ML24229A104

From kanterella
Jump to navigation Jump to search
Integrated Inspection Report 05000382/2023004, Disputed Non-Cited Violation Revised
ML24229A104
Person / Time
Site: Waterford Entergy icon.png
Issue date: 09/25/2024
From: Geoffrey Miller
NRC/RGN-IV/DORS
To: Sullivan J
Entergy Operations
References
EA-24-030, IR 2023004
Download: ML24229A104 (1)


See also: IR 05000382/2023004

Text

September 25, 2024

EA-24-030

Joseph Sullivan, Site Vice President

Entergy Operations, Inc.

17265 River Road

Killona, LA 70057

SUBJECT: WATERFORD STEAM ELECTRIC STATION, UNIT 3 - INTEGRATED

INSPECTION REPORT 05000382/2023004, DISPUTED NON-CITED

VIOLATION REVISED

Dear Joseph Sullivan:

On February 12, 2024, the U.S. Nuclear Regulatory Commission (NRC) issued the subject

inspection report, Agencywide Documents Access and Management System (ADAMS)

Accession No. ML24039A199. The inspection report documented a non-cited violation (NCV)

for the failure to maintain mitigation strategies for beyond-design basis external events as a

result of the failure to ensure that the starting batteries had sufficient capacity for the FLEX

(Diverse and Flexible Mitigation Capability) N and N+1 diesel generators to perform their

required functions, NCV 05000382/2023004-03.

In a letter dated March 11, 2024 (ML24071A185), you provided your written response and

contested NCV 05000382/2023004-03. On March 15, 2024 (ML24074A374), the NRC

acknowledged receipt of your letter.

The NRC conducted a detailed review of your March 11, 2024, letter and examined

circumstances and applicable regulatory requirements in accordance with Part I, Section 2.8 of

the NRC Enforcement Manual. The review included staff who were not involved in the original

inspection effort. The details of the NRCs evaluation are contained in the enclosure.

After consideration of the basis for your dispute of the NCV, the NRC concluded that the original

NCV remained valid. However, the staff revised the NCV to enhance its clarity and modified the

dates of noncompliance. The revised language for the NCV is provided in the enclosure. The

NRC will reissue Inspection Report 05000382/2023004 to document the revised NCV.

In addition, during the review of the issue, the NRC determined that the performance deficiency

needed enhancement. The revised language for the performance deficiency is provided in the

enclosure. The NRC also determined that when evaluating the significance of the finding, a

detailed risk evaluation was required. A Senior Reactor Analyst performed the detailed risk

evaluation and determined the overall risk significance of the finding was of very low safety

significance (Green). The revised language of the performance deficiency and the detailed risk

evaluation will also be included in the reissued inspection report.

J. Sullivan 2

In accordance with 10 CFR 2.390 of the NRCs Agency Rules of Practice and Procedure, a

copy of this letter and its enclosure will be made available electronically for public inspection in

the NRC Public Document Room and from the NRCs ADAMS, accessible from the NRC

website at http://www.nrc.gov/reading-rm/adams.html.

Should you have any questions concerning this letter, please contact John Dixon of my staff

at 817-200-1574.

Sincerely,

Geoffrey B. Miller, Director

Division of Operating Reactor Safety

Docket No. 05000382

License No. NPF-38

Enclosure:

NRC Evaluation of Licensee Response

to an NCV

Signed by Miller, Geoffrey

on 09/25/24

ML24229A104

SUNSI Review: ADAMS: Non-Publicly Available Non-Sensitive Keyword:

By: JGK Yes No Publicly Available Sensitive NRC-002

OFFICE SES:ACES RI:DORS:EB2 TL:ACES C:DORS:PBD C:DORS:EB2

NAME JKramer ASaunders BAlferink JDixon NTaylor

SIGNATURE /RA/ E /RA/ E /RA/ E /RA/ E /RA/ E

DATE 08/20/24 08/19/24 08/19/24 08/16/24 08/19/24

OFFICE RC OE OGC D:DORS

NAME DCylkowski DJones KGamin GMiller

SIGNATURE /RA/ E /RA/ E /NLO/ E /RA/ E

DATE 08/19/24 09/23/24 09/25/24 09/25/24

NRC Evaluation of Licensee Response to a Non-cited Violation (NCV)

