ML20149E960

From kanterella
Jump to navigation Jump to search
Ack Receipt of Informing NRC of Steps Taken to Address Open Items 266/87007-06 & 301/87007-06 Discussed in Insp Repts 50-266/87-07 & 50-301/87-07
ML20149E960
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 02/05/1988
From: Harrison J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Fay C
WISCONSIN ELECTRIC POWER CO.
References
NUDOCS 8802110327
Download: ML20149E960 (1)


See also: IR 05000266/1987007

Text

_ _ _ _ _ _ _ _ _

,

l

...

j

c

i

FEB 5 1988

Docket.No. 50-266

Docket No. 50-301

. Wisconsin Electric-Power Company

ATTN: Mr. C. W.-Fay

j

Vice President

"

Nuclear Power Department

,

231 West Michigan, Room 308

Milwaukee, WI 53201

Gentlemen:

Thank you for your letter dated January 13, 1988, informing us of the steps

you have taken to address Open Item (266/87007-06; 301/87007-06) which was

discussed in our report 50-266/87007; 50-301/87007, dated July 7, 1987.

We have reviewed your submittal and have no questions at this time. This item

will be further reviewed during a future inspection at your facility.

Sincerely,

i

gc,,1 Sig,d 17 U. U* IDI

~

J. J. Harrison, Chief

Engineering Branch

cc:

J. J. Zach, Plant Manager

cc w/ltr dtd 1/13/88:

DCD/DCB (RIDS)

Licensing Fee Management Branch

,

Resident Inspector, RIII

i

Virgil Kanable, Chief

Boiler Section

Charles Thompson, Chairman

1

Wisconsin Public Service

Comission

R. I. Braund (SLO),

WI Div of Emergency Government

Lawrence J. McDonnell, Chief

Radiation Protection Section

l

WI Department of Health and

Social Services, Division

of Health

IIg

III

R

mes/j(

Gardier

rison

02/04/88

02/Cr/88

02/05/88

i

8802110327 080205

PDR

ADOCK 05000266

i

g {} l

G

PDR

3 -

.

_ _ _ _

,

1

-

,

'

.

Wisconsin Electnc ma cwmr

231 W MICHIGAN,P.o BOX 2046, MILWAUKEE.W153201

(414)2M 2345

.

VPNPD-88-022

NRC-88-003

l

January 13, 1988

'

U. S. NUCLEAR REGULATORY COMMISSION

Document Control Desk

Washington, D.

C.

205ss

Gentlemen:

h

DOCKETS 50-266 AND 50-301

TECHNICAL EVALUATION OF FIRE DAMPER TESTS

POINT BEACH NUCLEAR PLANTS, UNITS 1 AND 2

In response to Inspection Report 50-266/87007(DRS);

50-301-87007(DRS), which we received with your letter dated

July 7, 1987, we are providing our Technical Evaluation of Fire

Damper Tests at Point Beach Nuclear Plant.

During development of the Technical Evaluation, we determined

that a damper closure verification test would be required.

Preparation of a test procedure and scheduling of the test so

as not to interfere with the Fall 1987 outage manpower

requirements delayed our verification of the Technical

Evaluation and submittal for Region III review.

We believe that our submittal of the enclosed Technical

Evaluation fulfills our commitment for open item

(266/87007-06;301/87007-06), Paragraph 3.e of the Inspection

Report.

Please contact us if you have any questions regarding this

submittal.

,

I

Very truly

ours,

l

860h%

l

C. W.

Fay

I

Vice President

,

l

Nuclear Power

Attachments

Copies to NRC Resident Inspector

NRC Regional Administrator - Region III

'JAN 191988

h ; C ! M O W M jPt

'

e

(

.

4

i.

TECHNICAL EVALUATION

OF

FIRE DAMPER TESTS

AT

POINT BEACH NUCLEAR PLANT

-

1.0 INTRODUCTION

During routine safety inspections between February 23 and June 26, 1987,

the inspector requested that the licensee provide justification regarding

the test methodology utilized to demonstrate that fire dampers will close

.

under normal air flow.

Provision of the requested justification was

identified as open item 266/87007-06; 301/87007-06 in the July 7, 1987

.

inspection report.

This Technical Evaluation is prepared in response to

the inspector's request.

S

2.0 PURPOSE

.

