NL-14-0342, Units 1 and 2, Seismic Hazard and Screening Report for CEUS Sites

From kanterella
(Redirected from ML14092A020)
Jump to navigation Jump to search
Units 1 and 2, Seismic Hazard and Screening Report for CEUS Sites
ML14092A020
Person / Time
Site: Farley  
Issue date: 03/31/2014
From: Pierce C
Southern Co, Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NL-14-0342
Download: ML14092A020 (87)


Text

Charles R. Pierce Regulatory Affairs Director Southern Nuclear Operating Company, Inc.

40 Inverness Center Parkway Post Office Box 1295 Birmingham, AL 35201 SOUTHERN COMPANY March 31, 2014 Docket Nos.: 50-348 50-364 NL-14-0342 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Joseph M. Farley Nuclear Plant - Units 1 and 2 Seismic Hazard and Screening Report for CEUS Sites

References:

1. NRC Letter, "Request for Information Pursuant to Title 10 of the Code of Federal Regulations 10 CFR 50.54(f Regarding Recommendations 2.1, 2.3, and 9.3, of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident," dated March 12, 2012.
2.

NEI Letter to NRC, "Proposed Path Forward for NTTF Recommendation 2.1:

Seismic Reevaluations," dated April 9, 2013. ML13101A379.

3. NRC Letter, EPRI Final Draft Report XXXXXX, Seismic Evaluation Guidance:

Augmented Approach for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic," as an Acceptable Alternative to the March 12, 2012, Information Request for Seismic Reevaluations, dated May 7, 2013. ML13106A331.

4. EPRI Report 1025287, "Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic.

ML12333A170.

5. NRC Letter, Endorsement of EPRI Final Draft Report 1025287, Seismic Evaluation Guidance, dated February 15, 2013. ML12319A074.

Ladies and Gentlemen:

On March 12, 2012, the Nuclear Regulatory Commission (NRC) issued Reference 1 to all power reactor licensees and holders of construction permits in active or deferred status. Enclosure 1 of Reference 1 requested each addressee in the Central and Eastern United States (CEUS) to submit a Seismic Hazard Evaluation and Screening Report within 1.5 years from the date of Reference 1.

In Reference 2, the Nuclear Energy Institute (NEI) requested NRC agreement to delay submittal of the final CEUS Seismic Hazard Evaluation and Screening Reports so that an update to the Electric Power Research Institute (EPRI) ground motion attenuation model could be completed and used to develop that information. NEI proposed that descriptions of subsurface materials and properties and base case velocity profiles be submitted to the NRC by AC) 1 -0

U.S. Nuclear Regulatory Commission NL-14-0342 Page 2 September 12, 2013, with the remaining seismic hazard and screening information submitted by March 31, 2014. NRC agreed with that proposed path forward in Reference 3.

Reference 4 contains industry guidance and detailed information to be included in the Seismic Hazard Evaluation and Screening Report submittals. NRC endorsed this industry guidance in Reference 5.

The attached Seismic Hazard Evaluation and Screening Report for the Joseph M.

Farley Nuclear Plant (FNP) site provides the information described in Section 4 of Reference 4 in accordance with the schedule identified in Reference 2.

This letter contains no NRC regulatory commitments. If you have any questions, please contact John Giddens at 205.992.7924.

Mr. C.R. Pierce states he is Director of Regulatory Affairs of Southern Nuclear Operating Company, is authorized to execute this oath on behalf of Southern Nuclear Operating Company and, to the best of his knowledge and belief, the facts set forth in this letter are true.

Respectfully submitted, C.R. Pierce Regulatory Affairs Director CRP/JMG/RCW Swrn to and subscribed before me this 3 day of fM.,J'-

,2014.

Notary Public My commission expires:

[,

o :

Joseph M. Farley Nuclear Plant - Units 1 and 2 Seismic Hazard Reevaluation and Screening for Risk Evaluation

U.S. Nuclear Regulatory Commission NL-14-0342 Page 3 cc:

Southern Nuclear Operating Company Mr. S. E. Kuczynski, Chairman, President & CEO Mr. D. G. Bost, Executive Vice President & Chief Nuclear Officer Ms. C. A. Gayheart, Vice President - Farley Mr. B. L. Ivey, Vice President - Regulatory Affairs Mr. B. J. Adams, Vice President - Engineering Mr. D. R. Madison, Vice President - Fleet Operations RTYPE: CFA04.054 U. S. Nuclear Requlatory Commission Mr. V. M. McCree, Regional Administrator Mr. G. E. Miller, NRR Project Manager - Farley Mr. S. A. Williams, NRR Project Manager - Farley Mr. P. K. Niebaum, Senior Resident Inspector - Farley Mr. J. R. Sowa, Resident Inspector - Farley Alabama Department of Public Health Dr. D. E. Williamson, State Health Officer

SOUTHERNAM COMPANY to SNC Letter NL-14-0342 Joseph M. Farley Nuclear Plant Units 1 and 2 Response to Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) Regarding Fukushima Near-Term Task Force Recommendation 2.1: Seismic for Seismic Hazard Reevaluation and Screening for Risk Evaluation This report provides information in response to NRC's March 12, 2012, 10CFR50.54(f) letter requesting nuclear power plant licensees to perform seismic hazard reevaluation and screening for risk evaluation pursuant to the recommendations in NRC's Near-Term Task Force review of the accident at the Fukushima Dai-ichi nuclear facility.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 1 1.0 Introduction Following the accident at the Fukushima Daiichi nuclear power plant resulting from the March 11, 2011, Great Tohoku Earthquake and subsequent tsunami, the NRC Commission established a Near Term Task Force (NTTF) to conduct a systematic review of NRC processes and regulations and to determine if the agency should make additional improvements to its regulatory system. The NTTF developed a set of recommendations intended to clarify and strengthen the regulatory framework for protection against natural phenomena. Subsequently, the NRC issued a 50.54(f) letter that requests information to assure that these recommendations are addressed by all U.S. nuclear power plants. The 50.54(f) letter requests that licensees and holders of construction permits under 10 CFR Part 50 reevaluate the seismic hazards at their sites against present-day NRC requirements. Depending on the comparison between the reevaluated seismic hazard and the current design basis, the result is either no further risk evaluation or the performance of a seismic risk assessment. Risk assessment approaches acceptable to the staff include a seismic probabilistic risk assessment (SPRA), or a seismic margin assessment (SMA). Based upon the risk assessment results, the NRC staff will determine whether additional regulatory actions are necessary.

This report provides the information requested in items (1) through (7) of the "Requested Information" section and Attachment 1 of the 50.54(f) letter pertaining to NTTF Recommendation 2.1 for Plant Farley Units 1 and 2, located in Houston County, Alabama. In providing this information, Southern Nuclear Operating Company (SNC) followed the guidance provided in the Seismic Evaluation Guidance: Screening, Prioritization, and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2. 1:

Seismic (EPRI 1025287, 2013a). The Augmented Approach, Seismic Evaluation Guidance:

Augmented Approach for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic (EPRI 3002000704, 2013c), has been developed as the process for evaluating critical plant equipment as an interim action to demonstrate additional plant safety margin, prior to performing the complete plant seismic risk evaluations.

The original geologic and seismic siting investigations for Plant Farley Units 1 and 2 were performed in accordance with Appendix A to 10 CFR Part 100 and meet General Design Criterion 2 in Appendix A to 10 CFR Part 50. The Safe Shutdown Earthquake Ground Motion (SSE) was developed in accordance with Appendix A to 10 CFR Part 100 and used for the design of seismic Category I systems, structures and components.

In response to the 50.54(f) letter and following the guidance provided in the SPID (EPRI 1025287, 2013a), a seismic hazard reevaluation was performed. For screening purposes, a Ground Motion Response Spectrum (GMRS) was developed.

Based on the results of the screening evaluation, Plant Farley Units 1 and 2 screens in under the special screening considerations for a Low Seismic Hazard Site per section 3.2.1.1 of the

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 2 SPID (EPRI 1025287, 2013a). Plant Farley screens in for a high frequency confirmation; and screens out for a spent fuel evaluation.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 3 2.0 Seismic Hazard Reevaluation Plant Farley Units 1 and 2 is located in southeast Alabama on the west side of the Chattahoochee River, about 6 miles north of the intersection of U.S. Highway 84 and State Highway 95. It is in the northeastern section of Houston County, Alabama, just across the river from Early County, Georgia. The site is about 100 miles southeast of Montgomery, Alabama, and about 180 miles south-southwest of Atlanta, Georgia.

The site is located in the extreme southeastern portion of the East Gulf Coastal Plain physiographic province, which covers about 65 percent of the State of Alabama. This province is underlain by Mesozoic and Cenozoic sedimentary rocks which dip southward at 10 to 25 feet per mile. These deposits consist of marine and nonmarine gravels, sands, silts, clays, marls, and their consolidated equivalents such as sandstone and limestone. In southeastern Alabama and southwestern Georgia, the gentle south-dipping Paleocene through Oligocene sequence is influenced by only minor structural features. These structures have been inactive since Miocene time, and do not affect materials underlying the site. The Lisbon formation (Eocene), which is a soft to moderately hard sedimentary rock and dense sand formation approximately 130 feet thick, is the principal material for most plant structures, but other structures are founded at essentially plant grade.

This region is one of the least seismically active regions in the United States and is characterized by few low-magnitude and low-intensity shocks. Historic records show that earthquakes have never been felt at the site with an intensity greater Modified Mercalli V and that no earthquake of epicentral intensity greater than Modified Mercalli IV has occurred within 150 miles of the plant site. Therefore, the maximum intensity postulated as having been experienced at the site, as a result of any historical earthquake, is a low to moderate V. This intensity corresponds to a surface acceleration of 0.03g on the Hershberger's (1956) curve.

Therefore, conservatively 0.10g surface acceleration was selected for the safe shutdown earthquake (SSE). The modified Newmark spectral shape with a peak ground acceleration of 0.1g defined the Farley Units 1 and 2 SSE.

2.1 Regional and Local Geology The regional and site (local) geology is described in detail in the Farley FSAR (SNC, 2014f)

Section 2.5.1.

The site is underlain by approximately 7,000 feet of relatively unconsolidated Mesozoic and Cenozoic sands, gravels, clays, claystones, sandstones, and limestones. These strata overlie unmetamorphosed Paleozoic consolidated sedimentary units and dip uniformly to the south. No structural features affect the material underlying the site. Sediments in this province were deposited as the Gulf of Mexico subsided and the site environment changed from continental to marine. These coastal plain deposits strike in an east-west direction and dip to the south at about 10 to 25 feet per mile (SNC, 2014f). As a result of the regional subsidence, these deposits

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 4 generally thicken from north to south. It is assumed that the physical properties of each stratigraphic unit along strike are similar.

The site is within a transitional zone between the Atlantic and Gulf Coastal Plain provinces.

However, the stratigraphy of the area is more closely allied with the Gulf Coastal Plain province.

Scattered deep borings in Houston County, Alabama, and Early County, Georgia, indicate that pre-Cretaceous basement rock underlying the site consists of flat lying, consolidated, unmetamorphosed Paleozoic formations. Overlying the basement rock are relatively unconsolidated sedimentary units that range in age from Jurassic to Recent. These units dip Gulfward at about 10 to 25 feet/mile and thicken downdip. Sea level fluctuations resulted in erosion of the units after their deposition.

Materials from the following geologic units, listed from oldest to youngest, were found in geologic and foundation borings drilled at the site: Tallahatta, Lisbon, and Moodys Branch formations of Eocene age; Residuum of Oligocene and Miocene age; and floodplain deposits of Pleistocene and Recent age. Pilot holes for two water wells drilled at the site penetrated below the Tallahatta formation. One of the holes extended into the following geologic units, listed from oldest to youngest: Ripley and Providence formations of Late Cretaceous age; Clayton formation of Paleocene age; and Nanafalia, Tuscahoma, and Hatchetigbee formations of Early Eocene age.

Structural features in the vicinity of the site include the Gordon anticline and the Apalachicola embayment. Other features of questionable existence in the site vicinity include the Chattahoochee anticline, Fort Gaines fault, Cypress fault, and several small anticlines in southeastern Alabama. None of these structural units are of significance to the site. These features are discussed in detail in FSAR subsection 2.5.1.1.6.1, Description of Tectonic Structures (SNC, 2014f). A site structural geologic map showing contours of the top of the Lisbon formation is presented on Figure 2.5-8 of (SNC, 2014f). The Lisbon is the foundation for the major plant structures. The contours indicate that the Lisbon surface has been modified by post-depositional erosion. The erosion occurred before deposition of the Moodys Branch formation in the Upland and western floodplain areas, and is presently occurring near the channel of the Chattahoochee River. Structural features do not appear to influence the Lisbon surface.

2.2 Probabilistic Seismic Hazard Analysis 2.2. 1 Probabilistic Seismic Hazard Analysis Results LCI (2013a) is the source of the information presented in the following section.

In accordance with the 50.54(f) letter and following the guidance in the SPID (EPRI 1025287, 2013a), a probabilistic seismic hazard analysis (PSHA) was completed (LCI, 2013a) using the recently developed Central and Eastern United States Seismic Source Characterization (CEUS-SSC) for Nuclear Facilities (CEUS-SSC, 2012) together with the updated EPRI Ground-Motion

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 5 Model (GMM) for the CEUS (EPRI, 2013b). For the PSHA, a lower-bound moment magnitude (Mw) of 5.0 was used, as specified in the 50.54(f) letter (NRC, 2012).

For the PSHA (LCI, 2013b), the CEUS-SSC background seismic sources out to a distance of 400 miles (640 km) around Farley were included. This distance exceeds the 200 mile (320 km) recommendation contained in NRC (2007) and was chosen for completeness. Background sources included in this site analysis are the following:

1. Atlantic Highly Extended Crust (AHEX)
2. Extended Continental Crust-Atlantic Margin (ECCAM)
3. Extended Continental Crust-Gulf Coast (ECCGC)
4. Gulf Highly Extended Crust (GHEX)
5. Mesozoic and younger extended prior - narrow (MESE-N)
6. Mesozoic and younger extended prior - wide (MESE-W)
7. Midcontinent-Craton alternative A (MIDCA)
8. Midcontinent-Craton alternative B (MIDCB)
9. Midcontinent-Craton alternative C (MIDCC)
10. Midcontinent-Craton alternative D (MIDCD)
11. Non-Mesozoic and younger extended prior - narrow (NMESE-N)
12. Non-Mesozoic and younger extended prior - wide (NMESE-W)
13. Paleozoic Extended Crust narrow (PEZN)
14. Paleozoic Extended Crust wide (PEZW)
15. Reelfoot Rift (RR)
16. Reelfoot Rift including the Rough Creek Graben (RR-RCG)
17. Study region (STUDYR)

Large magnitude CEUS-SSC (2012) Repeated Large Magnitude Earthquake (RLME) sources within 1,000 km of the site were also included in the analysis. These sources are:

1. Charleston
2. Commerce
3. Eastern Rift Margin Fault northern segment (ERM-N)
4. Eastern Rift Margin Fault southern segment (ERM-S)
5. Marianna
6. New Madrid Fault System (NMFS)
7. Wabash Valley For each of the above background sources, the Gulf version of the updated CEUS EPRI GMM (EPRI, 2013b) was used to model the travel path of seismic waves. For the Charleston RLME source, a combination of the Gulf and mid-continent versions of the updated CEUS EPRI GMM is created using a weighting of 36% and 64%, respectively. For the RLME sources in the Mississippi embayment (Commerce, ERM-N, ERM-S, Marianna, NMFS, and Wabash), a combination of the Gulf and mid-continent versions of the updated CEUS EPRI GMM is created using a weighting of 20% and 80%, respectively. These percentages represent the relative fraction of the seismic wave travel path through these regions from the source to Farley.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 6 2.2.2 Base Rock Seismic Hazard Curves Hazard curves at Farley are calculated for base rock conditions (LCI, 2013a).

The procedure to develop probabilistic seismic hazard curves for base rock follows standard techniques documented in the technical literature (e.g., McGuire, 2004). Separate seismic hazard calculations are conducted for the 7 spectral frequencies for which ground motion equations are available (100 Hz=peak ground acceleration or PGA, 25 Hz, 10 Hz, 5 Hz, 2.5 Hz, 1 Hz, and 0.5 Hz). As discussed in Section 2.2.1, ground motion equations from the updated EPRI Ground-Motion Model (GMM) for the CEUS (EPRI, 2013b) were used for the calculation of base rock hazard. All spectral accelerations presented herein correspond to 5% of critical damping (LCI, 2013a). Figure 2.2.2-1 shows the mean base rock seismic hazard curves for the 7 spectral frequencies. The digital values for the mean and fractile hazard curves are provided in Table 2.2.2-1a through Table 2.2.2-1g.

Deaggregation of seismic hazard is calculated by determining the contribution by moment magnitude (Mw), distance (R), and number of logarithmic standard deviations from the median spectral amplitude (e), grouping the contributions by Mw, R, and e bin (LCI, 2013b). The contributions are calculated for individual seismic sources and are aggregated for all sources.

The deaggregations are calculated by spectral frequency and mean annual frequency of exceedance (MAFE).

Deaggregation and determination of controlling Mw and R (LCI, 2013b) follows the methodology presented in Regulatory Guide 1.208 (NRC, 2007). Log-distance is used in the calculation of the controlling distance and linear-Mw is used in calculating the controlling magnitudes. When a substantial portion (> 5%) of the low frequency hazard (average of 1 and 2.5 Hz) is from distant sources (> 100 km), the controlling magnitude and distances are determined only from contributions from hazard at distances greater than 100 km. The resulting mean Mw and distance values from the controlling events are listed in Table 2.2.2-2 (LCI, 2013b).

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 7 Table 2.2.2-1a: Mean and Fractile Base Rock Seismic Hazard Curves for 100 Hz (PGA) at Farley (LCI, 2013a)

PGA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 2.46E-02 1.15E-02 1.82E-02 2.39E-02 3.23E-02 3.79E-02 0.001 1.54E-02 6.54E-03 1.07E-02 1.49E-02 2.04E-02 2.57E-02 0.005 3.84E-03 7.55E-04 1.72E-03 3.33E-03 5.83E-03 8.85E-03 0.01 1.46E-03 2.19E-04 4.43E-04 1.04E-03 2.19E-03 4.70E-03 0.015 7.27E-04 9.65E-05 1.84E-04 4.37E-04 9.93E-04 2.80E-03 0.03 1.93E-04 2.22E-05 4.07E-05 9.79E-05 2.46E-04 8.12E-04 0.05 7.25E-05 7.03E-06 1.44E-05 3.79E-05 9.93E-05 2.84E-04 0.075 3.57E-05 2.60E-06 7.23E-06 1.95E-05 5.35E-05 1.23E-04 0.1 2.24E-05 1.25E-06 4.56E-06 1.31 E-05 3.52E-05 7.45E-05 0.15 1.19E-05 4.07E-07 2.49E-06 7.34E-06 1.92E-05 3.79E-05 0.3 3.84E-06 5.83E-08 7.55E-07 2.46E-06 6.36E-06 1.20E-05 0.5 1.52E-06 1.20E-08 2.72E-07 9.79E-07 2.53E-06 4.77E-06 0.75 6.60E-07 3.33E-09 1.04E-07 4.13E-07 1.11E-06 2.1OE-06

1.

3.44E-07 1.29E-09 4.77E-08 2.07E-07 5.91E-07 1.13E-06 1.5 1.24E-07 3.42E-10 1.32E-08 6.83E-08 2.13E-07 4.37E-07

3.

1.57E-08 1.53E-10 9.51 E-10 6.64E-09 2.49E-08 6.54E-08

5.

2.50E-09 1.01 E-10 1.79E-10 8.85E-10 3.79E-09 1.25E-08 7.5 4.67E-10 9.11E-11 1.20E-10 2.22E-10 7.34E-10 2.57E-09

10.

1.26E-10 9.11E-11 1.01E-10 1.53E-10 2.84E-10 8.35E-10

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 8 Table 2.2.2-1b: Mean and Fractile Base Rock Seismic Hazard Curves for 25 Hz at Farley (LCl, 2013a)

SA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 3.09E-02 1.69E-02 2.46E-02 3.05E-02 3.73E-02 4.43E-02 0.001 2.08E-02 1.05E-02 1.57E-02 2.01 E-02 2.57E-02 3.33E-02 0.005 6.34E-03 1.87E-03 3.42E-03 5.83E-03 8.98E-03 1.32E-02 0.01 3.13E-03 6.45E-04 1.23E-03 2.57E-03 4.83E-03 8.OOE-03 0.015 1.88E-03 3.28E-04 6.17E-04 1.38E-03 2.92E-03 5.66E-03 0.03 6.73E-04 1.01 E-04 1.74E-04 4.07E-04 9.11E-04 2.57E-03 0.05 2.80E-04 3.90E-05 6.93E-05 1.57E-04 3.63E-04 1.13E-03 0.075 1.33E-04 1.74E-05 3.28E-05 7.55E-05 1.82E-04 5.12E-04 0.1 7.78E-05 9.65E-06 1.90E-05 4.63E-05 1.15E-04 2.80E-04 0.15 3.80E-05 3.95E-06 9.51E-06 2.46E-05 6.09E-05 1.18E-04 0.3 1.24E-05 6.83E-07 3.19E-06 8.98E-06 2.07E-05 3.52E-05 0.5 5.47E-06 1.64E-07 1.36E-06 4.07E-06 9.24E-06 1.53E-05 0.75 2.74E-06 4.98E-08 6.54E-07 2.07E-06 4.70E-06 7.55E-06

1.

1.62E-06 2.01E-08 3.79E-07 1.23E-06 2.80E-06 4.56E-06 1.5 7.23E-07 5.83E-09 1.53E-07 5.42E-07 1.29E-06 2.01 E-06

3.

1.44E-07 5.35E-10 2.35E-08 9.79E-08 2.64E-07 4.37E-07

5.

3.48E-08 1.57E-10 4.07E-09 2.07E-08 6.17E-08 1.20E-07 7.5 9.64E-09 1.53E-10 8.98E-10 4.98E-09 1.67E-08 3.73E-08

10.

3.53E-09 1.25E-10 3.14E-10 1.62E-09 6.09E-09 1.49E-08

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 9 Table 2.2.2-1c: Mean and Fractile Base Rock Seismic Hazard Curves for 10 Hza Farley (LCI, 2013a)

SA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 3.64E-02 2.32E-02 2.96E-02 3.63E-02 4.37E-02 4.83E-02 0.001 2.54E-02 1.49E-02 1.95E-02 2.49E-02 3.14E-02 3.63E-02 0.005 7.87E-03 3.37E-03 4.83E-03 7.55E-03 1.08E-02 1.36E-02 0.01 3.91E-03 1.16E-03 1.84E-03 3.47E-03 5.91E-03 8.23E-03 0.015 2.33E-03 5.42E-04 9.24E-04 1.90E-03 3.68E-03 5.66E-03 0.03 7.72E-04 1.32E-04 2.35E-04 5.27E-04 1.15E-03 2.42E-03 0.05 2.94E-04 4.70E-05 8.12E-05 1.84E-04 4.01E-04 1.01 E-03 0.075 1.29E-04 1.92E-05 3.47E-05 7.89E-05 1.79E-04 4.37E-04 0.1 7.12E-05 9.93E-06 1.90E-05 4.43E-05 1.04E-04 2.25E-04 0.15 3.18E-05 3.79E-06 8.35E-06 2.13E-05 5.05E-05 9.37E-05 0.3 9.02E-06 5.66E-07 2.32E-06 6.54E-06 1.51 E-05 2.53E-05 0.5 3.63E-06 1.18E-07 8.72E-07 2.68E-06 6.17E-06 1.01 E-05 0.75 1.68E-06 3.14E-08 3.84E-07 1.21 E-06 2.88E-06 4.77E-06 1

9.37E-07 1.15E-08 2.01 E-07 6.73E-07 1.64E-06 2.68E-06 1.5 3.82E-07 2.64E-09 7.23E-08 2.68E-07 6.73E-07 1.13E-06

3.

6.42E-08 2.53E-10 8.85E-09 3.95E-08 1.16E-07 2.13E-07

5.

1.36E-08 1.53E-10 1.38E-09 7.23E-09 2.35E-08 5.05E-08 7.5 3.34E-09 1.25E-10 3.19E-10 1.57E-09 5.75E-09 1.38E-08

10.

1.12E-09 1.01E-10 1.64E-10 5.27E-10 1.95E-09 4.90E-09

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 10 Table 2.2.2-1d: Mean and Fractile Base Rock Seismic Hazard Curves for 5 Hz at Farley (LCI, 2013a)

SA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 3.88E-02 2.42E-02 3.05E-02 3.90E-02 4.77E-02 5.20E-02 0.001 2.74E-02 1.53E-02 2.01 E-02 2.72E-02 3.52E-02 3.95E-02 0.005 8.02E-03 3.47E-03 5.05E-03 7.77E-03 1.10E-02 1.32E-02 0.01 3.79E-03 1.15E-03 1.90E-03 3.47E-03 5.66E-03 7.45E-03 0.015 2.13E-03 5.05E-04 8.85E-04 1.82E-03 3.28E-03 4.90E-03 0.03 5.94E-04 1.07E-04 1.92E-04 4.19E-04 8.85E-04 1.77E-03 0.05 1.92E-04 3.09E-05 5.75E-05 1.20E-04 2.68E-04 6.OOE-04 0.075 7.36E-05 1.13E-05 2.1OE-05 4.63E-05 1.07E-04 2.29E-04 0.1 3.75E-05 5.35E-06 1.05E-05 2.46E-05 5.66E-05 1.13E-04 0.15 1.53E-05 1.74E-06 4.19E-06 1.08E-05 2.49E-05 4.31 E-05 0.3 3.81E-06 1.98E-07 9.51E-07 2.80E-06 6.45E-06 1.05E-05 0.5 1.37E-06 3.37E-08 3.09E-07 9.93E-07 2.39E-06 3.95E-06 0.75 5.73E-07 7.66E-09 1.13E-07 4.13E-07 1.02E-06 1.74E-06

1.

2.95E-07 2.68E-09 5.20E-08 2.04E-07 5.35E-07 9.11E-07 1.5 1.07E-07 6.09E-10 1.53E-08 6.83E-08 1.92E-07 3.52E-07

3.

1.46E-08 1.53E-10 1.34E-09 7.34E-09 2.53E-08 5.42E-08

5.

2.64E-09 1.13E-10 2.39E-10 1.13E-09 4.50E-09 1.08E-08 7.5 5.74E-10 9.79E-11 1.42E-10 2.84E-10 1.02E-09 2.64E-09

10.

1.77E-10 9.11E-11 1.01E-10 1.62E-10 3.73E-10 9.37E-10

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 11 Table 2.2.2-1e: Mean and Fractile Base Rock Seismic Hazard Curves for 2.5 Hz at Farley (LCI, 2013a)

SA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 3.70E-02 2.32E-02 2.80E-02 3.63E-02 4.63E-02 5.12E-02 0.001 2.53E-02 1.40E-02 1.79E-02 2.46E-02 3.33E-02 3.79E-02 0.005 6.96E-03 3.05E-03 4.31 E-03 6.73E-03 9.65E-03 1.16E-02 0.01 3.29E-03 9.93E-04 1.60E-03 2.96E-03 4.98E-03 6.64E-03 0.015 1.81 E-03 4.19E-04 7.03E-04 1.51 E-03 2.88E-03 4.25E-03 0.03 4.38E-04 6.83E-05 1.20E-04 2.96E-04 6.93E-04 1.36E-03 0.05 1.11E-04 1.51 E-05 2.80E-05 6.83E-05 1.67E-04 3.90E-04 0.075 3.35E-05 4.43E-06 8.72E-06 2.04E-05 5.12E-05 1.16E-04 0.1 1.44E-05 1.84E-06 3.79E-06 9.11E-06 2.32E-05 4.63E-05 0.15 4.89E-06 4.90E-07 1.20E-06 3.33E-06 8.35E-06 1.51 E-05 0.3 1.01 E-06 3.84E-08 1.92E-07 6.64E-07 1.77E-06 3.23E-06 0.5 3.28E-07 5.05E-09 4.70E-08 1.98E-07 5.91E-07 1.10E-06 0.75 1.27E-07 1.08E-09 1.36E-08 7.03E-08 2.25E-07 4.56E-07

1.

6.25E-08 3.95E-10 5.27E-09 3.09E-08 1.10E-07 2.32E-07 1.5 2.12E-08 1.53E-10 1.27E-09 8.60E-09 3.73E-08 8.47E-08

3.

2.55E-09 1.01E-10 1.69E-10 7.77E-10 4.13E-09 1.13E-08

5.

4.12E-10 9.11E-11 1.08E-10 1.90E-10 6.93E-10 2.01E-09 7.5 8.16E-11 9.11E-11 1.01E-10 1.53E-10 2.19E-10 4.90E-10

10.

2.34E-11 9.11E-11 1.01E-10 1.53E-10 1.55E-10 2.32E-10

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 12 Table 2.2.2-1f: Mean and Fractile Base Rock Seismic Hazard Curves for 1 Hz at Farley (LCI, 2013a)

SA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 2.34E-02 1.08E-02 1.57E-02 2.32E-02 3.09E-02 3.63E-02 0.001 1.45E-02 6.64E-03 9.51E-03 1.42E-02 1.92E-02 2.35E-02 0.005 4.08E-03 1.05E-03 1.87E-03 3.79E-03 6.26E-03 8.12E-03 0.01 1.93E-03 2.42E-04 5.35E-04 1.57E-03 3.33E-03 4.90E-03 0.015 1.05E-03 8.60E-05 2.04E-04 7.23E-04 1.92E-03 3.09E-03 0.03 2.40E-04 1.13E-05 2.84E-05 1.18E-04 4.19E-04 8.72E-04 0.05 5.55E-05 2.22E-06 5.35E-06 2.25E-05 8.72E-05 2.32E-04 0.075 1.41 E-05 5.66E-07 1.32E-06 5.42E-06 1.98E-05 6.26E-05 0.1 4.98E-06 2.07E-07 4.98E-07 1.98E-06 6.93E-06 2.19E-05 0.15 1.16E-06 4.50E-08 1.29E-07 4.83E-07 1.84E-06 4.70E-06 0.3 1.46E-07 2.72E-09 1.13E-08 5.75E-08 2.46E-07 5.91E-07 0.5 4.15E-08 3.19E-10 1.79E-09 1.31E-08 6.54E-08 1.82E-07 0.75 1.51 E-08 1.53E-10 4.56E-10 3.63E-09 2.25E-08 7.03E-08

1.

