02 SENSING ELEMENT: CS/SC, CS/0, R/B (CONTROL STATION CONTACTS)

O I

l AR-304 Rev. 16 Page 25

l o.

ENCLOSURE _1 O (Page 25 of 56)

U ESD ANNL'NCIATOR RESPONSE ESD-]H1-04-03 0-04-03 DC PUMP B MOTOR OVERLOAD EVENT POINT 0201 INDICATED CONDITION:

o DCP-1B MOTOR AMPS >.115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DCP-1B HIGH MOTOR AMPS OPERATOR ACTIONS FOR A VALID ALARM:

o INSPECT PUMP AND MOTOR FOR PROPER OPERATION o IF INSPECTION REVEALS MOTOR OR PUMP MALFUNCTION CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DH TRAINS PER OP-404 DISCUSSION:

THE LOSS OF A DC PUMP REMOVES COOLING FOR THE DH PUMP, 85 PUMP, DC RW PUMP AND THE DC COOLED MAKE UP PUMP. ANY OF THESE PUMPS RUNNING WHEN THE DC PUMP TRIPS SHOULD BE SECURED AS 500N AS POSSIBLE. WITH THE EXCEPTION OF THE MAKE UP PUMP WHICH SHOULD BE SWAPPED OVER TO SW COOLING. IF DC PUMP HAS TO BE TRIPPED AFTER AN ES ACTUATION, HPI SEAL-IN RESET MUS' BE DEPRESSED BEFORE THE PUMP CAN BE SECURED.

REFERENCES:

DRAWING 208-019 SHEET DC-02 SENSING ELEMENT: 49X RELAY IN BREAKER CUBICLE O

V AR-304 Rev. 16 Page 26

ENCLOSURE 1 (Page 26 of 56)

ESDANNUNCIAT0kkESPONSE ESD-]H1-04-04 D-04-04 DC PUMP B OUT OF SERVICE EVENT POINT 0211 INDICATED CONDITION:

o DCP-1B BREAKER IS RACKED OUT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON DCP-1B CONTROL STATION

( o NO ES STATUS INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR DCF-1B BREAKER BEING RACKED OUT DISCUSSION:

ADDRESS TS REQUIREMENTS CONCERNING THIS CONDITION.

THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.

REFERENCES:

DRAWING 208-019 SHEET DC-02 SENSING ELEMENT: B/P CONTACTS IN THE DC PUMP BREAKER CUBICLE 1

AR-304 Rev. 16 Page 27

ENCLOSURE 1 (Page 27 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-04-04 0-04-04 l

~

DC PUMP B OUT OF SERVICE I i EVENT POINT 0213 I

INDICATED CONDITION:

o DCP-1B BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON DCP-1B CONTROL STATION g o ES STATUS LIGHTS INDICATE BREAKER POSITION OPERATOR ACiIONS FOR A VALID ALARM:

o VERIFY CLOSED DPDP-5B SWITCH 9 o VERIFY DC CONTROL POWER TOGGLE SWITCH ON DCP-1B BREAKER IS "0N" DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-019 SHEET DC-02 SENSING ELEMENT: 27C RELAY IN BREAKER CUBICLE O

AR-304 Rev. 16 Page 28

+.

l l*

) .  !

ENCLOSURE 1

-(-} (Page 28 of 56)

V ESD ANNUNCIATOR RESPONSE ESD-]H1-04-05 D-04-05 DC PUMP B DISCH PRESS LOW L

1 EVENT POINT 0202 INDICATED CONDITION:

o DCP-1B DISCHARGE PRESS 6RE IS <30 PSIG FOR > 5 SEC. AS SENSED BY DC-56-PS, WITH DCP-1B BREAKER CLOSED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DCP-1B DISCHARGE PRESSURE INDICATOR, DC-6-PI tO o DCP-1B CURRENT INDICATION V

OPERATOR ACTIONS FOR A val.ID ALARM:

o VERIFY DC SURGE TANK IS >8.5 FEET, IF NOT, NOTIFY AUX BLDG OPERATOR TO MANUALLY FILL DCT-1B o IF DISCHARGE PRESSURE CANNOT BE RECOVERED THEN CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DECAY HEAT TRAINS PER OP-404 DISCUSSION:

THE LOSS OF A DC PUMP REMOVES COOLING FOR THE DH PUMP, BS PUMP, DC RAW PUMP AND THE DC COOLED MAKE UP PUMP. ANY OF THESE PUMPS RUNNING WHEN THE DC PUMP IS LOST SHOULD BE SECURED AS 500N AS POSSIBLE, WITH THE EXCEPTION OF THE MAKE UP PUMP, WHICH SHOULD BE SWAPPED OVER TO SW COOLING. IF DC PUMP HAS TO BE TRIPPED AFTER AN ES ACTUATION, HPI SEAL-IN RESET MUST BE DEPRESSED BEFORE THE PUMP CAN BE SECURED.

