 Issue dateTitleTopic
ML20211M6498 October 1997Addenda 1 to Part 21 Rept Re Weldments on Opposed Piston & Coltec-Pielstick Emergency stand-by Diesel gen-set lube-oil & Jacket Water Piping Sys.Revised List of Potentially Affected Utils to Include Asterisked Utils,Submitted
ML20056E97519 August 1993Provides Insp Results & Safety Analysis Re Operational Amplifiers Discussed in 920917 & 23 Ltrs as Potential Safety Issue.Concludes That There Are No Safety Concerns W/Respect to Buffer Amplier Module.Ltr Not 10CFR21 Notification
ML20044G53126 May 1993Suppl to 921207 Part 21 Rept Re Declutch Sys Anomaly in Certain Types of Valve Actuators Supplied by Limitorque Corp.Limitorque Designed New Declutch Lever Which Will Be Available in First Quarter 1993Stroke time
ML20126J59631 December 1992Part 21 Rept Re Potential Loss of RHR Cooling During Nozzle Dam Removal.Nozzle Dams May Create Trapped Air Column Behind Cold Leg Nozzle Dam.Mod to Nozzle Dams Currently Underway. Ltrs to Affected Utils EnclHydrostatic
ML20125C7167 December 1992Part 21 Rept Re Possibility for Malfunction of Declutching Mechanisms in SMB/SB-000 & SMB/SB/SBD-00 Actuators. Malfunction Only Occurs During Seismic Event.Balanced Levers May Be Purchased from Vendor.List of Affected Utils EnclStroke time
Anchor Darling
ML20127P58623 November 1992Followup to 921005 Part 21 Rept Re Potential Defect in SB/SBD-1 Housing Cover Screws.Procedure Re Replacement of SBD-1 Spring Cover Bolts Encl.All Fasteners Should Be Loosened & Removed.List of Affected Utils Encl
ML20118B21923 September 1992Suppl to Part 21 Rept Re Potential Deviation in Some Bailey Controls Co 88 Series Modules,Transmitted Via .One Module Found Incapable of Reaching 100% Output at Max Rated Load.Recommends That Circuit Board Assemblies Be Inspected
ML20090L88018 March 1992Part 21 Re Cracked Piston Castings Received from Acme Foundry,Fairbanks Morse & General Casting.Magnetic Particle Insp of All Pistons Will Be Performed.List of Affected Plants Encl
ML17262A26230 November 1990Part 21 Rept Re Chilled Water Sys.Initially Reported on 901030.Evaluation of Perry Plant Will Be Sent by 901230
ML20012C1057 March 1990Part 21 Rept Re Several Failures of Fairbanks Morse Engine Div Piston Pins/Bushings on Upper Pistons.Caused by Incorrect Surface Pattern on Piston Pins.Piston Pins Under Listed Purchase Orders to Be Removed & Replaced
ML20205F32110 October 1988Part 21 Rept Re Potential Deviation from Tech Spec Concerning Ry Indicators Due to Operating Temp Effect on Analog Meter Movement.Initially Reported on 881006.Customers Verbally Notified on 881006-07
ML20245D9546 September 1988Part 21 Rept Re Condition Involving Inconel 600 Matl Used to Fabricate Steam Generator Tube Plugs & Found to Possess Microstructure Susceptible to Stress Corrosion Cracking
ML20203D02214 July 1986Part 21 Rept Re Air Monitoring Sys Probes Exhibiting Blue Tip Rather than Normal White Tip & Insensitive to Chlorine. Caused by Improper Handling/Storage.Advisory Bulletin Encl. Item Not Reportable Per Part 21
NRC-86-3142, Part 21 Rept Re Increased Failure Probability of Coils Used in Class 1E Motor Starters & Contactors Supplied to Nuclear Power Plants by Westinghouse.Replacement Coils Mfg for All Starters & Contactors on Encl List19 June 1986Part 21 Rept Re Increased Failure Probability of Coils Used in Class 1E Motor Starters & Contactors Supplied to Nuclear Power Plants by Westinghouse.Replacement Coils Mfg for All Starters & Contactors on Encl List
ML20134Q17429 August 1985Part 21 Rept Re Potential Maint Issues Associated w/Anker-Holth Snubbers.Owners of Anker-Holth Snubbers Will Be Informed of Problems & Sent Revs to Technical Instruction Manuals to Include Procedures for Seal & Fluid Maint
ML20210G99213 August 1985Part 21 Rept Re Failure of Isolated Worm Shaft Gear When Certain Critical Speeds Combined W/Repetitive Transfer of Actuator Clutch Mechanism from Manual (Handwheel) to Motor Drive Mode.Two Possible Solutions Noted
