ML20249B893

From kanterella
Jump to navigation Jump to search
PNO-76-157:on 760916,util Notified Region III That Leak Had Been Discovered in HPCI Test Return Line to Condensate Storage Tank
ML20249B893
Person / Time
Site: Dresden 
Issue date: 09/17/1976
From: Roy G, Thompson D, Warnick R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-76-157, NUDOCS 9806250006
Download: ML20249B893 (1)


Text

(W NN jy Q g

PRELIMINARY NOTIFICATION September 17, 1976 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-76-157 D

This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance. The information Presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

Facility:

Commonwealth Edison Company, Dresden 2 (DN 50-237)

Morris, Illinois

Subject:

UNPLANNED LOW LEVEL LIQUID RADIOACTIVITY RELEASE Commonwealth Edison Company notified IE:III (Glen Ellyn) on September 16, 1976, that a leak had been discovered in the HPCI test return line to the condensate storage tank. The contaminated water drained to an outside storm sewer which discharges into the reactor cooling pond and the~n into the Illinois River. The line was isolated. A sample of the sewer water l

was obtained and measured 2 x 10-6 uCi/ml. Following dilution with approximately 500,000 gpm, calculated activity discharged to the Illinois River was estimated to be 2 x 10-11 uCi/ml a value considerably lower than the Technical Specification limit (1 x ION uCi/ml). Line repair is in progress.

While the release does not represent a safety problem, this notification is issued based on a recent general interest exhibited by the Illinois Commerce Commission in the releases of radioactivity by Commonwealth Edison nuclear power plants.

The State ot Illinois has been notified. Neither the utility nor the NRC plan to make a press release.

Region III (Glen Ellyn) received notification of this occurrence by h

telephone from Commonwealth Edison Company at approximately 3:30 p.m.

/

on September 16, 1976.

Contact:

RFWarnick, IE x27261

GWRoy, IE x27261 DThompson, IE x27541 0,

Distribution:

Chairman Rowden Commissioner Mason S. J. Chilk, SECY Commissioner Gilinsky C. C. Kammerer, CA G. F. Murphy, JCAE Commissioner Kennedy L. V. Gossick, EDO E. Volgenau, OIE J. A. Harris, PA B. C. Rusche, NRR H. K. Shapar, ELD T. J. McTiernan, AIA K. R. Chapman, NMSS R. G. Ryan, OSP Transmitted: PBldg H St

MNBB Luge PRELIMINARY NOTIFICATION

,no 9806250006 760917 PDR 18cE PNO-76-157 PDR