Background:

On February 12, 2024, the U.S. Nuclear Regulatory Commission (NRC) issued Integrated

Inspection Report 05000382/2023004 that included an NCV of Title 10 of the Code of

Federal Regulations (10 CFR) 50.155(b)(1) (NCV 05000382/2023004-03) to Entergy

Operations, Inc. (Entergy or licensee). In a letter dated March 11, 2024, Entergy denied

NCV 05000382/2023004-03 and provided its position that Waterford Steam Electric Station,

Unit 3 (Waterford) complied with regulatory requirements for ensuring the Diverse and Flexible

Mitigation Capability (FLEX) diesel generators had sufficient capacity to perform their design

function.

The NRC staff performed an independent review of the licensees position as described in its

March 11, 2024, letter. The NRC staff reviewed regulatory requirements in 10 CFR 50.155, the

Waterford Final Integrated Plan (FIP), the Waterford Technical Requirements Manual, battery

vendor manuals, FLEX diesel generator vendor manuals, Electric Power Research Institute

(EPRI) FLEX Operating Experience Bulletins (OEBs)21-001 and 21-002, EPRI Preventative

Maintenance Basis for FLEX (PMBD), Waterford Flood Hazards Mitigation Strategies

Assessment, Regulatory Guide 1.226 Flexible Mitigation Strategies for Beyond-Design-Basis

Events (ML19058A012), Nuclear Energy Institute (NEI) 20-10 Mitigation of Beyond Design

Basis Events Program Description Template, Waterford Staffing Analysis during a FLEX event,

and NRC Inspection Report 05000382/2017009 related to FLEX compliance at Waterford,

including a Notice of Violation, issued on July 20, 2018.

Additionally, the staff interviewed Region IV and Office of Nuclear Reactor Regulation (NRR)

subject matter experts familiar with FLEX equipment requirements and regulations to gain a

valuable perspective on the development and evaluation of Waterfords strategies.

Topical Areas Discussed in Licensees Denial and NRC Evaluation

Topic 1: Operating Experience for FLEX Diesel Starting Battery Failures

The reviewer conducted a search for industry-facing documents related to starting battery

failures that impacted FLEX equipment reliability, including a review of NRC inspection

results.

EPRI OEB 21-001 Starting Batteries / Battery Chargers provided guidance on an

increasing trend in failure of FLEX starting batteries. It also provided a list of best practices

in maintenance and testing of FLEX equipment battery systems, including actions such as

the use of a battery tester to perform diagnostic checks of batteries and guidance for jump

starting machines with dead batteries in station procedures.

EPRI OEB 21-002 FLEX Equipment Functionality Assessments Related to Battery Failure

provided information on what to consider in functionality assessments of supported FLEX

equipment if starting batteries are found in FLEX equipment. The document addressed

whether there is alternate means of starting the supported piece of FLEX equipment and

whether there is sufficient time to perform the recovery actions.

Enclosure

Additionally, the staff noted that there have been several other similar enforcement actions

in recent years, including two nearly identical NCVs:

Consistent with NRC Order EA-12-049 for failure to implement a battery replacement

strategy, leading to a FLEX diesel generator failure to start.

the licensees failure to maintain the starting batteries for the steam generator fill pumps.

The staff noted that Waterford reviewed the South Texas Project FLEX battery failures in

WT-WTHQN-2021-00498-00005 which concluded that the preventative maintenance (PM)

program was adequate, resulting in no corrective actions. The staff determined that this was

a missed opportunity for the licensee to recognize that its maintenance practices were

inadequate and did not meet the guidance in OEB 21-001.