ML20126C6905 June 1985Part 21 Rept Re Generator Failure.Concurs W/Encl Louis Allis That Interpolar Connectors Be Removed
ML20129G44029 May 1985Part 21 Rept Re Failure of Inner Polar Connector Between Damper Bar Circuit on Generator Main Field.Cause of Failure Not Defined.Further Investigation Necessary
ML20010G68216 September 1981Part 21 Rept Re Heating, Ventilation & Air Conditioning Ductwork.New Design Info Shows Ducts Could Collapse If Subjected to High Negative Pressure Due to Dirty Filters. Stiffener Angles Will Be Added
ML20010C6886 August 1981Interim Deficiency Rept Re Potentially Reportable Diesel Generator Starting Air Sys Design,Initially Reported 810803. Generator Supplier Will Be Contacted to Determine Whether Deficiency Exists.Problem Suspected to Be Generic in NatureSafe Shutdown
ML20002D56213 January 1981Interim Deficiency Rept Re Electrical Component Cabinets Where Frame Is Welded to Embedded Steel Angles,Initially Reported 810109.Concrete Failure & Loss of Positive Anchorage Possible.Review Will Be Completed by 810306Safe Shutdown
ML17266A35931 October 1980Final Deficiency Rept Originally Reported on 800325 Re Defective Hydramotor Actuators for Dampers & Louvers.Caused by Mfg from Incorrect Matl.Dampers Reworked & Retested. Dampers & Louvers to Be Tested in Preoperational Program
ML20085A48313 December 1979Part 21 Rept Re Visual Linear Defects in ASME III Class 2 Core Flooding Sys Isolation Valve & Unacceptable Indications in Six ASME III Class 1 Decay Heat Sys Isolation Valves at Wppss.Cause Will Be Investigated
ML20090F40111 October 1977Part 21 Rept Re Defective Auxiliary Feed Pump Governor. Initially Reported on 770930.Governor Modified at Woodward Governor Co Facilities
ML19319C8953 October 1974Deficiency Rept Re Internals Handling Fixture Spherical Nut Retaining Device Potential to Become Unthreaded.Caused by Design Error.Capture Device Redesigned & Hole Drilled in Threaded Rod to Ensure Capture by Set Screw
ML19262A30926 April 1974Deficiency Rept Re 3/4 Inch Carbon Steel Nut Discovered on Top of Lower Grid Assembly at Interface of Core Positions L-2 & M-3.Found During post-hot Functional Insp of Reactor Internals.Addl Insps & Investigations in Progress
ML19270H51611 April 1974Deficiency Rept Re Buckling Inward of Upper Section of Sodium Thiosulfate Tank While Filling Tank.Caused by Negative Internal Pressures.Procedure for Establishing Geometry of Buckled Tank Plate Being Developed
ML19270H5154 April 1974Deficiency Rept Re Failure of Diesel Generators to Operate When Given Start Signal During Engineered Safeguards Surveillance Tests.Applicable Procedures Being Revised & Review Conducted of Safeguards Test Requirements
ML19210B22129 March 1974Ro:On 740329,nuclear Svc River Water Pump Failed During Hot Functional Test Sequence.Caused by Pump Shaft Fracture in Pump Motor Shaft Coupling Area.Motor & Pump Returned to Respective Vendors for Insp & Repair
ML19262A38015 March 1974Deficiency Rept Re Diaphragm Sucked Over Suction Screen Which Cut Off Flow During Draining of Condensate Storage Tank 1B.Condenser Vacuum Collapsed Suction Screen Which Punctured Diaphragm.New Screen Designed
ML19290A4957 March 1974Deficiency Rept Re Failure of 1B HPI Pump.Caused by Damage to Seal Rings of Two Stages of Pump & Personnel Errors. Repairs to Pump Completed Per Work Request Revision of Administrative Procedure 1012
ML19210B3481 March 1974Deficiency Rept Re Lack of Separation of Seven Circuits in Vicinity of Heating,Ventilation & Air Conditioning Panel Underneath Control Room Discovered During Jan 1974 Audit by General Public Utils Svc Corp
ML19290A48322 February 1974Final Deficiency Rept Re Revision of Specific Heat Curve for U Oxide Fuel as Utilized in Transient Computer Codes for Plant Safety Analyses.Forwards New Specific Heat Code & LOCA Limited Max Allowable Linear Heat Rate Graphs