REFERENCES:

DRAWING 208-019 SHEET DC-02 SENSING ELEMENT: DC-56-PS (D

v I

l AR-304 Rev. 16 Page 29

ENCLOSURE 1 (Page 29 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-04-06 D-04-06 I

DC TANK B LEVEL HIGH/ LOW EVENT POINT 0207 INDIC/TED CONDITION:

o "B" DC SURGE TANK LEVEL IS >11'" AS SENSED BY DC-52-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DC SURGE TANK LEVEL INDICATION, DC-54-LI -

o LOCAL SURGE TANK LEVEL INDICATION o DECREASING RCS LEVEL WHILE ON DECAY HEAT OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY AUTOMATIC DC SURGE TANK FILL VALVE, DCV-12 IS CLOSED IF NOT THEN MANUALLY ISOLATE DCV-12 BY CLOSING DCV-60 o VERIFY "B"DC SYSTEM RADIATION MONITOR, RML-6 READING IS NORMAL o IF ON DECAY HEAT REFER TO E0P-11 o CONSIDERATION SHOULD BE GIVEN TO ALTERNATE DH TRAINS PER OP-404 DISCUSSION:

IF THE HIGH SURGE TANK LEVEL IS DUE TO A DH TO DC LEAK THEN THE DC SURGE TANK MAY CONTINUE TO FILL. THE DC SURGE TANK VENTS TO THE AUX BLDG VENT HEADER SO CONSIDERATION SHOULD BE GIVEN TO DRAINING DC TO THE AUX BLDG SUMP TO PRFVENT OVERFLOWING THE TANK TO THE VENT DUCT AND ALIGNING THE DC SURGE TANK VENT TO THE WASTE GAS SYSTEM.

DC SURGE TANK FILL VALVE, DCV-12 SHOULD OPEN AT 8'6" AND CLOSE AT 11'"

REFERENCES:

DRAWING 208-019 SHEET DC-02 l SENSING ELEMENT: DC-52-LS NJ AR-304 Rev. 16 }%ge 30

EtiCL01URL1 (Page 30 of 56) f)\

\ _,

ESD ANNUNCIATOR RESPONSE ESD-JH1-04-06 D-04-06 DC TANK B LEVEL HIGH/ LOW EVENT POINT 0208 INDICATED CONDITION:

o "B" DC SURGE TANK LEVEL IS <8'6" AS SENSED BY DC-52-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DC SURGE TANK LEVEL INDICATION, DC-54-LI 4

o LOCAL SURGE TANK LEVEL INDICATION o OSCILLATING CURRENT INDICATIONS ON DCP-1G OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY AUTOMATIC DC SURGE TANK FILL VALVE, DCV-12 IS OPEN o HAVE AUX BLDG OPERATOR FILL DC SURCE TANK LOCALLY o CONSIDERATION SHOULD BE GIVEN TO ALTERNATE DH TRAINS PER OP-404 DISCUSSION:

FILL SOURCE FOR DC SURGE TANK IS UNIT 1/2 DEMIN WATER DC SURGE TANK FILL VALVE, DCV-12 SHOULD OPEN AT 8'6" AND CLOSE AT 11'"

REFERENCES:

DRAWING 208-019 SHEET DC-02

. SENSING ELEMENT: DC-52-LS N.J

{

AR-304 Rev. 16 Page 31

a.

ENCLOSURE 1 (Page 31 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-05-01 D-05-01 RC LOOP B l l VENT VLVS I l OPEN l l 1 i EVENT POINT 1877 INDICATED CONDITION:

o BOTH 8" LOOP VENT VALVES, RCV-163 AND RCV-164 ARE ENERGIZED.

t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOOP VENT VALVE POSITION INDICATION IS OPEN ON MCB 3 o LOOP VENT VALVE FLOW WHITE INDICATING LIGHT IS ON o RCS PRESSURE DECREASING OPERATOR ACTIONS FOR A VALID ALARM:

o CLOSE THE OPEN VENT VALVE IF NECESSARY DISCUSSION:

THE LOOP VENT VALVES ARE MOUNTED IN SERIES SO OPENING ONE VALVE SHOULD NOT CAUSE AN RCS LEAK,

REFERENCES:

DRAWING 208-047 SHEET RC-33 SENSING ELEMENT: POSITION SWITCH ON VALVES (33)

O l,

AR-304 Rev. 16 Page 32

. . . . . - ~ .

