4 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-III-85-87 Date August 2  !

This preliminary notification constitutes EARLY notice of events of POSSIBLE safety

or public interest significance. The information is as initially received without varification or evaluation, and is basically all that is known by the Region III lstaffonthisdate.

Facility. Comonwealth Edison Co. Licensee Emergency Classification: '

Dresden Unit 3 XX Notification of an Unusual Event Morris, IL 60450 Alert Site Area Emergency Docket No: 50-249 General Emergency Not Applicable

Subject:

MULTIPLE EQUIPMENT PROBLEMS

! On August 27, 1986, the licensee declared an unusual event and shut the unit down because of equipment problems which led to the inoperability of the High Pressure Coolant Injection (HPCI) System and the "B" train of the Core Spray System. The HPCI system had been previously declared inoperable because of a gland seal leakoff pump problem; the Core Spray System's "B" train pump discharge piping was depressurized due to a partially open test

return valve. These problems have been cqrrected.

l

> During the shutdown additional problems were identified. .The licensee intends to take this

' opportunity to correct these and other problems that already existed. These repair efforts

..are underway. These problems included a loose wire in the output breaker for shared L Units 2/3 Diesel Generator, a failed mini-flow valve in the Low Pressure Coolant Injection i (LPCI) System, blockage b3 small clams in a LPCI Heat Exchanger, a control rod drive problem, t and a stuck source range monitor.

Licensee Corporate management is on site to review the plant's status prior to a restart decision.

. Tha resident inspectors are reviewing the licensee's repair activities.

lTheStateofIllinoiswillbeinformed.

' Region III received notification of the ini

  • problems err-August 27, 1986. This

' information is curr t of 11 a.m. , 86 .

CONTACT: D. C. y# . emon 4

FTS 388-5546 FTS*388-5574 i

DISTRIBUTION:

H..St. ED0 NRR E/W Willste Mail: ADM:DMB Chairman Zech PA IE NMSS D0T:Trans only Comm. Roberts ELD OIA RES

Comm. Asselstine AE0D Comm. Bernthal Com. Carr SPj.7 Regional Offices

. ACRS '

SECY INP0)./dp NSAC 1 / k

1 CA RIII Res~ident Office PDR Licensee: J .'AJ-- (Corp. Office - Reactor Lic. Only) 96090903S2 960829 Region III Ol N -Ik 06-097 PDR Rev. November 1985