The purpose of this evaluation is to demonstrate that the methodology

I

'

used to test fire damper closure under normal air flow provides adequate

assurance that the dampers will function as required to maintain fire

barrier integrity.

l

I

t

3.0 SCOPE

N

'

4

,

,

I

The PBNP Fire Damper Summary is a list of fire dampers which are located

in the boundaries of fire areas containing Appendix R safe shutdown

i

components.

This evaluation covers fire dampers which are identified in

.

\\

the summary as' having been tested under normal air flow conditions.

The

,'

"

summary is attached as Table FD-1.

.

4.0 BASIS

In a previous evaluation we determined that it was not practical to

expect large multisection dampers to close against normal air flow.

Multisection dampers have been tested statically and a Standing Order

has been issued for PBNP operators to shut down ventilation for the

affected zone if a fire is detected in fire zones separated by such

dampers.

The Fire Damper Test Guidelines dated 03-04-86 were used to test fire

dampers under normal air flow. The guidelines are intended to be

generic and do not describe a standard test configuration with specific

dimensional tolerances.

However, we believe that a sufficient quantity

of dampers were tested in a conservative air flow configuration to

demonstrate that the dampers will operate as intended.

l

A fire damper is tested one time under normal air flow conditions for

design verification.

The initial normal air flow test was conducted on

dampers which have been in service between 0 and 17 years without any

noticed effect from aging.

Ten percent of the fire dampers listed in

Table FD-1 will be tested statically every 18 months to provide continued

damper operability.

Should more than 15% of the dampers tested fail to

close, an additional 10% of the listed dampers shall be tested until the

quantity of failed dampers is less than 15% of the quantity tested.

An

a

engineering review shall also be conducted to evaluate the reasons for

!

damper failure.

.

.

t

.

i

'

5.0 EVALUATION

-

5.1 Installed Configurations

The relative location of components in a ventilation system can

affect the outcome of fire damper testing. The components to be

considered are the fan, fire damper, inspection port and ventila-

tion grill.

By reviewing fire dampers installed at PBNP, we have

determined that seven types of installed configurations exist.

These configurations are shown on Figure FD-1.

5.2 Flow Characteristics

We have evaluated the flow characteristics for each fire damper

which is expected to close under normal air flow conditions. These

characteristics are listed in Table FD-2.

Since pressure drop across

the damper has the major effect on damper closure capability, we

conclude that if a damper of a given configuration has been success-

fully tested at a specific pressure drop, all dampers of the same

configuration which are subject to the same or lesser pressure drops

will also be operable under normal air flow conditions.

5.3 Other Effects

Several fire dampers have been functionally tested as part of Halon

fire suppression system discharge testing. This testing provides

,

added assurance that these dampers will function as designed. Where

.

I

,

b

.

.

a damper which is expected to c1Cse against normal air flow is in-

stalled in a branch parallel to a multi section damper located in the

-

I

same fire zone, the damper will operate because the fan which is

i

common to both dampers will be shutdown.

.

These effects are also identified in Table FD-2.

.

5.4 Figure FD-1 Evaluation

a) Detail (a) depicts fire dampert which are located in the fire

barrier without connecting ductwork. This configuration can be

'

tested from either side of the fire barrier without affecting air

,

flow through the damper.

Therefore we concluded that dampers

which are installed in accordance with Detail (a) and which have

been tested under normal air flow conditions are operable.

b) Detail (b) depicts fire dampers which are located in one branch

of a multibranch duct system. These fire dampers and fire dampers

which are installed in the other branches are not exposed to a

.

common fire area.

Therefore, during damper closure an air flow

i

,

i

path alternate to the affected damper is assured.

During a test

an open inspection port would increase air flow through the damper

i

'

in a conservative manner.

A successful test under this condition

l

t

demonstrates damper operability.

Reaching into the duct to

actuate or observe damper closure would obstruct flow in a noncon-

servative sanner.

For this condition, flow would increase through

the alternate branch just as it would for damper closure under

,

normal air flow conditions and the effect on the total ventilation

!

I

"

i

, . -

,

system performance would be negligible. Therefore, we concluded

that dampers which are installed in accordance with Detail (b) are

,

tested equivalent to normal air flow conditions and are operable.

Demper qualification by pressure drop exposure is not applicable

to Detail (b) configurations,

c) Detail (c) depicts fire dampers which are located in one branch

of a multibranch duct system. These fire dampers and fire dampers

which are installed in the other branches are not exposed to a

common fire area.

Therefore during damper closure an air flow

path alternate to the affected damper is assured. During a test

an open inspe,ction port would increase air flow through the damper

in a conservative manner.