ML19290A48219 February 1974Final Deficiency Rept Re Discrepancies Between Physical Cable Count & Cable Tray Loading Summary Quantities.Forwards Table W/Summary & Resolution of Audit Findings.Revised Pull Slips Issued for Circuits CG-415 & RV-844
ML19276H3554 February 1974Notifies That Reactor Bldg Spray Pump Motors Do Not Meet Design Criteria.Motors Not Able to Reach Normal Operating Speed within Six Seconds Under Worst Undervoltage Condition. No Corrective Action Will Be Taken
ML19210B26920 December 1973Deficiency Rept Re Bent Vent Valve Thermocouple Guide Tubes & Bent Thermocouple Nozzles on Reactor Vessel Closure Head. Caused by Misalignment of Nozzles on Head to Guide Tubes on Plenum.Corrected by Partial Removal of Nozzles
ML19210B25712 December 1973Deficiency Rept Re Discrepancies Between Physical Cable Count & Cable Tray Loading Summary Quantities.Seven of 20 Safeguard Cable Trays Randomly Selected Did Not Agree W/ Summary.Caused by Revised Pull Clips W/Routing Change
ML19210B3834 December 1973Deficiency Rept Re Partial Draining of RCS from 150 Inches to Near 0 Inches Pressurizer Level(Approx 40000 Gallons). Caused by Personnel Error.Operator Closed DH-V6A Valve. Plant Shut Down W/No Testing in Progress
ML19290A4889 November 1973Deficiency Rept Re Failure of Nuclear Svc River Water Pump 1B Motor.Caused by Length of Rope Tangled in Pump.No Immediate Corrective Action Required.Motor Sent to Vendor for Insp & Repair
ML19290A4774 October 1973Deficiency Rept Re Discovery of Limitorque Valve Operators DH-V-6A & BS-V-3B on Floor Removed from Respective Valves & Partially Wetted During 730831 de-energizing of Power to Perform Electrical Changes to TMI-1 Sys
ML19210B39221 September 1973Deficiency Rept Re Arc Suppression Diode Failure in Westinghouse Model DB-25 & DB-50 Breakers During Checkout. Caused by Exposure of Diodes to Voltage Spikes in Excess of Breakdown Voltage,Causing Diodes to Short Out
ML19250C10018 September 1973Deficiency Rept Re Failure of Stems on Core Flood Valves CF-V-1A & CF-V-1B Equipped W/Limitorque SMB-4 Operators. Diameter of Stem Caused Thread to Be Tapered.Stem Nut Would Bind & Prevent Further Opening by Hand Operation
ML19290A49820 August 1973Deficiency Rept Re Seismic I Hanging Conduit Lacking Appropriately Approved Detail Per Recent Audit.Addl Info Required for Approval Not Sent.Criteria & Drawings Will Be Prepared to Prevent Further Occurrences
ML19290A47220 August 1973Deficiency Rept:On 730515 Nuclear Svc River Water Pump 1C Motor Caught Fire & Supply Breaker Tripped During Operation Supporting Testing of Circulating Water Sys.On 730717 Knocking Noise & Burning Odor Emanated from Pump
ML19290A47317 August 1973Deficiency Rept Re Grease Leakage Discovered on 730720 from 2090P Casing Filler Mfg by Viscosity Oil Co Into Vertical Tendon Conduits.Liner Plate Checked & No Bulging or Buckling Found.Samples of Leaking Matl Taken
ML19290A4636 August 1973Deficiency Rept Re Apparent Breakdown in QA Program Including Insp & Testing of Protective Electrical Equipment & Circuitry.Qc Surveillance of Multi-Amp Engineering Svcs Reinstituted & Notification Procedures Begun
ML19290A45512 July 1973Final Deficiency Rept Re Completion of Valve Wall Thickness Verification Program.Wall Thickness of Valves Adequate. Records of Measurements & Evaluations Available at Site
ML19290A4434 June 1973Final Deficiency Rept Re Scratches Observed on 730514 at Eight Locations Around Top Outer Surface of Reactor Vessel Internal Thermal Shield After Removal of Lower Core Support Assembly Shipping Container
ML19290A4278 December 1972Deficiency Rept Re Anomalous Conditions in Seven Shop Welds During Pre Baseline Inservice Insp.All Are B&W Shop Welds. Submits Findings of B&W Nov 1972 Ultrasonic Testing of Specified Welds.Plans Further Exploratory Testing