7.07E-09 1.23E-10 2.13E-10 1.40E-09 9.93E-09 3.47E-08 1.5 2.24E-09 1.01E-10 1.53E-10 3.79E-10 2.84E-09 1.13E-08

3.

2.44E-10 9.11E-11 1.01E-10 1.53E-10 3.19E-10 1.25E-09

5.

3.72E-11 9.11E-11 1.01E-10 1.53E-10 1.53E-10 2.76E-10 7.5 7.12E-12 9.11E-11 9.11E-11 1.53E-10 1.53E-10 1.55E-10

10.

2.01E-12 9.11E-11 9.11E-11 1.53E-10 1.53E-10 1.53E-10

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 13 Table 2.2.2-1g: Mean and Fractile Base Rock Seismic Hazard Curves for 0.5 Hz at Farley (LC 2013a)

SA(g)

MEAN 0.05 0.16 0.50 0.84 0.95 0.0005 1.21 E-02 6.36E-03 8.47E-03 1.16E-02 1.57E-02 1.92E-02 0.001 7.74E-03 3.52E-03 4.90E-03 7.45E-03 1.05E-02 1.31 E-02 0.005 2.42E-03 2.80E-04 6.73E-04 2.04E-03 4.13E-03 5.83E-03 0.01 1.06E-03 4.70E-05 1.44E-04 6.83E-04 2.04E-03 3.33E-03 0.015 5.40E-04 1.40E-05 4.63E-05 2.72E-04 1.04E-03 1.92E-03 0.03 1.13E-04 1.44E-06 4.90E-06 3.42E-05 1.87E-04 5.05E-04 0.05 2.52E-05 2.57E-07 8.12E-07 5.75E-06 3.47E-05 1.20E-04 0.075 6.26E-06 6.09E-08 1.87E-07 1.25E-06 7.45E-06 2.92E-05 0.1 2.14E-06 2.01E-08 6.45E-08 4.19E-07 2.53E-06 9.51E-06 0.15 4.50E-07 3.84E-09 1.44E-08 8.98E-08 6.17E-07 1.90E-06 0.3 4.26E-08 2.60E-10 1.11E-09 7.23E-09 5.50E-08 2.1OE-07 0.5 1.10E-08 1.25E-10 2.04E-10 1.34E-09 1.11E-08 5.91E-08 0.75 3.93E-09 1.01E-10 1.53E-10 3.79E-10 3.19E-09 2.1OE-08

1.

1.85E-09 9.11E-11 1.13E-10 2.01E-10 1.31E-09 9.37E-09 1.5 5.97E-10 9.11E-11 1.01E-10 1.53E-10 3.84E-10 2.72E-09

3.

6.76E-11 9.11E-11 9.79E-11 1.53E-10 1.53E-10 3.42E-10

5.

1.08E-11 9.11E-11 9.11E-11 1.53E-10 1.53E-10 1.55E-10 7.5 2.13E-12 9.11E-11 9.11E-11 1.53E-10 1.53E-10 1.53E-10

10.

6.15E-13 9.11E-11 9.11E-11 1.53E-10 1.53E-10 1.53E-10 Table 2.2.2-2: Mean Mw and distance values for the high frequency cases (LCI, 2013b).

(HF) and low frequency (LF) 10"4 UHRS 10- UHRS 10"6 UHRS Low Frequency M 7.4*

7.4 7.5 Low Frequency R (km) 520 480 450 High Frequency M 6.4 6.0 6.0 High Frequency R (kin) 140 33 15 M and R calculated for R>100 km per NRC (2007), because the contribution to hazard for R>100 km is more than 5% of the total hazard.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 14 1E-2 Total Mean Rock Hazard by Frequency at Farley w'

U a'

a' C'

C 1E-3 IE-4

-25 Hz

-10 Hz

- 5 Hz

-PGA

-2.5 Hz

-1 Hz

-0.5 Hz 1E-5 -i--

1E-6 1E-7

+-

-- I 0.01 0.1 1

10 Spectral acceleration (g)

Figure 2.2.2-1: Mean base rock hazard curves for frequencies of 0.5, 1, 2.5, 5, 10, 25 and 100 (PGA)

Hz at Farley at 5% spectral damping.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 15 2.3 Site Response Evaluation A site response analysis was performed for the Farley site following the guidance contained in Seismic Enclosure 1 of the 3/12/2012 50.54(f) Request for Information and in the SPID (EPRI, 2013a) for nuclear power plant sites that are not sited on hard rock (defined as 2.83 km/sec or 9,200 feet/sec).

2.3. 1 Description of Subsurface Material SNC Calculation SC-SNC539158-004 (SNC, 2014a) is the source of the information presented in the following section.

Available site specific subsurface data were obtained from subsurface exploration for the FSAR (SNC, 2014f) and subsequent studies carried out for the independent spent fuel storage installation (ISFSI) foundations (SNC, 2001). However, these data are limited with regard to the determination of dynamic properties and a site-specific shear wave velocity (Vs) profile. For example, the previous site explorations extended only to an elevation of -150 feet, with plant grade at El. 155 feet (note, all elevations herein are with respect to mean sea level). Data included field and laboratory test results on representative samples from soil borings. The geologic conditions below El. -150 feet were developed for the FSAR using data from regional oil test wells and pilot holes drilled at the site for onsite water wells. A search of public records disclosed no recent nearby subsurface data. Historic subsurface data from nearby deep boreholes in Houston County were obtained from the State of Alabama Oil and Gas Board in Tuscaloosa, Alabama. These data included electric logs (e.g., resistivity, spontaneous potential (SP)), gamma ray logs, sonic logs, and stratigraphic (sample) logs. Table 2.3.1-1 provides a summary of the available data from three deep boreholes in proximity to the Farley site.

Based on the southerly offset distances of the wells from the Farley site, the changes in elevations due to dip range from about 23 to 288 feet as summarized in Table 2.3.1-1. These elevation changes are a function of the dip projected south along the offset distance, from the Farley site to the wells. For purposes of developing the stratigraphy of the soil/rock column at the site, these changes in elevation of stratigraphic units from the boreholes to the site were considered negligible due to the low angle of regional dip. The elevations of stratigraphic units at each borehole are not adjusted to account for dip and are assumed to be the same at the site.

Borehole 1394, to a depth of about 3,200 feet, contained sonic data that were converted to Vs data. Since borehole 1394 did not contain a sample log, the sample logs from boreholes 238 and 186, along with the SP and resistivity logs, were used to correlate material types and geologic units to borehole 1394. Stratigraphy from boreholes 238 and 186 was used below the termination depth of borehole 1394.

FSAR Section 2.5.1.2.2 provides a description of the geologic materials underlying the site to a depth of about 1,150 feet below plant grade based on; 1) subsurface exploration data near surface and 2) pilot holes drilled for water wells at the site to a depth of about 1,150 feet.

Stratigraphy below this depth was developed based on data from the nearby boreholes 1394,

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 16 238, and 186, and projected to the site as described above. Generally, the materials underlying the site consist of alternating layers of uncemented sands, clays, and indurated sediments, including claystone, siltstone, limestone and shale, typical of Coastal Plain sediments. These alternating layers vary within the strata such that sand, clay, limestone, and sandstone may be present within the same geologic formation. In addition, the thicknesses of these materials vary as shown in FSAR Figure 2B4-14. In this figure, the Lisbon Formation consists of siltstone, sandstone, limestone, and dense sand varying in thickness from about 10 feet to about 40 feet.

This figure also illustrates that the thickness of these materials varies both laterally and vertically. This variation in thickness and material type generally appears to be present throughout the soil/rock column as indicated on the sample logs for 186 and 238. Smith (1998) provides subsurface stratigraphy in the Dothan Area of Houston County. Dothan is about 16 miles west of the Farley Nuclear Plant. Generally, the layer thickness is reported to vary from about +/- 3 to +/- 25 percent. A best estimate summary of strata thicknesses and material descriptions are provided in Table 2.3.1-2. A +/- 10 percent variation in stratum thickness is recommended.

The groundwater level in the plant area is reported in FSAR Subsection 2B.6.1 as a "normal groundwater level" at El. 125 feet. The design groundwater level, as noted per FSAR Subsection 2B.6.1 is at El. 140 feet.

Table 2.3.1-1: Summary of NearbyBoreholes Permit No (Borehole No),

Southerly Offset Dist.

Well Name, (mi) I Change in El. Due Date logs Reor Inte Approx Distance to Dip (feet)

Logged Available Depth (feet)

238,

-2.3/

Resistivity 377 - 4012 A.L. Snell #1, 23 1950 SP 377-4012 4.3 miles south Sample 0 - 4012

1394, Resistivity 319-3200 P.E. Mixon #1,

-5.5 /

SP 319 - 3200 55 to 138 Gamma 2500-3060 18.8 miles west southwest 196639 39 Sonic 319-3193

186,

-11.5/

Resistivity 217-8099 E.P. Kirkland #1, 15 1949 SP 217-8099 20.5 miles southwest Sample 0 - 8100 Dip offset range based on dip of 10 to 25 feet per mile (SNC, 2014f)

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 17 Table 2.3.1-2: Best Estimate Plant Area Stratig aphy Elevation (ft)

Depth (ft)

Geologic Formation Top Base Top Base Thickness (ft)

(Group)

Material Description 185 0

i SSE Control Point (at Surface)

Overburden Sand, silty sand, clayey 185 95 0

90 90 (Fill and sand, and clay Residuum) 95 70 90 115 25 General foundation level SLisbon Calcareous and sandy 0 -25 115 210 95 (Claiborne) claystone; silty sandstone; sandstone; and uncemented sand Sandy, fossiliferous limestone; sand and clay Tallahatta beds; sandy, calcareous,

-25

-160 210 345 135 (Claiborne) claystone; and glauconitic, fossiliferous, calcareous sand H

hg (Bashi marl) Fossiliferous,

-160

-199 345 384 39 tcigbee calcareous, glauconitic, (lxsand and sandstone Silty and sandy 9 -carbonaceous clay;

~Tuscahoma

-199 i-439 384 624 240 calcareous, silty sandstone; S(Wilcox) and coarse-grained fossiliferous gravelly sand Medium to coarse sand;

~Nanafalia

-439

-554 624 739 115 (anacax) gravelly sand; and sandy and fossiliferous limestone Sandy and fossiliferous 4

79 limestone and coarse-

-554

-854 739 11,039 300 Formation

-554oMatioy grained sand and (dymicaceous, sandy clay Fine to coarse-grained micaceous, glauconitic, SProvidence fossiliferous sand; sandy,

-854

-939 1,039 1,124 85 Formation (Selma) calcareous, fossiliferous (e

)clay; and sandy, fossiliferous limestone Ripley Fine to medium-grained,

-939

-2,354 1,124 2,539 1,415 Formation calcareous micaceous, (Selma) glauconitic sand;

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 18 Elevation (ft)

Depth (ft)

Geologic Formation Top Base Top Base Thickness (ft)

(Group)

Material Description sandstone; and calcareous

_sandy clay Fine grained micaceous

-2,354

-2,554 2,539 2,739 200 Eutaw i

sandstone, Shale, glauconitic and fossiliferous sandstone,

-2,554

-3,014 2,739 3,199 460 Tuscaloosa fosiif sandstone glauconitic sand, coarse sand and gravel i i Sand, gravel, shale,

-3,014

-7,114 3,199 7,299 4,100 Cretaceous sandtrae, shale,

_______sandstone, micaceous clay Sandstone, claystone,

-7,114

-7,664 7,299 7,849 550 Paleozoic sandy shale, sand, micaceous shale

-7,664 7,849 Ordovician-Calcareous sandstone, age Period carbonaceous shale Notes: 1.

2.

3.

Stratigraphy and material descriptions from FSAR 2.5.1.2.2.

Stratigraphy below Ripley Formation (italic entries) taken from boreholes 238 and 186.

The geologic group was used to correlate materials between the various boreholes.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 19 2.3.2 Development of Base Case Profile and Nonlinear Material Properties SNC Calculation SC-SNC539158-004 (SNC, 2014a) is the source of the information presented in the following section.

The base case profiles for the Farley site were based on existing subsurface information contained in the FSAR for Units 1 and 2 (SNC, 2014f), as well as additional and more recent information obtained for the investigation carried out for the ISFSI study (SNC, 2001). The following paragraphs summarize that information.

Representative samples of the subsurface materials were tested in the laboratory to determine their classification in accordance with the Unified Soil Classification System (USCS, ASTM D-2487) during the explorations for Units 1 and 2 and recent investigations for the ISFSI (SNC, 2001). In addition, representative samples of the backfill soils were tested to determine their classification, during backfill construction. Table 2.3.2-1 provides a material description for the predominate soil type of each major geologic unit.

FSAR Subsection 2B7.2.1 notes the soil dry unit weight values at the site range from 85 to 120 pounds/foot3 (pcf) with soil moisture contents ranging from 10 to 30 percent. FSAR Figure 2B5B-7 provides estimated unit weight values for the near surface soils at various locations around the plant area. FSAR Tables 2B-10 and 2B-19 provide maximum dry unit weight values and optimum moisture content values for compacted fill (fill materials C-1, C-2, C-3, and C-5).

These values range from 106 pcf at 18.1 percent to 120 pcf at 11.8 percent moisture with corresponding total unit weight values of about 125 pcf and 134 pcf, respectively. Based on these FSAR references, a best estimate total unit weight of 125 pcf is recommended for the fill and overburden soils and the Lisbon Formation.

Based on the descriptions of the materials provided in FSAR Section 2.5.1.2.2 and the sample logs from boreholes 238 and 186, as summarized above in Table 2.3.1-2, a best estimate total unit weight value of 125 pcf is recommended for the underlying materials considering a distribution of sand, clay, limestone, siltstone, and sandstone (Navfac, 1986). Based on experience, a best estimate total unit weight value of 165 pcf is recommended for the Paleozoic materials at the base of the column. Unit weight values are summarized in Table 2.3.2-1.

Shallow shear wave velocity data are available, but deep data are limited to an offsite, but nearby petroleum well. FSAR Figure 2B5B-7 provides Vs values for various strata and locations at the site, including overburden, backfill, and the Lisbon Formation. The shear-and compression-wave velocitiy (Vs and Vp, respectively) values, along with Poisson's ratio values, from this figure have been reproduced in Table 2.3.2-2. Notes on the figure indicate that velocity data were obtained using refraction, uphole, and cross-hole methods. Raw velocity data were not available for review and no new velocity data were obtained for this study. The data are from the Plant Area (PA), River and Pond Intake, and the Pond Dam and Dike areas. These data from all areas along with Vs data from the ISFSI study (SNC, 2001) are combined into one plot and the best estimate Vs profile through the overburden/fill soils (including the fill) and weathered rock/Lisbon Formation is presented in Figure 2.3.2-1. This figure also illustrates the

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 20 recommended variation in the Vs profile. The variation is established using a logarithmic standard deviation of 0.35 (oyn = 0.35) for the overburden materials (above the Lisbon Formation) and a logarithmic standard deviation of 0.5 (OCn = 0.5) for Lisbon Formation. This is based on guidance described in Appendix B of the SPID (EPRI, 2013a). A value of 0.35 is used for the overburden materials based on the consistency of the site specific data. A value of 0.5 is used for Lisbon Formation given the variability of the site specific data.

Shear wave velocity data below the exploration depth at the plant was obtained from nearby historic data. Specifically, a downhole seismic (sonic) record from borehole 1394 near the site was obtained from the State of Alabama Oil and Gas Board as discussed previously. Based on the elevation of the drilling platform, depths were converted to elevation and these elevations were correlated to site data. Sonic data were converted to Vs data. The Poisson's ratio values, used to calculate Vs from the sonic data, were estimated based on material types presented in the sample log from borehole 238. The Vs profile developed from these sonic data is presented (green trace) in Figure 2.3.2-2. The profile identified with a red dotted line, labeled "Incremental Average - from Sonic Data", is a stepped profile averaged from discrete depth intervals. The profile below the "Incremental Average" is identified with a blue line and is labeled "Extrapolated". This "Extrapolated" profile was developed by projecting the slope in the lower portion of the "Incremental Average" profile to the Ordovician contact with the assumption that a Vs value of 9,200 fps occurs at the Ordovician contact - an approximate depth of 7,850 feet (El.

-7,664 feet). The profile identified with a heavy black line, labeled "Stepped Average", is a stepped profile averaged over large depth intervals. The data appear consistent with deep velocity data obtained elsewhere in the Coastal Plain in terms of consistency and increase in velocity with depth.

Figure 2.3.2-3 combines the shallow site-specific FSAR Vs data from Figure 2.3.2-1 with the deep interpreted sonic Vs data from Figure 2.3.2-2. The recommended variation (best estimate (BE) +/- 1 logarithmic standard deviation (/,n))

of Vs is also illustrated. As previously discussed, a logarithmic standard deviation of 0.35 is used for all overburden materials except for the Lisbon Formation where a logarithmic standard deviation of 0.5 is used. For discussion of the lower range and upper range profiles, see section 2.3.3.

The upper portion of the Vs profile, to Elevation -200 feet, is illustrated in Figure 2.3.2-4 at a smaller scale to provide clarity. The 16th (BE - sigma), 5 0 th (BE), and 8 4th (BE + sigma) soil/rock profiles are illustrated in Figure 2.3.2-3 and tabulated in Table 2.3.2-3. Also included in Table 2.3.2-3 are the 10th and 90th percentiles, which are used as the lower-range and upper-range profiles, as recommended in Appendix B of the SPID (EPRI, 2013a). Note that all Vs profiles should be capped at 9,200 fps.

For the randomization process (Appendix B-4.1 of the SPID (EPRI, 2013a)) it is suggested that the empirical or/v, is about 0.25 from the ground surface to a depth of about 15m (50 feet) where it reduces to 0.15, however, it is suggested herein that 0.25 be used to a depth of 90 feet and then reduced to 0.15 below that level for the remainder of the column. Further, a bound or cap of +/-2 unWv should be imposed on the profile to prevent unrealistic cases. Even with this

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 21 restriction, each randomization should be checked against the available site data to ensure unrealistic Vs profiles are not included.

2.3.2.1 Shear Modulus and Damping Curves SNC Calculations SC-SNC539158-004 (SNC, 2014a) and SC-SNC539158-006 (SNC, 2014b) are the source of the information presented in the following section.

2.3.2. 1.1 Fill and Overburden Shear modulus degradation and material damping relationships for fill soils are presented in FSAR Tables 2B-5, 2B-6, 2B-20, and 2B-21. The values of shear modulus degradation (G/Gmax) vs shear strain are plotted in Figure 2.3.2-5. Damping ratio values vs. shear strain are plotted in Figure 2.3.2-6. Note that FSAR data are represented with prefixes of C-1, C-2, C-3 and C-5 and represent test results on fill materials. These data were obtained using resonant column (RC) and cyclic triaxial test methods.

Published relationships (EPRI, 1993) of shear modulus degradation and material damping for granular and cohesive soils are plotted in Figure 2.3.2-5 and Figure 2.3.2-6 for comparison with site specific data. Granular soils are represented with the depth intervals of 0-20 feet, 20-50 feet, 50-120 feet, and 120-250 feet. Cohesive soils are represented with plasticity index (PI) values of 15 and 30. Note that the site specific damping values plot above (more damping) the published curves. Current understanding of the test methods used at the time suggests that these values are artificially high due to unaccounted for system damping. Therefore, based on the comparison of these data and to account for uncertainty, the shear modulus degradation and material damping of the fill and overburden soils should be evaluated using two sets of published curves - EPRI (1993) "20-50 feet" and "50-120 feet", both equally weighted. Note in Figure 2.3.2-5 and Figure 2.3.2-6, the curves labeled 0-20 feet through 120-250 feet are from EPRI (1993); the others are from site-specific testing on backfill samples from the Farley site.

The recommended shear modulus degradation and damping relationships for the fill and overburden are tabulated in Table 2.3.2-4.

2.3.2.1.2 Lisbon to Ripley Shear modulus degradation and material damping relationships for native (in situ) materials are presented in FSAR Figure 2B5B-7 (SNC, 2014f). These data are reproduced here in Table 2.3.2-5. FSAR Section 2B.7.2.2 (SNC, 2014f) describes the samples represented by the test results as "fresh rock specimens", soft clayey siltstone, and hard sandstone. Similar to the fill soils, these data were obtained from cyclic triaxial and resonant column tests. Figure 2.3.2-7 illustrates these data in terms of G/Gmax vs shearing strain and damping ratio in percent vs shear strain. Additional modulus reduction and damping ratio relationships from Idriss and Boulanger (2010) and Stokoe et al. (2003) are illustrated on Figure 2.3.2-7. Data from Idriss and Boulanger (2010) were scaled from Figure B-15 of that reference, while data from Stokoe (2003) were obtained using RCTS test methods on rock materials.

In reviewing Figure 2.3.2-7, the site specific data behave similarly to the Idriss and Boulanger (2010) results for both shear modulus degradation and damping versus shear strain. For

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 22 damping relationships, most of the site specific data range between 3 and 6 percent damping.

Again, given the current understanding of the test methods used at the time, these values are believed to be artificially high due to unaccounted for system damping. Therefore, for materials in the Lisbon to Ripley Formations, it is recommended to use the shear modulus degradation and damping relationship taken from Idriss and Boulanger (2010), as tabulated in Table 2.3.2-6.

2.3.2.1.3 Variation in Material Properties The variation of shear modulus degradation and material damping with shear strain is evaluated to develop a standard deviation for these properties. Site specific data presented in Figure 2.3.2-5 and Figure 2.3.2-6 were grouped according to shear strain. The mean and standard deviation of these groups were determined. Based on these results, the following guidelines are recommended for the variation of shear modulus reduction and damping with shear strain:

G/Gmax o

for shear strains < 0.0001, coefficient of variation (COV) = 0 o

for shear strains > 0.0001 and < 0.001, COV linear log relationship between 0 and 0.15 o

for shear strains> 0.001, COV = 0.15 Damping o

for all shear strains, COV = 0.2 The uncertainties in G/Grnax and damping are expected to be consistent throughout the soil/rock column. Thus, the variations outlined above should be applied to subsurface materials from the overburden through the Ripley Formation. Below the Ripley Formation, where shear modulus is assumed to remain constant with strain (no degradation), only the variation in damping is applied.

2.3.2.2 Kappa SNC Calculation SC-SNC539158-006 (SNC, 2014b) is the source of the information presented in the following section.

Based on the guidance in the Section B-5.1.3.1 of the SPID (EPRI, 2013a) the Farley site is considered a deep soil site thus a median kappa value of 0.04 sec is considered for the soil column. As specified in Section B-5.1.3.2 of the SPID (EPRI, 2013a) a natural log standard deviation of 0.4 was used to estimate the upper and lower range values of kappa. Table 2.3.2-7 summarizes the kappa values used for the site response analysis. This range encompasses the values (e.g., 0.060, 0.054, and 0.052 sec) listed in the SPID (EPRI, 2013a) for deep soil sites.

An additional estimate of the total site kappa may be made using the empirical relationship provided by Campbell (2009). Using this relationship and a profile thickness of 7849 ft, a total site kappa of 0.151 sec is calculated and is significantly larger (indicating more damping) than the values selected for consideration.

In the site response analyses, the material above the depth of 2539 ft is modeled as nonlinear with strain dependent shear-modulus reduction and material damping curves as discussed above in Section 2.3.2.1. Below the depth of 2539 ft, the material is considered to be linear for all analyses with damping ratio calibrated to provide the prescribed total site kappa at the surface of the site.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 23 Table 2.3.2-1: Summary of Total Unit Weight and Poisson's Ratio Values, Depth (feet)

Thickness G

u Total Unit Poisson's Top Base (feet)

Geologic unit Weight (pcf)

Ratio 0

SSE Control Point (at Surface) 0 90 90 Overburden (Fill and Insitu) 125 0.37 90 210 120 Lisbon 125 0.25 210 345 135 Tallahatta 125 0.25 345 384 39 Hatchetigbee 125 0.25 384 624 240 Tuscahoma 125 0.30 624 739 115 Nanafalia 125 0.25 739 1,039 300 Clayton 125 0.30 1,039 1,124 85 Providence 125 0.30 1,124 2,539 1415 Ripley 125 0.25 2,539 2,739 200 Eutaw 125 0.25 2,739 3,199 460 Tuscaloosa 125 0.25 3,199 7,299 4100 Cretaceous 125 0.25 7,299 Paleozoic and older 165 0.25

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 24 Table 2.3.2-2: Summary of Site Velocity Data(3)

Area Formation Elevation (feet)

VP V.

Poisson's From To (ft/sec)

(ft/sec)

Ratio (v)

Plant Area Overburden 175 150 1300 680 0.36 Plant Area Overburden 150 130 2100 970 0.36 Plant Area Wx Rock 1) 130 95 5000 2520 0.36 Plant Area Lisbon 95 65 10000 5360 0.33 Plant Area Lisbon

> 65 0 2) 6400 2000 0.4 Plant Area Backfill 155 125 2100 950 0.37 Pond Intake Overburden 180 175 1200 550-500 0.37 Pond Intake Overburden 175 130 2500 650-850 0.43 Pond Intake Overburden 130 100 5000 no data no data Pond Intake Lisbon

> 100 502) 8000 no data no data 1200-River Intake Overburden 110 100 1300 550-800 0.37 River Intake Overburden 100 80 2500 900 0.43 1400-River Intake Lisbon

> 80 55 2) 6200 1800 0.47-0.48 2200-River Intake Lisbon

> 55

02) 7200 2500 0.45 2200-Dam Overburden 140 120 2800 850-950 0.41 Dam Overburden 120 100 5000 4) 850-950 0.48 6200-Dam Lisbon

> 100 502) 6600 2200 0.43 2800-Dike Overburden Surface 130 3500 800-1000 0.45 Dike Overburden 130 100 500066ý 900 0.48 Dike Lisbon

> 100__

502) 62004)1 1350 0.48 Notes:

1) Wx - weathered rock
2) assumed elevation
3) data were reproduced from FSAR Figure 2B5B-7
4) VP likely represents VP of water (-5,000 fps)

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 25 Table 2.3.2-3: SoilRock Column Vs Profile Profiles 10th 16 th 50th 8 4 th 90th Elevation Percentile Percentile Percentile Percentile Percentile (feet)

(ft/sec)

(ft/sec)

(ft/sec)

(ft/sec)

(ft/sec) 185 518 572 812 1152 1273 95 1591 1831 3018 4976 5724 65 1038 1147 1628 2310 2553 50 1180 1304 1850 2625 2901 0

2321 2565 3640 5165 5709

-66 2033 2247 3189 4525 5001

-132 2560 2829 4015 5698 6297

-826 2581 2853 4048 5744 6349

-1716 2487 2749 3901 5536 6118

-2316 2899 3204 4546 6451 7130

-3316 3188 3523 5000 7095 7842

-4716 3507 3876 5500 7805 8626

-5916 3826 4228 6000 8514 9410

-7116 4017 4440 6300 8940 9880

-7664 5866 6483 9200 13055 14428

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 26 Table 2.3.2-4: Best Estimate Shear Modulus and Damping Relationships for Fill and Overburden Soils Modulus Modulus Shear Reduction Damping Reduction Damping Strain (G

)

(%)

(

%Imx

)

()

(G/Gmax)

(G/Ginax)

EPRI 20-50 feet EPRI 50-120 feet 0.0001 1

1.3 1

1.15 0.0003 1

1.3 1

1.15 0.0010 0.992 1.43 0.995 1.22 0.0032 0.94 2.04 0.951 1.63 0.0100 0.815 3.67 0.867 2.86 0.0316 0.589 7.14 0.665 5.51 0.1000 0.355 12.55 0.427 10.41 0.3162 0.161 19.39 0.21 17.04 1.0000 0.065 24.9 0.089 22.86 Table 2.3.2-5: Site Specific Shear Modulus and Damping for Lisbon to Riple, Formations.

Location Sample Torsional Shearing Shearing Damping Damping oaion El Strain Strain Strain G (psi)

G (ksf)

GIGma.

Ratio Ratio (feet)

(rad)

(in/in)

(%)

(dec.)

(%)

Rv Intake 3.50E-06 3.50E-06 3.50E-04 48300 6955.2 1.000 0.054 5.4 Sandy 17 7.90E-05 7.90E-05 7.90E-03 47400 6825.6 0.981 0.055 5.5 Siltstone 2.OOE-04 2.00E-04 2.OOE-02 46300 6667.2 0.959 0.058 5.8 3.30E-07 3.30E-07 3.30E-05 617000 88848.0 1.000 0.031 3.1 81 5.70E-06 5.70E-06 5.70E-04 606000 87264.0 0.982 0.038 3.8 Pond 2.OOE-05 2.OOE-05 2.OOE-03 596000 85824.0 0.966 0.039 3.9 Spillway I Sandston 3.1OE-07 3.1OE-07 3.1OE-05 655000 94320.0 1.000 0.038 3.8 Sandstone 81 3.40E-06 3.40E-06 3.40E-04 644000 92736.0 0.983 0.036 3.6 2.1OE-05 2.1OE-05 2.1OE-03 638000 91872.0 0.974 0.038 3.8 1.60E-06 1.60E-06 1.60E-04 124400 17913.6 1.000 0.014 1.4 Pond Pnd 7.90E-06 7.90E-06 7.90E-04 123400 17769.6 0.992 0.017 1.7 Intake I 52 Sandstone 8.30E-05 8.30E-05 8.30E-03 118000 16992.0 0.949 0.016 1.6 2.20E-04 2.20E-04 2.20E-02 117900 16977.6 0.948 0.024 2.4 6.60E-06 6.60E-06 6.60E-04 16500 2376.0 1.000 0.058 5.8 Plant 2.80E-05 2.80E-05 2.80E-03 16500 2376.0 1.000 0.059 5.9 Clayey 38 Claye 5.30E-05 5.30E-05 5.30E-03 16400 2361.6 0.994 0.060 6.0 Siltstone 4.1OE-04 4.1OE-04 4.1OE-02 16000 2304.0 0.970 0.065 6.5 Dam/

3.40E-06 3.40E-06 3.40E-04 36700 5284.8 1.000 0.041 4.1 Clayey 22 6.90E-05 6.90E-05 6.90E-03 36700 5284.8 1.000 0.055 5.5 Siltstone 2.40E-04 2.40E-04 2.40E-02 36500 5256.0 0.995 0.055 5.5 NO I TS: 1. uata in columns 1,2,3,6,9 taken trom -FSAH Figure 213b51-7

2. Torsional strain in radians taken as equal to shearing strain
3. Gmax taken as value of G at lowest strain value

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 27 Table 2.3.2-6: Best Estimate Shear Modulus and Damping Relationships for Lisbon to Ripley Formations.