A successful test under this condition

demonstrates damper operability Reaching into the duct to actuate

or observe damper closure would obstruct flow in a nonconservative

manner.

For this condition, flow would increase through the

alternate branch just as it would for damper closure under normal

air flow conditions and the effect on the total ventilation system

i

performance would be negligible.

Therefore, we conclude that

dampers which are installed in accordance with Detail (c) are

tested equivalent to normal air flow conditions and are operable.

Damper qualification by pressure drop exposure is not applicable

to Detail (c) configurations.

d) Detail (d) depicts fire dampers which arr 'ocated downstream of

all ventilation openings and inspectic* t

During a test an

.

,

open inspection port would increase

riU

chrough the damper

I

in a conservative manner.

A successt

ta:: under this condition

!

'

,

c

-

..

'

.

demonstrates damper operability. ReacPing into the duct to

.

l

actuate or observe damper closure would obstruct flow in a noncon-

servative manner. The s.'res of the duct, inspection port and

obstruction are variables which determine the conservatism of air

flow during damper testing. These variables would have to be

known and evaluated for individual damper tests in order to achieve

a positive determination.

Alternatively, we have reevaluated the

actual configuration for individual dampers which are installed

in accordance with Detail (d).

The damper and inspection port arrangement for dampers 21 and 22

is shown on Figure FD-24.

Because of the inspection port locations,

these dampers would be tested without obstructing the air flow.

Because of the right angle turn in the normal flow path and the

location of the inspection port, any opening during testing would

result in conservative additional air flow.

Therefore we conclude

that dampers 21 and 22 are operable. The arrangement for# amper

d

35 is shown on Figure FD-2b. This damper can also be tested without

obstructing the air flow.

Because of the right angle turn in the

normal flow path and the location of the inspection port, any

j

opening during testing would result in conservative additional air

flow. Therefore, we conclude that damper 35 is operable,

e) Detail (e) depicts fire dampers which are located upstream of all

ventilation openings and inspection ports. During testing an

open inspection port would increase air flow through the damper

l

in a conservative manner.

A successful test under this condition

demonstrates damper operability.

Reaching into the duct to

- _ - _ _ - _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

_

__

.

_

-

_

,

i

.

,

,

'

!

,

actuate or observe closure would obstruct flow in a nonconservative

,

e

manner.

The sizes of the duct, inspection port and obstruction

are variables which determine the conservatism of air flow during

'

damper testing.

These variables would have to be known and eval-

usted for individual damper tests in order to achieve a positive

'

determination.

Alternatively we have reevaluated the actual

configuration for fire dampers which are installed in accordance

with Detail (e).

,

The damper and inspection port arrangement for damper 34 is shown

,

on Figure FD-2c.

Because of the proximity of the inspection port

to the fire damper, this damper can be tested without obstructing

,

the air flow.

Therefore we concluded that damper 34 is operable,

f) Detail (f) depicts fire dampers which are located between the

inspection port and the ventilation grill upstream of the fan.

$

The inspection port is the only duct opening between the # damper

'

and the fan.

An open inspection port or an obstruction in the duct

would decrease air flow through the damper in a nonconservative

Dampers 31, 32 and 33 are installed in accordance with

manner.

Detail (f).

The installed configuration is identical for these

dampers except for damper size. The configuration for damper 33

is shown on Figure FE-2d.

The purpose of these fire dampers is to

'

,

protect the interior of the control building from an exposure fire

'

!

on the roof.

The dampers are installed below normally closed shut-

-

off dampers which were removed for fire damper installation and

,

testing.

Testing without the normal shutoff damper resistance to

f

flow was conservative.

The fact that these dampers were tested

'

l

2

1

-- .-__- -_ -

_- . _ _ _

_- _ _ _ - - - _ - - - _ _ .

-

- ., - _ _ - - ,

--

-

--

_.

.

...

,

,.

s

with air flow was a conservative action because the design

function of these dampers is to close under a no air flow condi-

-

tion.

Therefore, we concluded that dampers 31, 32 and 33 are

[

-

operable.

While this evaluation has demonstrated the operability of fire

,

dampers listed above, it does not provide justification for future

installations.

In the future, installation of fire dampers which

must close against air flow should not be installed in accordance

d

with detail (f).

'

i

!

g) Detail (g) depcits fire dampers which are located between the

,

inspection port and the ventilation grill down stream from the fan.