ENCLOSURE 1

, D -- (Page 32 of 56) b-ESD ANNUNCIATOR RESPONSE ESD-JH1-05-03 D-05-03

'l AH FAN 158 TROUBLE EVENT POINT 0398

-lINDICATEDCONDITION:

o AHF-158 BREAKER OPEN AND CONTROL HANDLE IN THE NORMAL AFTER START POSITION.

t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

,q i

o GREEN LIGHT WITH A RED FLAG ON CONTROL STATION g o AMBER ES STATUS LIGHT OPERATOR ACTIONS-FOR A VALID ALARM:

o START AHF-15A o INVESTIGATE CAUSE OF AIR HANDLING FAN TRIP.

s DISCUSSION:

AHF-153 IS THE COOLING FAN FOR DCP-1A AND DCP-18. THE PUMPS NORMALLY OPERATE WITHOUT EITHER AIR HANDLING FAN IN OPERATION BUT ARE REQUIRED DURING ACCIDENT SCENARIOS WHEN HEAT LOAD IN THE SEA WATER ROOM IS HIGH.

i

REFERENCES:

DRAWING 208-005 SHEET AH-43 SENSING ELEMENT: CS/SC, CS/0, 42/B RELAY AR-304 Rev. 16 Page 33

ENCLOSURE 1 O (Page 33 of 56)

ESD ANNUNCIATOR RESPONSE ESD-J H1-0 5 0-05-03

~'

AH FAN 158 TROUBLE EVENT POINT 0399 INDICATED CONDITION:

o AHF-15B AIR FLOW IS <0.058" WATER AS SENSED BY AH-408-DPS AND THE CONTROL HANDLE IS IN NORMAL AFTER START. ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTIONS FOR A VALID ALARM:

. o START AHF-15A o INVESTIGATE CAUSE OF LOW AIR FLOW.

DISCUSSION:

AHF-15B IS THE COOLING FAN FOR DCP-1A AND DCP-1B. THE PUMPS NORMALLY OPERATE WITHOUT EITHER AIR HANDLING FAN IN OPERATION BUT ARE REQUIRED DURING ACCIDENT SCENARIOS WHEN HEAT LOAD IN THE SEA WATER ROOM IS HIGri.

PRIMARY PLANT OPERATOR MAY CHECK LOCAL DIFFERENTIAL PRESSURE GAUGES AH-597-DPI (AHF-15A) AND AH-598-D?I (AHF-158) TO DETERMINE FILTER AIR ' FLOW CONDITIONS.

REFERENCES:

DRAWING 208-005 CHEET AH-43 SENSING ELEMENT: CS/SC, CS/0, AH-408-DPS

.p.

AR-304 Rev. 16 Page 34

. e ENCLOSURE 1 (Page 34 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-05-03 0-05-03 AH FAN 158 TROUBLE EVENT POINT 0400 INDICATED CONDITION:

o AHF-158 DISCHARGE DUCT TEMPERATURE IS >I35T AS SENSED BY AH-410-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

A o AHF-15B TRIPS 4

V o AHF-15B WHITE PERMISSIVE LIGHT ON CONTROL STATION IS OFF OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH DUCT TEMPERATURE o DO NOT ATTEMPT A START OF AH-15A UNTIL CAUSE OF HIGH TEMP IS DETERMINED DISCUSSION:

THIS CONDITION MAY INDICATE A FIRE IN THE EXHAUST DUCTWORK OF AHF-158.

IF A FIRE CONDITION DOES EXIST REFER TO AP-880 FOR FURTHER CUIDANCE.

REFERENCES:

DRAWING 208-005 SHEET AH-43 SENSING ELEMENT: AH-410-TS O

AR-304 Rev. 16 Page 35

s.