Shear Modulus Shear Strain Reduction Strain Damping (y)

(G/Gm.x)

()

1 0.0001 1.000 0.0001 0.375 0.0003 1.000 0.001 0.9 0.001 1.000 0.01 1.5 0.003 0.992 0.1 3.0 0.01 0.96 1.0 5.0 0.03 0.931 0.1 0.892 1.0 0.777 Table 2.3.2-7: Site Column

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 28 200 El GD

.9-S

'a 180.

160 140 120 1001 80 60 ~

4o 4-20 0

-4 IOverbu (01B),

Fill, and Lisbon Formation 4

I I

3000 4000 5000 1000 2000 6000 Shear Wave Velocity (fps) --

PA Lisbon

- Dike Lisbon PA OB Dam OB River Intake OB

  • ..4.. Fugro ISFSI Data Best Estimate + sd

- -" - Dam Lisbon

-- *--River Intake Lisbon PA Fill Dike OB Pond Intake OB Best Estimate Best Estimate - sd Figure 2.3.2-1: Site Vs Data for Overburden and Lisbon Formation

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 29 Vs (ft/s) 6.000 8,000 0

2,000 4,000 10,000 250

-250

-750

-1,250

-1,750

-2,250

-2,750

-3,250

-3,750 U

.2 3 -4,250

-4,750

-5,250

-5,750

-6,250

-6,750

-7,250

-7,750

-8,250 Sonic Vs Profile Avg-from Sonic Data Stepped Average

-Extrapolated Figure 2.3.2-2: Deep Vs Profile from Sonic Data

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 30 Shear Wave Velocity (fps) 0 2000 4000 6000 8000 10000 12000 14000 200 7

-800

-1800

-2800

-3800

  • -4800 --

-5800

-6800 -

-7800 M I I

II II I

I I

I I

IIII r.

4 i BE+ Sigma

- BE - Sigma

-BE 6-I f

-8 8 0 0 Figure 2.3.2-3: Best Estimate Vs Profile for Farley Plant Site

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 31 Shear Wave Velocity (fps) 0 2000 4000 6000 8000 10000 200 150 100 50 ci ci

.4-0 4-m ci w

0 Pond Dam/Dike crest elevation 195 feet, spillway crest elevation 185 feet o-I.....

o......*....

e.

.o.

e

.e.

Plant Grade elevation 154.5 feet

-i

-River Intake Grade elevation 115 feet I-S I

BE+ Sigma BE-Sigma I

BE A

I I--

I I

I II 0I I

0 I

£ 8

-50

-100

-150

-200 Figure 2.3.2-4: Best Estimate Vs Profile to Elevation -200 feet

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 32 0.9 0.8 0.7 ---- -..

0.6 0.501 0.3 0.2 0.1 4~

~

01 0.00001 0.0

.w 0.7-f o

t......

-1 0.00100 0.01000 0.10000 1.00000 Shear Strain (%)

0-20 ft 20-50 ft 50-120 ft 120-250 ft

- P1=15

- - - PI=30 N

C-1/RC A

C-2/RC 0

C-5/RC C-1/Cy-Trx C-2/Cy-Trx 0

C-3/Cy-Trx Figure 2.3.2-5: Shear Modulus Degradation Relationships - Fill and Overburden 35 0

30 25 20

~10 0

0.00001 M

0.00010 0.00100 0.01000 0.10000 1.00000 Shear Strain (%)

0-20 ft 20-50 ft 50-120 ft 120-250 ft P1=15

- PI=30 U

C-1/RC A

C-2/RC Figure 2.3.2-6: Damping Relationships - Fill and Overburden

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 33 1.0 0.9 0.8 0.7 0.6 0.5

- 0.4 E 0.3 0.2 0.1 AL A

mmý I

Min i-N1 71

-Or I 71 25 20 15 10°i 5 a 0.0 0

1.OE-05 1.OE-04 1.OE-03 1.OE-02 1.OE-01 1.OE+00 Shear Strain (%)

Sandy Siltstone

- Sandstone

- Sandstone

-Modulus Reduction, ldriss/Boulanger

- Damping, Idriss/Boulanger Sandy Siltstone Sandstone Sandstone

- -- - Clayey Siltstone

- -a- - Clayey Siltstone

- -*- - Sandstone Modulus Reduction, Stokoe Damping, Stokoe Clayey Siltstone N

Clayey Siltstone Sandstone Figure 2.3.2-7: Shear Modulus Reduction and Damping Relationships (Lisbon to Ripley)

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 34 2.3.3 Randomization of Base Case Profiles SNC Calculation SC-SNC539158-006 (SNC, 2014b) is the source of the information presented in the following section.

To account for the aleatory variability in material properties that is expected to occur across a site at the scale of a typical nuclear facility, variability in the assumed shear wave velocity (Vs) profiles has been incorporated in the site response calculations. For the Farley site, simulated shear wave velocity profiles were developed from the base case profile, as presented in Section 2.3.2. The lower range and upper range profiles were defined by the 10th and 90th percentile Vs profiles as recommended by the SPID (EPRI, 2013a), presented in Table 2.3.2-3. The simulation procedure generates a set of site-specific simulated soil profiles to represent the dynamic properties of the site while considering the uncertainty associated with each of these properties, and correlations between different parameters.

Consistent with the discussion in Appendix B of the SPID (EPRI, 2013a), the Vs randomization procedure made use of Vs correlation developed by Toro (1996). The USGS C model parameters were used for this median profile, while USGS B and D were used for the upper-range and lower-range Vs profiles, respectively.

Sixty simulated Vs profiles were generated for each base case profile. These simulated Vs profiles were generated using a natural log standard deviation of 0.25 over the upper 90 feet and a natural log standard deviation of 0.15 below that depth. In the correlation model, a limit of

+/- 2 standard deviations about the median value in each layer was assumed for the limits on random velocity fluctuations. All random velocities were limited to be less than or equal to 9200 ft/sec. The thicknesses of the layers were varied considering 10% variation in thickness, and models using a bounded beta distribution. The bounds of the distribution were assumed to be separated by 4 times the standard deviation.

Given the limited geotechnical information available, the following alternatives were considered:

three base case Vs models, two sets of curves are used to model the strain-dependent behavior of the soil layers, and three different total kappa values for a total of 18 different site columns (see Table 2.3.5-1 for considered alternative site columns). As an example, the simulated Vs profiles for the lower-range, median, and upper-range Vs models is shown in Figures 2.3.3-1, 2.3.3-2, and 2.3.3-3.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 35 Farley-VsL-G1-kM Simulated Vs Profiles (Top 8625 ft)

Shear Wave Velocity [ft/sec]

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

.Simulated Median Input BE 4-E 1000 -

I 20 0

I I

- -I 3000 4000 ------.------

5 000 -- - -- - -

-i 60700

- - -- -- - -I-7000 8

6000----------

F F

1 I

F F

I I

I I

I I

Figure 2.3.3-1: Simulated shear wave velocity profiles for the lower-range velocity model.

Seismic Hazard and Screening to NL-14-0342 Report - Farley Page 36 Farley-VsM-Gl-kM Simulated Vs Profiles (Top 8625 ft)

Shear Wave Velocity [ft/sec]

3000 4000 5000 6000 7000 0

0 r 1000 2000 8000 9000 10000 1000 2000 3000 "4000 5000 6000 7000 8000 Figure 2.3.3-2: Simulated shear wave velocity profiles for the median velocity model.

Seismic Hazard and Screening to NL-14-0342 Report - Farley Page 37 Farley-VsU-Gl-kM Simulated Vs Profiles (Top 8625 ft)

Shear Wave Velocity [ft/sec]

3000 4000 5000 6000 7000 8000 9000 10000 11000 1000 2000 3000

  • '4000 5000 6000 7000 8000 Figure 2.3.3-3: Simulated shear wave velocity profiles for the upper-range velocity model.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 38 2.3.4 Input Spectra SNC Calculation SC-SNC539158-001 (SNC, 2014d) and LCI (2013b) are the sources of the information presented in the following section.

Input base rock acceleration response spectra for the site amplification analysis are developed for a suite of high frequency (HF) and low frequency (LF) cases. These cases correspond to the UHRS ground motion values for MAFE levels of 103, 104, 105, 106, 10-, and 108. Separate spectral shapes are developed for HF and LF. The HF spectral shape has been anchored to the corresponding UHRS values at 100 Hz, 25 Hz, 10 Hz, 5 Hz, and 2.5 Hz in order to reflect accurately the UHRS values. In between these frequencies, the spectrum is logarithmically interpolated using the average of the CEUS single and double corner spectral shape model given in NUREG/CR-6728 (McGuire et al., 2001) using the deaggregation information for the Farley site (LCI, 2013b). For the MAFE level of 103 the deaggregation results for the 10-4 level are adopted and for MAFE levels of 10-7 and 10-8 the results for the 10-6 level are used. For frequencies between 2.5 Hz and 0.5 Hz, the spectral amplitudes are scaled using the spectral shape anchored to the 2.5 Hz amplitude value. For frequencies between 0.5 Hz (2 sec) and 0.1 Hz (10 sec), the spectrum has been extrapolated from the 0.5 Hz spectral value to a 0.1 Hz value with a 1/T shape, where T is period.

For the LF response spectrum the spectral shape - again based on the NUREG/CR-6728 spectral shapes as given this time by the LF deaggregation information for the Farley site -- is anchored to the UHRS values at 2.5 Hz, 1 Hz, and 0.5 Hz in order to reflect accurately the UHRS values. In between these frequencies, the spectrum is logarithmically interpolated using shapes anchored to the next higher and lower frequencies. Above 2.5 Hz, the spectral amplitudes are scaled using the spectral shape anchored to the 2.5 Hz amplitude. For frequencies between 0.5 Hz (2 sec) and 0.1 Hz (10 sec), the spectrum has been extrapolated from the 0.5 Hz spectral value to a 0.1 Hz value with a 1/T shape, where T is period.

For the LF response spectrum at MAFE of 103, the above procedure as for the MAFEs of 10-and 10-8, above, results in the high-frequency end of the LF response spectrum exceeding the 10-3 HF response spectrum - including the PSHA values - at high-frequencies. Therefore, the LF spectral shape is anchored to the UHRS values at all seven ground motion frequencies (100 (PGA), 25, 10, 5, 2.5, 1, and 0.5 Hz). Again, frequencies between 0.5 Hz (2 sec) and 0.1 Hz (10 sec), the spectrum has been extrapolated from the 0.5 Hz spectral value to a 0.1 Hz value with a 1/T shape, where T is period.

The HF and LF input spectra are plotted in Figure 2.3.4-1 for the MAFE levels of 10-4, 10s, and 10.6. The digital values corresponding to these HF and LF spectra are listed in Table 2.3.4-1 for an interpolated set of 40 spectral frequencies that include the reference seven spectral frequencies of 100 (PGA), 25, 10, 5, 2.5, 1, and 0.5 Hz.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 39 Table 2.3.4-1: Input HF and LF spectra for MAFE levels of 10-4, 10-5, and 10 6 at a suite of 40 s 3ectra frequencies.

Freq. (Hz) 104 HF (g) 104 LF (g) 10 5 HF (g) 10 5 LF (g) 106 HF (g) 10-6 LF (g) 100 4.23E-02 4.23E-02 1.67E-01 1.01 E-01 6.12E-01 2.61E-01 90 4.57E-02 4.56E-02 1.80E-01 1.09E-01 6.62E-01 2.83E-01 80 5.16E-02 5.15E-02 2.04E-01 1.25E-01 7.50E-01 3.22E-01 70 6.07E-02 6.05E-02 2.40E-01 1.48E-01 8.84E-01 3.82E-01 60 7.20E-02 7.16E-02 2.85E-01 1.77E-01 1.05E+00 4.57E-01 50 8.22E-02 8.17E-02 3.25E-01 2.04E-01 1.20E+00 5.28E-01 40 8.83E-02 8.76E-02 3.49E-01 2.22E-01 1.30E+00 5.75E-01 35 8.93E-02 8.87E-02 3.53E-01 2.27E-01 1.31 E+00 5.88E-01 30 8.90E-02 8.86E-02 3.51 E-01 2.30E-01 1.31 E+00 5.94E-01 25 8.73E-02 8.73E-02 3.43E-01 2.29E-01 1.28E+00 5.93E-01 20 8.98E-02 8.82E-02 3.41 E-01 2.26E-01 1.25E+00 5.85E-01 15 9.OOE-02 8.79E-02 3.25E-01 2.18E-01 1.16E+00 5.65E-01 12.5 8.84E-02 8.69E-02 3.08E-01 2.12E-01 1.08E+00 5.47E-01 10 8.48E-02 8.48E-02 2.83E-01 2.02E-01 9.69E-01 5.21 E-01 9

8.23E-02 8.22E-02 2.68E-01 1.96E-01 9.03E-01 5.08E-01 8

7.93E-02 7.91 E-02 2.50E-01 1.90E-01 8.31 E-01 4.92E-01 7

7.56E-02 7.55E-02 2.31 E-01 1.83E-01 7.53E-01 4.73E-01 6

7.12E-02 7.12E-02 2.1OE-01 1.74E-01 6.69E-01 4.49E-01 5

6.59E-02 6.59E-02 1.86E-01 1.62E-01 5.79E-01 4.20E-01 4

6.25E-02 6.22E-02 1.62E-01 1.48E-01 4.77E-01 3.84E-01 3.5 6.OOE-02 5.97E-02 1.48E-01 1.39E-01 4.22E-01 3.61 E-01 3

5.66E-02 5.64E-02 1.33E-01 1.28E-01 3.64E-01 3.34E-01 2.5 5.19E-02 5.19E-02 1.15E-01 1.15E-01 3.01E-01 3.01E-01 2

4.22E-02 5.41E-02 9.12E-02 1.16E-01 2.38E-01 2.72E-01 1.5 3.07E-02 5.13E-02 6.43E-02 1.07E-01 1.68E-01 2.27E-01 1.25 2.45E-02 4.70E-02 5.04E-02 9.65E-02 1.32E-01 1.95E-01 1

1.82E-02 4.07E-02 3.68E-02 8.25E-02 9.57E-02 1.58E-01 0.9 1.58E-02 4.03E-02 3.15E-02 8.23E-02 8.20E-02 1.57E-01 0.8 1.34E-02 3.92E-02 2.65E-02 8.06E-02 6.88E-02 1.52E-01 0.7 1.12E-02 3.73E-02 2.17E-02 7.72E-02 5.61E-02 1.45E-01 0.6 8.98E-03 3.47E-02 1.71 E-02 7.22E-02 4.42E-02 1.35E-01 0.5 6.92E-03 3.13E-02 1.29E-02 6.54E-02 3.31E-02 1.22E-01 0.4 5.53E-03 2.50E-02 1.03E-02 5.23E-02 2.65E-02 9.76E-02 0.35 4.84E-03 2.19E-02 9.02E-03 4.58E-02 2.32E-02 8.54E-02 0.3 4.15E-03 1.88E-02 7.73E-03 3.92E-02 1.99E-02 7.32E-02 0.25 3.46E-03 1.57E-02 6.44E-03 3.27E-02 1.65E-02 6.1OE-02 0.2 2.77E-03 1.25E-02 5.15E-03 2.62E-02 1.32E-02 4.88E-02 0.15 2.07E-03 9.39E-03 3.86E-03 1.96E-02 9.93E-03 3.66E-02 0.125 1.73E-03 7.83E-03 3.22E-03 1.64E-02 8.27E-03 3.05E-02 0.1 1.38E-03 6.26E-03 2.58E-03 1.31 E-02 6.62E-03 2.44E-02

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 40 Mean HF and LF rock spectra at Farley

1.

i 10-6 HF 10-6 LF CF*

10-5 HF I..'U"*-.

_1

=5 L O 4 HF

---... 10-4 LF 0.01 0.001 0.1 1

10 100 Frequency, Hz Figure 2.3.4-1: Input HF and LF spectra for MAFE levels of 10-4, 10-5, and 10-6 for a spectral damping of 5%.

2.3.5 Methodology SNC Calculation SC-SNC539158-005 (SNC, 2014c) is the source of the information presented in the following section.

To perform the site response analyses for the Farley site, a random vibration theory (RVT) approach has been employed. This process utilizes a simple, efficient approach for computing site-specific amplification functions and is consistent with existing NRC guidance and the SPID (EPRI, 2013a). The guidance contained in Appendix B of the SPID (EPRI, 2013a) on incorporating epistemic uncertainty in shear wave velocities, kappa, non-linear dynamic properties and source spectra for plants with limited at-site information was followed for the Farley site, and resulted in the consideration of 18 different site columns. These columns and associated weight factors are presented in Table 2.3.5-1.

For each combination of the base profiles and its corresponding 60 randomized profiles, described in Section 2.3.3, and input motions, described in Section 2.3.4, the site amplification is computed as the ratio between 5% damped geologic outcrop pseudo-acceleration response spectrum at the control point and bedrock. The analysis is carried out at 301 frequency points ranging from 0.1 to 100 Hz and equally spaced in logarithmic space. The median (computed as the logarithmic mean) and the logarithmic standard deviation (log-SD) of the site amplification at each frequency are then computed. The weighted average amplification and total standard

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 41 deviation are computed using the equations provided in the SPID (EPRI, 2013a) along with the weight factors in Table 2.3.5-1.

The probabilistic seismic hazard curves are defined at the following 38 frequencies (in units of Hz):

100 90 80 70 60 50 45 40 35 30 25 20 15 12.5 10 9 8 7 6 5 4 3 2.5 2 1.5 1.25 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.167 0.125 0.1 At each of these frequencies, the weighted average amplification and total standard are computed using linear interpolation in log-log space from the 301 site amplification values.

Table 2.3.5-1: Alternative Base Site Columns and Weights Shear Wave Strain-Dependent Velocity Property Curves Kappa Base Soil Base Soil Weight Weight Weight Column Weight Column Profile (wVs)

Profile (wG)

Profile (wk)

(WVs. wG. wk)

Name Lower (kL) 0.3 0.045 VsL Gi kL Set 0.5 Median (kM) 0.4 0.060 VsLG1 _kM Lower 0.3 Upper (kU) 0.3 0.045 VsL G1 kU 0.3 (VsL)

Lower (kL) 0.3 0.045 VsL G2 kL Set 2 0.5 Median (kM) 0.4 0.060 VsL G2 kM Upper (kU) 0.3 0.045 VsL G2 kU Lower (kL) 0.3 0.060 VsMG1 kL Set 0.5 Median (kM) 0.4 0.080 VsM G1 kM Median (G4 Upper (kU) 0.3 0.060 VsM G1 kU 0.4 (VsM)

Lower (kL) 0.3 0.060 VsMG2 kL St2 0.5 Median (kM) 0.4 0.080 VsMG2 kM (G2)

Upper (kU) 0.3 0.060 VsM G2 kU Lower (kL) 0.3 0.045 VsU G1 kL Set 0.5 Median (kM) 0.4 0.060 VsUG1 kM Upper 0.3 Upper (kU) 0.3 0.045 VsU G1 kU (VsU)

Lower (kL) 0.3 0.045 VsUG2 kL St2 0.5 Median (kM) 0.4 0.060 VsU G2 kM Upper (kU) 0.3 0.045 VsUG2 kU Total:

1.000

  • G1 designates the EPRI 20-50 ft strain-dependent property curves
  • G2 designates the EPRI 50-120 ft strain-dependent property curves 2.3.6 Amplification Functions SNC Calculation SC-SNC539158-005 (SNC, 2014c) is the source of the information presented in the following section.

The results of the site response analysis consist of amplification functions which describe the amplification (or de-amplification) of base rock motions as a function of frequency and input

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 42 base rock amplitude. The amplification functions are represented in terms of a median (computed as the logarithmic mean) amplification value and an associated logarithmic standard deviation (sigma) for each response spectral frequency and input base rock amplitude. As an example, the median and logarithmic standard deviation for the VsM_GI_kM site column are shown in Figure 2.3.6-1 and Figure 2.3.6-2. The data associated for these figures are tabulated in Table 2.3.6-1 for the high-frequency (HF) and low-frequency (LF) input motions at mean-annual frequencies of exceedance (MAFE) of 10-4 and 10-5. Similarly, the figures and data are provided for the VsM-G2_kM site column in Figure 2.3.6-3, Figure 2.3.6-4, and Table 2.3.6-2.

The weighted average amplification and total standard deviation are obtained by combining the results of each base profile using its associated weight factor using the method recommended by the SPID (EPRI, 2013a). The weighted average and total standard deviation are shown in Figure 2.3.6-5 and Figure 2.3.6-6. The associated data for the high-frequency (HF) and low-frequency (LF) input motions at mean-annual frequencies of exceedance (MAFE) of 10-4 and 10,5 are provided in Table 2.3.6-3. Note these tables in this section are provided in lieu of the submittal template Appendix Tables A.2-bl and A.2-b2.

Additionally, the weighted average amplification and total standard deviation, for the 1 E-3 through 1 E-7 MAFE, are reported at the seven frequencies of interest in Table A-2 in the Appendix.

At some frequencies, the calculated site amplification for high base rock amplitudes is less than the minimum value of 0.5 recommended by the SPID (EPRI, 2013a). The 0.5 limit is not imposed here in the calculation of the surface hazard because the intended purpose of this calculation is a best assessment of mean and fractile levels of the seismic response for plant risk assessment with no added conservatism.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 43 Farley VsM_GIkM E

U) a.

C.I.

ECL 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 0.1 10 100 Frequency [Hz]

Figure 2.3.6-1: The logarithmic mean site amplification for the VsMG1ikM site column for the considered input motions.

Farley VsMGIkM

'E 02 Z

0.6 0.5 0.4 0.3 0.2 0.1 0.1 1

10 100 Frequency [Hz]

Figure 2.3.6-2: The logarithmic standard deviation of the site amplification for the VsMG1ikM site column for the considered input motions.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 44 Table 2.3.6-1: The logarithmic mean and standard deviation of the site amplification (for 5%

damped PSA) computed for the VsM G1 kM profile and the HF4, LF4, HF5, and LF5 input motions.

Freq.

HF4 LF4 HF5 LF5 (Hz)

Median Log SD Median Log-SD Median Log-SD Median Log-SD 0.100 1.626 0.121 1.618 0.125 1.537 0.151 1.624 0.125 0.125 1.962 0.158 1.855 0.163 1.842 0.199 1.862 0.163 0.167 2.278 0.107 2.167 0.113 2.232 0.134 2.176 0.114 0.200 2.200 0.071 2.100 0.063 2.131 0.078 2.109 0.064 0.300 1.711 0.076 1.653 0.075 1.647 0.078 1.665 0.078 0.400 1.874 0.135 1.808 0.141 1.913 0.123 1.821 0.140 0.500 1.901 0.093 1.822 0.096 1.932 0.091 1.832 0.099 0.600 1.780 0.112 1.710 0.112 1.820 0.110 1.729 0.120 0.700 1.792 0.093 1.711 0.095 1.835 0.092 1.739 0.105 0.800 1.911 0.101 1.817 0.105 1.949 0.105 1.859 0.124 0.900 2.012 0.107 1.915 0.113 2.048 0.114 1.973 0.140 1.000 2.102 0.126 2.010 0.132 2.135 0.134 2.092 0.165 1.250 2.377 0.176 2.275 0.191 2.402 0.188 2.396 0.226 1.500 2.659 0.229 2.546 0.242 2.660 0.229 2.674 0.259 2.000 3.376 0.245 3.177 0.243 3.123 0.219 3.058 0.244 2.500 3.268 0.208 3.055 0.202 2.869 0.201 2.734 0.219 3.000 2.801 0.202 2.605 0.194 2.454 0.209 2.296 0.220 4.000 2.164 0.207 2.013 0.199 1.896 0.222 1.764 0.221 5.000 1.819 0.207 1.704 0.195 1.579 0.229 1.470 0.223 6.000 1.578 0.212 1.480 0.203 1.356 0.256 1.277 0.244 7.000 1.390 0.275 1.315 0.251 1.174 0.315 1.128 0.273 8.000 1.218 0.305 1.158 0.263 0.985 0.323 0.968 0.252 9.000 1.072 0.300 1.024 0.248 0.827 0.301 0.856 0.216 10.000 0.970 0.261 0.938 0.212 0.734 0.279 0.789 0.199 12.500 0.861 0.238 0.856 0.192 0.627 0.287 0.706 0.191 15.000 0.773 0.245 0.789 0.187 0.531 0.286 0.645 0.179 20.000 0.677 0.206 0.716 0.158 0.430 0.235 0.574 0.149 25.000 0.663 0.192 0.700 0.148 0.403 0.218 0.552 0.141 30.000 0.635 0.186 0.679 0.144 0.381 0.206 0.542 0.136 35.000 0.624 0.181 0.673 0.142 0.373 0.198 0.545 0.133 40.000 0.626 0.178 0.678 0.140 0.373 0.194 0.556 0.132 45.000 0.646 0.176 0.700 0.139 0.384 0.190 0.579 0.131 50.000 0.666 0.175 0.723 0.138 0.396 0.189 0.602 0.131 60.000 0.758 0.174 0.823 0.138 0.450 0.187 0.693 0.130 70.000 0.897 0.173 0.972 0.137 0.533 0.186 0.827 0.130 80.000 1.052 0.173 1.140 0.137 0.625 0.186 0.977 0.130 90.000 1.186 0.173 1.285 0.137 0.706 0.185 1.118 0.130 100.000 1.282 0.172 1.387 0.137 0.762 0.185 1.209 0.129

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 45 Farley VaMG2_kM

.r2 a.

CL E

ae U) 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 0.1 10 100 Frequency [Hz]

Figure 2.3.6-3: The logarithmic mean site amplification for the VsMG2_kM site column for the considered input motions.

Farley VsM-G2 kM C

0I U

U U,

0, 0

-j*1 Uz 0.5 0.45 0.4 0.35 0.3 0.25 0.2 0.15 0.1 0.05 0

0.1 100 Frequency [Hz]

Figure 2.3.6-4: The logarithmic standard deviation of the site amplification for the VsMG2_kM site column for the considered input motions.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 46 Table 2.3.6-2: The logarithmic mean and standard deviation of the site amplification (for 5%

damped PSA) computed for the VsMG2_kM profile and the HF4, LF4, HF5, and LF5 input motions.

Freq.

HF4 LF4 HF5 LF5 (Hz)

Median Log SD Median Log SD Median Log SD Median Log SD 0.100 1.622 0.112 1.612 0.116 1.528 0.140 1.616 0.117 0.125 1.957 0.152 1.848 0.155 1.832 0.190 1.853 0.156 0.167 2.289 0.114 2.175 0.121 2.241 0.142 2.182 0.121 0.200 2.207 0.070 2.105 0.065 2.136 0.074 2.112 0.065 0.300 1.703 0.080 1.642 0.076 1.642 0.083 1.652 0.078 0.400 1.881 0.141 1.812 0.145 1.920 0.131 1.821 0.146 0.500 1.902 0.105 1.821 0.109 1.933 0.105 1.825 0.112 0.600 1.770 0.106 1.695 0.103 1.810 0.108 1.707 0.109 0.700 1.827 0.124 1.739 0.125 1.864 0.122 1.758 0.133 0.800 1.922 0.126 1.822 0.128 1.952 0.129 1.849 0.142 0.900 2.021 0.138 1.915 0.140 2.049 0.144 1.954 0.161 1.000 2.128 0.147 2.023 0.148 2.149 0.155 2.079 0.175 1.250 2.389 0.193 2.276 0.202 2.401 0.206 2.374 0.245 1.500 2.696 0.257 2.581 0.275 2.681 0.260 2.690 0.300 2.000 3.395 0.267 3.203 0.259 3.139 0.227 3.076 0.227 2.500 3.249 0.199 3.060 0.190 2.912 0.185 2.814 0.199 3.000 2.834 0.184 2.655 0.177 2.533 0.187 2.402 0.199 4.000 2.228 0.189 2.085 0.182 1.981 0.208 1.860 0.209 5.000 1.848 0.215 1.746 0.205 1.630 0.242 1.548 0.228 6.000 1.609 0.235 1.527 0.214 1.415 0.252 1.348 0.225 7.000 1.427 0.231 1.347 0.208 1.225 0.246 1.172 0.223 8.000 1.227 0.237 1.164 0.211 1.016 0.261 1.008 0.221 9.000 1.078 0.279 1.041 0.241 0.863 0.305 0.896 0.232 10.000 0.989 0.298 0.964 0.253 0.769 0.313 0.825 0.228 12.500 0.892 0.245 0.885 0.205 0.668 0.286 0.746 0.204 15.000 0.786 0.239 0.805 0.192 0.556 0.283 0.671 0.190 20.000 0.689 0.204 0.730 0.166 0.450 0.231 0.594 0.156 25.000 0.671 0.191 0.711 0.158 0.417 0.210 0.568 0.146 30.000 0.644 0.186 0.691 0.155 0.395 0.201 0.558 0.142 35.000 0.632 0.182 0.684 0.152 0.385 0.194 0.561 0.139 40.000 0.634 0.179 0.689 0.151 0.385 0.188 0.571 0.138 45.000 0.654 0.177 0.711 0.150 0.397 0.185 0.594 0.136 50.000 0.675 0.175 0.734 0.149 0.409 0.183 0.618 0.136 60.000 0.768 0.174 0.836 0.149 0.464 0.181 0.711 0.135 70.000 0.908 0.174 0.987 0.148 0.550 0.180 0.849 0.135 80.000 1.065 0.173 1.157 0.148 0.645 0.179 1.003 0.135 90.000 1.201 0.173 1.305 0.148 0.729 0.179 1.148 0.135 100.000 1.298 0.173 1.409 0.148 0.787 0.179 1.241 0.135

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 47 0

E U)

.S E

0 U) 3.0 2.5 2.0 1.5 1.0 0.5 0.0 0.1 10 100 Frequency [Hz]

Figure 2.3.6-5: Weighted Average Median Amplification Factors at Ground Surface.