The inspection port is the only duct opening between the fan and

i

c

the damper.

An open inspection port or an obstruction in the duct

would decrease air flow through the damper in a nonconservative

'

manner.

Dampers 11A,12A,13A,14A,15A and 16A are installed

'

'

in accordance with detail (g). The configuration for damper 11A,

!

which is exposed to the largest pressure drop requirement is shown

1

on Figure FD-2e. We have ratested this damper with the inspec-

,

tion port opening sealed except for passage of the damper trip

i

j

wire.

The damper closed successfully. Therefore we concluded

that dampers installed in accordance with detail (g) which must

i

close against an air flow pressure drop less than .264 inches of

'

i

i

!

wcter are operable.

In the future, fire dampers which must close

i

against higher air flow pressure drops should not be installed in

l

l

accordance with detail (g).

i

,

,

i

-.

. .

- .

--

__

_ _ _ _

- - _ _ _ _ - - - _ _ . .

. _ _ , - _ _ - - . _ _ _ _ ,

.

__1

.

.

.

.

.

_ _ _ _ _ _ _ _ _ _ _

l :-

s

.)

.

.

6.0 CONCLUSION

..

This Technical Evaluation demonstrates that fire dampers installed at

PBNP prior to January 1, 1988, which are expected to close against normal

air flow, have been tested in a manner which provides adequate assurance

that the dampers will operate as required.

Fire dampers which are

installed after January 1,1988 shall be installed in accordance with

Figures FD-2a, b or c or shall be tested in accordance with Operating

Instruction 01-88, Fire Dampers.

.

t

4

l

--

_ _ _ - _ . - _ _ _ _ _ __

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _

__

TABLE FD-1

P8MP FIRE DAMPER STUDY

Damper

Install.

Penetra-

Survey

HVAC

Damper Fusible

Test

Fan Off

Associated

Associated

No.

Docu.

tion No.

Dwg.

Dwg.

