. . _ - . -

i l CENTER 00R - i V ENERGY 1

  • >i 300 Madtson Avenue  ;

DonM C. SheMon -

Toledo, OH 43652Kl01  !

Vice Presiderd Nm

?

Davis Besse (419)249-2 2 -

l 1

Docket Number 50-346.

License Number'NPF-3 Serial Number 1875-1 November 30,-1990 United States Nuclear Regulatory Commission ,

Document Control Desk 1 Vashington, D. C.- 20555

Subject:

License Amendment Request to Revise the Steam and Feedvater i-Rupture Control System.Hain Steam Low Pressure Block Permit l Setpoint i

Gentlemen:

I Enclosed is an application for an amendment to'the Davis-Besse' Nuclear-Power Station, Unit 1 (DBNPS), Operating License, Number NPF-3, Appendix A Technical Specifications. -The proposed changes' involve Technical Specification 3/4.3.2.2, Instrumentation,- Steam and Feedvater Rupture Control System Instrumentation. }

The proposed changes vould : increase 1the1 Steam and Feedvater Rupture Control System (SFRCS) Main Steam (MS) low pressure block _ permit setpoint from 700 "

psig to 750 psig and increase the' steam pressure setpoint'where the block permit is automatically-removed from 750 psig to 800 psig. These changes will increase the pressure margin between the. SFRCS block permit .and :the SFRCS MS low pressure trip setpoint of 591.6 psig. This~. vill ~ minimize the

. possibility of-an inadvertent-MS low pressure trip from< occurring during plant cooldown and heatup operations.

Toledo Edison requests that this amendment be issued-by the Nuclear-Regulatory Commission by June 15,'1991, with implementation within 45-days-following issuance.

l l'

i l I

'9012110236 901130 PDR ADOCK 05000346 P PDC 0f Operating Companies.  ! k Cleveland Electric muminating Toledo Edrson

- - _ x _

.. -Dockot Nu ber 50-34'? 6-

  • . Liccusa Nunbar NPF-3 Serial Number 1875 iPage 2 If you have any questions-regarding this amendment request, please contact-Mr.-.R. V. Schrauder, Manager - Nuclear Licensing, at-(419) 249-2366.

~

.Very truly yours, PWS/mmb o g,g enclosure

-cci P. M. Byron, DB-1 NRC-Senior Resident Inspector:

A. B. Davis, Regional Administrator, NRC' Region III H. D.-Lynch, DB-1 NRC' Senior Project-' Manager Utility Radiological Safety Board

_ _ _ _ _ _ - _ - _ _ - . _ _ - - - _ _ - _ _ - - _ - _ _ - . _ - - - - ~ _ _ - - - - .