C a

0

-j a

a Z

0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0

0.1 10 100 Frequency [Hz]

Figure 2.3.6-6: Total Logarithmic Standard Deviations for Amplification Functions at Ground Surface.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 48 Table 2.3.6-3: The weighted average median and total logarithmic standard deviation of the site amplification (for 5% damped PSA) the HF4, LF4, HF5, and LF5 in ut motions.

Freq.

HF4 LF4 HF5 LF5 (Hz)

Median Log-SD Median Log-SD Median Log-SD Median Log-SD 0.100 1.837 0.459 1.828 0.444 1.771 0.482 1.836 0.447 0.125 1.959 0.383 1.873 0.381 1.857 0.414 1.880 0.383 0.167 1.863 0.260 1.799 0.257 1.765 0.277 1.810 0.260 0.200 1.815 0.213 1.760 0.209 1.721 0.222 1.775 0.212 0.300 1.888 0.254 1.834 0.256 1.849 0.253 1.854 0.272 0.400 1.777 0.167 1.731 0.171 1.812 0.162 1.773 0.210 0.500 1.918 0.267 1.869 0.275 1.942 0.261 1.912 0.312 0.600 1.844 0.270 1.801 0.280 1.877 0.267 1.849 0.319 0.700 1.967 0.334 1.917 0.348 1.990 0.328 1.946 0.367 0.800 2.013 0.339 1.956 0.354 2.033 0.339 1.974 0.362 0.900 2.087 0.387 2.021 0.393 2.101 0.381 2.019 0.386 1.000 2.152 0.426 2.086 0.422 2.155 0.410 2.069 0.405 1.250 2.397 0.468 2.276 0.454 2.336 0.426 2.201 0.427 1.500 2.532 0.444 2.380 0.428 2.421 0.398 2.278 0.406 2.000 2.668 0.389 2.493 0.376 2.466 0.353 2.313 0.367 2.500 2.563 0.344 2.428 0.324 2.334 0.319 2.200 0.333 3.000 2.430 0.307 2.286 0.289 2.182 0.301 2.024 0.326 4.000 2.067 0.313 1.940 0.298 1.808 0.331 1.663 0.359 5.000 1.686 0.332 1.601 0.304 1.448 0.363 1.352 0.362 6.000 1.431 0.361 1.368 0.320 1.207 0.401 1.153 0.373 7.000 1.268 0.386 1.222 0.336 1.049 0.432 1.025 0.377 8.000 1.129 0.400 1.097 0.342 0.911 0.446 0.916 0.368 9.000 1.016 0.412 0.997 0.345 0.795 0.459 0.832 0.360 10.000 0.922 0.416 0.920 0.344 0.703 0.471 0.770 0.355 12.500 0.790 0.428 0.822 0.345 0.573 0.495 0.677 0.351 15.000 0.710 0.416 0.760 0.330 0.489 0.479 0.617 0.326 20.000 0.637 0.369 0.700 0.293 0.409 0.430 0.556 0.287 25.000 0.621 0.348 0.683 0.280 0.381 0.400 0.532 0.269 30.000 0.591 0.329 0.658 0.267 0.358 0.369 0.518 0.252 35.000 0.579 0.318 0.650 0.261 0.348 0.353 0.520 0.244 40.000 0.579 0.311 0.653 0.257 0.348 0.342 0.528 0.239 45.000 0.597 0.307 0.674 0.255 0.358 0.336 0.549 0.236 50.000 0.615 0.303 0.695 0.253 0.368 0.331 0.571 0.234 60.000 0.698 0.299 0.790 0.251 0.417 0.325 0.656 0.232 70.000 0.825 0.297 0.933 0.250 0.493 0.322 0.783 0.231 80.000 0.967 0.296 1.093 0.249 0.578 0.320 0.925 0.230 90.000 1.090 0.295 1.232 0.249 0.654 0.319 1.058 0.230 100.000 1.178 0.295 1.330 0.249 0.705 0.318 1.144 0.230

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 49 2.3.7 Control Point Seismic Hazard Curves SNC Calculation SC-SNC539158-002 (SNC, 2014e) is the source of the information presented in the following section.

The procedure to develop probabilistic site-specific control point hazard curves used in the present analysis follows the methodology described in McGuire et al. (2001) and Section B-6.0 of the SPID (EPRI, 2013a). This procedure (referred to as Method 3) computes a site-specific control point hazard curve for a broad range of spectral accelerations given the site-specific bedrock hazard curve and site-specific estimates of soil or soft-rock response (i.e., median amplification factors) and associated uncertainties (i.e., sigma in natural log units) presented in the previous section.

As part of the implementation of Method 3, base rock hazard curves for 31 spectral frequencies in addition to the original seven frequencies of 100 Hz (PGA), 25 Hz, 10 Hz, 5 Hz, 2.5 Hz, 1 Hz, and 0.5 Hz are initially developed and used in the application of Method 3 to capture the resulting expected site resonance characteristics from the site response analysis. Given the base rock hazard curves from the seven reference spectral frequencies, UHRS are developed for this suite of 38 spectral frequencies over the range of 0.1 to 100 Hz. UHRS are computed for annual frequencies of exceedances of 10-3, 104, 105, 10-6, 1007, and 10-8. For the interpolation of ground motions at the additional 31 spectral frequencies, the average of the CEUS base rock single-corner and double-corner spectral shape models (McGuire et al., 2001) is used with an M, of 6.5 at a distance of 50 km. This average spectral shape for each UHRS is constrained to be equal to the ground motion value for each of the seven reference spectral frequencies. For frequencies less than 0.5 Hz, a constant slope of 1/T is adopted, where T is the spectral period.

This methodology for the interpolation of additional spectral frequencies for the base rock hazard curves was applied to both the mean and fractile sets of base rock hazard curves.

The resulting 38 base rock hazard curve sets (i.e., mean and five fractile levels of 5 th, 16 th, 5 0 th, 8 4th, and 9 5th) were used in the Method 3 approach (McGuire et al., 2001) to estimate the control point seismic hazard curves for 38 spectral frequencies along with the median site amplification factors and associated sigma values from the high frequency (HF) and low frequency (LF) input spectra. For frequencies equal to 5 Hz and higher the results from only the HF cases were used and for frequencies equal to 2.5 Hz and lower only the results from the LF cases were used. For frequencies between 2.5 Hz and 5 Hz the results from both the HF and LF cases were combined using weights that are computed based on the log interpolation of the difference in the given frequency value from the two end member values of 2.5 Hz and 5 Hz.

The mean control point hazard curves for the seven reference spectral frequencies for the Farley site are shown in Figure 2.3.7-1. Tabulated values of the control point hazard curves and site response amplification functions are provided in the attached Appendix Table A-1 and A-2, respectively.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 50 Farley, Mean 1.0E-03 100 Hz 25 Hz 10 Hz

...... 5Hz 2.5 Hz 1 Hz 0.5 Hz 1.OE-04 +-

1.0E 4C 1.OE-06

-I-1.OE-07 +

0.01 0.1 1

10 PSA (g)

Figure 2.3.7-1: Control point mean hazard curves for spectral frequencies of 0.5, 1, 2.5, 5, 10, 25 and 100 Hz at the Farley site. The hazard curve relates the pseudo-spectral acceleration (PSA) to the annual frequency of exceedance (AFE).

2.4 Control Point Response Spectra SNC Calculation SC-SNC539158-002 (SNC, 2014e) is the source of the information presented in the following section.

The control point hazard curves described above and provided in the Tables A-i a through A-i g of Appendix A for the seven reference frequencies have been used to develop uniform hazard response spectra (UHRS) and the ground motion response spectrum (GMRS). The UHRS were obtained through linear interpolation in log-log space to estimate the spectral acceleration at each of the 38 spectral frequencies for the 1 E-4 and 1 E-5 per year hazard levels.

The 1 E-4 and 1 E-5 UHRS, along with a design factor (DF) are used to compute the GMRS at the control point using the criteria in Regulatory Guide 1.208 (NRC, 2007). The UHRS and GMRS spectral accelerations are shown in Figure 2.4-1, as well as tabulated in Table 2.4-1.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 51 Table 2.4-1: UHRS for 10-4 and 10-5 and GMRS at control point for Farley.

Frequency Mean UHRS (g)

Mean UHRS (g)

GMRS (Hz)

(AFE=1 04)

(AFE=1 0-5)

(g) 100.000 0.0563 0.1356 0.0682 90.000 0.0563 0.1357 0.0683 80.000 0.0564 0.1360 0.0684 70.000 0.0566 0.1365 0.0687 60.000 0.0569 0.1372 0.0690 50.000 0.0575 0.1388 0.0698 45.000 0.0582 0.1409 0.0708 40.000 0.0584 0.1417 0.0712 35.000 0.0593 0.1447 0.0726 30.000 0.0607 0.1495 0.0749 25.000 0.0633 0.1588 0.0793 20.000 0.0679 0.1723 0.0858 15.000 0.0788 0.2043 0.1013 12.500 0.0867 0.2295 0.1133 10.000 0.0962 0.2543 0.1256 9.000 0.1025 0.2694 0.1332 8.000 0.1086 0.2851 0.1410 7.000 0.1149 0.2998 0.1485 6.000 0.1199 0.3070 0.1526 5.000 0.1281 0.3193 0.1596 4.000 0.1426 0.3339 0.1690 3.000 0.1474 0.3207 0.1647 2.500 0.1464 0.3070 0.1588 2.000 0.1642 0.3440 0.1780 1.500 0.1551 0.3305 0.1704 1.250 0.1379 0.2981 0.1533 1.000 0.1038 0.2277 0.1167 0.900 0.0971 0.2164 0.1106 0.800 0.0885 0.2001 0.1020 0.700 0.0821 0.1887 0.0958 0.600 0.0681 0.1570 0.0797 0.500 0.0625 0.1437 0.0730 0.400 0.0445 0.0993 0.0507 0.300 0.0366 0.0818 0.0418 0.200 0.0230 0.0503 0.0258 0.167 0.0200 0.0443 0.0227 0.125 0.0168 0.0388 0.0197 0.100 0.0138 0.0326 0.0165

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 52 Farley: UHRS and GMRS 1.OE+O0 I S1.0E-01 4A 1.0E-02 Method 3 (10-5)

Method 3 GMRS SMethod 3 (10-4) 1 10 I

0.1 100 Frequency (Hz)

Figure 2.4-1: UHRS for 1 E-4 and 1 E-5 and GMRS at control point for Farley.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 53 3.0 Plant Design Basis and Beyond Design Basis Evaluation Ground Motion The design basis ground motion for Plant Farley Units 1 and 2 is identified in the FSAR (SNC, 2014f). In particular the Plant Farley SSE is defined in sections 1.2.1.6 Seismology, 2.5.2.10 Safe Shutdown Earthquake, and 3.7.1 Seismic Input.

3. 1 SSE Description of Spectral Shape The SSE was developed in accordance with 10 CFR Part 100, Appendix A through an evaluation of the maximum earthquake potential for the region surrounding the site. This region is one of the least seismically active regions in the United States and is characterized by few low-magnitude and low-intensity shocks. Historic records show that earthquakes have never been felt at the site with an intensity greater Modified Mercalli V and that no earthquake of epicentral intensity greater than Modified Mercalli IV has occurred within 150 miles of the plant site. Therefore, the maximum intensity postulated as having been experienced at the site, as a result of any historical earthquake, is a low to moderate V. This intensity corresponds to a surface acceleration of 0.03g on the Hershberger's (1956) curve. Therefore, conservatively 0.10g surface acceleration was selected for the safe shutdown earthquake (SSE). The modified Newmark spectral shape with a peak ground acceleration of 0.1g defines the Farley Units 1 and 2 SSE. The 5% damped horizontal SSE is provided in Table 3.3-1 and shown in Figure 3.3-1.

Table 3.3-1: SSE for Plant Farley Units 1 and 2.

Frequency (Hz)

SSE (g) 0.10 0.005 0.217 0.023 0.5 0.053 1.0 0.105 2.0 0.21 2.5 0.21 4.0 0.21 6.67 0.21 8.0 0.17 9.0 0.15 10.0 0.13 12.5 0.10 33.0 0.10 100.0 0.10

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 54 Farley Units 1 and 2 0.5 0.4 0-

.3 0.3 tM

.S E

is 0.2 0.0 0.1 1

10 Frequency [Hz]

Figure 3.3-1: Horizontal SSE for Plant Farley Units 1 and 2 100 3.2 Control Point Elevation The SSE control point elevation is defined at Elevation 155 feet which is general plant grade.

There are safety related structures founded at plant grade. The SPID (EPRI, 2013a) section 2.4.2 Figure 2-2 is representative of the Farley site conditions. Also FSAR (SNC, 2014f) Figure 3.7-62 "Seismic Instrumentation" shows a free field acceleration sensor in the free field which is surface mounted. This fact supports the location of the control point for the SSE and therefore the GMRS is at general plant grade.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 55 4.0 Screening Evaluation In accordance with SPID (EPRI, 2013a) Section 3, a screening evaluation has been performed as described below.

4.1 Risk Evaluation Screening (1 to 10 Hz)

In the 1 to 10 Hz part of the response spectrum, Plant Farley Units 1 and 2 screens in under the special screening considerations for a Low Seismic Hazard Site per section 3.2.1.1 of the SPID (EPRI, 2013a).

4.2 High Frequency Screening (> 10 Hz)

For a portion of the range above 10 Hz, the GMRS exceeds the SSE; therefore, Plant Farley Units 1 and 2 screens in for a high frequency confirmation.

4.3 Spent Fuel Pool Evaluation Screening (1 to 10 Hz)

In the 1 to 10 Hz part of the response spectrum, Plant Farley Units 1 and 2 screens in under the special screening considerations for a Low Seismic Hazard Site per section 3.2.1.1 of the SPID (EPRI, 2013a). Therefore, a spent fuel pool evaluation will not be performed.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 56 5.0 Interim Actions Based on the screening evaluation, the expedited seismic evaluation described in EPRI Report No. 3002000704 (EPRI, 2013c) is limited to Expedited Seismic Equipment List items that have their fundamental natural frequencies below the highest frequency where the GMRS exceeds the SSE (EPRI 2013c, section 2.2.1.1) as proposed in letter to NRC dated April 9, 2013 (ML13101A379) and agreed to by NRC in a letter dated May 7, 2013 (ML13106A331).

Consistent with NRC letter dated February 20, 2014, [ML14030A046] the seismic hazard reevaluations presented herein are distinct from the current design and licensing bases of Plant Farley Units 1 and 2. Therefore, the results do not call into question the operability or functionality of SSCs and are not reportable pursuant tol 0 CFR 50.72, "Immediate notification requirements for operating nuclear power reactors," and10 CFR 50.73, "Licensee event report system.

The NRC letter also requests that licensees provide an interim evaluation or actions to demonstrate that the plant can cope with the reevaluated hazard while the expedited approach and risk evaluations are conducted. In response to that request, NEI letter dated March 12, 2014 (NEI, 2014), provides seismic core damage risk estimates using the updated seismic hazards for the operating nuclear plants in the Central and Eastern United States. These risk estimates continue to support the following conclusions of the NRC GI-199 Safety/Risk Assessment:

Overall seismic core damage risk estimates are consistent with the Commission's Safety Goal Policy Statement because they are within the subsidiary objective of 10 4/year for core damage frequency. The GI-199 Safety/Risk Assessment, based in part on information from the U.S. Nuclear Regulatory Commission's (NRC's) Individual Plant Examination of External Events (IPEEE) program, indicates that no concern exists regarding adequate protection and that the current seismic design of operating reactors provides a safety margin to withstand potential earthquakes exceeding the original design basis.

Plant Farley Units 1 and 2 is included in the March 12, 2014 risk estimates (NEI, 2014). Using the methodology described in the NEI letter, all plants were shown to be below 10 4/year; thus, the above conclusions apply.

The recent 2.3 Seismic Walkdowns provide additional assurance that Plant Farley Units 1 and 2 is maintaining the seismic capacity of the plant.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 57 2.3 Seismic Walkdowns In the 2012 to 2014 time frame the 2.3 Seismic Walkdowns were performed at Farley for a broad range of safety related equipment. Final reports have been submitted to the NRC.

Plant Farley had no significant degraded, non-conforming or unanalyzed conditions that warranted modification to the plant. Plant Farley had no-as found conditions that would prevent SSCs from performing their required safety functions.

The 2.3 Seismic Walkdown Equipment List for Unit 1 included 28 components that had seismic issues previously identified during the IPEEE program. The 2.3 Seismic Walkdown teams verified that the recommended resolutions to the IPEEE issues associated with the 28 items had been implemented. The 2.3 Seismic Walkdown Equipment List for Unit 2 included 18 components that had seismic issues previously identified during the IPEEE program.

Implementation of these modifications was verified during the 2.3 Seismic walkdowns.

Farley Design Basis In-structure Response Spectra (ISRS)

For informational purposes it should be noted that the 5% damped response spectrum for the Farley synthesized time history as shown in Figure 3.7-5 of the Farley FSAR (SNC, 2014f) exceed the Farley SSE. In particular for the frequency range of 1 to about 1.5 Hz the exceedance is about 38% to 20% respectively. Therefore, the time history response spectrum exceeds the GMRS in that same frequency range. This time history was used to develop in-structure response spectra (ISRS) for the seismic design and/or seismic qualification of all safety related systems and components mounted in the safety related structures: e.g. piping, batteries and battery racks, electrical equipment, etc.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 58 6.0 Conclusions In accordance with the 50.54(f) (NRC, 2012) request for information, a seismic hazard and screening evaluation was performed for Plant Farley Units 1 and 2. A GMRS was developed solely for purpose of screening for additional evaluations in accordance with the SPID (EPRI, 2013a).

Based on the results of the screening evaluation, Plant Farley Units 1 and 2 screens in under the special screening considerations for a Low Seismic Hazard Site per section 3.2.1.1 of the SPID (EPRI, 2013a).

Plants Farley Units 1 and 2 screens in for a high frequency confirmation.

Plant Farley Units 1 and 2 screens out of a Spent Fuel Pool evaluation.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 59 7.0 References Campbell, K. W., "Estimates of shear-wave Q and Ko for unconsolidated and semiconsolidated sediments in Eastern North America," Bulletin of the Seismological Society of America, 99.4: 2009: 2365-2392.

"Central and Eastern United States Seismic Source Characterization (CEUS-SSC) for Nuclear Facilities," NUREG-2115, DOE/NE-01 40, EPRI 1021097, 6 Volumes, January 2012.

Electric Power Research Institute (EPRI), "Modeling of Dynamic Soil Properties", Appendix 7.A of Report No. TR-102293 entitled Guidelines for Determining Design Basis Ground Motions, Palo Alto, CA, 1993.

Electric Power Research Institute (EPRI), "Seismic Evaluation Guidance, Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic," Report No. 1025287, February 28, 2013a.

Electric Power Research Institute (EPRI), "EPRI (2004, 2006) Ground-Motion Model (GMM)

Review Project," Report No. 3002000717, June 13, 2013b.

Electric Power Research Institute (EPRI), "Seismic Evaluation Guidance: Augmented Approach for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1 -

Seismic," Report No. 3002000704, May 31, 2013c.

Hershberger, John. "A comparison of earthquake accelerations with intensity ratings." Bulletin of the Seismological Society of America 46.4 (1956): 317-320.

Idriss, I.M. and R.W. Boulanger, "SPT-Based Liquefaction Triggering Procedures", Department of Civil and Environmental Engineering, University of California, Davis, CA, December 2010.

Lettis Consultants International (LCI, 2013a). "Farley Seismic Hazard and Screening Report,"

LCI Project 1041, Rev. 1, October 30, 2013.

Lettis Consultants International (LCI, 2013b). "CEUS SSC Probabilistic Seismic Hazard Analysis for Southern Nuclear Operating Company: Farley Nuclear Station," LCI Project 1071, Rev. 0, November 14, 2013.

McGuire, R.K. Seismic Hazard and Risk Analysis, Earthquake Engineering Research Institute, Monograph MNO-10, 2004.

McGuire, R.K., W. J. Silva, and C.J. Costantino. Technical Basis for Revision of Regulatory Guidance on Design Ground Motions, Hazard and Risk Consistent Ground Motion Spectra Guidelines, U.S. Nuclear Regulatory Commission, NUREG/CR-6728, November 2001.

Naval Facilities Engineering Command (Navfac), Soil Mechanics - Design Manual 7.01, Alexandria, VA, 1986.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 60 Nuclear Energy Institute (Anthony Pietrangelo). "Proposed Path Forward for NTTF Recommendation 2.1: Seismic Reevaluations," Document No. ML13101A379, April 9, 2013.

Nuclear Energy Institute (NEI). Letter

Subject:

"Seismic Risk Evaluations for Plants in the Central and Eastern United States." March 12, 2014.

Nuclear Regulatory Commission (NRC), "A Performance-Based Approach to Define the Site-Specific Earthquake Ground Motion," U.S. Nuclear Regulatory Commission Regulatory Guide 1.208, 2007.

Nuclear Regulatory Commission (NRC) (E Leeds and M Johnson), Letter to All Power Reactor Licensees et al., "Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) Regarding Recommendations 2.1, 2.3 and 9.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-lchi Accident," March 12, 2012.

Silva, W.J., N. Abrahamson, G. Toro and C. Costantino, "Description and validation of the stochastic ground motion model," Report Submitted to Brookhaven National Laboratory, Associated Universities, Inc. Upton, New York 11973, Contract No. 770573, 1996.

Smith, Charles C., "Subsurface Stratigraphy and Water Resources of the Dothan Area, Houston County, Alabama", Gulf Coast Association of Geological Societies Transactions Vol XLVIII, 1998.

Southern Nuclear Operating Company (SNC), Geotechnical Site Evaluation, Independent Spent Fuel Storage Installation (ISFSI), Farley Nuclear Plant, Earth Science and Environmental Engineering Technical Services, Southern Company Services, Inc., 2001.

Southern Nuclear Operating Company (SNC), Unit 1 and 2 Soil/Rock Column, Calculation Number: SC-SNC539158-004 Ver. 1, 2014a.

Southern Nuclear Operating Company (SNC), Soil Profile Simulation for the Farley Site, Calculation Number: SC-SNC539158-006, Ver. 1, 2014b.

Southern Nuclear Operating Company (SNC), Site Response Analysis for the Farley Site, Calculation Number: SC-SNC539158-005, Ver. 1, 2014c.

Southern Nuclear Operating Company (SNC), Development of mean high frequency and low frequency rock spectra for MAFEs of 10-3 10-7 and 10-8 for Farley, Calculation Number:

SC-SNC539158-001, Ver. 1, 2014d.

Southern Nuclear Operating Company (SNC), Development of Surface Hazard and Uniform Hazard Response Spectra for Farley Site, Calculation Number: SC-SNC539158-002 Ver. 1, 2014e.

Southern Nuclear Operating Company (SNC), Joseph M. Farley Nuclear Plant Units 1 and 2 Final Safety Analysis Report (FSAR), Rev. 25, 2014f.

Stokoe, K.H, W.K. Choi, and F-Y Meng, Summary Report - Dynamic Laboratory Tests:

Unweathered and Weathered Shale Proposed Site of Building 9720-82, Oak Ridge Tennessee, University of Texas, Austin Texas, May 2003.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page 61 Toro, G.R., "Probabilistic Models of Site Velocity Profiles for Generic and Site-Specific Ground Motion Amplification Studies," Published as an appendix in Silva et al (1996), 1996.

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-1 Appendix A Table A-la. 100 Hz (PGA) Seismic Hazard Curves at Farley,.

Mean 5 "h Fractile 16h Fractile 5 0 th Fractile 84t Fractile 9 5 th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0125 1.080E-03 0.0041 1.067E-03 0.0066 1.090E-03 0.0102 1.093E-03 0.0149 1.073E-03 0.0267 1.034E-03 0.0132 1.069E-03 0.0043 1.060E-03 0.0070 1.080E-03 0.0108 1.083E-03 0.0158 1.060E-03 0.0282 1.011E-03 0.0140 1.055E-03 0.0045 1.051 E-03 0.0074 1.068E-03 0.0114 1.069E-03 0.0167 1.043E-03 0.0297 9.824E-04 0.0148 1.037E-03 0.0047 1.039E-03 0.0078 1.051E-03 0.0121 1.052E-03 0.0177 1.021E-03 0.0313 9.484E-04 0.0156 1.014E-03 0.0049 1.025E-03 0.0082 1.031 E-03 0.0128 1.029E-03 0.0187 9.942E-04 0.0331 9.088E-04 0.0165 9.850E-04 0.0052 1.007E-03 0.0087 1.005E-03 0.0135 1.001E-03 0.0198 9.615E-04 0.0349 8.640E-04 0.0175 9.505E-04 0.0054 9.860E-04 0.0092 9.743E-04 0.0143 9.673E-04 0.0209 9.230E-04 0.0368 8.145E-04 0.0185 9.102E-04 0.0057 9.612E-04 0.0097 9.384E-04 0.0151 9.278E-04 0.0221 8.791E-04 0.0388 7.610E-04 0.0196 8.646E-04 0.0060 9.328E-04 0.0103 8.976E-04 0.0160 8.828E-04 0.0234 8.302E-04 0.0409 7.046E-04 0.0208 8.142E-04 0.0063 9.010E-04 0.0109 8.523E-04 0.0169 8.327E-04 0.0248 7.773E-04 0.0432 6.465E-04 0.0220 7.600E-04 0.0066 8.659E-04 0.0115 8.033E-04 0.0179 7.784E-04 0.0262 7.213E-04 0.0456 5.879E-04 0.0232 7.032E-04 0.0070 8.280E-04 0.0122 7.515E-04 0.0189 7.211E-04 0.0277 6.635E-04 0.0481 5.300E-04 0.0246 6.450E-04 0.0073 7.877E-04 0.0128 6.978E-04 0.0200 6.619E-04 0.0293 6.052E-04 0.0507 4.737E-04 0.0260 5.867E-04 0.0077 7.458E-04 0.0136 6.434E-04 0.0211 6.021E-04 0.0310 5.476E-04 0.0535 4.202E-04 0.0275 5.296E-04 0.0081 7.027E-04 0.0144 5.892E-04 0.0224 5.429E-04 0.0328 4.918E-04 0.0564 3.701E-04 0.0292 4.746E-04 0.0085 6.592E-04 0.0152 5.362E-04 0.0237 4.856E-04 0.0346 4.387E-04 0.0595 3.238E-04 0.0309 4.227E-04 0.0089 6.159E-04 0.0160 4.852E-04 0.0250 4.310E-04 0.0366 3.890E-04 0.0628 2.818E-04 0.0327 3.743E-04 0.0094 5.734E-04 0.0170 4.366E-04 0.0265 3.800E-04 0.0388 3.431 E-04 0.0662 2.440E-04 0.0346 3.300E-04 0.0098 5.320E-04 0.0179 3.911E-04 0.0280 3.331E-04 0.0410 3.013E-04 0.0699 2.105E-04 0.0366 2.897E-04 0.0103 4.922E-04 0.0190 3.487E-04 0.0296 2.904E-04 0.0434 2.636E-04 0.0737 1.811E-04 0.0387 2.535E-04 0.0109 4.543E-04 0.0200 3.097E-04 0.0313 2.523E-04 0.0459 2.299E-04 0.0777 1.555E-04 0.0410 2.212E-04 0.0114 4.185E-04 0.0212 2.740E-04 0.0332 2.184E-04 0.0485 2.OOOE-04 0.0820 1.333E-04 0.0433 1.927E-04 0.0120 3.848E-04 0.0224 2.416E-04 0.0351 1.887E-04 0.0513 1.737E-04 0.0865 1.142E-04 0.0459 1.675E-04 0.0126 3.534E-04 0.0237 2.123E-04 0.0371 1.628E-04 0.0543 1.506E-04 0.0912 9.788E-05 0.0485 1.454E-04 0.0132 3.241E-04 0.0250 1.860E-04 0.0392 1.404E-04 0.0574 1.305E-04 0.0963 8.394E-05 0.0514 1.260E-04 0.0139 2.970E-04 0.0265 1.625E-04 0.0415 1.210E-04 0.0607 1.130E-04 0.1015 7.207E-05 0.0544 1.091 E-04 0.0146 2.718E-04 0.0280 1.416E-04 0.0439 1.044E-04 0.0642 9.787E-05 0.1071 6.196E-05 0.0575 9.440E-05 0.0153 2.485E-04 0.0296 1.231E-04 0.0464 9.018E-05 0.0679 8.476E-05 0.1130 5.336E-05 0.0609 8.158E-05 0.0161 2.270E-04 0.0313 1.068E-04 0.0491 7.796E-05 0.0718 7.345E-05 0.1192 4.602E-05 0.0644 7.045E-05 0.0169 2.071E-04 0.0330 9.254E-05 0.0520 6.746E-05 0.0759 6.371E-05 0.1257 3.977E-05 0.0682 6.080E-05 0.0178 1.886E-04 0.0349 8.002E-05 0.0550 5.843E-05 0.0803 5.531E-05 0.1326 3.441E-05 0.0722 5.244E-05 0.0186 1.715E-04 0.0369 6.910E-05 0.0582 5.065E-05 0.0850 4.807E-05 0.1399 2.982E-05 0.0764 4.521E-05 0.0196 1.557E-04 0.0390 5.959E-05 0.0615 4.393E-05 0.0899 4.182E-05 0.1476 2.587E-05 0.0808 3.897E-05 0.0206 1.410E-04 0.0413 5.134E-05 0.0651 3.811E-05 0.0950 3.642E-05 0.1557 2.247E-05 0.0855 3.358E-05 0.0216 1.274E-04 0.0436 4.418E-05 0.0688 3.306E-05 0.1005 3.175E-05 0.1642 1.953E-05 0.0905 2.894E-05 0.0227 1.148E-04 0.0461 3.798E-05 0.0728 2.868E-05 0.1063 2.770E-05 0.1732 1.698E-05 0.0958 2.493E-05 0.0238 1.031E-04 0.0487 3.261E-05 0.0770 2.487E-05 0.1124 2.418E-05 0.1828 1.476E-05