Rating Rating

Condition

or other

Fan

Area

1

MR 83-151

51

M-7-4-40

M-116

3 Hour

212F

Norm Air Flow

N/A

W30A&8

U1 Chg. Pump ha

2

MR 83-151

El

M-7-4-41

M-116

3 Hour

212F

Norm Air Flow

N/A

W30A&8

U1 Chg. Pump Am

3

MR 83-151

51

M-7-4-39

M-116

3 Hour

212F

Norm Air Flow

N/A

W30A&B

U1 Chg. Pump Am

4

MR 83-151

M1

M-7-4-38

M-116

3 Hour

212F

Norm Air Flow

N/A

W30A&8

U1 Chg. Pur

'Js

5

MR 83-151

N1

M-2007-6-47

M-122

3 Hour

212F

Norm Air Flow

N/A

W30A&8

U2 Chg. Pump Am

6

MR 83-151

51

M-2007-6-48

M-122

3 Hour

212F

Norm Air Flow

N/A

W30A&8

U2 Chg. Pump Am

7

MR 83-151

51

M-2007-6-49

M-122

3 Hour

212F

Norm Air Flow

N/A

W30A&8

U2 Chg. Pump Its

8

MR 83-151

51

M-2007-6-50

M-122

3 Hour

212F

Norm Air Flow

N/A

, W30A&8

U2 Chg. Pump ha

9

MR 83-151

E5

M-7-4-14

M-116

3 Hour

212F

Static

MR 86-127

IW98

PA8 El 8 Area 4

10

MR 83-151

F1

M-7-4-47

M-116

3 Hour

212F

Static

MR 86-127

IW98

PA8 El 8 Area 4

11

MR 83-151

E7

M-7-4-14

M-116

3 Hour

212F

Static

MR 86-127

IW9C

PA8 E1 8 Area 4

12

MR 83-151

M

M-5-4-1

M-116

3 Hour

212F

Static

MR 86-127

IW9C

FA8 El 8 Area 4

13

MR 83-151

E2

M-7-4-11

M-116

3 Hour

212F

Static

MR 96-127

IW90

PA8 El 8 Area 4

14

MR 83-151

F31

M-0-40

M-116

3 Hour

212F

Static

MR 86-127

IW90

PA8 El 8 Area 4

15

MR 83-151

El

M-2007-6-15

M-122

3 Hour

212F

Static

MR 86-127

2W9C

Cryogenic lha

16

MR 83-151

F1

M-2007-6-46-3 M-122

3 Hour

212F

Static

MR 86-127

2W9C

Cryogenic h

17

MR 83-151

52

M-7-4-13

M-116

3 Hour

212F

Static

MR 86-127

W30A&B

PA8 El 8 Area 4

18

MR 83-151

513

M-7-4-13

M-116

3 Hour

212F

Static

MR 86-127

W27A&B

PA8 E1 8 Area 4

19

MR 83-151

518

M-7-4-13

M-116

3 Hour

212F

Static

MR 86-127

W32

PA8 El 8 Area 4

20

MR 83-151

W3

M-7-4-15

M-116

3 Hour

212F

Static

MR 86-127

W30A&B

PA8 El 8 Ar" 4

21

MR 83-151

N1

M-7-3-67

M-111

3 Hour

212F

Nonn Air Flow

N/A

W10A

Battery he .

22

MR 83-151

N1

M-7-3-69

M-111

3 Hour

212F

Norm Air Flow

N/A

W108

Battery Ihm

23

MR 85-015-1

M

M-5-4-1

M-116

3 Hour

165F

Static

MR 86-127

W27A&8

PA8 El 8 Area 4

24

MR 85-015-1

G

M-5-4-1

M-116

3 Hour

165F

Norm Air Flow

N/A

W27A&B

PA8 E1 8 Area 4

25

MR 85-015-1

F9

M-1-3-53

M-109

3 Hour

165F

Static

MR 86-127

W13A1&A2

HVAC Equip Am

26

MR 85-015-1

F1

M-0-39

M-110

3 Hour

165F

Static

MR 86-127

W13A1&A2

HVAC Equip Am

27

MR 85-015-1

F9

M-1-3-53

M-109

3 Hour

286

Static

MR 86-127

W13A1&A2

Control Rm

28

MR 85-015-1

F1

M-0-39

M-110

3 Hour

286

Static

MR 86-127

W13A1&A2

Control Rm

29

MR 85-015-1

F9

M-1-3-53

M-109

3. Hour

165F

Static

MR 86-127

W1381&82

HVAC Equip Am

30

MR 85-015-1

F9

M-1-3-53

M-103

3 Hour

286

Static

MR 86-127

W1381&B2

HVAC Equip Am

31

MR 85-015-2

C19

M10-3-54

M-5004 3 Hour

286

Norm Air Flow

N/A

W13C

Cont. 81dg. Reef

32

MR 85-015-2

C18

M10-3-54

M-5004 3 Hour

286

Norm Air Flow

N/A

W13C

- Cont. 81dg. Reef

33

MR 85-015-2

C17

M-10-3-54

M-5004 3 Hour

286

  • iorm Air Flow

N/A

W13C

Cont. 81dg. Noof

34

MR 85-015-3

F7

M-1-3-53

M-109

3 Hour

165F

Norm Air flow

N/A

WIS

Control Rm -

.

.

-

--

- - - - - - - -

-

- - -

-_____._.2.. _ _ . _ _ _ _ , _ _ , _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

_ _ ._ _ _ _ __

-.

. _ _ _ _ _ _ _

_

-

.

..

_

TABLE FD-1 (Ccnt'd.)

-

%

7 U

PBNP FIRE DAMPER STUDY

_.

.

Danper

Install.

Penetra-

Survey

HVAC

Damper Fusible

Test

Fan Off

Associated

Associated

No.

Docu.

tion No.

Dwg.

Dwg.

Rating Rating

Cond', tion

or other

Fan

Area

l

l

l

l

35

MR 85-015-3

N6

M-7-3-15

M-111

3 Hour

165F

Norm Air flow

N/A

Wil

Air Comp Rm

36

MR 85-015-3

S1

M-1-3-5')

M-109

3 Hour

165F

Norm Air Flow

N/A

W13Bl&B2

Comp Rm

,

37

MR 85-015-4

S2

M-1-3-50

M-109

3 Hour

165F

Norm Air Flow

N/A

W13Bl&B2

Comp Rm

i

1A

MR 613

57

M-7-3-9

M-111

3 Hour

160F

Norm Air Flow

N/A

N/A

El 8 Bat Rm

2A

MR 613

53

M-7-3-10

M-111

3 Hour

160F

Norm Air Flow

N/A

N/A

El 8 Bat 'm

3A

/R 613

56

M-7-3-3

M-111

3 Hour

160F

Norm Air Flow

N/A

N/A

El 8 AFI

.a

4A

MR 613

E13

M-7-3-4

-

3 Hour

160F

Norm Air Flow

N/A

N/A

El 8 AFP Rm

SA

MR 613

W8

M-7-3-22

-

3 Hour

160F

Norm Air Flow '