1 I

  • . l ENCLOSURE 1 l

/ (Page 35 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-05-05 D-05-05 DC PUMP B SUC T TEMP HIGH EVENT POINT 0209 INDICATED CONDITION:

o DCP-1B SUCTION TEMPERATURE IS >105*F AS SENSED BY DC-58-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: _

o DCP-1B SUCTION TEMP INDICATION, DC-39-TI O o DC RAW WATER TEMPERATURE INDICATOR RW-12-TI OR RW-32-TI o DH COOLER TEMPERATURE INDICATORS DH-2-TI2 OR DH-6-TI2 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE RWP-3B RUNNING o VERIFY RAW WATER DELTA TEMP FOR DHCCC HEAT EXCHANGER IS <10' o IF "B" DC TRAIN TEMPERATURE CANNOT BE REDUCED THEN CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DECAY HEAT TRAINS PER OP-404.

DISCUSSION:

THIS CONDITION MAY INDICATE A FOULED DC HEAT EXCHANGER. INDICATIONS ARE:

HIGH RWP-38 DISCHARGE PRESSURE, HIGH RW DIFFERENTIAL TEMP OP LOW DC DIFFERENTIAL TEMP ACROSS THE DC HEAT EXCHANGER. ALSO VENTING THE DC HEAT EXCHANGER SHOULD BE CONSIDERED. IF DC PUMP HAS TO BE TRIPPED AFTER AN ES ACTUATION,-HPI SEAL-IN RESET MUST BE DEPRESSED BEFORE THE PUMP CAN BE SECURED.

REFERENCES:

DRAWING 208-019 SHEET DC-03 SENSING ELEMENT: DC-58-TS v

AR-304 Rev. 16 Page 36

3, ENCLOSURE 1 f]. (Page 36 of $6)

V-ESD ANNUNCIATOR RESPONSE ESD-JH1-05-06 D-05-06 l -l I I BS/DH PUMP B l I DC FLOW l l LOW EVENT POINT 1221 INDICATED CONDITION:

o DECAY HEAT PUMP 1B DC FLOW IS <30 GPM ).S SENSED BY DC-68-FIS WITH DHP-1B BKR CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o DHP-1B LOCAL DC FLOW INDICATOR INDICATES LOW FLOW

. (~ '

s o - COMPUTER POINT X323 WHICH MONITORS DHP-1B MOTOR STATOR TEMP o COMPUTER GROUP 74 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE DCP-1B. RUNNING o INCREASE FLOW TO DHP-1B BY THROTTLING DCV-36 OR DCV-119 AS REQUIRED i

l DISCUSSION:

1 THE MAXIMUM ALLOWABLE DH -PUMP STATOR TEMP IS 265' F (129.4'C, AS READ ON l COMPUTER POINT X323). CONSIDERATION SHOULD BE MADE IN SHUTTING DOWN THE

, PUMP IF THIS-TEMP IS REACHED.

l DCV-36 AND DCV-119 ARE SEALED THROTTLED VALVES, IF CHANGES ARE MADE TO THEIR POSITION ADMINISTRATIVE MEASURES MUST BE CONSIDERED.

I

REFERENCES:

DRAWING 208-019 SHEET DC-03 SENSING ELEMENT: DC-68-FIS i

i (~) -

l .V -

l AR-304 Rev.=16 Page 37 l

E_NCLOSURE 1 (Page 37 of 56) -

ESD ANNUNCIATOR RESPONSE ESD-]H1-05-06 D-05-06 1

l l l l '

BS/DH PUMP B l l DC FLOW l l LOW 2Z EVENT POINT 1223 INDICATED CONDITION:

o BUILDING SPRAY PUMP 18 DC FLOW IS <25 GPM AS SENSED BY DC-74-FIS WITH BSP-18 BREAKER CLOSED I

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

lV; o BSP-1B LOCAL DC FLOW INDICATOR INDICATES LOW FLOW o COMPUTER POINT X314 WHICH MONITORS BSP-1B MOTOR STATOR TEMP o COMPUTER POINTS X312 AND X313 WHICH MONITOR BSP-1B PUMP TEMPS o COMPUTER GROUP 82 OPERATOR ACTIONS FOR A VALID ALARM:

o INSURE DCP-1B RUNNING o INCREASE FLOW TO BSP-1B BY THROTTLING DCV-34 OR DCV-117 AS REQUIRED DISCUSSION:

THE MAXIMUM ALLOWABLE BS PUMP SfATOR TEMP IS 300* F. (149'O CONSIDERATION SHOULD BE MADE IN SHUTTING DOWN THE PUMP IF THIS TEMP IS REACHED.

