ML062480114: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 3: Line 3:
| issue date = 09/28/2006
| issue date = 09/28/2006
| title = Issuance of Amendment Re; Partial Approval of Request Associated with the Ultimate Heat Sink Dry Cooling Tower Fans
| title = Issuance of Amendment Re; Partial Approval of Request Associated with the Ultimate Heat Sink Dry Cooling Tower Fans
| author name = Fields M B
| author name = Fields M
| author affiliation = NRC/NRR/ADRO/DORL/LPLIV
| author affiliation = NRC/NRR/ADRO/DORL/LPLIV
| addressee name = Venable J E
| addressee name = Venable J
| addressee affiliation = Entergy Operations, Inc
| addressee affiliation = Entergy Operations, Inc
| docket = 05000382
| docket = 05000382
| license number = NPF-038
| license number = NPF-038
| contact person = Fields M B, NRR/DORL, 415-3062
| contact person = Fields M, NRR/DORL, 415-3062
| case reference number = TAC MC5065
| case reference number = TAC MC5065
| document type = Letter, License-Operating (New/Renewal/Amendments) DKT 50, Safety Evaluation
| document type = Letter, License-Operating (New/Renewal/Amendments) DKT 50, Safety Evaluation

Revision as of 13:29, 13 July 2019

Issuance of Amendment Re; Partial Approval of Request Associated with the Ultimate Heat Sink Dry Cooling Tower Fans
ML062480114
Person / Time
Site: Waterford Entergy icon.png
Issue date: 09/28/2006
From: Fields M
NRC/NRR/ADRO/DORL/LPLIV
To: Venable J
Entergy Operations
Fields M, NRR/DORL, 415-3062
References
TAC MC5065
Download: ML062480114 (10)


Text

September 28, 2006Mr. Joseph E. VenableVice President Operations Entergy Operations, Inc.

17265 River Road Killona, LA 70066-0751

SUBJECT:

WATERFORD STEAM ELECTRIC STATION, UNIT 3 - ISSUANCE OFAMENDMENT RE: PARTIAL APPROVAL OF REQUEST ASSOCIATED WITH THE ULTIMATE HEAT SINK DRY COOLING TOWER FANS (TAC NO. MC5065)

Dear Mr. Venable:

The Commission has issued the enclosed Amendment No. 208 to Facility Operating LicenseNo. NPF-38 for the Waterford Steam Electric Station, Unit 3. This amendment consists of changes to the Technical Specifications (TSs) in response to your application dated November 5, 2004.The amendment modifies Technical Specification (TS) 3.7.4, "Ultimate Heat Sink," to provideclarification that the ambient temperature monitoring requirement that is specified in TS 3.7.4.donly applies when the affected ultimate heat sink train is considered to be operable. The Commission is not approving the request to delete TS 3.7.4.c, which would allow the plant totake credit for the dry cooling tower fans that are not protected from tornado missiles when a tornado warning is in effect. A copy of our related Safety Evaluation is also enclosed. The Notice of Issuance related toTS 3.7.4.d will be included in the Commission's next biweekly Federal Register notice. TheNotice of Denial related to TS 3.7.4.c will also be included in the Commission's next biweeklyFederal Register notice.Sincerely,/RA/Mel B. Fields, Senior Project ManagerPlant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor RegulationDocket No. 50-382

Enclosures:

1. Amendment No. 208 to NPF-382. Safety Evaluationcc w/encls: See next page

Pkg ML062570486 (ML062480114, TS Page: ML062720172)OFFICENRR/LPL4/PMNRR/LPL4/LANRR/SBPB/(A)BCNRR/ITSB/BCOGCNRR/LPL4/BCNAMEMFieldsLFeizollahiCLiTKobetzMYoungDTeraoDATE9/25/069/25/066/13/069/25/069/22/069/26/06 ENTERGY OPERATIONS, INC.DOCKET NO. 50-382WATERFORD STEAM ELECTRIC STATION, UNIT 3AMENDMENT TO FACILITY OPERATING LICENSEAmendment No. 208License No. NPF-381.The Nuclear Regulatory Commission (the Commission) has found that:A.The application for amendment by Entergy Operations, Inc. (EOI) datedNovember 5, 2004, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I;B.The facility will operate in conformity with the application, the provisions of theAct, and the rules and regulations of the Commission;C.There is reasonable assurance (i) that the activities authorized by thisamendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with theCommission's regulations;D.The issuance of this amendment will not be inimical to the common defense andsecurity or to the health and safety of the public; andE.The issuance of this amendment is in accordance with 10 CFR Part 51 of theCommission's regulations and all applicable requirements have been satisfied. 2.Accordingly, the license is amended by changes to the Technical Specifications asindicated in the attachment to this license amendment, and paragraph 2.C.2. of FacilityOperating License No. NPF-38.3.This license amendment is effective as of its date of issuance and shall be implementedwithin 60 days from the date of issuance.FOR THE NUCLEAR REGULATORY COMMISSION/RA/David Terao, ChiefPlant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications and Facility Operating License No. NPF-38Date of Issuance: September 28, 2006 ATTACHMENT TO LICENSE AMENDMENT NO. 208TO FACILITY OPERATING LICENSE NO. NPF-38DOCKET NO. 50-382Replace page 4 of Operating License No. NPF-38 with the attached revised page 4. Replace the following page of the Appendix A Technical Specifications with the attachedrevised page. The revised page is identified by an amendment number and contains a marginal line indicating the area of change. REMOVEINSERT3/4 7-133/4 7-13 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATIONRELATED TO AMENDMENT NO. 208 TOFACILITY OPERATING LICENSE NO. NPF-38ENTERGY OPERATIONS, INC.WATERFORD STEAM ELECTRIC STATION, UNIT 3DOCKET NO. 50-38

21.0INTRODUCTION

By application dated November 5, 2004 (Agencywide Documents Access and ManagementSystem (ADAMS) Accession No. ML043150218), Entergy Operations, Inc. (the licensee),

requested changes to the Technical Specifications (TSs) for Waterford Steam Electric Station, Unit 3 (Waterford 3).Specifically, the licensee proposes to revise TS 3.7.4, "Ultimate Heat Sink [UHS]," to provideclarification that the ambient temperature monitoring requirement that is specified in TS 3.7.4.donly applies when the affected ultimate heat sink train is considered to be operable and to delete TS 3.7.4.c. Deleting TS 3.7.4.c. would allow the plant to take credit for the dry coolingtower (DCT) fans that are not protected from tornado missiles when a tornado warning is in effect. The TS Bases would also be changed in accordance with the Waterford 3 TS Bases Control Program (TS 6.16).

2.0REGULATORY EVALUATION

Title 10 of the Code of Federal Regulations (10 CFR) Section 50.36, "Technical specifications,"requires that the TSs include items in five specific categories. These categories include:

(1) safety limits, limiting safety system settings, and limiting control settings; (2) limitingconditions for operation; (3) surveillance requirements; (4) design features; and (5)administrative controls. The acceptability of the proposal to modify TS 3.7.4.d and delete TS3.7.4.c is based in part on continued compliance with 10 CFR 50.36.Waterford 3 is designed to withstand the effects of tornado and high wind generated missiles soas not to impact the health and safety of the public in accordance with the requirements specified by 10 CFR Part 50, Appendix A, General Design Criteria (GDC) 2 and 4. The Waterford 3 design basis as originally reviewed and approved by the Nuclear Regulatory Commission (NRC) and reflected in Section 3.5.1.4 of the Waterford 3 Final Safety AnalysisReport credited protective features for satisfying these GDC requirements. In reviewing requests of this nature, the NRC staff verifies that a methodology exists that assures the plantdesign and licensing basis continue to meet GDC 2 and 4.