N/A

N/A

El 8 AFP Rn

6A

MR 613

E49

M-7-3-23-1

M-111

3 Hour

160F

Norm Air Flow

N/A

N/A

El 3 AFP Rm

7A

MR 613

E48

M-7-3-23-2

M-111

3 Hour

160F

Norm Air Flow

N/A

N/A

El 8 AFP Rm

8A

MR 622

H5

M-5-3-31

N/A

3 Hour

160F

N/A

N/A

N/A

CRNorthWig

9A

MR 622

512

M-5-3-32

N/A

3 Hour

160F

N/A

N/A

N/A

CR South Wig

10A

MR 622

E7

M-5-3-33

N/A

3 Hour

160F

N/A

N/A

N/A

CR East Wind

11A

Orig.Constr

F12

M-5-3-30

M-110

1.5 Hour 160F

Norm Air Flow

N/A

HX65A

DG Rm Heatic'

12A

Orig.Constr

F11

M-5-3-30

M-110

1.5 Hour 160F

Norm Air Flow

N/A

HX65A

DG Rm Heatic

13A

Orig.Constr

F8

M-5-3-30

M-110

1.5 Hour 160F

Norm Air Flow

N/A

HX65B

DG Rm Heatiri

14A

Orig.Constr

F7

M-5-3-30

M-110

1.5 Hour 160F

Norm Air Flow

N/A

HX65B

DG Rm Heatfr

15A

Orig.Constr

F2

M-5-3-30

M-110'

1.5 Hour 160F

Norm Air Flow

N/A

HX78

Air Coup Rm

Heating

16A

Orig.Constr

F1

M-5-3-30

M-110

1.5 Hour 160F

Norm Air Flow

N/A

HX78

Air Crsp Rm

Heating

17A

Orig.Constr

F14

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12A

DG Air I

aq

18A

Orig.Constr

F14

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12A

DG Air Exnat

19A

Orig.Constr

F14

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12B

DG Air Exhat

20A

Orig.Constr

F14

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12B

DG Air Exhat

21A

Orig.Constr

F13

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12C

DG Air Exhat

22A

Orig.Constr

F13

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12C

DG Air Exhat

23A

Orig.Constr

F13

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W12D

DG Air Exhat

24A

Orig.Constr

F13

M-5-3-30

M-110

1.5 Hour 165F

Static

N/A

W120

DG Air Exhat

25A

MR 784

58

M-2005-6-37

EB45A-5 3 Hour

160F

Norm Air Flow

N/A

AHU1A&lB

White Inveri

26A

MR 784

E7

M-2005-6-388 EB45A-5 3 Hour

160F

Norm Air flow

N/A

ANU1A&l8

White Inveri

27A

MR 784

C14

M-2005-6-44B EB45A-5 3 Hour

160F

Norm Air Flow

N/A

ANUIA&l8

Yellow inves

28A

MR 784

CIS

M-2005-6-44B EB45A-5 3 Hour

160F

Norm if- Flow

N/A

AHUIA&lB

Yellow Invei

29A

MR 784

E7

M-2005-6-38B EB45A-5 3 Hour

160F

Norir. Air Flow

N/A

AHUIA&lB

DIOS Bat Rm

. -

__

TABLE FD-1 (Cont'd.)

PBNP FIRE DAMPER STUDY

Damper

Instsl17

Penetra-

Survey

HVAC

Damper Fusible

Test

Fan Off

Associated

' Associated

No.

Docu.

tion No.

Dwg!

Dwg.

Rating Rating

Condition

or cther

Fan

Area

l

l

30A

MR 784

N12

M-2005-6-18

EB45A-5 3 Hour

160F

Norm Air Flow

N/A

AHU1A&l8

D105 Bat Rm

I

31A

MR 784

S4

M-2005-6-41

EB45A-5 3 Hour

160F

Norm Air Flow

N/A

AHU1A&l8

D106 Bat Rn

32A

MR 784

E22

M-2005-6-20

EB45A-5 3 Hour

160F

Norm Air Flow

N/A

AHU1A&lB

D106 Bat Rm

C

!

!

i

!

.f

(

i

a

.

.

e

4

4

l

e

e

- - - - - -

--

- - .

y

mw.