Topic 2: Importance of Batteries in FLEX Diesel Generators

Licensees Contention:

The licensee asserted that batteries are considered FLEX-support equipment and are not

subject to the requirements of the Order EA-12-049 (now codified in 10 CFR 50.155) as

equipment necessary to support the Phase 2 strategies. The licensee further asserted that

the EPRI PMBD for FLEX equipment templates refers to batteries and battery chargers as

supporting equipment, and it is widely recognized that the expectation to maintain the

equipment to meet the FLEX strategies was the intended target of the EPRI FLEX PM

template.

Furthermore, the licensee asserted that since the industry-wide implementation of

NEI 12-06, it has been widely discussed throughout the industry that an occurrence of a

non-start of a FLEX diesel generator due to battery failure does not constitute a failure of

that equipment to perform its function.

NRC Evaluation:

The staff reviewed the NRC-endorsed EPRI PMBD documentation, which clearly details that

diesel generator batteries are an integral component of the FLEX diesel generator. The

document also details the batteries as a common failure cause in diesel engines. The staff

also reviewed the Waterford Steam Electric Station, Unit 3, Final Integrated Plan, revision 1,

dated July 20, 2016. The Final Integrated Plan states at Section 2.19.6 that [m]aintenance

and testing of FLEX equipment is governed by the Entergy Preventive Maintenance (PM)

Program as described in EN-DC-324. The Entergy PM Program is consistent with INPO

AP-913 and utilizes the EPRI Preventive Maintenance Basis Database as an input in

development of fleet specific Entergy PM Basis Templates. The staff reviewed Waterfords

PM basis document for FLEX diesel generators 1000 KW and below, which clearly states

that batteries are considered a component of the FLEX diesel generator, contrary to the

statement provided in the licensees letter. The staff reviewed the online version of the

PMBD and determined that FLEX batteries being detailed solely as FLEX support

equipment was not supported by the online database.

2

Additionally, the staff interviewed several subject matter experts who were involved in the

formative discussions of the FLEX policy documents (including staff from Region IV and

multiple former Japan Lessons Learned Project Directorate staff members in NRR), and

none recalled any conclusion being reached that starting batteries for FLEX equipment

would be treated as FLEX support equipment.

Regarding the failures of the starting batteries, the staff reviewed the FIP and determined

that the primary design function for N and N+1 diesel generator is to provide 480 V AC

power to recharge the safety related DC batteries and provide AC power for various FLEX

equipment. As described in the issued violation, the minimum capacity of the batteries on

the N and N+1 diesels were not ensured. This directly affected the function of the FLEX

diesels to provide AC power in the documented timeline. The staff reviewed EPRI PMBD

and the licensees PM template, both of which include diesel generator starting batteries as

integral components of the diesel. The diesel generator would not be able to perform its

design function without the batteries. As stated below, the staff did not view any of the other

batteries described by the licensee as being available options during a FLEX event, nor did

the staff agree that replacing these batteries with anything other than a like-for-like spare

would be a skill-of-the-craft activity.

Additionally, the licensees contention is not consistent with industry guidance, including

OEB 21-001, which states a failure of a starting battery could impact the capability to

perform a mitigating strategy.

The licensee referenced OEB 21-002 in asserting that a supported piece of FLEX

equipment need not be considered non-functional based on a starting battery failure, if the

following conditions are met for declaring the supported piece of FLEX equipment functional

but degraded:

  • An alternate means of starting the supported piece of FLEX equipment is available

(e.g., jumper cables, spare batteries).

  • There is sufficient time to perform the recovery actions to start the supported FLEX

equipment within the time allotted.

The NRC staff determined that neither of the conditions in OEB 21-002 would be met if a

flood, tornado, tornado missile, or hurricane impacted the N+1 building such that it was

inaccessible.

The staff found no evidence in the review of the formative FLEX guidance documents to

support the licensees position on FLEX diesel functionality without starting batteries. While

the staff agrees that the function of the diesel generator assembly is to provide AC power,

the diesel engine must be started (providing relative motion to the generator field) and that

action requires functional batteries.