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-2 Mean eth Fractile t Fractile 5 dh Fractile 8 4 th Fractile 9 5eh Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.1014 2.148E-05 0.0251 9.239E-05 0.0515 2.797E-05 0.0815 2.156E-05 0.1189 2.111E-05 0.1928 1.283E-05 0.1073 1.851E-05 0.0263 8.251E-05 0.0545 2.397E-05 0.0862 1.869E-05 0.1258 1.843E-05 0.2034 1.115E-05 0.1136 1.594E-05 0.0276 7.347E-05 0.0576 2.051E-05 0.0912 1.620E-05 0.1330 1.609E-05 0.2145 9.687E-06 0.1202 1.374E-05 0.0290 6.521 E-05 0.0609 1.754E-05 0.0964 1.404E-05 0.1407 1.404E-05 0.2263 8.407E-06 0.1272 1.184E-05 0.0305 5.772E-05 0.0643 1.499E-05 0.1020 1.216E-05 0.1488 1.225E-05 0.2387 7.289E-06 0.1346 1.020E-05 0.0320 5.093E-05 0.0680 1.281 E-05 0.1079 1.054E-05 0.1574 1.068E-05 0.2518 6.314E-06 0.1424 8.787E-06 0.0337 4.482E-05 0.0719 1.095E-05 0.1141 9.133E-06 0.1665 9.299E-06 0.2656 5.463E-06 0.1507 7.571E-06 0.0354 3.934E-05 0.0760 9.359E-06 0.1207 7.917E-06 0.1761 8.090E-06 0.2802 4.721E-06 0.1595 6.524E-06 0.0371 3.445E-05 0.0804 8.008E-06 0.1277 6.865E-06 0.1862 7.029E-06 0.2956 4.077E-06 0.1688 5.621E-06 0.0390 3.009E-05 0.0849 6.861E-06 0.1351 5.955E-06 0.1970 6.100E-06 0.3118 3.516E-06 0.1787 4.843E-06 0.0410 2.622E-05 0.0898 5.886E-06 0.1429 5.167E-06 0.2083 5.286E-06 0.3290 3.031E-06 0.1891 4.172E-06 0.0430 2.280E-05 0.0949 5.058E-06 0.1512 4.485E-06 0.2203 4.574E-06 0.3470 2.611E-06 0.2001 3.594E-06 0.0452 1.978E-05 0.1004 4.353E-06 0.1599 3.895E-06 0.2330 3.952E-06 0.3661 2.248E-06 0.2118 3.094E-06 0.0475 1.712E-05 0.1061 3.751E-06 0.1692 3.383E-06 0.2465 3.410E-06 0.3861 1.935E-06 0.2241 2.663E-06 0.0499 1.478E-05 0.1121 3.237E-06 0.1789 2.938E-06 0.2607 2.938E-06 0.4073 1.665E-06 0.2372 2.290E-06 0.0524 1.272E-05 0.1186 2.797E-06 0.1893 2.551E-06 0.2757 2.528E-06 0.4297 1.433E-06 0.2510 1.968E-06 0.0551 1.092E-05 0.1253 2.418E-06 0.2002 2.214E-06 0.2916 2.172E-06 0.4533 1.233E-06 0.2656 1.689E-06 0.0578 9.352E-06 0.1325 2.091E-06 0.2118 1.920E-06 0.3084 1.864E-06 0.4782 1.062E-06 0.2811 1.449E-06 0.0608 7.982E-06 0.1401 1.809E-06 0.2240 1.664E-06 0.3262 1.597E-06 0.5044 9.141E-07 0.2975 1.241E-06 0.0638 6.790E-06 0.1481 1.564E-06 0.2370 1.439E-06 0.3450 1.367E-06 0.5321 7.871E-07 0.3149 1.061E-06 0.0670 5.757E-06 0.1565 1.352E-06 0.2507 1.243E-06 0.3649 1.169E-06 0.5613 6.778E-07 0.3332 9.062E-07 0.0704 4.866E-06 0.1655 1.167E-06 0.2652 1.071E-06 0.3859 9.986E-07 0.5921 5.837E-07 0.3526 7.727E-07 0.0740 4.099E-06 0.1749 1.006E-06 0.2805 9.209E-07 0.4082 8.519E-07 0.6246 5.026E-07 0.3732 6.578E-07 0.0777 3.442E-06 0.1849 8.661E-07 0.2967 7.897E-07 0.4317 7.259E-07 0.6589 4.327E-07 0.3950 5.591E-07 0.0816 2.882E-06 0.1955 7.440E-07 0.3139 6.753E-07 0.4566 6.177E-07 0.6950 3.724E-07 0.4180 4.745E-07 0.0857 2.406E-06 0.2066 6.376E-07 0.3320 5.758E-07 0.4829 5.250E-07 0.7332 3.204E-07 0.4423 4.020E-07 0.0901 2.003E-06 0.2184 5.452E-07 0.3512 4.895E-07 0.5108 4.456E-07 0.7734 2.755E-07 0.4681 3.402E-07 0.0946 1.663E-06 0.2309 4.649E-07 0.3715 4.150E-07 0.5402 3.778E-07 0.8159 2.367E-07 0.4954 2.874E-07 0.0994 1.378E-06 0.2441 3.953E-07 0.3930 3.508E-07 0.5714 3.198E-07 0.8607 2.032E-07 0.5243 2.425E-07 0.1044 1.138E-06 0.2580 3.351E-07 0.4157 2.957E-07 0.6043 2.703E-07 0.9079 1.742E-07 0.5549 2.043E-07 0.1097 9.388E-07 0.2728 2.832E-07 0.4398 2.487E-07 0.6392 2.281 E-07 0.9577 1.492E-07 0.5872 1.720E-07 0.1152 7.724E-07 0.2884 2.386E-07 0.4652 2.085E-07 0.6760 1.922E-07 1.0103 1.275E-07 0.6214 1.445E-07 0.1210 6.341E-07 0.3048 2.004E-07 0.4921 1.745E-07 0.7150 1.617E-07 1.0657 1.088E-07 0.6577 1.212E-07 0.1271 5.195E-07 0.3222 1.678E-07 0.5205 1.456E-07 0.7562 1.358E-07 1.1242 9.266E-08 0.6960 1.016E-07 0.1335 4.247E-07 0.3407 1.400E-07 0.5506 1.212E-07 0.7998 1.138E-07 1.1859 7.870E-08 0.7366 8.489E-08 0.1403 3.464E-07 0.3601 1.163E-07 0.5824 1.007E-07 0.8459 9.510E-08 1.2510 6.664E-08 0.7795 7.080E-08 0.1473 2.819E-07 0.3807 9.635E-08 0.6161 8.340E-08 0.8947 7.931E-08 1.3197 5.625E-08 0.8250 5.889E-08 0.1548 2.289E-07 0.4024 7.948E-08 0.6517 6.887E-08 0.9463 6.595E-08 1.3921 4.731E-08 0.8730 4.884E-08 0.1626 1.854E-07 0.4254 6.529E-08 0.6894 5.670E-08 1.0008 5.466E-08 1.4685 3.962E-08

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-3 Mean 5eh Fractile 16 h Fractile 5 dh Fractile 8 4th Fractile 95h Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.9239 4.036E-08 0.1708 1.497E-07 0.4497 5.339E-08 0.7293 4.651E-08 1.0585 4.513E-08 1.5491 3.304E-08 0.9778 3.322E-08 0.1794 1.206E-07 0.4754 4.344E-08 0.7714 3.800E-08 1.1196 3.711E-08 1.6342 2.742E-08 1.0348 2.722E-08 0.1884 9.682E-08 0.5026 3.516E-08 0.8160 3.091E-08 1.1841 3.038E-08 1.7238 2.263E-08 1.0951 2.219E-08 0.1979 7.747E-08 0.5313 2.830E-08 0.8632 2.502E-08 1.2524 2.474E-08 1.8185 1.857E-08 1.1590 1.798E-08 0.2079 6.174E-08 0.5616 2.264E-08 0.9131 2.015E-08 1.3246 2.003E-08 1.9183 1.515E-08 1.2265 1.449E-08 0.2184 4.900E-08 0.5937 1.799E-08 0.9659 1.613E-08 1.4010 1.612E-08 2.0236 1.228E-08 1.2980 1.160E-08 0.2294 3.870E-08 0.6276 1.420E-08 1.0217 1.283E-08 1.4818 1.289E-08 2.1346 9.886E-09 1.3737 9.214E-09 0.2410 3.040E-08 0.6635 1.112E-08 1.0808 1.014E-08 1.5672 1.023E-08 2.2518 7.902E-09 1.4538 7.265E-09 0.2532 2.375E-08 0.7014 8.648E-09 1.1432 7.956E-09 1.6575 8.059E-09 2.3754 6.268E-09 1.5385 5.682E-09 0.2659 1.843E-08 0.7415 6.669E-09 1.2093 6.193E-09 1.7531 6.297E-09 2.5057 4.933E-09 1.6282 4.405E-09 0.2794 1.420E-08 0.7838 5.099E-09 1.2792 4.783E-09 1.8542 4.878E-09 2.6433 3.851 E-09 1.7231 3.385E-09 0.2934 1.086E-08 0.8286 3.864E-09 1.3532 3.662E-09 1.9611 3.745E-09 2.7883 2.981E-09 1.8235 2.576E-09 0.3082 8.232E-09 0.8759 2.902E-09 1.4314 2.778E-09 2.0742 2.849E-09 2.9414 2.287E-09 1.9298 1.941 E-09 0.3238 6.186E-09 0.9260 2.159E-09 1.5141 2.088E-09 2.1937 2.146E-09 3.1028 1.739E-09 2.0423 1.448E-09 0.3401 4.605E-09 0.9789 1.590E-09 1.6017 1.554E-09 2.3202 1.600E-09 3.2731 1.310E-09 2.1614 1.068E-09 0.3573 3.393E-09 1.0348 1.160E-09 1.6943 1.145E-09 2.4540 1.181E-09 3.4528 9.769E-10 2.2874 7.796E-10 0.3753 2.474E-09 1.0939 8.370E-10 1.7922 8.351E-10 2.5955 8.623E-10 3.6423 7.216E-10 2.4207 5.626E-10 0.3942 1.783E-09 1.1564 5.978E-10 1.8958 6.024E-10 2.7451 6.226E-10 3.8422 5.276E-10 2.5619 4.013E-10 0.4141 1.271E-09 1.2224 4.224E-10 2.0054 4.297E-10 2.9034 4.445E-10 4.0531 3.818E-10 2.7112 2.829E-10 0.4350 8.947E-10 1.2923 2.951E-10 2.1213 3.030E-10 3.0708 3.137E-10 4.2755 2.733E-10 2.8692 1.970E-10 0.4570 6.219E-10 1.3661 2.039E-10 2.2440 2.112E-10 3.2479 2.188E-10 4.5102 1.936E-10 3.0365 1.355E-10 0.4800 4.268E-10 1.4441 1.393E-10 2.3737 1.454E-10 3.4351 1.508E-10 4.7577 1.356E-10 3.2135 9.204E-11 0.5042 2.889E-10 1.5266 9.404E-11 2.5109 9.892E-11 3.6332 1.026E-10 5.0189 9.395E-11 3.4008 6.172E-11 0.5297 1.930E-10 1.6139 6.274E-11 2.6561 6.646E-11 3.8427 6.900E-11 5.2943 6.435E-11

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-4 Table A-lb. 0.5 Hz Seismic Hazard Curves at Farley_.

Mean 5" Fractile lh Fractile 5dh Fractile 84"h Fractile 95th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0104 1.077E-03 0.0022 1.072E-03 0.0036 1.073E-03 0.0079 1.079E-03 0.0152 1.088E-03 0.0210 1.090E-03 0.0108 1.076E-03 0.0023 1.071E-03 0.0038 1.072E-03 0.0081 1.078E-03 0.0158 1.086E-03 0.0219 1.089E-03 0.0112 1.074E-03 0.0024 1.069E-03 0.0039 1.070E-03 0.0084 1.076E-03 0.0164 1.085E-03 0.0227 1.087E-03 0.0117 1.072E-03 0.0025 1.067E-03 0.0041 1.068E-03 0.0087 1.074E-03 0.0170 1.083E-03 0.0236 1.084E-03 0.0121 1.069E-03 0.0026 1.065E-03 0.0042 1.066E-03 0.0091 1.072E-03 0.0176 1.080E-03 0.0246 1.081E-03 0.0126 1.065E-03 0.0027 1.061 E-03 0.0044 1.062E-03 0.0094 1.068E-03 0.0182 1.076E-03 0.0255 1.076E-03 0.0131 1.060E-03 0.0028 1.056E-03 0.0046 1.057E-03 0.0097 1.064E-03 0.0189 1.071 E-03 0.0266 1.070E-03 0.0137 1.053E-03 0.0029 1.049E-03 0.0048 1.051 E-03 0.0101 1.058E-03 0.0196 1.065E-03 0.0276 1.063E-03 0.0142 1.045E-03 0.0031 1.041 E-03 0.0049 1.044E-03 0.0105 1.051 E-03 0.0203 1.057E-03 0.0287 1.053E-03 0.0148 1.034E-03 0.0032 1.031E-03 0.0051 1.034E-03 0.0108 1.042E-03 0.0210 1.047E-03 0.0298 1.041E-03 0.0154 1.021 E-03 0.0033 1.018E-03 0.0053 1.022E-03 0.0112 1.031 E-03 0.0218 1.035E-03 0.0310 1.027E-03 0.0160 1.005E-03 0.0035 1.002E-03 0.0055 1.008E-03 0.0117 1.018E-03 0.0225 1.021 E-03 0.0322 1.009E-03 0.0166 9.866E-04 0.0036 9.843E-04 0.0058 9.910E-04 0.0121 1.003E-03 0.0234 1.005E-03 0.0335 9.891E-04 0.0173 9.649E-04 0.0038 9.633E-04 0.0060 9.714E-04 0.0125 9.851E-04 0.0242 9.857E-04 0.0348 9.657E-04 0.0180 9.402E-04 0.0039 9.392E-04 0.0062 9.490E-04 0.0130 9.646E-04 0.0251 9.638E-04 0.0362 9.391E-04 0.0187 9.126E-04 0.0041 9.123E-04 0.0065 9.238E-04 0.0135 9.414E-04 0.0260 9.391E-04 0.0376 9.094E-04 0.0195 8.821E-04 0.0042 8.826E-04 0.0067 8.958E-04 0.0139 9.156E-04 0.0269 9.117E-04 0.0391 8.767E-04 0.0203 8.491E-04 0.0044 8.504E-04 0.0070 8.653E-04 0.0145 8.872E-04 0.0279 8.817E-04 0.0407 8.413E-04 0.0211 8.138E-04 0.0046 8.160E-04 0.0073 8.326E-04 0.0150 8.564E-04 0.0289 8.492E-04 0.0423 8.035E-04 0.0220 7.766E-04 0.0048 7.799E-04 0.0076 7.979E-04 0.0155 8.235E-04 0.0300 8.145E-04 0.0440 7.638E-04 0.0228 7.381E-04 0.0050 7.425E-04 0.0078 7.617E-04 0.0161 7.888E-04 0.0311 7.780E-04 0.0457 7.226E-04 0.0238 6.987E-04 0.0052 7.042E-04 0.0082 7.244E-04 0.0167 7.525E-04 0.0322 7.399E-04 0.0475 6.806E-04 0.0247 6.589E-04 0.0054 6.655E-04 0.0085 6.864E-04 0.0173 7.152E-04 0.0334 7.008E-04 0.0494 6.381E-04 0.0257 6.192E-04 0.0056 6.270E-04 0.0088 6.482E-04 0.0179 6.772E-04 0.0346 6.610E-04 0.0513 5.957E-04 0.0268 5.800E-04 0.0058 5.889E-04 0.0092 6.102E-04 0.0186 6.389E-04 0.0358 6.21 OE-04 0.0534 5.540E-04 0.0278 5.417E-04 0.0061 5.517E-04 0.0095 5.728E-04 0.0193 6.007E-04 0.0371 5.812E-04 0.0555 5.133E-04 0.0290 5.046E-04 0.0063 5.157E-04 0.0099 5.363E-04 0.0200 5.630E-04 0.0385 5.420E-04 0.0577 4.740E-04 0.0301 4.690E-04 0.0066 4.811E-04 0.0103 5.010E-04 0.0207 5.262E-04 0.0399 5.038E-04 0.0599 4.364E-04 0.0313 4.351E-04 0.0069 4.481E-04 0.0107 4.671E-04 0.0215 4.904E-04 0.0413 4.667E-04 0.0623 4.008E-04 0.0326 4.030E-04 0.0071 4.169E-04 0.0111 4.348E-04 0.0222 4.560E-04 0.0428 4.312E-04 0.0648 3.672E-04 0.0339 3.728E-04 0.0074 3.873E-04 0.0115 4.041 E-04 0.0231 4.232E-04 0.0443 3.973E-04 0.0673 3.358E-04 0.0353 3.444E-04 0.0077 3.596E-04 0.0120 3.752E-04 0.0239 3.919E-04 0.0460 3.652E-04 0.0700 3.067E-04 0.0367 3.179E-04 0.0080 3.336E-04 0.0125 3.480E-04 0.0248 3.624E-04 0.0476 3.350E-04 0.0728 2.796E-04 0.0382 2.932E-04 0.0084 3.093E-04 0.0130 3.225E-04 0.0257 3.347E-04 0.0493 3.068E-04 0.0756 2.547E-04 0.0397 2.703E-04 0.0087 2.867E-04 0.0135 2.987E-04 0.0266 3.087E-04 0.0511 2.805E-04 0.0786 2.318E-04 0.0413 2.490E-04 0.0091 2.656E-04 0.0140 2.766E-04 0.0276 2.845E-04 0.0530 2.561E-04 0.0817 2.107E-04 0.0430 2.292E-04 0.0094 2.460E-04 0.0146 2.559E-04 0.0286 2.619E-04 0.0549 2.335E-04 0.0850 1.914E-04 0.0447 2.109E-04 0.0098 2.277E-04 0.0151 2.366E-04 0.0296 2.410E-04 0.0569 2.126E-04 0.0883 1.738E-04

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-5 Mean 5h Fractile 16th Fractile 5 dh Fractile 8 4 th Fractile 9eh Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0465 1.939E-04 0.0102 2.107E-04 0.0157 2.187E-04 0.0307 2.215E-04 0.0590 1.935E-04 0.0918 1.576E-04 0.0484 1.781 E-04 0.0107 1.949E-04 0.0163 2.020E-04 0.0318 2.035E-04 0.0611 1.758E-04 0.0954 1.428E-04 0.0504 1.634E-04 0.0111 1.801 E-04 0.0170 1.865E-04 0.0330 1.868E-04 0.0633 1.597E-04 0.0992 1.293E-04 0.0524 1.499E-04 0.0116 1.663E-04 0.0177 1.720E-04 0.0342 1.713E-04 0.0656 1.449E-04 0.1031 1.169E-04 0.0545 1.372E-04 0.0120 1.535E-04 0.0183 1.585E-04 0.0355 1.570E-04 0.0680 1.313E-04 0.1072 1.055E-04 0.0567 1.255E-04 0.0125 1.415E-04 0.0191 1.460E-04 0.0368 1.438E-04 0.0704 1.190E-04 0.1115 9.514E-05 0.0590 1.146E-04 0.0130 1.302E-04 0.0198 1.342E-04 0.0381 1.315E-04 0.0730 1.076E-04 0.1159 8.565E-05 0.0614 1.045E-04 0.0136 1.197E-04 0.0206 1.232E-04 0.0395 1.201E-04 0.0756 9.730E-05 0.1204 7.698E-05 0.0638 9.517E-05 0.0141 1.098E-04 0.0214 1.129E-04 0.0409 1.096E-04 0.0784 8.787E-05 0.1252 6.908E-05 0.0664 8.649E-05 0.0147 1.006E-04 0.0223 1.033E-04 0.0424 9.989E-05 0.0812 7.928E-05 0.1301 6.187E-05 0.0691 7.846E-05 0.0153 9.192E-05 0.0231 9.439E-05 0.0440 9.090E-05 0.0842 7.144E-05 0.1353 5.533E-05 0.0719 7.105E-05 0.0159 8.384E-05 0.0240 8.604E-05 0.0456 8.259E-05 0.0872 6.432E-05 0.1406 4.938E-05 0.0748 6.422E-05 0.0166 7.631 E-05 0.0250 7.827E-05 0.0473 7.492E-05 0.0904 5.784E-05 0.1462 4.400E-05 0.0778 5.794E-05 0.0173 6.930E-05 0.0260 7.104E-05 0.0490 6.786E-05 0.0937 5.196E-05 0.1520 3.914E-05 0.0809 5.219E-05 0.0180 6.280E-05 0.0270 6.434E-05 0.0508 6.137E-05 0.0971 4.663E-05 0.1580 3.477E-05 0.0842 4.694E-05 0.0187 5.678E-05 0.0280 5.815E-05 0.0526 5.541E-05 0.1006 4.180E-05 0.1642 3.084E-05 0.0876 4.214E-05 0.0195 5.124E-05 0.0292 5.245E-05 0.0546 4.995E-05 0.1042 3.743E-05 0.1707 2.731E-05 0.0911 3.779E-05 0.0203 4.614E-05 0.0303 4.720E-05 0.0566 4.497E-05 0.1080 3.349E-05 0.1775 2.416E-05 0.0948 3.384E-05 0.0211 4.148E-05 0.0315 4.241E-05 0.0586 4.042E-05 0.1119 2.994E-05 0.1845 2.135E-05 0.0986 3.026E-05 0.0220 3.723E-05 0.0327 3.803E-05 0.0608 3.629E-05 0.1160 2.675E-05 0.1918 1.885E-05 0.1026 2.704E-05 0.0229 3.336E-05 0.0340 3.404E-05 0.0630 3.255E-05 0.1202 2.387E-05 0.1994 1.663E-05 0.1068 2.413E-05 0.0238 2.985E-05 0.0354 3.043E-05 0.0653 2.916E-05 0.1245 2.130E-05 0.2072 1.466E-05 0.1111 2.152E-05 0.0248 2.669E-05 0.0367 2.717E-05 0.0677 2.610E-05 0.1290 1.899E-05 0.2154 1.292E-05 0.1155 1.917E-05 0.0258 2.383E-05 0.0382 2.422E-05 0.0701 2.334E-05 0.1337 1.692E-05 0.2239 1.138E-05 0.1202 1.707E-05 0.0268 2.126E-05 0.0397 2.157E-05 0.0727 2.086E-05 0.1386 1.507E-05 0.2328 1.002E-05 0.1250 1.518E-05 0.0279 1.895E-05 0.0413 1.919E-05 0.0754 1.863E-05 0.1436 1.342E-05 0.2420 8.822E-06 0.1301 1.349E-05 0.0291 1.687E-05 0.0429 1.706E-05 0.0781 1.663E-05 0.1488 1.195E-05 0.2516 7.764E-06 0.1353 1.198E-05 0.0303 1.502E-05 0.0446 1.515E-05 0.0810 1.484E-05 0.1542 1.064E-05 0.2615 6.832E-06 0.1408 1.064E-05 0.0315 1.335E-05 0.0463 1.344E-05 0.0839 1.324E-05 0.1598 9.465E-06 0.2718 6.012E-06 0.1465 9.432E-06 0.0328 1.186E-05 0.0481 1.192E-05 0.0870 1.181E-05 0.1655 8.422E-06 0.2826 5.289E-06 0.1524 8.358E-06 0.0342 1.053E-05 0.0500 1.056E-05 0.0902 1.053E-05 0.1715 7.493E-06 0.2938 4.653E-06 0.1585 7.400E-06 0.0356 9.338E-06 0.0520 9.345E-06 0.0935 9.380E-06 0.1778 6.667E-06 0.3054 4.093E-06 0.1649 6.546E-06 0.0370 8.273E-06 0.0541 8.266E-06 0.0969 8.355E-06 0.1842 5.932E-06 0.3174 3.601E-06 0.1716 5.787E-06 0.0385 7.323E-06 0.0562 7.305E-06 0.1004 7.439E-06 0.1909 5.278E-06 0.3300 3.168E-06 0.1785 5.111E-06 0.0401 6.475E-06 0.0584 6.452E-06 0.1041 6.621E-06 0.1978 4.696E-06 0.3430 2.787E-06 0.1857 4.511E-06 0.0418 5.720E-06 0.0607 5.694E-06 0.1079 5.890E-06 0.2050 4.178E-06 0.3566 2.452E-06 0.1932 3.979E-06 0.0435 5.048E-06 0.0631 5.023E-06 0.1119 5.238E-06 0.2124 3.718E-06 0.3707 2.158E-06 0.2010 3.506E-06 0.0453 4.450E-06 0.0656 4.428E-06 0.1159 4.655E-06 0.2201 3.308E-06 0.3853 1.899E-06 0.2091 3.088E-06 0.0471 3.919E-06 0.0681 3.901E-06 0.1202 4.135E-06 0.2281 2.944E-06 0.4006 1.672E-06

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-6 Mean 5h Fractile leh Fractile 5 dh Fractile 8 4 th Fractile 95th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.2175 2.718E-06 0.0490 3.449E-06 0.0708 3.436E-06 0.1246 3.672E-06 0.2363 2.620E-06 0.4164 1.472E-06 0.2263 2.391E-06 0.0510 3.032E-06 0.0736 3.026E-06 0.1291 3.258E-06 0.2449 2.332E-06 0.4329 1.297E-06 0.2354 2.103E-06 0.0531 2.664E-06 0.0765 2.664E-06 0.1338 2.890E-06 0.2538 2.075E-06 0.4500 1.143E-06 0.2449 1.848E-06 0.0553 2.339E-06 0.0795 2.345E-06 0.1387 2.563E-06 0.2630 1.847E-06 0.4678 1.007E-06 0.2548 1.624E-06 0.0576 2.053E-06 0.0826 2.063E-06 0.1438 2.271E-06 0.2725 1.644E-06 0.4863 8.886E-07 0.2651 1.426E-06 0.0599 1.800E-06 0.0859 1.816E-06 0.1491 2.012E-06 0.2824 1.463E-06 0.5055 7.843E-07 0.2758 1.252E-06 0.0624 1.579E-06 0.0893 1.598E-06 0.1545 1.782E-06 0.2926 1.302E-06 0.5255 6.926E-07 0.2869 1.099E-06 0.0650 1.383E-06 0.0928 1.406E-06 0.1602 1.578E-06 0.3032 1.159E-06 0.5462 6.121E-07 0.2984 9.648E-07 0.0676 1.212E-06 0.0964 1.238E-06 0.1660 1.397E-06 0.3142 1.031E-06 0.5678 5.412E-07 0.3105 8.465E-07 0.0704 1.062E-06 0.1002 1.089E-06 0.1721 1.236E-06 0.3256 9.173E-07 0.5903 4.789E-07 0.3230 7.425E-07 0.0733 9.301E-07 0.1042 9.582E-07 0.1784 1.094E-06 0.3374 8.160E-07 0.6136 4.240E-07 0.3360 6.512E-07 0.0763 8.146E-07 0.1083 8.429E-07 0.1849 9.673E-07 0.3496 7.258E-07 0.6379 3.757E-07 0.3496 5.709E-07 0.0794 7.133E-07 0.1125 7.413E-07 0.1916 8.555E-07 0.3623 6.454E-07 0.6631 3.330E-07 0.3637 5.004E-07 0.0827 6.246E-07 0.1170 6.518E-07 0.1986 7.565E-07 0.3754 5.737E-07 0.6893 2.953E-07 0.3784 4.384E-07 0.0860 5.469E-07 0.1216 5.729E-07 0.2059 6.688E-07 0.3891 5.099E-07 0.7165 2.620E-07 0.3936 3.840E-07 0.0896 4.787E-07 0.1264 5.033E-07 0.2134 5.911E-07 0.4032 4.530E-07 0.7449 2.325E-07 0.4095 3.362E-07 0.0932 4.190E-07 0.1313 4.420E-07 0.2212 5.223E-07 0.4178 4.024E-07 0.7743 2.064E-07 0.4260 2.943E-07 0.0971 3.666E-07 0.1365 3.880E-07 0.2293 4.615E-07 0.4329 3.572E-07 0.8049 1.833E-07 0.4432 2.575E-07 0.1010 3.207E-07 0.1419 3.404E-07 0.2377 4.075E-07 0.4486 3.170E-07 0.8367 1.627E-07 0.4611 2.252E-07 0.1052 2.804E-07 0.1474 2.984E-07 0.2464 3.598E-07 0.4649 2.811 E-07 0.8698 1.444E-07 0.4797 1.968E-07 0.1095 2.450E-07 0.1532 2.614E-07 0.2554 3.175E-07 0.4817 2.492E-07 0.9042 1.282E-07 0,4990 1.719E-07 0.1140 2.139E-07 0.1593 2.289E-07 0.2647 2.801E-07 0.4992 2.208E-07 0.9399 1.137E-07 0.5844 1.OOOE-07 0.1425 1.OOOE-07 0.2022 1.OOOE-07 0.3552 1.OOOE-07 0.6293 1.OOOE-07 0.9799 1.OOOE-07