_-_

_ _ _ - - _

.

-.

TA8LE FD-2

.

l

Damper

Size

Air Flow

Velocity

Press.0 rop

Section

Velocity

Press. Drop

FD-1 Configuration

'

I

No.

In.

cfm

fpm

In. Water

In.

fpm

In. Water

Installed Evaluated

1

16x34

7460

1975

.120

16x17

3950

433

b

b

2

18x34

8260

1944

.120

18x17

3887

.433

b

b

3

20x34

9060

1919

.120

20x17

3838

.400

b

b

4

20x36

9860

1972

.120

20x18

3944

433

b

b

5

6x12

300

600

.012

6x12

600

.012

b

b

6

8x18

1000

1000

.030

8x18

1000

.030

b

b

7

12x18

1700

1134

.034

12x18

1134

.034

b

b

8

12x24

2403

1200

.037

12x24

1200

.037

b

b

21

12x12

470

470

.019

12x12

470

.019

d

a..

22

12x12

470

470

.019

12x12

470

.019

d

a,d

24

14x30

4050

1388

.054

14x30

1388

.054

c

a(2)

31

30x30

12000

1920

.120

30x30

1920

.120

f

f

32

30x30

12000

1920

.120

30x30

1920

.120

f

f

33

18x30

12000

3200

.296

18x30

3200

.296

f

f

'

34

6x18

550

734

.017

6x18

734

.017

e

a,e

35

22x25

2200

576

.012

22x25

576

.012

d

a,d

36

18x36

5500

1222

.037

18x36

1222

.037

b

b

37

18x30

5500

1467

.060

18x30

1467

.060

e

c

1

1A

12x24

470

235

.002

12x24

235

.002

a

a

2A

12x24

470

235

.002

12x24

235

.002

a

a

'

3A

18x24

940

313

.003

18x24

313

93

a

a(1)

4A

12x12

300

300

.003

12x12

300

.003

a

a(1)

SA

12412

300

300

.003

12x12

300

.003

a

a(1)

6A

20x30

3750

900

.025

20x30

900

.025

c

c(1)

7A

30x36

2810

375

.005

30x36

375

.005

a

)

11A

12x12

1500

1500

.060

12x12

3000

.264

g

g-

12A

12x12

1500

1500

.060

12x12

3000

.264

g

g

13A

12x12

1500

1500

.060

12x12

3000

.264

g

g

14A

12x12

1500

1500

.060

12x12

3000

.264

g

g

15A

12x12

1150

1150

.034

12x12

2300

.124

g

g

16A

12x12

1150

1150

.034

12x12

2300

.124

g

g

25A

16x24

3230

1210

037

16x24

1210

.037

b

b

26A

8x24

3230

2422

.147

8x24

2422

.147

b

b

27A

12x20

2550

1530

.065

12x20

1530

.065

b

b

28A

16x16

2550

1435

.057

16x16

1435

.057

b.

b

_ _ _ _ _ _ _ _ _ _ - _ _ .

!

TABLE FD-2 (C:nt'd.)

Damper

Size

Air Flow

Velocity

Press. Drop

Section

Velocity

Press. Drop

FD-1 Configuration

No.

In.

cfm

fpm

In. Water

In.

fpm

In. Water

Installed Evaluated

1

29A

12x12

1840

1840

.090

12x12

1840

.090

b

b

30A

12x16

1840

1380

.054

12x16

1380

.054

a

a

31A

12x16

1520

1140

.034

12x16

1140

.034

b

b

32A

12x12

1520

1520

.0E5

12x12

1520

.065

a

a

(1) Damper functionally tested during Halon fire suppression system discharge tests.

7

!

(2) Shutdown of fans W-27A&B enhances damper operability.

!

,

i

%

l

!

l

-

l

.

.

.

.

.

.

.

.

. ..

. -

= - -.

.

-

_ _ _ _ _ _ _

8

-

man--

FIGURE

FD-I

.

.

Legend

O ra n

si

~

lli da rn pe r

..

y inspection pcrt

2 grtII

( o.)

g

Ill

13 1

g

3

D

,i

,,

-

il

.

"

"

1P

( b)

(c)

q

lli

l$l

g

3

M

N

b

'

,,

-

(d)

(e)

g

Ill

$1

g

'

D

l

3

.

.

..

..

(f)

(9)

'. FIGURE

FD-2a'

~.

LEGEND

f)

WALL

kN

?-hR FIRE BLkklER

n . FAN.