DCV-34 AND DCV-117 ARE SEALED THROTTLED VALVES, IF CHANGES ARE MADE TO THEIR POSITION, ADMINISTRATIVE MEASURES MUST BE CONSIDERED.

REFERENCES:

DRAWING 208-019 SHEET DC-03 SENSING ELEMENT: DC-74-FIS AR-304 Rev. 16 Page 38

v

-q,

\

ENCLOSURE 1-(Page 38 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-06-02 0-06-02 DH RW PUMP B TRIP EVENT POINT 0018 INDICATED CONDITION:

o RWP-3B BREAKER IS OPEN WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT WITH RED FLAG ON RWP-3B CONTROL STATION b' o AMBER ES STATUS LIGHT 4

OPERATOR ACTIONS FOR A VALID ALARM:-

o CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DECAY HEAT TRAINS PER l AP-404 DISCUSSION:

THE AMOUNT OF DECAY HEAT LOAD AND THE INITIAL TEMPERATURE OF SYSTEM WILL DETERMINE HOW FAST THE DECAY HEAT TRAINS SHOULD BE TRANSFERRED.

-REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-050 SHEET RW-05 SENSING ELEMENT: 52S/B, 52H/A, CS/SC, CS/0 O

. V AR-304 Rev.-16 Page 39

ENCLOSURE 1 p

y) .

(Page 39 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-06-03 D-06-03 DH RW PUMP B MOTOR OVERLOAD EVENT POINT 0017 INDICATED CONDITION o RWP-3B MOTOR AMPS E115% RATED LOAD.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

N o HIGH RWP-3B MOTOR AMPS i o RWP-3B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o CONSIDERATION SHOULD BE GIVEN TO ALTERNATING DECAY HEAT TRAINS PER '

OP-404 DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR THE Ib'STANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-050 SHEET RW-05 SENSING ELEMENT: RELAY 51 V

AR-304 Rev. 16 Pase 40

ENCLOSURE 1

/] (Page 40 of $6) w/

ESD ANNUNCIATOR RESPONSE ] ESD-JH1-06-04 D-06-04 DH RW PUMP B g OUT OF SERVICE EVENT POINT 0016 INDICATED CONDITION:

o RWP-3B BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION #HICH WILL VERIFY ALARM:

(N o NO IkDICATING LIGHTS ON CONTROL STATION o ES STATUS LIGHTS INDICATE BREAKER POSITION

!]

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY CLOSED DPDP-5B SWITCH 10 o VERIFY DC KNIFE SWITCH FOR RWP-3B BREAKER CLOSED DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

THIS IS AN EXPECTED ALARM FOR BREAKER TACCING OPERATIONS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-050 SHEET RW-05 SENSING ELEMENT: RELAY 27C LOCATED INSIDE BREAKER CUBICLE FOR RWP-3B (D

U AR-304 Rev. 16 Page 41

ENCLOSURE 1

[- (Page 41 of $6)

ESD ANNUNCIATOR RESPONSE ESD-JH1-06-04 A-06-04

~

DH RW PUMP B OUT OF SERVICE EVENT POINT 0019 INDICATED CONDITION:

o RWP-3B BREAKER IS RACKED OUT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O V

o NO INDICATING LIGHTS ON RWP-3B CONTROL STATION o NO ES STATUS INDICATION 5

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS

REFERENCES:

DRAWING 208-050 SHEET RW-05 SENSING ELEMENT: CONTACT 52H/b IN BREAKER CUBICLE FOR RWP-3B ry AR-304 Rev 16 Page 42

ENCLOSURE 1 (Page 42 of 56) ,

ESD ANNUNCIATOR RESPONSE ESD-JH1-06 05 D-06-05 DH RW PUMP B DISCH PRESU LOW i

i EVENT POINT 0021 INDICATED CONDITION:

o RWP-38 DISCHARGE PRESS <15 PSIG AS SENSED BY RW-61-P5 WITH PUMP BREAKER CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

.,Q o RWP-3B DISCHARGE PRESSURE INDICATOR, RW-8-PI g ,

OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR PUMP CONTROL STATION CURRENT METER o SECURE PUMP IF SIGNS OF CAVITATION ARE EVIDENT DISCUSSION:

CONSIDERATION SHOULD BE GIVEN TO Pl. ACING THE ALTERNATE DECAY HEAT TRAIN IN SERVICE PER OP-404.