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-7 Table A-ic. 1 Hz Seismic Hazard Curves at Farley Mean 5 th Fractile 16h Fractile 50d Fractile 84' Fractile 95eh Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0153 1.077E-03 0.0051 1.068E-03 0.0071 1.069E-03 0.0127 1.076E-03 0.0202 1.084E-03 0.0278 1.088E-03 0.0160 1.073E-03 0.0053 1.064E-03 0.0073 1.066E-03 0.0132 1.072E-03 0.0210 1.080E-03 0.0290 1.084E-03 0.0167 1.069E-03 0.0055 1.060E-03 0.0076 1.062E-03 0.0137 1.068E-03 0.0218 1.075E-03 0.0302 1.080E-03 0.0173 1.063E-03 0.0057 1.056E-03 0.0079 1.057E-03 0.0142 1.063E-03 0.0227 1.070E-03 0.0314 1.074E-03 0.0181 1.057E-03 0.0060 1.050E-03 0.0082 1.051E-03 0.0147 1.057E-03 0.0236 1.063E-03 0.0327 1.067E-03 0.0188 1.049E-03 0.0062 1.044E-03 0.0086 1.045E-03 0.0153 1.050E-03 0.0246 1.056E-03 0.0341 1.059E-03 0.0196 1.041 E-03 0.0064 1.037E-03 0.0089 1.037E-03 0.0159 1.042E-03 0.0256 1.047E-03 0.0355 1.050E-03 0.0204 1.031 E-03 0.0067 1.028E-03 0.0092 1.029E-03 0.0165 1.033E-03 0.0266 1.037E-03 0.0370 1.039E-03 0.0213 1.020E-03 0.0069 1.019E-03 0.0096 1.019E-03 0.0172 1.023E-03 0.0277 1.026E-03 0.0385 1.027E-03 0.0222 1.007E-03 0.0072 1.008E-03 0.0100 1.008E-03 0.0178 1.011E-03 0.0288 1.013E-03 0.0401 1.013E-03 0.0231 9.922E-04 0.0075 9.962E-04 0.0104 9.959E-04 0.0185 9.981E-04 0.0299 9.984E-04 0.0418 9.977E-04 0.0241 9.761E-04 0.0078 9.829E-04 0.0108 9.822E-04 0.0192 9.838E-04 0.0311 9.824E-04 0.0435 9.805E-04 0.0251 9.584E-04 0.0081 9.682E-04 0.0112 9.671E-04 0.0200 9.679E-04 0.0324 9.647E-04 0.0453 9.614E-04 0.0261 9.388E-04 0.0084 9.520E-04 0.0116 9.505E-04 0.0207 9.506E-04 0.0337 9.453E-04 0.0472 9.405E-04 0.0272 9.176E-04 0.0087 9.344E-04 0.0121 9.324E-04 0.0216 9.317E-04 0.0350 9.243E-04 0.0492 9.179E-04 0.0283 8.946E-04 0.0090 9.154E-04 0.0125 9.129E-04 0.0224 9.113E-04 0.0365 9.016E-04 0.0512 8.934E-04 0.0295 8.701 E-04 0.0094 8.949E-04 0.0130 8.919E-04 0.0233 8.894E-04 0.0379 8.772E-04 0.0533 8.671 E-04 0.0307 8.439E-04 0.0097 8.731E-04 0.0135 8.694E-04 0.0242 8.660E-04 0.0394 8.513E-04 0.0556 8.393E-04 0.0320 8.163E-04 0.0101 8.499E-04 0.0141 8.456E-04 0.0251 8.412E-04 0.0410 8.239E-04 0.0579 8.099E-04 0.0334 7.874E-04 0.0105 8.254E-04 0.0146 8.206E-04 0.0261 8.152E-04 0.0427 7.952E-04 0.0603 7.792E-04 0.0348 7.573E-04 0.0109 7.998E-04 0.0152 7.943E-04 0.0271 7.879E-04 0.0444 7.652E-04 0.0628 7.473E-04 0.0362 7.263E-04 0.0113 7.731E-04 0.0158 7.670E-04 0.0281 7.596E-04 0.0462 7.343E-04 0.0654 7.144E-04 0.0377 6.944E-04 0.0118 7.455E-04 0.0164 7.388E-04 0.0292 7.304E-04 0.0480 7.025E-04 0.0681 6.807E-04 0.0393 6.620E-04 0.0122 7.172E-04 0.0170 7.099E-04 0.0303 7.005E-04 0.0500 6.700E-04 0.0709 6.464E-04 0.0409 6.292E-04 0.0127 6.881E-04 0.0177 6.803E-04 0.0315 6.699E-04 0.0520 6.371E-04 0.0739 6.118E-04 0.0426 5.963E-04 0.0132 6.587E-04 0.0184 6.503E-04 0.0327 6.390E-04 0.0541 6.039E-04 0.0769 5.771E-04 0.0444 5.634E-04 0.0137 6.289E-04 0.0191 6.200E-04 0.0340 6.078E-04 0.0562 5.707E-04 0.0801 5.426E-04 0.0463 5.308E-04 0.0142 5.990E-04 0.0198 5.897E-04 0.0353 5.766E-04 0.0585 5.377E-04 0.0834 5.084E-04 0.0482 4.986E-04 0.0148 5.691E-04 0.0206 5.594E-04 0.0367 5.455E-04 0.0608 5.051E-04 0.0869 4.748E-04 0.0502 4.670E-04 0.0153 5.394E-04 0.0214 5.293E-04 0.0381 5.147E-04 0.0633 4.729E-04 0.0905 4.420E-04 0.0523 4.363E-04 0.0159 5.100E-04 0.0222 4.997E-04 0.0396 4.843E-04 0.0658 4.416E-04 0.0943 4.100E-04 0.0545 4.065E-04 0.0166 4.811E-04 0.0231 4.705E-04 0.0411 4.546E-04 0.0685 4.11OE-04 0.0982 3.792E-04 0.0567 3.777E-04 0.0172 4.528E-04 0.0240 4.421E-04 0.0427 4.255E-04 0.0712 3.815E-04 0.1022 3.496E-04 0.0591 3.501E-04 0.0179 4.252E-04 0.0249 4.144E-04 0.0444 3.974E-04 0.0741 3.531E-04 0.1065 3.213E-04 0.0616 3.238E-04 0.0185 3.985E-04 0.0259 3.876E-04 0.0461 3.702E-04 0.0771 3.260E-04 0.1109 2.944E-04 0.0641 2.987E-04 0.0193 3.726E-04 0.0269 3.618E-04 0.0479 3.441E-04 0.0802 3.001E-04 0.1155 2.690E-04 0.0668 2.750E-04 0.0200 3.478E-04 0.0280 3.370E-04 0.0497 3.190E-04 0.0834 2.755E-04 0.1203 2.450E-04 0.0696 2.526E-04 0.0208 3.240E-04 0.0291 3.133E-04 0.0516 2.952E-04 0.0867 2.523E-04 0.1253 2.226E-04

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-8 Mean 5eh Fractile 1 6*h Fractile 5 dh Fractile 8 4th Fractile 950h Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0725 2.316E-04 0.0216 3.013E-04 0.0302 2.907E-04 0.0536 2.725E-04 0.0902 2.305E-04 0.1305 2.017E-04 0.0755 2.119E-04 0.0224 2.797E-04 0.0314 2.693E-04 0.0557 2.511E-04 0.0938 2.101E-04 0.1359 1.822E-04 0.0787 1.935E-04 0.0233 2.592E-04 0.0326 2.490E-04 0.0579 2.309E-04 0.0976 1.911 E-04 0.1415 1.643E-04 0.0820 1.764E-04 0.0242 2.399E-04 0.0339 2.299E-04 0.0601 2.119E-04 0.1015 1.733E-04 0.1474 1.477E-04 0.0854 1.605E-04 0.0251 2.216E-04 0.0352 2.120E-04 0.0624 1.942E-04 0.1056 1.569E-04 0.1535 1.324E-04 0.0889 1.458E-04 0.0261 2.045E-04 0.0365 1.951E-04 0.0649 1.776E-04 0.1099 1.418E-04 0.1599 1.185E-04 0.0927 1.322E-04 0.0271 1.884E-04 0.0380 1.794E-04 0.0674 1.621E-04 0.1143 1.278E-04 0.1665 1.058E-04 0.0965 1.197E-04 0.0281 1.734E-04 0.0394 1.647E-04 0.0700 1.478E-04 0.1189 1.150E-04 0.1735 9.419E-05 0.1005 1.082E-04 0.0292 1.594E-04 0.0410 1.510E-04 0.0727 1.345E-04 0.1236 1.032E-04 0.1807 8.370E-05 0.1047 9.765E-05 0.0303 1.464E-04 0.0426 1.383E-04 0.0755 1.222E-04 0.1286 9.250E-05 0.1882 7.421 E-05 0.1091 8.797E-05 0.0315 1.342E-04 0.0442 1.264E-04 0.0784 1.109E-04 0.1338 8.274E-05 0.1960 6.566E-05 0.1137 7.912E-05 0.0327 1.230E-04 0.0460 1.155E-04 0.0815 1.005E-04 0.1391 7.386E-05 0.2041 5.797E-05 0.1184 7.104E-05 0.0340 1.125E-04 0.0478 1.054E-04 0.0846 9.092E-05 0.1447 6.581E-05 0.2126 5.108E-05 0.1233 6.368E-05 0.0353 1.029E-04 0.0496 9.608E-05 0.0879 8.215E-05 0.1505 5.853E-05 0.2214 4.492E-05 0.1285 5.698E-05 0.0367 9.395E-05 0.0515 8.748E-05 0.0913 7.412E-05 0.1566 5.196E-05 0.2306 3.942E-05 0.1338 5.090E-05 0.0381 8.572E-05 0.0535 7.956E-05 0.0948 6.678E-05 0.1629 4.605E-05 0.2401 3.453E-05 0.1394 4.539E-05 0.0396 7.814E-05 0.0556 7.228E-05 0.0985 6.009E-05 0.1694 4.073E-05 0.2501 3.019E-05 0.1452 4.041 E-05 0.0411 7.115E-05 0.0578 6.560E-05 0.1023 5.400E-05 0.1762 3.597E-05 0.2605 2.635E-05 0.1513 3.590E-05 0.0427 6.473E-05 0.0601 5.946E-05 0.1063 4.846E-05 0.1833 3.171E-05 0.2713 2.296E-05 0.1576 3.185E-05 0.0443 5.883E-05 0.0624 5.385E-05 0.1104 4.343E-05 0.1907 2.791E-05 0.2826 1.997E-05 0.1642 2.820E-05 0.0460 5.342E-05 0.0648 4.871E-05 0.1147 3.887E-05 0.1984 2.453E-05 0.2943 1.735E-05 0.1710 2.492E-05 0.0478 4.846E-05 0.0673 4.401E-05 0.1191 3.474E-05 0.2063 2.152E-05 0.3065 1.505E-05 0.1782 2.199E-05 0.0497 4.392E-05 0.0700 3.973E-05 0.1237 3.101E-05 0.2146 1.886E-05 0.3192 1.304E-05 0.1856 1.936E-05 0.0516 3.977E-05 0.0727 3.582E-05 0.1285 2.764E-05 0.2232 1.650E-05 0.3325 1.128E-05 0.1933 1.702E-05 0.0536 3.597E-05 0.0755 3.226E-05 0.1335 2.461E-05 0.2322 1.442E-05 0.3463 9.754E-06 0.2014 1.494E-05 0.0556 3.251E-05 0.0785 2.903E-05 0.1387 2.188E-05 0.2415 1.258E-05 0.3606 8.426E-06 0.2098 1.309E-05 0.0578 2.936E-05 0.0815 2.609E-05 0.1440 1.943E-05 0.2512 1.097E-05 0.3756 7.273E-06 0.2185 1.145E-05 0.0600 2.649E-05 0.0847 2.342E-05 0.1496 1.723E-05 0.2613 9.555E-06 0.3912 6.275E-06 0.2277 1.OO0E-05 0.0623 2.388E-05 0.0880 2.101E-05 0.1554 1.526E-05 0.2718 8.315E-06 0.4074 5.412E-06 0.2372 8.721E-06 0.0647 2.150E-05 0.0914 1.883E-05 0.1614 1.350E-05 0.2828 7.230E-06 0.4243 4.668E-06 0.2470 7.593E-06 0.0672 1.935E-05 0.0950 1.685E-05 0.1677 1.192E-05 0.2941 6.283E-06 0.4419 4.026E-06 0.2574 6.601E-06 0.0698 1.740E-05 0.0987 1.507E-05 0.1742 1.052E-05 0.3059 5.457E-06 0.4603 3.473E-06 0.2681 5.731E-06 0.0725 1.563E-05 0.1025 1.346E-05 0.1809 9.273E-06 0.3182 4.737E-06 0.4794 2.998E-06 0.2793 4.970E-06 0.0753 1.403E-05 0.1065 1.201E-05 0.1879 8.164E-06 0.3310 4.111E-06 0.4993 2.589E-06 0.2909 4.304E-06 0.0782 1.259E-05 0.1106 1.071E-05 0.1952 7.179E-06 0.3443 3.567E-06 0.5200 2.238E-06 0.3030 3.723E-06 0.0812 1.128E-05 0.1150 9.537E-06 0.2028 6.306E-06 0.3582 3.095E-06 0.5416 1.937E-06 0.3157 3.217E-06 0.0844 1.01OE-05 0.1194 8.486E-06 0.2106 5.534E-06 0.3726 2.685E-06 0.5641 1.678E-06 0.3289 2.777E-06 0.0876 9.040E-06 0.1241 7.543E-06 0.2188 4.852E-06 0.3875 2.330E-06 0.5875 1.456E-06 0.3426 2.396E-06 0.0910 8.083E-06 0.1289 6.699E-06 0.2272 4.249E-06 0.4031 2.023E-06 0.6118 1.265E-06

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-9 Mean 5 h Fractile leh Fractile 5 dh Fractile 8 4 th Fractile 9 5Eh Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.3569 2.065E-06 0.0945 7.223E-06 0.1339 5.943E-06 0.2360 3.718E-06 0.4193 1.756E-06 0.6372 1.102E-06 0.3717 1.779E-06 0.0982 6.448E-06 0.1391 5.267E-06 0.2452 3.251E-06 0.4361 1.526E-06 0.6637 9.608E-07 0.3872 1.532E-06 0.1020 5.753E-06 0.1446 4.663E-06 0.2547 2.840E-06 0.4537 1.326E-06 0.6912 8.396E-07 0.4034 1.319E-06 0.1059 5.128E-06 0.1502 4.125E-06 0.2645 2.479E-06 0.4719 1.153E-06 0.7199 7.352E-07 0.4202 1.135E-06 0.1100 4.568E-06 0.1560 3.645E-06 0.2748 2.162E-06 0.4909 1.004E-06 0.7498 6.451E-07 0.4378 9.770E-07 0.1142 4.065E-06 0.1621 3.218E-06 0.2854 1.885E-06 0.5106 8.743E-07 0.7809 5.673E-07 0.4560 8.411E-07 0.1186 3.615E-06 0.1684 2.838E-06 0.2965 1.642E-06 0.5311 7.622E-07 0.8133 4.998E-07 0.4750 7.243E-07 0.1232 3.212E-06 0.1750 2.501E-06 0.3080 1.429E-06 0.5524 6.651E-07 0.8471 4.413E-07 0.4948 6.241E-07 0.1280 2.852E-06 0.1818 2.201E-06 0.3199 1.243E-06 0.5746 5.809E-07 0.8822 3.903E-07 0.5155 5.380E-07 0.1329 2.530E-06 0.1889 1.936E-06 0.3323 1.081E-06 0.5977 5.078E-07 0.9188 3.459E-07 0.5370 4.642E-07 0.1381 2.242E-06 0.1962 1.700E-06 0.3452 9.399E-07 0.6217 4.444E-07 0.9570 3.070E-07 0.5594 4.008E-07 0.1434 1.985E-06 0.2039 1.492E-06 0.3585 8.167E-07 0.6467 3.894E-07 0.9967 2.729E-07 0.5827 3.465E-07 0.1489 1.756E-06 0.2118 1.309E-06 0.3724 7.094E-07 0.6727 3.415E-07 1.0380 2.429E-07 0.6070 2.998E-07 0.1547 1.551E-06 0.2201 1.146E-06 0.3868 6.159E-07 0.6997 2.997E-07 1.0811 2.164E-07 0.6323 2.597E-07 0.1606 1.369E-06 0.2286 1.003E-06 0.4018 5.347E-07 0.7279 2.634E-07 1.1260 1.930E-07 0.6587 2.252E-07 0.1668 1.208E-06 0.2375 8.772E-07 0.4174 4.640E-07 0.7571 2.316E-07 1.1727 1.723E-07 0.6862 1.956E-07 0.1733 1.064E-06 0.2468 7.662E-07 0.4335 4.026E-07 0.7875 2.039E-07 1.2214 1.538E-07 0.7148 1.700E-07 0.1800 9.361E-07 0.2564 6.686E-07 0.4503 3.492E-07 0.8192 1.796E-07 1.2721 1.374E-07 0.7446 1.479E-07 0.1869 8.228E-07 0.2664 5.829E-07 0.4678 3.029E-07 0.8521 1.583E-07 1.3248 1.227E-07 0.7757 1.289E-07 0.1941 7.223E-07 0.2767 5.077E-07 0.4859 2.626E-07 0.8863 1.396E-07 1.3798 1.096E-07 0.8080 1.123E-07 0.2016 6.333E-07 0.2875 4.417E-07 0.5047 2.277E-07 0.9220 1.231E-07 1.4371 9.784E-08 0.8417 9.801 E-08 0.2094 5.545E-07 0.2987 3.839E-07 0.5242 1.974E-07 0.9590 1.086E-07 1.4967 8.729E-08 0.8768 8.556E-08 0.3397 1.OOOE-07 0.4297 1.OOOE-07 0.6281 1.OOOE-07 0.9975 9.583E-08 1.5588 7.781 E-08

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-10 Table A-id. 2.5 Hz Seismic Hazard Curves at Farle_

Mean 5' Fractile 16 h Fractile 5 dh Fractile 84th Fractile 9 5th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0200 1.105E-03 0.0100 1.086E-03 0.0126 1.096E-03 0.0179 1.107E-03 0.0251 1.113E-03 0.0340 1.117E-03 0.0210 1.105E-03 0.0103 1.086E-03 0.0132 1.096E-03 0.0187 1.106E-03 0.0263 1.113E-03 0.0356 1.117E-03 0.0220 1.104E-03 0.0107 1.086E-03 0.0137 1.096E-03 0.0195 1.106E-03 0.0275 1.112E-03 0.0373 1.116E-03 0.0230 1.103E-03 0.0112 1.085E-03 0.0143 1.097E-03 0.0204 1.105E-03 0.0288 1.111E-03 0.0390 1.115E-03 0.0241 1.102E-03 0.0116 1.084E-03 0.0149 1.096E-03 0.0213 1.104E-03 0.0301 1.110E-03 0.0408 1.114E-03 0.0252 1.101E-03 0.0120 1.083E-03 0.0156 1.095E-03 0.0223 1.103E-03 0.0315 1.108E-03 0.0427 1.112E-03 0.0264 1.098E-03 0.0125 1.082E-03 0.0162 1.093E-03 0.0233 1.101E-03 0.0330 1.106E-03 0.0447 1.109E-03 0.0277 1.095E-03 0.0130 1.081E-03 0.0169 1.091E-03 0.0244 1.098E-03 0.0345 1.103E-03 0.0468 1.105E-03 0.0290 1.092E-03 0.0135 1.078E-03 0.0177 1.088E-03 0.0255 1.094E-03 0.0361 1.098E-03 0.0490 1.101E-03 0.0303 1.086E-03 0.0140 1.076E-03 0.0184 1.084E-03 0.0266 1.090E-03 0.0378 1.093E-03 0.0513 1.094E-03 0.0318 1.080E-03 0.0145 1.073E-03 0.0192 1.079E-03 0.0278 1.084E-03 0.0396 1.086E-03 0.0537 1.086E-03 0.0333 1.072E-03 0.0151 1.069E-03 0.0201 1.073E-03 0.0291 1.076E-03 0.0414 1.077E-03 0.0562 1.076E-03 0.0348 1.061 E-03 0.0157 1.064E-03 0.0209 1.066E-03 0.0304 1.067E-03 0.0433 1.066E-03 0.0588 1.064E-03 0.0365 1.049E-03 0.0163 1.058E-03 0.0218 1.057E-03 0.0318 1.056E-03 0.0453 1.052E-03 0.0616 1.049E-03 0.0382 1.034E-03 0.0169 1.050E-03 0.0228 1.046E-03 0.0332 1.043E-03 0.0475 1.036E-03 0.0644 1.030E-03 0.0400 1.016E-03 0.0176 1.042E-03 0.0237 1.033E-03 0.0347 1.027E-03 0.0497 1.016E-03 0.0674 1.009E-03 0.0419 9.948E-04 0.0182 1.032E-03 0.0248 1.018E-03 0.0363 1.008E-03 0.0520 9.937E-04 0.0706 9.835E-04 0.0439 9.706E-04 0.0189 1.020E-03 0.0258 1.OOOE-03 0.0379 9.865E-04 0.0544 9.677E-04 0.0739 9.548E-04 0.0459 9.432E-04 0.0197 1.006E-03 0.0270 9.799E-04 0.0397 9.620E-04 0.0569 9.384E-04 0.0773 9.225E-04 0.0481 9.127E-04 0.0204 9.910E-04 0.0281 9.572E-04 0.0414 9.344E-04 0.0596 9.057E-04 0.0809 8.868E-04 0.0504 8.790E-04 0.0212 9.736E-04 0.0293 9.318E-04 0.0433 9.038E-04 0.0624 8.699E-04 0.0847 8.478E-04 0.0527 8.424E-04 0.0220 9.542E-04 0.0306 9.039E-04 0.0453 8.704E-04 0.0653 8.311 E-04 0.0887 8.059E-04 0.0552 8.033E-04 0.0229 9.327E-04 0.0319 8.736E-04 0.0473 8.344E-04 0.0683 7.897E-04 0.0928 7.615E-04 0.0578 7.620E-04 0.0238 9.093E-04 0.0333 8.409E-04 0.0495 7.960E-04 0.0715 7.462E-04 0.0971 7.152E-04 0.0606 7.189E-04 0.0247 8.838E-04 0.0347 8.061E-04 0.0517 7.556E-04 0.0748 7.011E-04 0.1017 6.675E-04 0.0634 6.747E-04 0.0256 8.565E-04 0.0362 7.696E-04 0.0541 7.137E-04 0.0783 6.549E-04 0.1064 6.192E-04 0.0664 6.298E-04 0.0266 8.274E-04 0.0378 7.316E-04 0.0565 6.706E-04 0.0819 6.082E-04 0.1114 5.708E-04 0.0695 5.847E-04 0.0276 7.967E-04 0.0394 6.926E-04 0.0591 6.269E-04 0.0857 5.616E-04 0.1166 5.230E-04 0.0728 5.401E-04 0.0287 7.647E-04 0.0411 6.528E-04 0.0617 5.831E-04 0.0897 5.157E-04 0.1220 4.763E-04 0.0763 4.963E-04 0.0298 7.316E-04 0.0429 6.127E-04 0.0645 5.397E-04 0.0939 4.709E-04 0.1277 4.313E-04 0.0798 4.539E-04 0.0310 6.976E-04 0.0447 5.727E-04 0.0674 4.970E-04 0.0983 4.277E-04 0.1337 3.884E-04 0.0836 4.132E-04 0.0322 6.629E-04 0.0467 5.331E-04 0.0705 4.555E-04 0.1029 3.866E-04 0.1399 3.480E-04 0.0876 3.744E-04 0.0334 6.280E-04 0.0487 4.943E-04 0.0737 4.156E-04 0.1077 3.477E-04 0.1464 3.103E-04 0.0917 3.380E-04 0.0347 5.929E-04 0.0508 4.566E-04 0.0770 3.775E-04 0.1127 3.114E-04 0.1533 2.754E-04 0.0960 3.039E-04 0.0360 5.581E-04 0.0530 4.202E-04 0.0805 3.415E-04 0.1179 2.777E-04 0.1604 2.434E-04 0.1005 2.722E-04 0.0374 5.237E-04 0.0552 3.854E-04 0.0841 3.077E-04 0.1234 2.467E-04 0.1679 2.144E-04 0.1053 2.431E-04 0.0389 4.900E-04 0.0576 3.523E-04 0.0880 2.763E-04 0.1291 2.184E-04 0.1757 1.882E-04 0.1102 2.164E-04 0.0404 4.572E-04 0.0601 3.211E-04 0.0919 2.473E-04 0.1352 1.928E-04 0.1839 1.647E-04

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-11 Mean 5dh Fractile 16h Fractile 5 01h Fractile 8 4 th Fractile 95 h Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.1154 1.921E-04 0.0419 4.254E-04 0.0627 2.918E-04 0.0961 2.206E-04 0.1415 1.697E-04 0.1925 1.438E-04 0.1209 1.701 E-04 0.0435 3.948E-04 0.0654 2.644E-04 0.1004 1.962E-04 0.1480 1.491 E-04 0.2015 1.253E-04 0.1266 1.502E-04 0.0452 3.656E-04 0.0682 2.390E-04 0.1050 1.740E-04 0.1549 1.306E-04 0.2109 1.089E-04 0.1325 1.324E-04 0.0469 3.377E-04 0.0712 2.156E-04 0.1097 1.540E-04 0.1621 1.143E-04 0.2208 9.459E-05 0.1388 1.164E-04 0.0488 3.113E-04 0.0742 1.940E-04 0.1147 1.360E-04 0.1697 9.981E-05 0.2311 8.203E-05 0.1453 1.021E-04 0.0506 2.864E-04 0.0774 1.742E-04 0.1199 1.198E-04 0.1776 8.707E-05 0.2418 7.105E-05 0.1522 8.943E-05 0.0526 2.630E-04 0.0808 1.561 E-04 0.1253 1.054E-04 0.1859 7.587E-05 0.2531 6.150E-05 0.1594 7.816E-05 0.0546 2.411 E-04 0.0843 1.396E-04 0.1310 9.248E-05 0.1945 6.605E-05 0.2649 5.319E-05 0.1669 6.819E-05 0.0567 2.207E-04 0.0879 1.246E-04 0.1369 8.104E-05 0.2036 5.746E-05 0.2773 4.599E-05 0.1747 5.938E-05 0.0589 2.016E-04 0.0917 1.111E-04 0.1431 7.090E-05 0.2131 4.995E-05 0.2902 3.975E-05 0.1830 5.163E-05 0.0612 1.840E-04 0.0956 9.880E-05 0.1496 6.194E-05 0.2230 4.340E-05 0.3038 3.435E-05 0.1916 4.481E-05 0.0635 1.676E-04 0.0998 8.775E-05 0.1564 5.403E-05 0.2334 3.770E-05 0.3180 2.969E-05 0.2007 3.884E-05 0.0660 1.524E-04 0.1041 7.781E-05 0.1635 4.708E-05 0.2442 3.273E-05 0.3328 2.567E-05 0.2101 3.362E-05 0.0685 1.385E-04 0.1085 6.889E-05 0.1708 4.097E-05 0.2556 2.842E-05 0.3483 2.221E-05 0.2200 2.907E-05 0.0712 1.256E-04 0.1132 6.090E-05 0.1786 3.562E-05 0.2675 2.467E-05 0.3646 1.923E-05 0.2304 2.511E-05 0.0739 1.138E-04 0.1181 5.375E-05 0.1867 3.094E-05 0.2799 2.142E-05 0.3816 1.667E-05 0.2413 2.167E-05 0.0768 1.029E-04 0.1232 4.738E-05 0.1951 2.685E-05 0.2930 1.860E-05 0.3994 1.446E-05 0.2526 1.869E-05 0.0797 9.295E-05 0.1285 4.170E-05 0.2039 2.330E-05 0.3066 1.615E-05 0.4181 1.256E-05 0.2645 1.612E-05 0.0828 8.384E-05 0.1341 3.665E-05 0.2132 2.020E-05 0.3209 1.404E-05 0.4376 1.093E-05 0.2770 1.390E-05 0.0860 7.551 E-05 0.1398 3.217E-05 0.2228 1.752E-05 0.3358 1.221 E-05 0.4580 9.526E-06 0.2901 1.199E-05 0.0893 6.792E-05 0.1459 2.821E-05 0.2329 1.519E-05 0.3515 1.063E-05 0.4794 8.317E-06 0.3038 1.034E-05 0.0927 6.099E-05 0.1522 2.471E-05 0.2434 1.317E-05 0.3678 9.269E-06 0.5017 7.273E-06 0.3181 8.930E-06 0.0963 5.470E-05 0.1587 2.162E-05 0.2545 1.142E-05 0.3849 8.091E-06 0.5251 6.372E-06 0.3331 7.718E-06 0.1000 4.898E-05 0.1656 1.890E-05 0.2660 9.912E-06 0.4029 7.072E-06 0.5496 5.591E-06 0.3488 6.679E-06 0.1039 4.380E-05 0.1727 1.651E-05 0.2780 8.607E-06 0.4216 6.190E-06 0.5753 4.915E-06 0.3652 5.788E-06 0.1079 3.912E-05 0.1801 1.441E-05 0.2906 7.481E-06 0.4413 5.427E-06 0.6021 4.327E-06 0.3824 5.023E-06 0.1120 3.489E-05 0.1879 1.256E-05 0.3037 6.508E-06 0.4618 4.766E-06 0.6302 3.815E-06 0.4005 4.367E-06 0.1164 3.107E-05 0.1960 1.095E-05 0.3175 5.667E-06 0.4833 4.191E-06 0.6597 3.368E-06 0.4194 3.803E-06 0.1208 2.764E-05 0.2045 9.542E-06 0.3319 4.941E-06 0.5058 3.691E-06 0.6904 2.978E-06 0.4391 3.318E-06 0.1255 2.455E-05 0.2133 8.309E-06 0.3469 4.314E-06 0.5294 3.255E-06 0.7227 2.635E-06 0.4598 2.899E-06 0.1303 2.179E-05 0.2225 7.233E-06 0.3626 3.771E-06 0.5540 2.874E-06 0.7564 2.334E-06 0.4815 2.537E-06 0.1354 1.931E-05 0.2321 6.293E-06 0.3790 3.300E-06 0.5798 2.540E-06 0.7917 2.070E-06 0.5042 2.223E-06 0.1406 1.710E-05 0.2421 5.474E-06 0.3961 2.892E-06 0.6068 2.247E-06 0.8286 1.837E-06 0.5280 1.950E-06 0.1460 1.512E-05 0.2525 4.760E-06 0.4141 2.538E-06 0.6350 1.989E-06 0.8673 1.631E-06 0.5529 1.713E-06 0.1516 1.336E-05 0.2634 4.138E-06 0.4328 2.230E-06 0.6646 1.761E-06 0.9078 1.450E-06 0.5790 1.506E-06 0.1575 1.179E-05 0.2747 3.597E-06 0.4524 1.961 E-06 0.6955 1.561 E-06 0.9501 1.289E-06 0.6063 1.325E-06 0.1635 1.040E-05 0.2866 3.126E-06 0.4729 1.726E-06 0.7279 1.383E-06 0.9945 1.147E-06 0.6349 1.166E-06 0.1698 9.163E-06 0.2989 2.716E-06 0.4943 1.521E-06 0.7618 1.226E-06 1.0409 1.021E-06 0.6648 1.027E-06 0.1764 8.066E-06 0.3118 2.360E-06 0.5166 1.341E-06 0.7973 1.087E-06 1.0895 9.092E-07

