(7 771 o ..' LICENSEE EVENT REPORT g

t j CONTROL eLOcK: l l l l l l (PLEASE PRINT OR TYPE ALL REQUIRED INF2RMATION) l0 lt]6 lV 7 9 l ALICENSEE lN l ACODE lS l 1 l@l15 0 l 0l -l 0 l LICENSE 14 0] 0 ]NUVSEH 0 ] 0 l - l 0 l 025l@l26 4 l LICENSE 1 l I l TYPE 1 l IJOl@lSi CAIl l@

bd CON'T 7

o 1 6

En*CE 60 lL l@l0 61 l5 l0 l0 l0 l3 l3 l8 @l DOCKET NUMBEH 68 063l 2 l EVENT 2 l 9OATE l 8 l 0 l@l74 0 l 3REPORT 75 l 2 l DATE 818 l O80l@

EVENT DESCRIPTION AND PROBADLE CONSEQUENCES h l 012 l l On February 20, 1980, it was discovered that the Foxboro model E17DM transmitter which 10 i 3 i l had previously been installed to replace Rosemount model 1152115A2AO on casing cooling l l0 l4 l l tank level transmitter LT-RS 103A, was not sesmically qualified as required. 'Ih e j l0 Isl I health and safety of the general public were not affected by this event. Reportable l IO lc l l pursuant to T. S . 6. 9.1.9. C. l l0l7ll l 101811 I DE CODE S SC E COMPONENT CODE SUB O'E S ODE 7

O 9 8

lSlBj@

9 10 11

@ l Xl@ lIlN l S lT lR lU [@ {@ { @

12 ;3 18 19 20

_ SEQUE NTI AL OCCURRENCE REPORT REVISION LER RO EVENT YE AR R E POR T NO. CODE TYPE N O.

@ REP l8l0l 22 g l0l3l1l 24 26 y

27 l 0l 3[

28 7J y30 y31

]

32

_ 21 23 AKEN ACT ON ON PL T ME HOURS 22 SB IT D FOR US. SU PL1 R MAN FACTURER j ggl34H lg 33 l35Zlg g g 36 l0l0j0l 31 l

43 gg di gg 42

]g e

lF u

l1 l8 l0 [g j 47 i CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h l i l 0 l l The substitution was evaluated by an engineering study which, due to a misinterpre- l l3 g i ; l tation of the data available, incorrectly determined the replacement transmitter to l

, 7 l to be qualified. A Rosemount transmitter, similar to the original, was removed from l 3 ., l the Unit 2 casing cooling system and installed in place of the non-qualified l'oxboro l

, ,, l component. l 7 8 9 80 ST S  % POWER OTH E R STATUS 015 O RY DISCOVERY DESCRIPTION i s ]@ l 1 l 0 l 0 lgl NA l lDl@l Notification from A/E l A TIVITY CO TENT HELEASED OF 9ELEASE AMOUNT OF ACTIVITY LOCATION OF RELE ASE 1 6

@ l NA l l N/A l 7 8 9 10 11 44 45 80 PERSONNEL EXPOSURES NUYRER TYPE DESCRIPTION LtDJ" *l I I l@lZI@l" "

I PERSONNE L iN;uWiES NUV9E R DESCRIPTION A

li18110101Ol@l 7 8 9 11 12 80 I

LOSS OF OR DAMAGE TO FACsLITY TYPE DESCRIPTION FrralZI@l NA 800403o 21l [

7 8 9 10 60 ISS g @ DESCRIPTION l NA l lllllllllllll{

7 8 9 10 68 69 80 &

NAME OF PREPARER t' D r's r to righ t PHONE: (703) - S9 '-51 < 1

s -

Virginia Electric & Power Company North Anna Power Station, Unit #1

Attachment:

Page 1 of 1 Docket No. 50-338 Report No. LER 80-31/03L-0 Description of Event During the past refueling outage, casing cooling tank level transmitter "

LT-RS103A failed requiring the installed transmitter to be replaced. Because the level transmitter model (Rosemount model 1152115A2AO) was no longer available due to discontinuation, a Foxboro transmitter model E17DM was installed af ter an engineering evaluation determined it suitable. On February 29, 1980, it was discovered that the Foxboro transmitter which was installed was not seismically qualified as required.

Probable Consequences of Occurrence The casing cooling tank level transmitters provide level indication in the control room as well as secure the casing cooling system by closing the system supply valves (MOV-RS100A and L) on low tank level. With a transmitter not seismically qualified, a malfunction could develop in the event of a seismic occurrence which could jeopardize the proper operation of the casing cooling system. Because the discrepancy was discovered and rectified, the health and safety of the general public were not affected. There are no generic implications associated with this event.

Cause of Event The improper level transmitter was installed because the engineering l study which evaluated the substitution misinterpreted the data available and incorrectly determined the replacement transmitter to be qualified.

Immediate Corrective Action A Rosemount level transmitter, identical to the original, was removed from the Unit 2 casing cooling system and installed in place of the 1 non-seismically qualified Foxboro transmitter. The Rosemount transmitter was then calibrated in accordance with applicable calibration procedures.

Scheduled Corrective Action Foxboro model E13DM level transmitters that have been seismically l

qualified and are acceptable for use on the casing cooling tanks will be '

installed in the Unit 2 casing cooling system and used as spares for Unit 1.

o o Action Taken to Prevent Recurrence Personnel responsible for the preparation and review of the Engineering Study were advised of the mistake made and reinstructed accordingly.

l