Q'

BbCKDRLFT DAMPER

l2l

F l P.E 1:4MPER

.

I AS PE C TICl; P: F:T

.

i

j

c

r

.

.

.

,

_ gL

/2"

,

,/

i

,

.

'

,.

,

,

-

-

s .,

'\\

.

h.

-

,,

,

_

.

,

/

. . . , '

" FL k

l

~\\

} \\

~o~

\\

k

N

i

,

,.'

l

-

xx.

-

.

l

/

9"

,k

12."

x

ic"

'

'

.

s

>

.

./

'

.

SlDE

FROUT

E L E \\'A T ION

E L EVATI Oli

1

!

l

eso.n

tes in

,

. _ . .__

.-

'flGURE

FD- 2b

-

e

,.-

.

u

.

L E SEla p

.

l

-

kl ' e i

y

n

h

F A t4

)

FIEE DAMPE F

-

INS FECTl0l! FORT

a

,

o

.

,/

../

'I

t-

.

//

_l'"-

36"

'

'

'

-

,/ / ,/

/

,

,/ /}

_

_

,

-

-

'7

=i

s

,,

/

s

e

FLO W

N

y

s

~

l

\\

.'

l

,

l

30"

-

v

=

i

i

,y

/

/

i

,

.

,

.

.

,

'

/' ,

42"

s

"

.<

,

'

,-

.

,

,

'

, . -

j

.

,

i

l

l

S I l' E

mkt

El.fVA7sote

E L E il T ION

,

l

i

l

l

!

non.

,

(04-83)

j

.

..

L

' FIG UR E

Tb-2c

,

,

_

e

L E 3 Ell:'

.,

/1

FLCCR

4

\\'1 FIHE DAF PE R

,

liiEF ECT IOl! P0F;7

.

.

i

a

p

1)

.

.

.

i

r,

.,

{.

8

'

l

i

<

'

n

$

%

- q"

}

,

o

cb

(N

/ ,/

1

/

,-

'

-

,.

/

'

,'

,'

i


.,

,

,

,A

%

/

,MA

( \\l

,

,

,

N* '

<

,

,

---.


,

,

-

,

^g

=*

/

i

f

+ G%

-

I8"

I

l

'

.

!

SIDE

FRONT

'

ELEVATl3N

E LE VATl01/

'

i

l

4

f

f

804 21

(EN)

. - - . - . .-

-

-

-

.

- - . .

. .

.

.

_ , .

_. _._,

. _ . _ _ _ _

- - - - - - - - -

.,

,

,

,

.

.

FIG UR E

FD 2 d

'

.

L E C- E h'D

!/

l,

F i. C M

b+ E!i'J7 C
: DAMFER

.-___

/; FIP E DAM P E.R

. . _ .

.

It.'S PE C T10H PORT

.

1

!

i

I

-

.

.

il

t

9

,,

-

l

!

,

1

i

=

i

y o , FLOW TO ThN

  • ,

m

I

>

N

e

1L"

=

,

,

v

2I

.

>\\

l

4

go"

-

R

-

g"

_

.;

i

i

,,

.

'

'

'

l

)-

c

, , , , .-


- -

-

. , ,

.L

_s

s s s s s ' s

-

,.

_

.

I

-

+l<,_____.--.--_.

s

.s

.-

-

\\/l

'

-

,

i

_

. . .

---

.-

._. .--

-

I

J

s

.

,,_

i

/.

.,

f

l-

5/DE

FRONT

E L E VLT10N

E L E VI.T ION

son-n

(ed - 83)

_ _ . _ . . . . . .

_ _ _ _ _

_

_

..

l

'

' FIG UR E

FD- 2 e '

)

'

'(

L E G F l. L-

f)

FL C?P

(

[\\}

FlF.E OhY,PE R

INSF EC TlCl] CRT

.

,

/

.

I? Jia.

.

n

18 sn.

'

.

o"

..

1

r-N

04"

14"i

l

I

IVN

2

i

t

I

C

1

4

i

"

I*" dia

A8"

i?

'

!

1

Sch.40

t

. . .A

1

l

.

l

/

~

<

e'

i.%

s.s

_ .

/

1

I

t

r

R'1DE

F R Ol:T

E_L__E V h i I ).

E.L.._E Y AT 10H

.

_ . . . . _ .

l

t

I

l

6

....u

fee-8H '

-

l

5

-

.

. - -