3.0TECHNICAL EVALUATION

3.1Proposed Change to Delete TS 3.7.4.cTS 3.7.4.c currently requires all nine of the tornado protected DCT fans for Waterford 3 to beoperable whenever a tornado warning for the Waterford site is in effect. Entergy has completed a risk assessment using the Electric Power Research Institute (EPRI) TORMIS methodology to show that the probability of a tornado missile causing damage to the unprotected DCT fans issufficiently small to allow the unprotected DCT fans to also be credited for tornado mitigation. The licensee indicated that allowing the unprotected DCT fans to be credited as proposedwould provide additional flexibility in maintaining the UHS operable whenever a tornado warningis in effect for the Waterford 3 site, thereby reducing operational burden.Similar to Waterford 3, the design bases of nuclear power plants typically credited protectivefeatures for satisfying the provisions of GDC 2 and 4 with respect to tornado missiles. During subsequent inspections and design reviews, NRC inspectors and licensees found that some ofthe structures, systems, and components (SSCs) that should have been protected from theeffects of tornado missiles were not adequately protected in accordance with the design basis of the plant. As an alternative to implementing costly plant modifications to correct these vulnerabilities, EPRI developed the TORMIS methodology for assessing the probability ofdamage to SSCs that were relied upon for tornado mitigation but were not adequately protectedfrom tornado missiles. Plant modifications would not be required for situations where the probability of damage due to tornado missiles was demonstrated to be sufficiently small by theTORMIS analysis. The NRC staff approved use of the TORMIS methodology in a safetyevaluation dated October 26, 1983, indicating that the TORMIS methodology could be utilizedfor assessing the need for positive tornado missile protection for specific safety-related plant features but that use of the TORMIS methodology (or any tornado missile probabilistic study)should be limited to the evaluation of specific plant features where additional costly tornado missile protective barriers or alternative systems are under consideration.After the operating license for Waterford 3 was issued and contrary to the original plant designbasis, the licensee identified SSCs that were not protected from the effects of tornado missiles. License Amendment No. 168 for Waterford 3, dated September 7, 2000 (ADAMS Accession No. ML003749019), subsequently approved the licensee's use of the TORMIS methodology for demonstrating that these specific SSCs do not require the installation of additional tornado missile protective barriers due to the low probability that a tornado missile will strike theseunprotected SSCs. The acceptability of the licensee's amendment request to delete TS 3.7.4.c is based uponcontinued compliance with GDC 2 and 4 in a manner that is consistent with the plant licensingbasis and based upon consistency with prior NRC approvals. As clarified in LicenseAmendment No. 168 for Waterford 3 and consistent with other applications of the TORMIS methodology that have been approved by the NRC: a) the deterministic approach in theStandard Review Plan (SRP) should continue to be used to assure adequate protection of SSCs from the effects of tornado missiles and the TORMIS methodology should be used on a case-by-case basis for assessing specific plant features which are exceptions; and b) the TORMIS methodology may not be used for justifying the permanent or temporary removal of existing barriers. The licensee's request to credit use of the six unprotected DCT fans as an alternative to usingthe protected DCT fans and to eliminate the TS requirement that the nine protected DCT fansbe operable whenever a tornado warning is in effect is tantamount to allowing tornado missile barriers for as many as six protected DCT fans to be removed on a temporary basis. While crediting the unprotected DCT fans does not cause tornado missile barriers to be physically removed or modified, the result is the same in that the barriers are not necessary (and couldjust as well be removed) if the equipment they are designed to protect is not required to be operable. The NRC staff had previously provided this viewpoint in a letter to Entergy datedMay 27, 2004 (ADAMS Accession No. ML041490149). In addition, deleting TS 3.7.4.c would permit up to six of the protected fans to be inoperable for an extended period of time. Using TORMIS to justify taking credit for unprotected SSCs that are not required to be relied upon for tornado mitigation by the plant design basis (other than for demonstrating defense-in-depth)and/or as a means of relaxing existing TS requirements is not consistent with the