3

Topic 3: Whether Replacing FLEX Diesel Starting Batteries is a Skill of the Craft

Activity

Licensees Contention:

The licensee asserted that with the diverse and flexible solutions offered in the FLEX

procedures, the ability to jump, swap, or replace a battery immediately is within the design of

the FIP for FLEX implementation, is considered skill of the craft, and does not need to be

part of a procedure.

NRC Evaluation:

The staff reviewed the licensees skill of the craft position and determined that the

replacing of a like for like battery is very well within the skill of the craft. However, if the

batteries are of different configurations the following could be affected: connections, cable

length, and starting amperage. The staff reviewed photos provided by the licensee of the

battery configurations on the N, N+1, FLEX water transfer pump (FWTP) and air compressor

diesels. The N and N+1 diesels each use a pair of large 8D type batteries with both

terminals on one end, connected in series to make a 24-volt starting circuit. The reviewer

noted that the cables connecting the batteries appear to have little or no slack. By contrast,

the FWTP and air compressor each have a single 12-volt battery and are smaller batteries

with terminals on either end. Both of these smaller batteries would have to be used to create

the needed 24-volt circuit and would likely require a new cable to be configured in the field

to connect them together.

The staff interviewed the Waterford Emergency Preparedness manager who was a Senior

Reactor Operator (SRO) at Waterford when the strategies were developed, who described

the manner in which Waterford would implement the battery replacement strategy if the

batteries on the N diesel were found dead. The former SRO stated he would immediately

direct the operators to scavenge the batteries from either the FWTP or the station black out

air compressor without first attempting to troubleshoot or to start the N+1 diesel generator

(contrary to the FIP). This misstatement highlights the importance of having written

procedures governing the conduct of FLEX strategies, as valuable time in the FLEX timeline

would be lost in the effort to start the N diesel using a single 12-volt battery.

The staff emphasizes that the need for procedures is extremely important due to operations

making mistakes when a viable path, such as the N+1 diesel, might be present. The staff

also noted that there are no recovery actions within the licensees procedures to restore the

cannibalized batteries for the FWTP and station blackout air compressor which are needed

later in the FLEX timeline. The staff also noted that OEB 21-001 recommends as a best

practice to include instructions for jump starting engines in the equipment operating

procedures, which the licensee has not implemented.

The staff determined that replacing the N or N+1 batteries with the smaller batteries from the

FWTP and air compressor should not be viewed as a skill of the craft activity for the auxiliary

operators. Time spent by auxiliary operators learning how to connect smaller batteries and

building new cables in the field would have an adverse effect on the FLEX timeline, as

discussed later in this evaluation.

4

Topic 4: Spare Battery Availability During a Beyond-Design-Basis External Event

Licensees Contention:

The licensee stated that it is important to note that the FLEX equipment necessary to

mitigate the beyond design basis external event was still functional. The licensee noted that

the inspection report stated that Because there was a set of ready spare batteries that

would be able to be changed out in an actual event, the function of the FLEX AC power

supply was not considered fully lost. All FLEX functions could still be completed within the

time allotted.

NRC Evaluation:

The staff considered this position and noted that the assumptions in the FIP state, in part,

that other equipment, such as portable AC power sources, portable back-up DC power

supplies, spare batteries, and equipment for 10 CFR 50.54(hh)(2), may be used provided it

is reasonably protected from the applicable external hazards and has predetermined

hookup strategies with appropriate procedural guidance and the equipment is stored

in a relative close vicinity of the site [emphasis added]. The staff noted that the licensee

did not have procedures for changing out the batteries, and the N+1 building is only

designed as per ASCE 7-10 Minimum Design Loads for Buildings and Other Structures,

standard and is not designed to withstand all environmental conditions as detailed in the

Updated Safety Analysis Report (flood, extreme winds, hurricane, seismic).