REFERENCE 3: DRAWING 208-050 SHEET RW-05 SENSING ELEMENT: CON 1ACT 525/a, RW-61-P5 AR-304 Rev. 16 Page 43

ENCLOSURE 1 (Page 43 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-07-01 07-01 l no is0LATION I I E8 e l l ACTUATION I I I I L _..

EVENT POINT 0932  :

INDICATED CONDITION:

o RB ISOLATION ACTUATION "B" ,

i l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o RB PRESSURE >4 PSIG o MANUAL ACTUATION OF RB ISOLATION AND COOLING o ES STATUS LIGHTS FOR AFFECTED CHANNELS CHANGE STATE l

OPERATOR ACTIONS FOR A VALID ALARM

o REFER TO E0P i

DISCUSSION:

THIS INDICATES THAT RB ISOLATION "B" HAS OCCURRED ON TWO OUT OF THREE CHANNELS, MANUAL RB ISOLATION ACTUATION HAS BEEN INITIATED.  ;

l

REFERENCES:

DRAWING 208-029 SHEET ESB-57 SENSING ELEMENT: 6321/RB1, 63Z1/RB2, 63Z/RB3, OR 1X1F/RBB l -\

-AR-304 Rev. 16 Page 44

. , , -.. , - . . -- - - , . - - - , , - . , , , ., g . _ . , --ne ,, .n. . _ . ,

. - . - - . . . . . . - - - _ - -- . . . . . . ~ _ - _ . - _ - . . - . - . - - - - - . - . - . - ._ ~

EELOSURE__1 (Page 44 of 56)

O E50 ANNUNCIATOR RESPONSE ESD-JH1-07-02 0-07-02 i

SW PUMP B TRIP EVENT POINT 1828 .

INDICATED CONDITION:

o SWP-IB BREAKER IS OPEN WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT WITH RED FLAG ON SWP-1B CONTROL STATION O

\ o AMBER ES STATUS LIGHT OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AUTO START OF SWP-LA o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o REFER TO AP-330 DISCUSSION:

EXERCISE CARE WHEN STARTING ALTERNATE SW PUMPS. ENSURE ANY FAILURES SUCH AS IMPROPER FLOW PAT!! OR SURGE TANK VOLUME, WHICH MAY HAVE DIRECTLY OR INDIRECTLY HAVE CAUSED THIS PUMP TO TRIP DO NOT CAUSE ALTERNATE PUMPS TO TRIP AFTER THEY ARE STARTED.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-056 SHEET SW-03 SENSING ELEMENT: 525/8, 52H/A, CS/SC, CS/0 AR-304 .Rev. 16 oage 45

ENCLOSURE 1 (Page 45 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-07-03 0-07-03 SW PUMP B MOTOh OVERLOAD l

EVENT PCINT 1827 INDICATED CONDITION  !

o SWP-18 MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o HIGH MOTOR AMPS ON SWP-1B o SWP-1B TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o START SWP-1A o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR THE INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED.

INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACIUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOP,TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-056 SHEET SW-03  :

SENSING ELEMENT: RELAY 51

. O, AR-304 Rev. 16 Page 46

.__.__.__.__._._...__.m. - __....._._ ___..._._.. _ .._.. _ _

3 i ENCLOSURE 1 (Page 46 of 56)

ESB ANNUNCIATOR RESPONSE ESD-JH1-07-04 D-07-04 !

SW PUMP B OUT OF SERVICE EVENT POINT 1820 l

INDICATED CONDITION:

o SWP-18 BREAKER RACKED OUT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o NO INDICATING LIGHTS ON SWP-1B CONTROL STATION o NO ES STATUS INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS,

REFERENCES:

DRAWING 208-050 SHEET SW-03 SENSING ELEMENT: CONTACT 52H/b IN BREAKER CUBICLE O

^

4

' AR-304 Rev. 16 Page 47

+ ,

ENCLOSURE 1 ,

(P;ge 47 of 56)

ESB ANNUNCIATOR RESPONSE ESD-JH1-07-04 D-07-04 4

SW PUMP B OUT OF SERVICE i

EVENT POINT 1854 INDICATED CONDITION:

o SWP-IB BREAKER HAS NO DC CONTROL POWER.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: _

O o NO INbiCATING LIGHTS ON SWP-1B CONTROL STATION o ES STATUS LIGHTS INDICATE BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY DC KNIFE SWITCH FOR SWP-18 BREAKER CLOSED.

o VERIFY CLOSED DPDP-5B SWITCH 10.

DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION. THIS IS AN EXPECTED ALARM FOR BREAKEF TAGGING OPERATIONS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-050 SHEET SW-03 SENSING ELEMENT: RELAY 27C LOCATED INSIDE BREAKER CUBICLE FOR SWP-1B AR-304 Rev. 16 Page'48

ENCLOSURE 1 (Page 48 of 56) l ESD ANNUNCIATOR RESPONSE ESD-JH1-07-05 D-07-05  ;

SW PUMP B AUTO START EVENT POINT 1829 INDICATED CONDITION: ,

o SWP-1B BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT WITH A GREEN FLAG ON SWP-1B CONTROL STATION O

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY ADEQUATE SW PUMP DISCHARGE PRESSURE SW-2-PI o INVESTIGATE THE CAUSE OF SWP-1B AUTO START DISCUSSION:

ANY AUTO START OF SWP-1B GIVES THIS ALARM (e.g. .. ES OR LOW SW SUPPLY HEADER PRESSURE).

l l

REFERENCES:

DRAWING 208-056 SHEET SW-03

, SENSING ELEMENT: 52S/a, CS/ST, CS/0 t .. .

I

.AR-304 Rev. 16 .Page 49

ENCLOSURE 1 O (Page 49 of $6)

ESD ANNUNCIATOR RESPONSE ESD-JH1-07-06 D-07-06 I

I SW PUMP B 1 l

l LOCKED OU1 ZZZZZ Z EVENT POINT 1899  !

INDICATED CONDITION:

o SWP-1B IN PULL-TO-LOCK POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SWP-18 CONTROL HANDLE ON MCB OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP 330 1

DISCUSSION:

REFERENCES:

DRAWING 208 056 SHEET SW-03 SENSING ELEMENT: CB-ESFB-MP4 O

AR-304 Rev. 16 Page 50

- __ _ _ . _.-_____-___ _ _._ _ __ _ _ _ __. _ , .._ ._ _ _ ____.._ __ _ __ _ . _ .- - m ..-- _. _ _ _ _ _ _ _ _ _

e. [

i e,

ENCLOSURE 1 1 (Page 50 of $6) 7 ESD ANNUNCIATOR RESPONSE ESD-JH1-08-01 D-08-01 t

i I SW RW PUMP B l I LOCKED OUT I I l I I I EVENT POINT 1915 INDICATED CONDITION:

o RWP-28 CONTROL HANDLE IN PULL-TO-LOCK POSITION

+1 REDUNDANT INDICr40N w 'N WILL VERIFY ALARM:

i o RWP-28 CONTROL HANDLE ON MCB OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-330 DISCUSSION:

REFERENCES:

DRAWING 208-050 SHEET RW-03 SENSING E'.EMENT: CB-ESFB-ML4 O

AR-304

~

Rev. 16 Page 51

-_ . = _ _ _ _ . _ _ . _ . . _ _ _ _ _ _ _ - - _ . _ . _ _ . _ _ _

ECL01URE_1 (Page 51 of 56)

ESO ANNUNCIATOR RESPONSE ESD-JH1-08-02 0-08-02 I

t i

SW RW PUMP 8 TRIP EVENT POINT 0010 INDICATED CONDITION:

o RWP-28 BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

4 O o CREEN LIGHT WITH A RED FLAG ON RWP-28 CONTROL STATION o AMBER ES STATUS LIGHT o LOW SW RW SYSTEM PRESSURE RW-23-PI, IF NO OTHER PUMP RUNNING OPERATOR ACTIONS FOR A VALID ALARM:

o START RWP-2A o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

ENSURE ANY FAILURE THAT IS COMMON TO RWP-2A IS CORRECTED PRIOR TO STARTING RWP-2A TO PRACLUDE RENDE!:ING IT UNAVAILABLE / INOPERABLE.

ENSURE A P';0PER FLOW PATH IS AVAILABLE PRIOR TO STARTING RWP-2A.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-050 SHEET RW-03  :

SENSING ELEMENT: 525/B, 52H/A. CS/SC, CS/0-s

-AR-304 - Rev. 16 Page 52

- m l, , --,-w - ,n--,--'- ,,e ,

ENCLOSURE 1 (Page 52 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-08 D-08-03 f

SW RW PUMP B MOTOR OVERLOAD EVENT POINT 0009 INDICATED CONDITION l o RWP-28 MOTOR AMPS >115% R/TED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS ON RWP-28 CONTROL STATION O o RWP-28 TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o START RWP-2A o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

THIS ALARM INDICATES-THAT EITHER THE TIMED OVERCURRENT OR THE INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY i,CTUATION WILL TRIP THE BREAKER.