NRC-approved application of the TORMIS methodology or the reasons why TORMIS wasinitially developed. In particular, the NRC has approved the use of the TORMIS methodologyonly for the evaluation of specific plant features where additional costly tornado missile protective barriers or alternative systems are under consideration. More specifically, consistentwith previous license amendments in which the staff has approved plant-specific application of the TORMIS methodology (such as License Amendment No. 168 for Waterford 3), use of the TORMIS methodology is limited to demonstrating adequate protection and compliance with the provisions of GDC 2 and 4 for those SSCs that are not adequately protected from tornadomissiles as required by the plant design basis. Therefore, because the licensee's proposed use of TORMIS is not consistent with the NRC-approved application of the TORMIS methodology,the proposed change to delete TS 3.7.4.c is unacceptable. Similarly, the proposed editorialchanges that would be appropriate if TS 3.7.4.c were deleted are also unacceptable.The TORMIS methodology is not recognized by the NRC as an approved method for justifyingthe elimination of existing tornado protected SSCs or tornado barriers nor for justifying the elimination or relaxation of TS (or other) requirements that have been established for thoseSSCs and barriers. As stated in the NRC safety evaluation that approved License AmendmentNo. 168 for Waterford 3, the deterministic approach in the current SRP for tornados should continue to be used, with the probabilistic risk assessment approach employed on a case-by-case basis for assessing specific plant features which are exceptions. Along these lines, use of the TORMIS methodology to justify taking credit for additional SSCs that are not tornado protected (but satisfy all other applicable design-basis requirements) and are needed in order to resolve licensing basis deficiencies that have been identified, is consistent with the staff'sapproved use of the TORMIS methodology. Accordingly, licensees may use TORMIS for this purpose and for justifying proposed TS changes that are affected in this regard. However, any future proposed use of TORMIS should be specifically focused on resolving design-basis problems that have been identified and not for promoting (in total or in part) operationalflexibility or convenience. 3.2Proposed Change to Modify TS 3.7.4.dTS 3.7.4.d requires the licensee to verify that the minimum UHS fan requirements specified byTS Table 3.7-3 are satisfied at least once every 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> when any UHS fan is inoperable. The capability of each UHS train to dissipate the design-basis heat load is dependent in part on theambient temperature conditions and the number of fans that are available for circulating the air. As the number of operable fans is reduced, the ambient temperature must be limited to a lowervalue in order to accommodate the same heat load without exceeding the assumed maximum UHS outlet water temperature (among other things). However, if a UHS train is inoperable for some reason, it cannot be credited for dissipating its design-basis heat load irrespective of how many of its fans are operable or what the ambient temperature conditions are. The proposed change to TS 3.7.4.d provides clarification that the ambient temperature monitoring requirementthat is specified only applies when the affected UHS train is considered to be operable.

Because the proposed change is a clarification of the existing requirement that is consistentwith the intent of the specification, the proposed change to TS 3.7.4.d is considered to beacceptable.

4.0STATE CONSULTATION

In accordance with the Commission's regulations, the Louisiana State official was notified of theproposed issuance of the amendment. The State official had no comments.

5.0ENVIRONMENTAL CONSIDERATION

The amendment changes a requirement with respect to installation or use of a facilitycomponent located within the restricted area as defined in 10 CFR Part 20. The NRC staff hasdetermined that the amendment involves no significant increase in the amounts, and nosignificant change in the types, of any effluents that may be released offsite, and that there isno significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendment involves no significant hazards consideration, and there has been no public comment on such finding published December 7, 2004 (69 FR 70717). Accordingly, the amendment meets the eligibilitycriteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendments.

6.0CONCLUSION

The Commission has concluded, based on the considerations discussed above, for theproposed change to TS 3.7.4.d only, that: (1) there is reasonable assurance that the healthand safety of the public will not be endangered by operation in the proposed manner, (2) suchactivities will be conducted in compliance with the Commission's regulations, and (3) theissuance of the amendments will not be inimical to the common defense and security or to thehealth and safety of the public.The Commission has further concluded, based on the considerations discussed above, that theproposed change to TS 3.7.4.c is considered to be unacceptablePrincipal Contributor: J. Tatum Date: September 28, 2006 May 2006Waterford Steam Electric Station, Unit 3 cc:

Vice President Operations Support Entergy Operations, Inc.

P.O. Box 31995 Jackson, MS 39286-1995DirectorNuclear Safety Assurance Entergy Operations, Inc.

17265 River Road Killona, LA 70066-0751Wise, Carter, Child & Caraway P.O. Box 651 Jackson, MS 39205 General Manager Plant OperationsWaterford 3 SES Entergy Operations, Inc.

17265 River Road Killona, LA 70066-0751Licensing ManagerEntergy Operations, Inc.

17265 River Road Killona, LA 70066-0751Winston & Strawn LLP1700 K Street, N.W.

Washington, DC 20006Resident Inspector/Waterford NPSP.O. Box 822 Killona, LA 70066-0751Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011Parish President Council St. Charles Parish

P.O. Box 302 Hahnville, LA 70057Executive Vice President & Chief Operating Officer Entergy Operations, Inc.

P.O. Box 31995 Jackson, MS 39286-1995Chairman Louisiana Public Services Commission P.O. Box 91154 Baton Rouge, LA 70825-1697Richard Penrod, Senior Environmental ScientistState Liaison Officer Office of Environmental Services Northwestern State University Russell Hall, Room 201 Natchitoches, LA 71497