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-12 Mean 5k" Fractile leh Fractile 5 dh Fractile 8 4 th Fractile 95Ih Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.6961 9.051E-07 0.1832 7.095E-06 0.3253 2.051E-06 0.5400 1.183E-06 0.8344 9.640E-07 1.1403 8.101E-07 0.7290 7.976E-07 0.1902 6.236E-06 0.3393 1.782E-06 0.5645 1.044E-06 0.8732 8.549E-07 1.1935 7.221E-07 0.7633 7.031E-07 0.1976 5.476E-06 0.3539 1.549E-06 0.5900 9.216E-07 0.9139 7.581E-07 1.2492 6.439E-07 0.7993 6.198E-07 0.2052 4.805E-06 0.3692 1.347E-06 0.6167 8.137E-07 0.9565 6.723E-07 1.3075 5.744E-07 0.8370 5.465E-07 0.2131 4.213E-06 0.3851 1.172E-06 0.6446 7.185E-07 1.0010 5.962E-07 1.3686 5.126E-07 0.8765 4.820E-07 0.2213 3.691E-06 0.4017 1.020E-06 0.6738 6.345E-07 1.0476 5.288E-07 1.4324 4.576E-07 0.9178 4.251E-07 0.2299 3.231E-06 0.4190 8.883E-07 0.7043 5.602E-07 1.0964 4.690E-07 1.4993 4.086E-07 0.9611 3.750E-07 0.2387 2.826E-06 0.4371 7.740E-07 0.7362 4.945E-07 1.1474 4.159E-07 1.5692 3.650E-07 1.0064 3.308E-07 0.2479 2.469E-06 0.4560 6.748E-07 0.7695 4.364E-07 1.2008 3.689E-07 1.6425 3.260E-07 1.0538 2.919E-07 0.2575 2.156E-06 0.4756 5.886E-07 0.8043 3.851E-07 1.2567 3.272E-07 1.7191 2.913E-07 1.1035 2.576E-07 0.2674 1.881E-06 0.4961 5.138E-07 0.8407 3.397E-07 1.3152 2.902E-07 1.7994 2.602E-07 1.1556 2.274E-07 0.2777 1.640E-06 0.5175 4.487E-07 0.8788 2.995E-07 1.3765 2.575E-07 1.8833 2.325E-07 1.2100 2.007E-07 0.2884 1.428E-06 0.5398 3.920E-07 0.9185 2.641E-07 1.4406 2.284E-07 1.9712 2.077E-07 1.2671 1.772E-07 0.2995 1.243E-06 0.5631 3.425E-07 0.9601 2.327E-07 1.5076 2.025E-07 2.0632 1.855E-07 1.3268 1.564E-07 0.3111 1.081 E-06 0.5874 2.994E-07 1.0036 2.050E-07 1.5778 1.796E-07 2.1595 1.656E-07 1.3894 1.381E-07 0.3231 9.388E-07 0.6127 2.618E-07 1.0490 1.805E-07 1.6513 1.593E-07 2.2603 1.478E-07 1.4549 1.219E-07 0.3355 8.149E-07 0.6391 2.288E-07 1.0964 1.589E-07 1.7282 1.412E-07 2.3658 1.319E-07 1.5235 1.076E-07 0.3484 7.068E-07 0.6667 2.OOOE-07 1.1461 1.398E-07 1.8086 1.251E-07 2.4762 1.176E-07 1.5954 9.500E-08 0.3619 6.125E-07 0.6954 1.748E-07 1.1979 1.230E-07 1.8928 1.109E-07 2.5917 1.048E-07 1.6706 8.383E-08 0.3758 5.304E-07 0.7254 1.527E-07 1.2522 1.081E-07 1.9809 9.818E-08 2.7127 9.327E-08 1.7493 7.394E-08 0.3903 4.589E-07 0.7567 1.333E-07 1.3088 9.503E-08 2.0732 8.689E-08 2.8393 8.296E-08 1.8318 6.519E-08 0.4054 3.968E-07 0.7893 1.163E-07 1.3681 8.347E-08 2.1697 7.685E-08 2.9718 7.371E-08 1.9182 5.744E-08 0.5793 1.OOOE-07 0.8269 1.OOOE-07 1.4300 7.327E-08 2.2707 6.792E-08 3.1105 6.541E-08

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-13 Table A-le. 5 Hz Seismic Hazard Curves at Farley.

Mean 5d Fractile 16h Fractile 50dh Fractile 84th Fractile 9 5eh Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0226 1.097E-03 0.0107 1.082E-03 0.0141 1.096E-03 0.0199 1.102E-03 0.0281 1.099E-03 0.0393 1.096E-03 0.0238 1.094E-03 0.0112 1.080E-03 0.0148 1.094E-03 0.0209 1.099E-03 0.0296 1.095E-03 0.0413 1.091 E-03 0.0250 1.089E-03 0.0117 1.077E-03 0.0155 1.090E-03 0.0220 1.095E-03 0.0311 1.090E-03 0.0433 1.084E-03 0.0263 1.083E-03 0.0122 1.073E-03 0.0163 1.085E-03 0.0231 1.089E-03 0.0327 1.082E-03 0.0455 1.075E-03 0.0277 1.075E-03 0.0127 1.068E-03 0.0171 1.078E-03 0.0243 1.081 E-03 0.0343 1.073E-03 0.0478 1.063E-03 0.0291 1.065E-03 0.0132 1.062E-03 0.0179 1.069E-03 0.0255 1.071E-03 0.0361 1.061E-03 0.0502 1.049E-03 0.0306 1.051 E-03 0.0138 1.054E-03 0.0188 1.058E-03 0.0268 1.058E-03 0.0379 1.046E-03 0.0528 1.031 E-03 0.0322 1.035E-03 0.0144 1.044E-03 0.0197 1.043E-03 0.0282 1.042E-03 0.0399 1.027E-03 0.0554 1.009E-03 0.0339 1.014E-03 0.0150 1.032E-03 0.0207 1.026E-03 0.0296 1.023E-03 0.0419 1.004E-03 0.0582 9.840E-04 0.0356 9.898E-04 0.0157 1.018E-03 0.0217 1.005E-03 0.0311 9.988E-04 0.0441 9.771E-04 0.0612 9.545E-04 0.0375 9.611E-04 0.0163 1.001 E-03 0.0228 9.808E-04 0.0327 9.710E-04 0.0463 9.460E-04 0.0642 9.210E-04 0.0394 9.282E-04 0.0170 9.813E-04 0.0239 9.526E-04 0.0344 9.389E-04 0.0487 9.109E-04 0.0675 8.836E-04 0.0415 8.912E-04 0.0178 9.591E-04 0.0251 9.206E-04 0.0361 9.026E-04 0.0512 8.717E-04 0.0709 8.426E-04 0.0436 8.504E-04 0.0185 9.341 E-04 0.0264 8.850E-04 0.0380 8.625E-04 0.0538 8.291 E-04 0.0744 7.986E-04 0.0459 8.063E-04 0.0193 9.064E-04 0.0277 8.462E-04 0.0399 8.190E-04 0.0566 7.834E-04 0.0782 7.520E-04 0.0482 7.596E-04 0.0202 8.760E-04 0.0291 8.044E-04 0.0419 7.726E-04 0.0595 7.354E-04 0.0821 7.035E-04 0.0507 7.11OE-04 0.0210 8.433E-04 0.0305 7.604E-04 0.0441 7.240E-04 0.0625 6.858E-04 0.0863 6.540E-04 0.0534 6.612E-04 0.0219 8.084E-04 0.0320 7.146E-04 0.0463 6.740E-04 0.0657 6.354E-04 0.0906 6.041E-04 0.0561 6.11OE-04 0.0229 7.717E-04 0.0336 6.677E-04 0.0487 6.234E-04 0.0691 5.850E-04 0.0952 5.545E-04 0.0590 5.614E-04 0.0239 7.336E-04 0.0353 6.205E-04 0.0512 5.730E-04 0.0726 5.354E-04 0.1000 5.061E-04 0.0621 5.129E-04 0.0249 6.945E-04 0.0370 5.735E-04 0.0538 5.235E-04 0.0764 4.873E-04 0.1050 4.594E-04 0.0653 4.662E-04 0.0260 6.548E-04 0.0388 5.274E-04 0.0565 4.757E-04 0.0803 4.412E-04 0.1103 4.148E-04 0.0687 4.218E-04 0.0271 6.149E-04 0.0408 4.828E-04 0.0594 4.300E-04 0.0844 3.975E-04 0.1159 3.728E-04 0.0723 3.800E-04 0.0283 5.753E-04 0.0428 4.399E-04 0.0624 3.869E-04 0.0887 3.567E-04 0.1217 3.337E-04 0.0760 3.412E-04 0.0295 5.364E-04 0.0449 3.993E-04 0.0656 3.467E-04 0.0932 3.189E-04 0.1279 2.977E-04 0.0799 3.054E-04 0.0308 4.984E-04 0.0471 3.611E-04 0.0689 3.096E-04 0.0980 2.842E-04 0.1343 2.646E-04 0.0841 2.726E-04 0.0321 4.617E-04 0.0495 3.254E-04 0.0724 2.757E-04 0.1030 2.527E-04 0.1411 2.347E-04 0.0884 2.428E-04 0.0335 4.264E-04 0.0519 2.925E-04 0.0761 2.448E-04 0.1083 2.241E-04 0.1482 2.077E-04 0.0930 2.159E-04 0.0349 3.929E-04 0.0545 2.622E-04 0.0800 2.170E-04 0.1139 1.985E-04 0.1557 1.835E-04 0.0978 1.917E-04 0.0364 3.611E-04 0.0572 2.345E-04 0.0841 1.921E-04 0.1197 1.756E-04 0.1635 1.619E-04 0.1029 1.700E-04 0.0380 3.312E-04 0.0600 2.094E-04 0.0884 1.698E-04 0.1258 1.552E-04 0.1718 1.427E-04 0.1082 1.506E-04 0.0396 3.032E-04 0.0630 1.866E-04 0.0929 1.499E-04 0.1323 1.371 E-04 0.1804 1.257E-04 0.1139 1.333E-04 0.0413 2.771E-04 0.0661 1.660E-04 0.0976 1.323E-04 0.1390 1.211E-04 0.1895 1.107E-04 0.1198 1.179E-04 0.0431 2.528E-04 0.0694 1.475E-04 0.1026 1.168E-04 0.1462 1.070E-04 0.1991 9.753E-05 0.1260 1.042E-04 0.0449 2.303E-04 0.0729 1.309E-04 0.1078 1.030E-04 0.1536 9.453E-05 0.2091 8.589E-05 0.1325 9.201E-05 0.0469 2.096E-04 0.0765 1.160E-04 0.1133 9.086E-05 0.1615 8.355E-05 0.2196 7.565E-05 0.1394 8.123E-05 0.0489 1.904E-04 0.0803 1.028E-04 0.1191 8.016E-05 0.1698 7.387E-05 0.2307 6.664E-05 0.1466 7.168E-05 0.0510 1.728E-04 0.0843 9.090E-05 0.1251 7.072E-05 0.1785 6.535E-05 0.2423 5.871E-05

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-14 Mean 5 th Fractile 16th Fractile 5 dh Fractile 8 4th Fractile 9eth Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.1542 6.322E-05 0.0532 1.567E-04 0.0884 8.033E-05 0.1315 6.240E-05 0.1876 5.784E-05 0.2546 5.174E-05 0.1622 5.573E-05 0.0555 1.418E-04 0.0928 7.093E-05 0.1382 5.507E-05 0.1972 5.123E-05 0.2674 4.560E-05 0.1706 4.911E-05 0.0579 1.283E-04 0.0974 6.257E-05 0.1452 4.861E-05 0.2073 4.539E-05 0.2809 4.020E-05 0.1794 4.326E-05 0.0604 1.159E-04 0.1022 5.515E-05 0.1526 4.292E-05 0.2179 4.023E-05 0.2950 3.544E-05 0.1887 3.810E-05 0.0630 1.046E-04 0.1073 4.857E-05 0.1604 3.791E-05 0.2291 3.567E-05 0.3099 3.124E-05 0.1985 3.354E-05 0.0657 9.427E-05 0.1126 4.274E-05 0.1686 3.348E-05 0.2408 3.163E-05 0.3255 2.754E-05 0.2087 2.952E-05 0.0685 8.488E-05 0.1182 3.759E-05 0.1772 2.958E-05 0.2532 2.805E-05 0.3419 2.427E-05 0.2196 2.597E-05 0.0715 7.634E-05 0.1241 3.303E-05 0.1862 2.614E-05 0.2661 2.488E-05 0.3592 2.140E-05 0.2309 2.285E-05 0.0746 6.859E-05 0.1302 2.902E-05 0.1957 2.310E-05 0.2798 2.206E-05 0.3773 1.886E-05 0.2429 2.009E-05 0.0778 6.157E-05 0.1367 2.548E-05 0.2057 2.042E-05 0.2941 1.956E-05 0.3963 1.661E-05 0.2555 1.767E-05 0.0811 5.521E-05 0.1435 2.237E-05 0.2161 1.805E-05 0.3092 1.734E-05 0.4163 1.464E-05 0.2687 1.553E-05 0.0846 4.945E-05 0.1506 1.963E-05 0.2272 1.596E-05 0.3250 1.537E-05 0.4372 1.289E-05 0.2826 1.366E-05 0.0883 4.426E-05 0.1581 1.722E-05 0.2387 1.411E-05 0.3416 1.361 E-05 0.4593 1.136E-05 0.2973 1.201E-05 0.0921 3.958E-05 0.1659 1.512E-05 0.2509 1.248E-05 0.3591 1.205E-05 0.4824 1.OOOE-05 0.3127 1.055E-05 0.0960 3.536E-05 0.1741 1.327E-05 0.2637 1.104E-05 0.3775 1.067E-05 0.5068 8.806E-06 0.3289 9.276E-06 0.1002 3.156E-05 0.1828 1.165E-05 0.2771 9.762E-06 0.3969 9.441E-06 0.5323 7.752E-06 0.3459 8.153E-06 0.1045 2.815E-05 0.1918 1.023E-05 0.2912 8.634E-06 0.4172 8.350E-06 0.5591 6.824E-06 0.3639 7.167E-06 0.1090 2.509E-05 0.2013 8.985E-06 0.3061 7.638E-06 0.4385 7.382E-06 0.5873 6.005E-06 0.3827 6.299E-06 0.1137 2.234E-05 0.2113 7.896E-06 0.3217 6.756E-06 0.4610 6.523E-06 0.6169 5.284E-06 0.4025 5.537E-06 0.1186 1.988E-05 0.2218 6.942E-06 0.3380 5.976E-06 0.4846 5.761E-06 0.6480 4.648E-06 0.4234 4.867E-06 0.1237 1.767E-05 0.2328 6.106E-06 0.3553 5.286E-06 0.5094 5.086E-06 0.6807 4.088E-06 0.4453 4.278E-06 0.1290 1.570E-05 0.2443 5.372E-06 0.3734 4.675E-06 0.5355 4.488E-06 0.7150 3.595E-06 0.4684 3.760E-06 0.1346 1.394E-05 0.2564 4.728E-06 0.3924 4.135E-06 0.5629 3.958E-06 0.7510 3.161E-06 0.4927 3.304E-06 0.1404 1.236E-05 0.2692 4.161E-06 0.4124 3.656E-06 0.5918 3.488E-06 0.7889 2.778E-06 0.5182 2.903E-06 0.1464 1.095E-05 0.2825 3.663E-06 0.4334 3.232E-06 0.6221 3.072E-06 0.8286 2.441E-06 0.5451 2.550E-06 0.1527 9.697E-06 0.2965 3.225E-06 0.4555 2.856E-06 0.6539 2.705E-06 0.8704 2.145E-06 0.5733 2.239E-06 0.1593 8.577E-06 0.3112 2.839E-06 0.4787 2.522E-06 0.6874 2.379E-06 0.9143 1.884E-06 0.6030 1.965E-06 0.1662 7.580E-06 0.3266 2.498E-06 0.5031 2.227E-06 0.7226 2.091E-06 0.9604 1.654E-06 0.6342 1.723E-06 0.1733 6.692E-06 0.3428 2.198E-06 0.5287 1.965E-06 0.7596 1.837E-06 1.0088 1.453E-06 0.6671 1.51OE-06 0.1808 5.902E-06 0.3598 1.933E-06 0.5556 1.732E-06 0.7985 1.612E-06 1.0596 1.276E-06 0.7017 1.322E-06 0.1886 5.200E-06 0.3777 1.699E-06 0.5839 1.526E-06 0.8394 1.414E-06 1.1130 1.120E-06 0.7380 1.157E-06 0.1967 4.577E-06 0.3964 1.493E-06 0.6137 1.343E-06 0.8824 1.239E-06 1.1691 9.835E-07 0.7763 1.012E-06 0.2052 4.025E-06 0.4161 1.311E-06 0.6450 1.180E-06 0.9276 1.085E-06 1.2281 8.635E-07 0.8165 8.835E-07 0.2140 3.535E-06 0.4367 1.150E-06 0.6778 1.036E-06 0.9751 9.489E-07 1.2900 7.582E-07 0.8588 7.709E-07 0.2233 3.101E-06 0.4583 1.008E-06 0.7123 9.087E-07 1.0250 8.296E-07 1.3550 6.658E-07 0.9033 6.721E-07 0.2329 2.718E-06 0.4811 8.829E-07 0.7486 7.958E-07 1.0775 7.248E-07 1.4233 5.847E-07 0.9501 5.854E-07 0.2429 2.379E-06 0.5049 7.726E-07 0.7868 6.961E-07 1.1327 6.329E-07 1.4951 5.135E-07 0.9993 5.094E-07 0.2534 2.081E-06 0.5300 6.754E-07 0.8269 6.079E-07 1.1907 5.522E-07 1.5704 4.510E-07 1.0511 4.429E-07 0.2643 1.817E-06 0.5562 5.898E-07 0.8690 5.302E-07 1.2517 4.816E-07 1.6496 3.961E-07

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-15 Mean 5rh Fractile 16 h Fractile 5 01h Fractile 8 4th Fractile 95th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 1.1055 3.848E-07 0.2757 1.585E-06 0.5838 5.144E-07 0.9133 4.618E-07 1.3158 4.198E-07 1.7327 3.478E-07 1.1628 3.341E-07 0.2875 1.381E-06 0.6128 4.481E-07 0.9598 4.016E-07 1.3832 3.657E-07 1.8201 3.055E-07 1.2231 2.898E-07 0.2999 1.201 E-06 0.6432 3.899E-07 1.0087 3.488E-07 1.4540 3.184E-07 1.9118 2.682E-07 1.2864 2.513E-07 0.3129 1.044E-06 0.6750 3.386E-07 1.0601 3.026E-07 1.5285 2.771E-07 2.0082 2.354E-07 1.3531 2.178E-07 0.3263 9.056E-07 0.7085 2.940E-07 1.1141 2.621E-07 1.6068 2.410E-07 2.1094 2.066E-07 1.4232 1.886E-07 0.3404 7.845E-07 0.7436 2.547E-07 1.1709 2.268E-07 1.6891 2.095E-07 2.2157 1.812E-07 1.4969 1.633E-07 0.3551 6.786E-07 0.7805 2.203E-07 1.2305 1.960E-07 1.7756 1.821 E-07 2.3274 1.588E-07 1.5745 1.413E-07 0.3703 5.861E-07 0.8192 1.903E-07 1.2932 1.692E-07 1.8665 1.581E-07 2.4447 1.391E-07 1.6561 1.222E-07 0.3863 5.054E-07 0.8598 1.641E-07 1.3591 1.459E-07 1.9621 1.372E-07 2.5680 1.217E-07 1.7419 1.056E-07 0.4029 4.350E-07 0.9025 1.413E-07 1.4283 1.257E-07 2.0626 1.190E-07 2.6974 1.065E-07 1.8321 9.120E-08 0.4203 3.738E-07 0.9472 1.214E-07 1.5011 1.082E-07 2.1682 1.031E-07 2.8334 9.298E-08 1.9270 7.872E-08 0.4384 3.207E-07 0.9942 1.041 E-07 1.5776 9.307E-08 2.2792 8.923E-08 2.9762 8.111 E-08 2.0269 6.790E-08 0.4573 2.746E-07 1.0435 8.918E-08 1.6580 7.995E-08 2.3959 7.715E-08 3.1262 7.066E-08 2.1319 5.851E-08 0.4770 2.347E-07 1.0952 7.624E-08 1.7424 6.861E-08 2.5186 6.664E-08 3.2838 6.146E-08 2.2424 5.036E-08 0.4975 2.002E-07 1.1495 6.505E-08 1.8312 5.882E-08 2.6476 5.748E-08 3.4493 5.337E-08 2.3585 4.330E-08 0.5190 1.704E-07 1.2065 5.540E-08 1.9245 5.036E-08 2.7832 4.950E-08 3.6232 4.626E-08 2.4807 3.717E-08 0.5413 1.448E-07 1.2664 4.708E-08 2.0225 4.306E-08 2.9257 4.257E-08 3.8058 4.002E-08 2.6093 3.187E-08 0.5647 1.228E-07 1.3292 3.994E-08 2.1256 3.677E-08 3.0756 3.654E-08 3.9976 3.454E-08 2.7445 2.727E-08 0.5890 1.039E-07 1.3951 3.381E-08 2.2339 3.135E-08 3.2331 3.130E-08 4.1991 2.975E-08 2.8867 2.329E-08 0.6144 8.770E-08 1.4642 2.856E-08 2.3477 2.669E-08 3.3987 2.676E-08 4.4108 2.556E-08 3.0362 1.985E-08 0.6408 7.386E-08 1.5368 2.408E-08 2.4673 2.267E-08 3.5727 2.283E-08 4.6331 2.191E-08 3.1935 1.687E-08 0.6684 6.206E-08 1.6130 2.025E-08 2.5930 1.923E-08 3.7557 1.942E-08 4.8667 1.872E-08 3.3590 1.431 E-08 0.6972 5.201E-08 1.6930 1.699E-08 2.7251 1.627E-08 3.9480 1.649E-08 5.1120 1.596E-08

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-16 Table A-if. 10 Hz Seismic Hazard Curves at Farle__

Mean 5m Fractile 16h Fractile 5dh Fractile 84' Fractile 95th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0227 1.OOOE-03 0.0096 1.OOOE-03 0.0130 1.OOOE-03 0.0192 1.000E-03 0.0277 1.000E-03 0.0411 1.OOOE-03 0.0269 8.927E-04 0.0113 9.108E-04 0.0151 9.155E-04 0.0224 9.063E-04 0.0339 8.602E-04 0.0529 7.866E-04 0.0284 8.570E-04 0.0119 8.839E-04 0.0159 8.828E-04 0.0237 8.714E-04 0.0357 8.222E-04 0.0557 7.453E-04 0.0300 8.185E-04 0.0124 8.550E-04 0.0168 8.473E-04 0.0250 8.334E-04 0.0377 7.817E-04 0.0586 7.024E-04 0.0317 7.774E-04 0.0130 8.242E-04 0.0177 8.093E-04 0.0264 7.929E-04 0.0398 7.392E-04 0.0617 6.584E-04 0.0334 7.343E-04 0.0136 7.917E-04 0.0187 7.692E-04 0.0278 7.501E-04 0.0419 6.951E-04 0.0650 6.137E-04 0.0353 6.898E-04 0.0143 7.577E-04 0.0197 7.273E-04 0.0294 7.056E-04 0.0442 6.500E-04 0.0684 5.691E-04 0.0373 6.443E-04 0.0149 7.226E-04 0.0208 6.843E-04 0.0310 6.599E-04 0.0467 6.045E-04 0.0720 5.248E-04 0.0394 5.985E-04 0.0157 6.866E-04 0.0220 6.405E-04 0.0327 6.137E-04 0.0492 5.591E-04 0.0758 4.815E-04 0.0415 5.529E-04 0.0164 6.501E-04 0.0232 5.964E-04 0.0346 5.675E-04 0.0519 5.144E-04 0.0798 4.396E-04 0.0439 5.081E-04 0.0172 6.133E-04 0.0245 5.527E-04 0.0365 5.220E-04 0.0548 4.709E-04 0.0841 3.993E-04 0.0463 4.646E-04 0.0180 5.766E-04 0.0258 5.097E-04 0.0385 4.775E-04 0.0578 4.289E-04 0.0885 3.611 E-04 0.0489 4.228E-04 0.0188 5.403E-04 0.0272 4.679E-04 0.0407 4.347E-04 0.0610 3.888E-04 0.0932 3.251E-04 0.0516 3.830E-04 0.0197 5.046E-04 0.0287 4.277E-04 0.0429 3.938E-04 0.0643 3.511E-04 0.0981 2.916E-04 0.0545 3.456E-04 0.0206 4.699E-04 0.0303 3.892E-04 0.0453 3.551E-04 0.0679 3.157E-04 0.1033 2.605E-04 0.0575 3.106E-04 0.0216 4.362E-04 0.0320 3.528E-04 0.0478 3.190E-04 0.0716 2.829E-04 0.1087 2.320E-04 0.0607 2.782E-04 0.0226 4.038E-04 0.0337 3.187E-04 0.0505 2.855E-04 0.0755 2.527E-04 0.1145 2.061E-04 0.0641 2.485E-04 0.0237 3.728E-04 0.0356 2.868E-04 0.0533 2.547E-04 0.0797 2.251E-04 0.1205 1.826E-04 0.0677 2.213E-04 0.0248 3.433E-04 0.0376 2.573E-04 0.0563 2.266E-04 0.0841 2.001E-04 0.1269 1.615E-04 0.0714 1.967E-04 0.0260 3.154E-04 0.0396 2.302E-04 0.0594 2.010E-04 0.0887 1.775E-04 0.1336 1.425E-04 0.0754 1.744E-04 0.0272 2.891 E-04 0.0418 2.053E-04 0.0627 1.780E-04 0.0936 1.572E-04 0.1406 1.257E-04 0.0796 1.544E-04 0.0285 2.645E-04 0.0441 1.827E-04 0.0662 1.573E-04 0.0987 1.391E-04 0.1481 1.107E-04 0.0841 1.365E-04 0.0298 2.415E-04 0.0465 1.623E-04 0.0699 1.389E-04 0.1041 1.229E-04 0.1559 9.741E-05 0.0887 1.206E-04 0.0313 2.201E-04 0.0491 1.438E-04 0.0738 1.225E-04 0.1098 1.086E-04 0.1641 8.570E-05 0.0937 1.064E-04 0.0327 2.002E-04 0.0518 1.272E-04 0.0779 1.079E-04 0.1159 9.589E-05 0.1728 7.540E-05 0.0989 9.379E-05 0.0343 1.818E-04 0.0547 1.123E-04 0.0822 9.506E-05 0.1222 8.468E-05 0.1819 6.633E-05 0.1044 8.264E-05 0.0359 1.648E-04 0.0577 9.905E-05 0.0868 8.369E-05 0.1289 7.478E-05 0.1915 5.836E-05 0.1102 7.278E-05 0.0376 1.492E-04 0.0608 8.722E-05 0.0917 7.367E-05 0.1360 6.606E-05 0.2016 5.136E-05 0.1164 6.407E-05 0.0394 1.349E-04 0.0642 7.671E-05 0.0968 6.485E-05 0.1435 5.837E-05 0.2123 4.521E-05 0.1229 5.639E-05 0.0412 1.217E-04 0.0677 6.740E-05 0.1022 5.710E-05 0.1514 5.160E-05 0.2235 3.982E-05 0.1297 4.962E-05 0.0432 1.097E-04 0.0714 5.916E-05 0.1078 5.028E-05 0.1597 4.564E-05 0.2353 3.507E-05 0.1369 4.365E-05 0.0452 9.872E-05 0.0754 5.189E-05 0.1138 4.428E-05 0.1685 4.037E-05 0.2477 3.090E-05 0.1446 3.840E-05 0.0473 8.872E-05 0.0795 4.547E-05 0.1202 3.901E-05 0.1777 3.573E-05 0.2608 2.724E-05 0.1526 3.377E-05 0.0496 7.963E-05 0.0839 3.983E-05 0.1269 3.438E-05 0.1875 3.163E-05 0.2746 2.401E-05 0.1611 2.970E-05 0.0519 7.137E-05 0.0885 3.486E-05 0.1339 3.030E-05 0.1978 2.801E-05 0.2891 2.116E-05 0.1701 2.611 E-05 0.0543 6.389E-05 0.0934 3.050E-05 0.1414 2.672E-05 0.2087 2.480E-05 0.3044 1.865E-05 0.1796 2.296E-05 0.0569 5.713E-05 0.0985 2.668E-05 0.1493 2.356E-05 0.2201 2.196E-05 0.3204 1.644E-05 0.1896 2.018E-05 0.0596 5.102E-05 0.1040 2.333E-05 0.1576 2.078E-05 0.2322 1.944E-05 0.3374 1.449E-05

