Deficiency Rept Re Anomalous Conditions in Seven Shop Welds During Pre Baseline Inservice Insp.All Are B&W Shop Welds. Submits Findings of B&W Nov 1972 Ultrasonic Testing of Specified Welds.Plans Further Exploratory Testing
ML19290A427
Person / Time
Site: Crane 
Issue date: 12/08/1972
From: John Miller
METROPOLITAN EDISON CO.
To:
Shared Package
ML19290A426 List:
References
NUDOCS 7911070606
Download: ML19290A427 (3)


Text

.

' gra f : yggy u-..

2 a:::.,

nr. -.nm

/

METROPOLITAN EDISON COMPANY su=icim Or asnem pusuc unUTis: CORPORATION

.T OFFICE BOX 542 READING, PENNSYLVANI A 19603 TELEPHONE 215 - 929-36o1 December 8,1972 Mr. R. Kruesi, Director Directorate of Regulatory Operations United Sta*.es Atomic Energy Commission Washington, D. C.

20545

Dear Mr. Kruesi:

SUBJECT:

THREE MILE ISLA'ID NUCLEAR STATION UNIT 1 DOCKET No. 50-289 ULTRASONIC INDICATIONS IN REACTOR COOLANT PIPING This letter is to further clarify the telephone conversation with Region I DRO Office on November 8,1972, concerning anomalous conditions in seven shop welds during pre-baseline inservice inspection.

Pre-baseline ultrasonic examinations performed of welds in the reactor coolant system indicated that there were five welds that had ultrasonic reflectors greater than permitted by the ANSI B31.7 Code. All these welds are B&W shop welds.

The welds are identified as follows:

WELD NO.

LOCATION / TYPE CON-057 Pump 1C (Northwest) Suction Leg -- Stainless Steel Girth Weld.

RC-078 Pump 1C (Northwest) Suction Leg -- Stainless Steel Carbon Steel Transition Girth Weld.

RC-097 Pump 1D (Southwest) Suction Leg - Stainless Steel Carbon Steel Transition Girth Weld.

CON-022 Hot Leg Elbow on Top of West Steam Generator --

Carbon Steel Girth Weld CON-019 Hot Leg in Elbow on Top of East Steam Generator --

Carbon Steel Longitudinal Weld.

NOTE: Two other carbon steel welds, numbers RC-063 and RC-013 were previously identified as containing UT indications; however, the indications are acceptable per ANSI B31.7 requirements.

1556 358 491107o[D6

s -

Radiographic examinations of stainless steel welds CON-057 and RC-078 were perfor ed.

The RT films were evaluated independently of the UT results, and the RT evaluation essentially confirms the presence of indications at the same locations found by UT.

A UT examination was performed from the inside of weld CC"-057 and this examination confirmed the original UT examination which was perfor=ed from the outside surface.

The third stainless steel weld, RC-097 located in the southwest leg below the reactor coolant pu=p, is not accessible from the inside for radio-graphic examination since the pump internals are installed in that leg.

Early in November 1972, B&W performed additional UT examination of weld CON-057. Concurrently, they reviewed the RT films of welds CON-057 and RC-078.

The following is a su==ary of B&W's results:

1.

B&W confirmed the presence of reflectors in their UT examination performed from the outside surface of weld CON-057.

They were also able to locate these sa2e type reflectors in the weld when perforcing UT from the inside surface.

In addition, loss of back reflection of the UT signal through the weld using a longitudinal beam was observed.

B&W concluded that the UT reflectors were caused by the coarse granular structure in the veld and near the line of fusion between the weld and base metal.

B&W would not classify the reflectors as unacceptable linear indications.

2.

B&W stated that none of the indications shown on the films of both CON-057 and RC-078 exceeded code limits of acceptability.

In the case of CON-057, B&W concluded that the film indications which appeared to be pockets of slag were not interconnected.

In the case of RC-078, B&W concluded that the linear indications are granular phenomena occurring at the line of fusion as a result of a scalloping effect induced during welding.

B&W requested that an additional RT examination of CON-057 be made to obtain films for composite viewing, rather than for single film reviewing.

3.

B&W has agreed with the UT exanination of the two carben steel welds CON-022 and CON-019.

They are attempting to either justify the acceptance of the indications or the carben steel welds will have to be repaired.

Since the parties cannot agree concerning the acceptability of the indica-tions in the stainless steel welds, we are preparing to perform exploratory sampling of one of these welds.

The results of this destructive sacpling will determine if the indications are grain anomalous conditions or actual defects.

Once the question to the existence of the indication in a stainless s teel weld is settled, this will resolve the questions in the two remaining welds.

The indications in the carbon steel welds are being analyzed by D&W.

If in their analysis they cannot justify the UT indications, i.e., code case or fracture mechanics, then the indications will be removed and the welds repaired.

1556 359

the Any further technical infor ation you require will be available at Three Mile Island site for your review.

Very truly yours, 0

(~ '

i LhLb v

3. G. Miller V,1ce President

/

cc:

Mr. J. P. O'Reilly 1556 360

.