IT-IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWINb 208-050 SHEET RW-03 SENSING ELEMENT: RELAY 51 AR-304 -

Rev. Page 53 p -

% n

  • p+ W -

- - . _. ..-_ - - . . - . - ~ . . . __ - . -

_ .. ..~ . . _.

  • . r ENCLOSURE 1 O (Page 53 of 56)

D-08-04 ESD ANNUNCIATOR RESPONSE ESD-JH1-08-04 SW RW PUMP R OUT OF BERVICE 1

EVENT POINT 0008 INDICATED CONDITION:

o RWP-28 BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM: -

o NO INDICATING LIGHTS ON RWP-28 CONTROL STATION o ES STATUS LIGHTS INDICATE BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY CLOSED DPDP-5B SWITCH 10 o VERIFY DC KNIFE SWITCH IS CLOSED FOR RWP-28 BREAKER DISCUSSION:

-THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-050 SHEET RW-03 SENSING ELEMENT: RELAY 27C LOCATED INSIDE BREAKER CUBICLE FOR RWP-28 O

'AR-304 Rev. 16 Page 54 -

. _ - ~ _

- . _ _ - _ _ . _ . . _ . _ - --~

0 i

1 l

ENCLOSURE 1 (Page 54 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-08-04 D-08-04 SW RW PUMP B OUT OF SERVICE EVENT POINT 0023 INDICATED CONDITION:

o BREAKER FOR RWP-28 BREAKER IS RACKED OUT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o NO INDICATING LIGHTS ON RWP-28 CONTROL STATION o NO ES STATUS INDICATION FOR RWP-2B OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWINC 208-050 SHEET RW-03 SENSING ELEMENT: CONTACT 52H/b IN BREAKER CUBICLE FOR RWP-2B O

-AR-304 _

Rev. 16 Page 55 >-

e* ]

0 ,

ENCLOSURE 1 (Page 55 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-08-05 D-08-05 i

SW RW PUMP B AUTO START EVENT POINT 0011 INDICATED CONDITION:

o RWP-28 BREAKER CLOSED WITH CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION. ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RWP-28 RED INDICATING LIGHT WITH A GREEN FLAG ON THE CONTROL STATION s

OPERATOR ACT. IONS FOR A VALID ALARM:

o VERIFY RW PUMP DISCHARGE PRESSURE RW-23-PI o ItuESTICATE THE CAUSE OF RWP-2B AUTO START t

DISCUSSION:

ANY AUTO START OF RWP-28 GIVES THIS ALARM (e.g., ES OR LOW RW SUPPLY HEADER PRESSURE).

REFERENCES:

DRAWING 208-050 SHEET RW-03 SENSING ELEMENT: 525/a, CS/ST, CS/0 AR-304 Rev. 16 ._

Page 56

ce o,

ENCLOSURE 1 (Page 56 of 56)

ESD ANNUNCIATOR RESPONSE ESD-JH1-08-06 D-08-06 l

l l

l ES 8 I ACTUATIOfw i l TEST 8YPA88 222222 EVENT POINT 0770 ,

INDICATED CONDITION:

o ANY E*., "B" TEST SELECTOR SWITCH NOT IN THE "0FF PUSHED IN" POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM; p o RED ' MONTHLY TEST' OR RED ' REFUELING TEST' LIGHT Ii,LUMINATED ON ONE OR Q MORE OF THE FOLLOWING SWITCHES: ,

HPI AUTO TEST SELECT SWITCH "B" L.PI AUTO TEST SELE G SWITCH "B" RB 150 AUTO TEST SELECT SWITCH "B" OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO SP-358A, SP-3588, OR SP-358C AS APPLICABLE. TO RESTORE AFFECTED SWITCH DISCUSSION:.

THIS ALARM INDICATES THAT ES SYSTEMS MAY NOT FUNCTION PROPERLY ON AN AUTOMATIC OR MANUAL ES ACTUATION.

REFERENCES:

DRAWING 208-028 SHEET ESAB-06 SENSING ELEMENT: T54/RCB, SS4/RCA. SS4/RBB L