r GULF STATES UTILITIES COMPANY

%E4 BEND STAfiCN PC57 Of f N E 801220 St FR ANCIS ALLE LOV15' AN A 7077S AeE A CCOE $C4 635 6094 346 8651 March 15, 1988 RBG- 27569 Mr. J. Dale Givens, Assistant Secretary Office of Water Resources Department of Environmental Quality Post Office Box 44091, capitol Station Baton Rouge, LA 70804-4091

Dear Sir:

File Code Gl.I1.2 Water Discharge Permit No. WPO409 River Bend Station - Unit i On the morning of Thursday, March 10, 1988, analysis of a sample collected at 10:05 a.m. indicated a Total Residual Chlorine (TRC) of less than 0.1 mg/l at Outfall 005 of the above-referenced permit. The permitted minimum TRC at Outfall 005 is 0.8 mg/1.

At 2:50 p.m. on the sane day, a sample was collected and analysis showed a TRC of 0.85 mg/l resulting in approximately five hours of non-compliance.

The excursion apparently occurred as a result of higher than normal flow, associated with heavy rainfall on the preceding two days, which depleted the hypochloritt tablets out of the bottom of the chlorinator tube. The tablete absorbed water which caused them to swell slightly end fail to drop to the bottom of the chlorinator tube.

The excursion was corrected by reloading t'e chlorinator tube with dry hypochlorite tablets. Evaluation of the chlorination system at Outfall 005 will be conducted to determine appropriate corrective actions to prevent a recurrence.

I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on cy inquiry of the person or persons uno manage the system, or those perr.ons directly responsible for gathering the information submitted, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.  !

l Sincerely,

++:>-

8803210462 880315 PDR eni r ce Pres W nt ADOCK 05000453 l S DCD River Bend Nuclear Group 9 l JCD/ E JVC/ch V

e .

cc: tapitol Regional Office Water Pollution Control Division 11720 Airline Highway Baton Rouge, LA 70817-1720 U.S. Nuclear' Regulatory Commission Document Control Desk Washington, D.C. 20555 U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76011 NRC Resident Inspector P.O. Box 1051 St. Francisville, LA 70775 l