Furthermore, the staff reviewed the previously issued NOV 05000382/2017009-01 which

took exception with the licensees failure to create procedural guidance to protect the N+1

diesel from the effects of postulated events. In order to consider the spare batteries as

available for the strategy, the spare batteries from the N+1 building must also be protected

from these events. Therefore, the staff was not able to credit this position.

Topic 5: Maintenance of the Flex Diesel Batteries

Licensees Contention:

The licensee asserted the diesel generators are appropriately tested and maintained to

ensure their function.

NRC Evaluation

OEB 21-001 was specifically issued to address inadequate maintenance practices on FLEX

batteries. It states, in part, that FLEX equipment starting batteries and battery charger

related events have been the most common equipment operating experience (OE) entries

shared in the EPRI FLEX Equipment Maintenance Event Collaboration Site. The document

specifically calls out capacity of the batteries as a concern that should result in regular

capacity testing. In addition, OEB 21-001 referenced EPRI 3002012818, Insights from the

FLEX Preventative Working Group which provided additional guidance for the storage,

maintenance and periodic replacement of FLEX batteries.

5

On April 18, 2023, the licensee performed maintenance work orders on the FLEX N and

FLEX N+1 diesel generators. These inspections included ensuring that the supporting

batteries for the FLEX equipment had clean tops, tight connections and measured the

output voltage on the connected battery charger as a measure of battery health. The

licensee stated it is appropriate to consider these work orders to be failure detection

activities. Both diesels were found in a failed state a month later despite the licensees

satisfactory completion of these failure detection activities. The licensee PM process failed

to identify that the batteries on the N FLEX diesel did not have the required starting capacity.

The staff noted that the licensees practice of measuring terminal voltage on the battery with

the charger connected provides no information about the state of charge or capacity of the

battery, contrary to the recommendations of OEB 21-001. The inadequacy of this approach

was demonstrated by the failure of the N diesel in May 2023, which had adequate terminal

voltage until the operators attempted to start the diesel and the battery voltage dropped

immediately.

The staff reviewed testing of the diesel generator batteries and found that the licensee was

not performing battery capacity testing to ensure the minimum capacity was maintained for

the batteries. The staff noted that in the issued report, the resident inspectors included an

observation of multiple failures of other batteries in different systems onsite, suggesting a

larger adverse trend at the station in the way that flooded lead acid batteries are being

maintained.

The maintenance that was performed on the batteries just weeks before did not ensure the

batteries would perform their function of starting the diesel generator. Therefore, the staff

was not able to credit the licensees position that starting batteries on the FLEX diesel

generators were being properly maintained.

Topic 6: Impact of Battery Swaps on the FLEX Timeline

Licensees Contention:

The licensee described that the equipment necessary to perform the required FLEX function

(that of the diesel generator) was not compromised. The ability to start the diesel generator

was degraded, but the functionality of the diesel generator was not in question and met the

required timeline.

NRC Evaluation

The licensees FIP states, in part, that the site has 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to get the FLEX diesel operating

before failure of the safety related batteries. In support of this overall strategy, the licensee

established a timeline of actions for each operator in procedure CIN-2016-00017,

Waterford 3 Steam Electric Station Phase 2 Staffing Assessment, Revision 1. The

following table shows a subset of the time-critical actions required to accomplish this

strategy. Actions that are specifically related to restoring AC power from the N or N+1

diesels are highlighted in green.

6

The reviewer noted that AO#3 is tasked with setting up the FLEX diesel, but a start attempt

of the N diesel does not occur until AO#1 begins that process 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> into the event. AO#1

then has 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> of control room supervisor support time assigned due to the importance of

establishing AC power to the overall strategy. The reviewers assume that the initial starting

attempt for the N diesel occurs at approximately 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> into the event.

Based on the NRCs position in the safety evaluation for FLEX, and as documented in NOV

05000382/2017009-01, the spare equipment outside of the nuclear plant island structure

(NPIS) cannot be credited during a flood, levee failure, tornado missile, localized intense

precipitation, or hurricane (extreme conditions) due to the building/haul path being

inaccessible. The licensees FIP requires that the credited N+1 equipment be moved into the

NPIS prior to foreseeable external events.

