- _ _ ___

/R V "

pbv- k..

L! $

HOCHESTER GAS AND ELECTRIC CORPORATION

  • 89 EAST AVENUE. ROCHESTER, N.Y.14649

.....--,,.c. ,..

l l July 31, 1979 l

Director of Nuclear Reactor Regulation Attention: Mr. Dennis L. Ziemann, Chief Operating Reactors Branch No. 2 S. Nuclear Regulatory Commission

.. a sh ing ton , D.C. 20555

Subject:

Undervoltage Protection R.E. Ginna Nuclear Power Plant Docket No. 50-244 Lear Mr. Ziemann:

In response to your letter of July 12, 1979, the following letter is submitted.

Question 1. Provide the voltage setpoint trip and time delay and I the tolerance on the 4160 volt side for the second l level voltage protection monitors in the Technical Specification.

Response: As shown-on the enclosed single line for train A (from our submittal of May 1, 1978), the undervoltage load shedding and sequencing system is entirely at th e 4 80V level. Since there are no 4160V saret.

related loads, there are no undervoltage prctocticn monitors for the load shedding and sequencing system at that level.

Question 2. State the operating modes, total number of channels, and number of channels to trip on the under-vcitage degradation protection system. Refer to Table

3. 3-3, NRC letter, " Safety Evaluation and Statement of Staf f Positions Relative to the Emergency Pcm r Systems For Operating Reactors," June 2, 1977.

l Describe the coincident log ic us ed .

Pesponse: The operating modes, total number of channels, and number of channels to trip are. described in our is Application for Amendment to Operating License The coincident logic enclosed with this response.

used in this design is described in our s: tmittal t <.,

j you, dated July 24, 1979, under the sub]ect " Amendne., t s to Prior Design Modifications on Undervoltagc Prctect :a-l

f f y , .

of the type customarily held in confidence by its owner due to its unique nature; has been transmitted to us and to you L in confidence; it not generally available in public scurces; f

and the public disclosure of which would cause substantial

! harm tc the competitive position of the owner, Rochester Gas and Electric in that it has high commerical value developed with substantial expenditures of effort and money.by its 7<c, owner which could not be easily dupicated by others.

Therefore,' pursuant to 10 C.F.R. Section 2.790 of

! the Commissions Rules of Practice and Part 9.5 of the Ccm-a missions Regulations, we request that the enclosed Figure 1

,j and Enclosure A be withheld from 'public disclosure.
y

- Very truly yours, Robert S. Faron LeBOEUF, LAMB, LEIBY & MacRae Attorneys for Rochester Gas and Electric Corporation

Enclosures e

i i

f

- - p