PNO-IV-89-025, on 890406,util Declared Notification of Unusual Event at Facility Due to One Inoperable Diesel Generator.Util Declared Diesel Generator 12 Operable After Replacing Defective Resistor in Governor Control Circuit

From kanterella
(Redirected from ML20248J811)
Jump to navigation Jump to search
PNO-IV-89-025:on 890406,util Declared Notification of Unusual Event at Facility Due to One Inoperable Diesel Generator.Util Declared Diesel Generator 12 Operable After Replacing Defective Resistor in Governor Control Circuit
ML20248J811
Person / Time
Site: South Texas STP Nuclear Operating Company icon.png
Issue date: 04/06/1989
From: Holler E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
References
PNO-IV-89-025, PNO-IV-89-25, NUDOCS 8904170070
Download: ML20248J811 (2)


-____ __ ._

j[ . - April 6, 1989 PRELIMINARY NOTIFICATION-0F EVENT OR UNUSUAL OCCURRENCE -- PN0-IV-89-25 This preliminary notificatica constitutes EARLY notice of events of POSSIBLE safety or public interest significance. The information is as initially received

- without verification or evaluation, and is basically all that is- known by the Region IV staff on this date.  ;

FACILITY: Houston Lighting & Power Company Licensee Emergency Classification:

South Texas Project, Unit 1 X Notification of Unusual Event

-Docket: 50-498 Alert Site Area Emergency ,

General Emergency  !

Not Applicable

SUBJECT:

NOTIFICATION OF UNUSUAL EVENT (N0VE)

At approximately 8:30 a.m. (CDT), April 6,1989, Houston Lighting & Power l Company (HL&P) declared a NOVE at South Texas Project (STP), Unit 1, because of a Technical Specification (TS) Limiting Condition for Operation (LCO) requiring reactor shutdown. Prior to the NOVE, STP, Unit 1, was o l reactor power with the No.11 ESF diesel generatorinoperable (DG) perating atof94 percent because j planned maintenance. With one DG inoperable, TS 3.8.1.1 requires testing of the i remaining two DGs within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. DG No. 13 tested satisfactory. At approximately 5:54 a.m. , DG No.12 failed its required operability test. ,

TS 3.8.1.1 requires that with 2 or 3 of the DGs inoperable, at least 2 DGs must i be restored to operable status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or the plant must be in hot standby (Mode 3) within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown (Mode 5) within the '

following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. STP, Unit 1, commenced a power reduction at 8:38 a.m.

At approximately' 11i46 a.m. (CDT), with STP, Unit 1, at 40 percent reactor power, the No.11 DG was declared operable after successful completion of its postmaintenance test run. At 7:50 p.m. (CDT), HL&P declared the No. 12 DG operable after replacing a defective resistor in the DG governor control circuit and terminated the NOVE.

Neither the licensee nor the NRC plans to issue a press release.

The state of Texas will be informed.

Region IV received notification of this occurrence by telephone from Region IV inspector onsite at 9 a.m. and from the H00 at 8:35 p.m. Region IV has informed EDO, NRR, and PA.

This information has been confirmed with a licensee representative.

l CONTACT: E. J. Holler, FTS 728-8287 4

C:DRP/D l D:DRP [

RDPiart a EJHoller:cs LJCallan 4/7/89 4/7/89 4/7/89 yy

/g 8904170070 89040A / Ok PDR 18cE PNO-IV-89-025 PNV

- _ _ _ _ _ - _ _ _ _ _ __ ]

. D4STRI5UTION:

l. OWFN NMBB NL MAIL: DCS (Orig. IE34)

Chmn. Zech SECY NMSS XEDTI RES DOT (Transp.Only)

{

t Comm. Robrrts CA NRR ARM Comm. Carr OGC OIA OGC FAX: (5520: 89 0 # Y Comm. Rogers GPA OI TTP0 egions & HQ)

Conn. Curtiss PA SLITP H-St PDR ACRS ED0 OE PDR NSAC RRI NRC Ops Ctr Licensee (Reactor) i DISTRIBUTION: ]

NRCRES, RESPN Research (Paula Dorm)  !

NRCRM, AE0D AE00 (Patty Wilson) i NRCRM, BROWN ARM (Karen Brown) l NRCRMP, 0IADW Inspector & Auditor (Displaywriter/PC)

NRCRMP, 0IDW Investigations (Displaywriter/PC) i 1NRC02, OPAPN GPA:Public Affairs (Glady Ordaz)

INRC0304, SLIPN GPA: State / Local Indian Tribes Program (Brenda Hill) 1NRC0304, NMSSPN Nuclear Material Safety & Safeguards (Pat Graaf) 1NRC0506, NMSSPN Nuclear Material Safety & Safeguards (Cathy Jenkins) i 1F' 708, OEPN Enforcement (Betty Summers) ,

INRC1112, NRRPN NuclearReactorRegulation(DonnaBerean) l 1NRC1516, 0GCPN General Counsel (Edna Downs) l INRC1718, ZECHPN Chairman (Lois Altoft)

INRC1718, ED0PN Executive Director for Operations (Doris Day) .

1NRC1718, OCAPN GPA: Congressional Affairs (Janice Hester) }

hRCRI, RIPN Region I NRCRII, RIIPN Region II NRCRIII RIIIPN Region III NRCRTV, RIVPN Region IV ,

NRCRV, RVPN Region V 1

f

- _ - _ _ _ _ _ _ _ _ _ _ _