The staff determined as per procedure CIN-2016-00017, the N diesel is discovered to be

non-functional approximately 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> into the recovery. The licensee would have to start

troubleshooting the N diesel, determine the problem, or move on to the N+1 diesel which

should be pre-staged for foreseeable external events. In the case of some external events,

the operators would have to move the N+1 diesel to the NPIS at this time. There are no

procedural steps to test the N+1 before moving it to make sure it functions properly. Setting

up the N+1 diesel requires re-entering the procedural attachment (rerouting cables,

realigning 480 VAC circuit breakers, etc.) which is a three-hour activity in the timeline. Once

the operators finish aligning the N+1 diesel and discover that it also has failed starting

batteries, the operators would then be forced to consider other sources of starting power for

either the N or N+1 diesel. The last effort for the licensee is to pull batteries from other FLEX

equipment without written procedures as to which equipment to scavenge, how to hook up

batteries with different terminal configurations, or how to assemble the cables which might

be required to do so. The lack of procedural guidance significantly challenges the remaining

time left in the FIP strategy after the N and N+1 diesels are discovered to be in a failed

state. Furthermore, the licensees FLEX strategies are silent on where the operators would

obtain batteries to restore the function of the FWTP and FLEX air compressor when they are

needed later in the FLEX timeline.

7

Based on a review of the actions that would be required to recover from the failure of the

starting batteries of both the N and N+1 diesels, and the uncertain outcomes and timing of

actions to connect off-schedule batteries from other equipment, the NRC staff concluded

that the licensees strategy to restore AC power to a safety bus within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after a

beyond design basis event was unlikely to be successful.

Revised NCV 05000382/2023004-03 and Revised Performance Deficiency

As a result of the evaluation above, the NRC will revise the NCV to enhance its clarity and

modify the dates of noncompliance to begin with the effective date of 10 CFR 50.155 and end

with the date on which the noncompliance was corrected, and will revise the performance

deficiency as follows:

Revised NCV 05000382/2023004-03

Title 10 CFR 50.155(b)(1), states, in part, strategies and guidelines to mitigate beyond-

design-basis events from natural phenomena must be capable of being implemented site-

wide and must include maintaining or restoring core cooling capabilities.

The licensee established Waterford Steam Electric Station, Unit 3, Final Integrated Plan,

revision 1, dated July 20, 2016, to meet the requirements of NRC Order EA-12-049. This

order was codified and made generically applicable by 10 CFR 50.155, on September 9,

2019 (84 FR 39684). Section 2.19.6, Equipment Maintenance and Testing, of the Final

Integrated Plan describes, in part, the licensees actions for complying with 10 CFR 50.155

for maintenance and testing of the FLEX equipment. This includes maintenance and testing

of the starting batteries for the FLEX N and N+1 diesel generators to ensure sufficient

capacity to perform their required functions.

Contrary to the above, from September 9, 2019, to May 16, 2023, the licensee failed to

maintain mitigation strategies for beyond-design basis external events. Specifically, the

licensee failed to maintain mitigation strategies for beyond-design basis external events

because the preventive maintenance program, section 2.19.6, Equipment Maintenance and

Testing, of the Final Integrated Plan, which describes the licensees actions for complying

with 10 CFR 50.155, failed to ensure that the starting batteries had sufficient capacity for the

FLEX N and N+1 diesel generators to perform their required functions.

Revised Performance Deficiency

The licensee failed to maintain mitigation strategies for beyond-design-basis external events

because the preventive maintenance program, section 2.19.6, Equipment Maintenance and

Testing, of the Final Integrated Plan, which describes the licensees actions for complying

with 10 CFR 50.155, failed to ensure that the starting batteries had sufficient capacity for the

FLEX N and N+1 diesel generators to perform their required functions.

8