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-17 0.2001 1.774E-05 0.0624 4.551E-05 0.1097 2.040E-05 0.1664 1.833E-05 0.2450 1.721E-05 0.3552 1.276E-05 0.2113 1.559E-05 0.0654 4.055E-05 0.1157 1.783E-05 0.1756 1.618E-05 0.2584 1.523E-05 0.3739 1.124E-05 0.2230 1.369E-05 0.0684 3.609E-05 0.1221 1.559E-05 0.1854 1.427E-05 0.2726 1.347E-05 0.3937 9.895E-06 0.2355 1.202E-05 0.0717 3.209E-05 0.1288 1.363E-05 0.1957 1.259E-05 0.2876 1.190E-05 0.4145 8.707E-06 0.2486 1.056E-05 0.0751 2.850E-05 0.1359 1.192E-05 0.2066 1.11OE-05 0.3034 1.052E-05 0.4364 7.657E-06 0.2624 9.264E-06 0.0786 2.529E-05 0.1434 1.042E-05 0.2181 9.790E-06 0.3201 9.284E-06 0.4594 6.730E-06 0.2771 8.127E-06 0.0823 2.242E-05 0.1513 9.118E-06 0.2303 8.631E-06 0.3376 8.190E-06 0.4837 5.911E-06 0.2925 7.127E-06 0.0862 1.985E-05 0.1596 7.980E-06 0.2431 7.606E-06 0.3562 7.219E-06 0.5092 5.189E-06 0.3088 6.247E-06 0.0903 1.756E-05 0.1684 6.986E-06 0.2566 6.700E-06 0.3758 6.357E-06 0.5361 4.551E-06 0.3260 5.473E-06 0.0945 1.552E-05 0.1777 6.117E-06 0.2709 5.900E-06 0.3964 5.593E-06 0.5644 3.989E-06 0.3442 4.792E-06 0.0990 1.370E-05 0.1874 5.358E-06 0.2860 5.192E-06 0.4182 4.916E-06 0.5942 3.494E-06 0.3633 4.194E-06 0.1036 1.209E-05 0.1977 4.695E-06 0.3019 4.567E-06 0.4411 4.317E-06 0.6256 3.058E-06 0.3836 3.669E-06 0.1085 1.065E-05 0.2086 4.114E-06 0.3187 4.014E-06 0.4654 3.787E-06 0.6587 2.675E-06 0.4049 3.207E-06 0.1137 9.377E-06 0.2201 3.605E-06 0.3365 3.526E-06 0.4909 3.319E-06 0.6935 2.337E-06 0.4275 2.801E-06 0.1190 8.246E-06 0.2322 3.159E-06 0.3552 3.095E-06 0.5179 2.906E-06 0.7301 2.041E-06 0.4513 2.446E-06 0.1246 7.244E-06 0.2450 2.768E-06 0.3750 2.715E-06 0.5464 2.541E-06 0.7686 1.780E-06 0.4765 2.133E-06 0.1305 6.357E-06 0.2585 2.425E-06 0.3959 2.379E-06 0.5764 2.220E-06 0.8092 1.552E-06 0.5030 1.859E-06 0.1367 5.572E-06 0.2727 2.124E-06 0.4179 2.083E-06 0.6080 1.937E-06 0.8520 1.352E-06 0.5310 1.619E-06 0.1431 4.879E-06 0.2877 1.859E-06 0.4412 1.823E-06 0.6414 1.688E-06 0.8970 1.177E-06 0.5606 1.409E-06 0.1499 4.268E-06 0.3036 1.627E-06 0.4658 1.593E-06 0.6767 1.470E-06 0.9444 1.024E-06 0.5918 1.225E-06 0.1569 3.728E-06 0.3203 1.422E-06 0.4917 1.390E-06 0.7139 1.278E-06 0.9942 8.896E-07 0.6248 1.064E-06 0.1643 3.253E-06 0.3379 1.242E-06 0.5191 1.212E-06 0.7531 1.11OE-06 1.0467 7.726E-07 0.6596 9.225E-07 0.1721 2.835E-06 0.3565 1.084E-06 0.5480 1.056E-06 0.7944 9.631E-07 1.1020 6.705E-07 0.6964 7.993E-07 0.1802 2.468E-06 0.3761 9.454E-07 0.5785 9.181E-07 0.8381 8.345E-07 1.1602 5.815E-07 0.7352 6.916E-07 0.1887 2.146E-06 0.3968 8.234E-07 0.6107 7.973E-07 0.8841 7.223E-07 1.2215 5.040E-07 0.7761 5.977E-07 0.1976 1.864E-06 0.4187 7.163E-07 0.6447 6.914E-07 0.9327 6.244E-07 1.2860 4.365E-07 0.8193 5.158E-07 0.2070 1.616E-06 0.4417 6.223E-07 0.6806 5.986E-07 0.9839 5.391E-07 1.3539 3.778E-07 0.8650 4.445E-07 0.2167 1.400E-06 0.4661 5.399E-07 0.7185 5.175E-07 1.0380 4.649E-07 1.4254 3.267E-07 0.9132 3.825E-07 0.2270 1.211E-06 0.4917 4.677E-07 0.7585 4.465E-07 1.0950 4.004E-07 1.5007 2.824E-07 0.9641 3.287E-07 0.2377 1.046E-06 0.5188 4.045E-07 0.8008 3.846E-07 1.1551 3.444E-07 1.5800 2.439E-07 1.0178 2.820E-07 0.2489 9.023E-07 0.5473 3.493E-07 0.8454 3.307E-07 1.2186 2.958E-07 1.6634 2.106E-07 1.0745 2.416E-07 0.2606 7.772E-07 0.5774 3.011E-07 0.8925 2.838E-07 1.2855 2.538E-07 1.7513 1.816E-07 1.1343 2.066E-07 0.2729 6.685E-07 0.6092 2.591E-07 0.9421 2.431E-07 1.3562 2.175E-07 1.8438 1.565E-07 1.1975 1.764E-07 0.2858 5.741E-07 0.6428 2.225E-07 0.9946 2.078E-07 1.4307 1.861E-07 1.9412 1.348E-07 1.2642 1.504E-07 0.2993 4.923E-07 0.6781 1.908E-07 1.0500 1.772E-07 1.5093 1.591E-07 2.0437 1.160E-07 1.3347 1.280E-07 0.3134 4.214E-07 0.7155 1.632E-07 1.1085 1.509E-07 1.5922 1.358E-07 2.1516 9.971E-08 1.4090 1.088E-07 0.3282 3.602E-07 0.7549 1.393E-07 1.1702 1.282E-07 1.6796 1.157E-07 2.2653 8.563E-08 1.4875 9.225E-08 0.3437 3.073E-07 0.7964 1.186E-07 1.2353 1.087E-07 1.7719 9.847E-08 2.3849 7.345E-08 1.5704 7.811E-08 0.3599 2.618E-07 0.8402 1.008E-07 1.3041 9.192E-08 1.8692 8.368E-08 2.5109 6.293E-08 1.6579 6.603E-08 0.3769 2.226E-07 0.8865 8.549E-08 1.3767 7.759E-08 1.9719 7.101E-08 2.6435 5.385E-08 1.7502 5.571E-08 0.3947 1.889E-07 0.9353 7.230E-08 1.4534 6.535E-08 2.0802 6.015E-08 2.7831 4.601E-08 1.8477 4.693E-08 0.4133 1.600E-07 0.9868 6.100E-08 1.5343 5.492E-08 2.1945 5.087E-08 2.9301 3.925E-08

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-18 1.9507 3.945E-08 0.4328 1.352E-07 1.0411 5.133E-08 1.6198 4.605E-08 2.3151 4.295E-08 3.0849 3.343E-08 2.0593 3.310E-08 0.4532 1.141E-07 1.0984 4.308E-08 1.7100 3.853E-08 2.4422 3.619E-08 3.2478 2.843E-08 2.1741 2.772E-08 0.4746 9.606E-08 1.1588 3.606E-08 1.8052 3.216E-08 2.5764 3.044E-08 3.4193 2.412E-08 2.2952 2.316E-08 0.4970 8.070E-08 1.2226 3.010E-08 1.9057 2.678E-08 2.7179 2.555E-08 3.5999 2.043E-08 2.4230 1.932E-08 0.5204 6.765E-08 1.2899 2.505E-08 2.0118 2.225E-08 2.8672 2.139E-08 3.7900 1.726E-08 2.5580 1.607E-08 0.5450 5.659E-08 1.3609 2.078E-08 2.1238 1.844E-08 3.0248 1.788E-08 3.9902 1.455E-08 2.7005 1.334E-08 0.5707 4.722E-08 1.4358 1.719E-08 2.2421 1.524E-08 3.1909 1.490E-08 4.2009 1.224E-08 2.8510 1.104E-08 0.5976 3.931E-08 1.5149 1.418E-08 2.3670 1.257E-08 3.3662 1.239E-08 4.4228 1.027E-08 3.0098 9.119E-09 0.6258 3.265E-08 1.5982 1.165E-08 2.4988 1.033E-08 3.5511 1.027E-08 4.6564 8.588E-09 3.1775 7.510E-09 0.6554 2.705E-08 1.6862 9.547E-09 2.6379 8.474E-09 3.7462 8.493E-09 4.9023 7.163E-09 3.3545 6.167E-09 0.6863 2.235E-08 1.7790 7.795E-09 2.7848 6.929E-09 3.9520 7.002E-09 5.1613 5.958E-09 3.5414 5.049E-09 0.7187 1.841 E-08 1.8770 6.342E-09 2.9399 5.649E-09 4.1691 5.754E-09 5.4339 4.939E-09 3.7387 4.121E-09 0.7526 1.513E-08 1.9803 5.142E-09 3.1036 4.591E-09 4.3981 4.714E-09 5.7208 4.082E-09 3.9470 3.352E-09 0.7881 1.240E-08 2.0893 4.154E-09 3.2764 3.720E-09 4.6397 3.849E-09 6.0230 3.362E-09 4.1669 2.717E-09 0.8253 1.013E-08 2.2043 3.343E-09 3.4588 3.004E-09 4.8946 3.131E-09 6.3411 2.760E-09 4.3990 2.195E-09 0.8642 8.251E-09 2.3256 2.681E-09 3.6514 2.417E-09 5.1635 2.538E-09 6.6760 2.258E-09 4.6441 1.767E-09 0.9050 6.699E-09 2.4536 2.141E-09 3.8547 1.938E-09 5.4471 2.050E-09 7.0286 1.840E-09 4.9028 1.417E-09 0.9477 5.422E-09 2.5886 1.704E-09 4.0694 1.549E-09 5.7464 1.649E-09 7.3998 1.494E-09 5.1759 1.131 E-09 0.9924 4.373E-09 2.7311 1.350E-09 4.2960 1.233E-09 6.0620 1.321 E-09 7.7906 1.208E-09 5.4643 8.998E-10 1.0393 3.516E-09 2.8815 1.065E-09 4.5352 9.772E-10 6.3950 1.054E-09 8.2021 9.733E-10

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-19 Table A-lg 25 Hz Seismic Hazard Curves at Farle__

Mean 5 m Fractile l6t Fractile 50dh Fractile 84th Fractile 9 5 th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.0186 1.000E-03 0.0061 1.OOOE-03 0.0093 1.000E-03 0.0149 1.OOOE-03 0.0222 1.OOOE-03 0.0378 1.OOOE-03 0.0243 7.223E-04 0.0079 7.940E-04 0.0120 7.831E-04 0.0191 7.600E-04 0.0301 6.664E-04 0.0562 4.508E-04 0.0258 6.678E-04 0.0083 7.544E-04 0.0127 7.346E-04 0.0203 7.067E-04 0.0319 6.120E-04 0.0593 4.015E-04 0.0274 6.127E-04 0.0088 7.137E-04 0.0135 6.846E-04 0.0215 6.519E-04 0.0338 5.580E-04 0.0626 3.553E-04 0.0290 5.578E-04 0.0092 6.723E-04 0.0143 6.341E-04 0.0228 5.967E-04 0.0358 5.051E-04 0.0661 3.124E-04 0.0307 5.041 E-04 0.0097 6.309E-04 0.0152 5.839E-04 0.0242 5.419E-04 0.0379 4.542E-04 0.0698 2.733E-04 0.0326 4.526E-04 0.0103 5.898E-04 0.0161 5.346E-04 0.0256 4.886E-04 0.0401 4.060E-04 0.0737 2.380E-04 0.0346 4.038E-04 0.0108 5.496E-04 0.0171 4.870E-04 0.0272 4.375E-04 0.0425 3.610E-04 0.0778 2.065E-04 0.0366 3.584E-04 0.0114 5.105E-04 0.0181 4.415E-04 0.0289 3.894E-04 0.0451 3,194E-04 0.0821 1.786E-04 0.0388 3.165E-04 0.0120 4.730E-04 0.0192 3.984E-04 0.0306 3.446E-04 0.0478 2.814E-04 0.0867 1.541E-04 0.0412 2.784E-04 0.0126 4.373E-04 0.0204 3.580E-04 0.0325 3.034E-04 0.0506 2.471E-04 0.0915 1.327E-04 0.0436 2.440E-04 0.0133 4.034E-04 0.0216 3.203E-04 0.0344 2.661E-04 0.0536 2.164E-04 0.0966 1.142E-04 0.0463 2.132E-04 0.0140 3.715E-04 0.0229 2.856E-04 0.0365 2.325E-04 0.0568 1.890E-04 0.1019 9.828E-05 0.0490 1.858E-04 0.0147 3.415E-04 0.0243 2.537E-04 0.0387 2.025E-04 0.0602 1.648E-04 0.1076 8.457E-05 0.0520 1.617E-04 0.0155 3.135E-04 0.0258 2.245E-04 0.0411 1.761E-04 0.0638 1.435E-04 0.1136 7.282E-05 0.0551 1.404E-04 0.0163 2.873E-04 0.0273 1.980E-04 0.0436 1.528E-04 0.0676 1.249E-04 0.1199 6.275E-05 0.0584 1.218E-04 0.0172 2.630E-04 0.0290 1.741E-04 0.0462 1.325E-04 0.0716 1.086E-04 0.1266 5.413E-05 0.0619 1.056E-04 0.0181 2.403E-04 0.0307 1.526E-04 0.0490 1.148E-04 0.0758 9.440E-05 0.1336 4.675E-05 0.0657 9.140E-05 0.0191 2.192E-04 0.0326 1.334E-04 0.0520 9.943E-05 0.0803 8.206E-05 0.1411 4.043E-05 0.0696 7.908E-05 0.0201 1.996E-04 0.0346 1.163E-04 0.0552 8.613E-05 0.0851 7.134E-05 0.1489 3.499E-05 0.0738 6.839E-05 0.0211 1.814E-04 0.0367 1.012E-04 0.0585 7.463E-05 0.0902 6.204E-05 0.1572 3.032E-05 0.0782 5.912E-05 0.0223 1.645E-04 0.0389 8.778E-05 0.0621 6.469E-05 0.0956 5.398E-05 0.1660 2.629E-05 0.0829 5.109E-05 0.0234 1.488E-04 0.0413 7.603E-05 0.0658 5.610E-05 0.1012 4.699E-05 0.1752 2.281E-05 0.0879 4.414E-05 0.0247 1.342E-04 0.0438 6.573E-05 0.0698 4.867E-05 0.1073 4.092E-05 0.1849 1.980E-05 0.0932 3.813E-05 0.0260 1.208E-04 0.0464 5.675E-05 0.0741 4.225E-05 0.1137 3.566E-05 0.1952 1.718E-05 0.0988 3.294E-05 0.0274 1.084E-04 0.0492 4.892E-05 0.0786 3.670E-05 0.1204 3.108E-05 0.2061 1.491E-05 0.1047 2.846E-05 0.0288 9.695E-05 0.0522 4.213E-05 0.0833 3.189E-05 0.1276 2.709E-05 0.2176 1.294E-05 0.1110 2.458E-05 0.0304 8.647E-05 0.0554 3.624E-05 0.0884 2.773E-05 0.1352 2.362E-05 0.2297 1.122E-05 0.1177 2.124E-05 0.0320 7.689E-05 0.0588 3.115E-05 0.0938 2.411E-05 0.1432 2.059E-05 0.2424 9.723E-06 0.1247 1.834E-05 0.0337 6.817E-05 0.0623 2.675E-05 0.0995 2.097E-05 0.1517 1.794E-05 0.2559 8.419E-06 0.1322 1.584E-05 0.0355 6.027E-05 0.0661 2.296E-05 0.1055 1.825E-05 0.1608 1.563E-05 0.2702 7.283E-06 0.1402 1.368E-05 0.0373 5.313E-05 0.0701 1.970E-05 0.1119 1.587E-05 0.1703 1.360E-05 0.2852 6.294E-06 0.1486 1.181E-05 0.0393 4.671E-05 0.0744 1.690E-05 0.1187 1.381 E-05 0.1805 1.183E-05 0.3011 5.433E-06 0.1575 1.020E-05 0.0414 4.097E-05 0.0789 1.449E-05 0.1259 1.201E-05 0.1912 1.028E-05 0.3178 4.685E-06 0.1670 8.798E-06 0.0436 3.584E-05 0.0837 1.243E-05 0.1335 1.044E-05 0.2026 8.924E-06 0.3355 4.035E-06 0.1770 7.587E-06 0.0459 3.128E-05 0.0887 1.067E-05 0.1416 9.077E-06 0.2147 7.736E-06 0.3542 3.472E-06 0.1877 6.539E-06 0.0484 2.724E-05 0.0941 9.159E-06 0.1502 7.885E-06 0.2274 6.697E-06 0.3739 2.984E-06 0.1990 5.632E-06 0.0509 2.367E-05 0.0998 7.868E-06 0.1593 6.846E-06 0.2410 5.788E-06 0.3947 2.561E-06

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-20 Mean eh Fractile 16 h Fractile 5 dh Fractile 8 4th Fractile 95th Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 0.2109 4.847E-06 0.0536 2.053E-05 0.1059 6.763E-06 0.1690 5.939E-06 0.2553 4.996E-06 0.4167 2.197E-06 0.2236 4.168E-06 0.0565 1.776E-05 0.1123 5.818E-06 0.1793 5.149E-06 0.2705 4.304E-06 0.4398 1.882E-06 0.2370 3.581E-06 0.0595 1.534E-05 0.1191 5.009E-06 0.1901 4.459E-06 0.2866 3.703E-06 0.4643 1.612E-06 0.2513 3.073E-06 0.0626 1.322E-05 0.1264 4.315E-06 0.2017 3.858E-06 0.3037 3.180E-06 0.4902 1.379E-06 0.2664 2.635E-06 0.0660 1.137E-05 0.1340 3.719E-06 0.2139 3.335E-06 0.3217 2.727E-06 0.5174 1.179E-06 0.2824 2.256E-06 0.0695 9.752E-06 0.1422 3.206E-06 0.2269 2.878E-06 0.3409 2.334E-06 0.5462 1.008E-06 0.2993 1.930E-06 0.0731 8.349E-06 0.1508 2.764E-06 0.2407 2.481E-06 0.3612 1.994E-06 0.5766 8.608E-07 0.3173 1.648E-06 0.0770 7.131E-06 0.1599 2.383E-06 0.2553 2.136E-06 0.3827 1.701E-06 0.6087 7.350E-07 0.3364 1.405E-06 0.0811 6.077E-06 0.1696 2.053E-06 0.2708 1.835E-06 0.4054 1.449E-06 0.6426 6.275E-07 0.3566 1.197E-06 0.0854 5.167E-06 0.1799 1.768E-06 0.2872 1.574E-06 0.4296 1.232E-06 0.6783 5.355E-07 0.3780 1.017E-06 0.0899 4.383E-06 0.1908 1.521E-06 0.3047 1.348E-06 0.4551 1.046E-06 0.7161 4.570E-07 0.4008 8.632E-07 0.0947 3.710E-06 0.2024 1.306E-06 0.3231 1.152E-06 0.4822 8.865E-07 0.7559 3.899E-07 0.4248 7.312E-07 0.0997 3.133E-06 0.2147 1.120E-06 0.3428 9.821E-07 0.5109 7.502E-07 0.7980 3.326E-07 0.4504 6.182E-07 0.1050 2.640E-06 0.2277 9.590E-07 0.3636 8.354E-07 0.5413 6.338E-07 0.8424 2.836E-07 0.4774 5.216E-07 0.1106 2.220E-06 0.2415 8.191E-07 0.3856 7.088E-07 0.5735 5.346E-07 0.8892 2.419E-07 0.5061 4.393E-07 0.1165 1.863E-06 0.2562 6.980E-07 0.4090 5.998E-07 0.6077 4.502E-07 0.9387 2.062E-07 0.5365 3.692E-07 0.1227 1.560E-06 0.2717 5.931E-07 0.4339 5.063E-07 0.6438 3.785E-07 0.9909 1.757E-07 0.5688 3.097E-07 0.1292 1.304E-06 0.2882 5.026E-07 0.4602 4.261E-07 0.6822 3.178E-07 1.0461 1.496E-07 0.6030 2.592E-07 0.1360 1.087E-06 0.3057 4.246E-07 0.4881 3.575E-07 0.7228 2.663E-07 1.1043 1.273E-07 0.6392 2.165E-07 0.1432 9.049E-07 0.3243 3.576E-07 0.5177 2.991E-07 0.7658 2.228E-07 1.1657 1.082E-07 0.6776 1.805E-07 0.1509 7.515E-07 0.3439 3.001E-07 0.5492 2.495E-07 0.8114 1.861E-07 1.2306 9.187E-08 0.7183 1.502E-07 0.1589 6.227E-07 0.3648 2.51OE-07 0.5825 2.075E-07 0.8596 1.552E-07 1.2991 7.788E-08 0.7615 1.247E-07 0.1673 5.149E-07 0.3869 2.092E-07 0.6179 1.720E-07 0.9108 1.291E-07 1,3714 6.590E-08 0.8072 1.033E-07 0.1762 4.246E-07 0.4104 1.737E-07 0.6554 1.422E-07 0.9650 1.073E-07 1.4477 5.564E-08 0.8557 8.536E-08 0.1855 3.494E-07 0.4353 1.437E-07 0.6951 1.171E-07 1.0224 8.891E-08 1.5282 4.686E-08 0.9072 7.038E-08 0.1954 2.867E-07 0.4617 1.183E-07 0.7373 9.617E-08 1.0833 7.352E-08 1.6132 3.935E-08 0.9617 5.788E-08 0.2057 2.346E-07 0.4897 9.706E-08 0.7821 7.870E-08 1.1478 6.064E-08 1.7030 3.294E-08 1.0195 4.746E-08 0.2166 1.913E-07 0.5194 7.927E-08 0.8295 6.417E-08 1.2161 4.987E-08 1.7978 2.747E-08 1.0807 3.880E-08 0.2281 1.556E-07 0.5509 6.444E-08 0.8799 5.214E-08 1.2884 4.089E-08 1.8978 2.282E-08 1.1457 3.161E-08 0.2403 1.261E-07 0.5844 5.214E-08 0.9333 4.220E-08 1.3651 3.340E-08 2.0034 1.887E-08 1.2145 2.566E-08 0.2530 1.018E-07 0.6198 4.197E-08 0.9899 3.401E-08 1.4464 2.718E-08 2.1149 1.553E-08 1.2875 2.074E-08 0.2664 8.187E-08 0.6574 3.361E-08 1.0500 2.730E-08 1.5324 2.203E-08 2.2325 1.272E-08 1.3649 1.669E-08 0.2806 6.558E-08 0.6973 2.676E-08 1.1138 2.181E-08 1.6236 1.776E-08 2.3568 1.036E-08 1.4469 1.337E-08 0.2955 5.230E-08 0.7396 2.118E-08 1.1813 1.733E-08 1.7203 1.425E-08 2.4879 8.390E-09 1.5338 1.065E-08 0.3111 4.152E-08 0.7845 1.666E-08 1.2530 1.370E-08 1.8226 1.137E-08 2.6263 6.753E-09 1.6260 8.433E-09 0.3277 3.280E-08 0.8321 1.302E-08 1.3291 1.077E-08 1.9311 9.017E-09 2.7725 5.401E-09 1.7237 6.637E-09 0.3450 2.578E-08 0.8825 1.011E-08 1.4098 8.416E-09 2.0460 7.105E-09 2.9267 4.291E-09 1.8273 5.189E-09 0.3634 2.015E-08 0.9361 7.788E-09 1.4953 6.533E-09 2.1678 5.560E-09 3.0896 3.385E-09 1.9371 4.029E-09 0.3826 1.565E-08 0.9929 5.956E-09 1.5861 5.037E-09 2.2968 4.320E-09 3.2615 2.652E-09

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-21 Mean eh Fractile 16 h Fractile 5 dh Fractile 8 4th Fractile 95h Fractile PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE PSA (g)

AFE 2.0535 3.104E-09 0.4029 1.209E-08 1.0531 4.520E-09 1.6824 3.856E-09 2.4335 3.331 E-09 3.4430 2.062E-09 2.1769 2.373E-09 0.4243 9.279E-09 1.1170 3.402E-09 1.7845 2.929E-09 2.5783 2.548E-09 3.6345 1.591E-09 2.3077 1.800E-09 0.4469 7.073E-09 1.1848 2.540E-09 1.8928 2.207E-09 2.7318 1.933E-09 3.8368 1.218E-09 2.4463 1.353E-09 0.4706 5.354E-09 1.2567 1.879E-09 2.0076 1.649E-09 2.8944 1.454E-09 4.0502 9.245E-10 2.5933 1.008E-09 0.4955 4.023E-09 1.3329 1.378E-09 2.1295 1.222E-09 3.0666 1.084E-09 4.2756 6.961E-10 2.7492 7.442E-10 0.5218 3.000E-09 1.4138 1.002E-09 2.2587 8.969E-10 3.2491 8.004E-10 4.5135 5.197E-10 2.9144 5.442E-10 0.5495 2.219E-09 1.4995 7.211E-10 2.3958 6.523E-10 3.4425 5.856E-10 4.7646 3.846E-10 3.0895 3.941E-10 0.5787 1.628E-09 1.5905 5.141E-10 2.5412 4.699E-10 3.6474 4.243E-10 5.0298 2.821E-10 3.2751 2.825E-10 0.6094 1.185E-09 1.6870 3.629E-10 2.6955 3.351E-10 3.8644 3.043E-10 5.3096 2.051E-10 3.4719 2.005E-10 0.6418 8.544E-10 1.7893 2.536E-10 2.8591 2.365E-10 4.0944 2.161E-10 5.6051 1.477E-10 3.6806 1.407E-10 0.6758 6.106E-10 1.8979 1.754E-10 3.0326 1.652E-10 4.3381 1.519E-10 5.9169 1.054E-10 3.9017 9.776E-11 0.7117 4.324E-10 2.0130 1.201E-10 3.2167 1.142E-10 4.5963 1.056E-10 6.2462 7.451E-11 4.1362 6.717E-11 0.7495 3.032E-10 2.1352 8.131E-11 3.4119 7.808E-11 4.8698 7.263E-11 6.5937 5.217E-11 4.3848 4.564E-11 0.7892 2.106E-10 2.2647 5.447E-11 3.6190 5.279E-11 5.1596 4.942E-11 6.9606 3.617E-11 4.6482 3.066E-11 0.8311 1.448E-10 2.4021 3.609E-11 3.8386 3.529E-11 5.4667 3.325E-11 7.3479 2.483E-11 4.9276 2.036E-11 0.8752 9.858E-11 2.5478 2.365E-11 4.0716 2.332E-11 5.7920 2.213E-11 7.7567 1.688E-11 5.2237 1.337E-11 0.9217 6.641E-11 2.7024 1.532E-11 4.3187 1.523E-11 6.1367 1.456E-11 8.1883 1.136E-11 5.5375 8.676E-12 0.9706 4.427E-11 2.8664 9.815E-12 4.5808 9.834E-12 6.5019 9.468E-12 8.6440 7.566E-12 5.8703 5.564E-12 1.0221 2.919E-11 3.0403 6.215E-12 4.8589 6.273E-12 6.8889 6.087E-12 9.1249 4.989E-12 6.2230 3.526E-12 1.0763 1.904E-11 3.2247 3.890E-12 5.1538 3.954E-12 7.2989 3.868E-12 9.6326 3.256E-12 6.5970 2.208E-12 1.1335 1.229E-11 3.4203 2.406E-12 5.4666 2.462E-12 7.7333 2.430E-12 10.1686 2.103E-12 6.9934 1.366E-12 1.1936 7.841E-12 3.6278 1.471E-12 5.7983 1.515E-12 8.1935 1.508E-12 10.7344 1.345E-12 7.4137 8.350E-13 1.2570 4.948E-12 3.8479 8.888E-13 6.1503 9.206E-13 8.6811 9.252E-13 11.3317 8.507E-13

Seismic Hazard and Screening Report - Farley to NL-14-0342 Page A-22 Table A-2. Weighted average median and logarithmic standard deviation of amplification factors for Farlev Units 1 and 2.

0.5 Hz 1.0 Hz 2.5 Hz 5.0 Hz Motion Input Log Input Log Input Log Input Log Name PSA(g) Median SD PSA (g) Median SD PSA (g) Median SD PSA (g) Median SD HF3 0.0027 1.926 0.271 0.0070 2.154 0.421 0.0200 2.721 0.360 0.0226 1.900 0.317 LF3 0.0103 1.864 0.267 0.0153 2.071 0.423 0.0201 2.620 0.346 0.0226 1.832 0.287 HF4 0.0069 1.918 0.267 0.0182 2.152 0.426 0.0518 2.563 0.344 0.0659 1.686 0.332 LF4 0.0313 1.869 0.275 0.0407 2.086 0.422 0.0520 2.428 0.324 0.0659 1.601 0.304 HF5 0.0129 1.942 0.261 0.0368 2.155 0.410 0.1149 2.334 0.319 0.1860 1.448 0.363 LF5 0.0653 1.912 0.312 0.0825 2.069 0.405 0.1153 2.200 0.333 0.1620 1.352 0.362 HF6 0.0331 1.930 0.277 0.0957 2.127 0.393 0.3010 2.032 0.326 0.5789 1.118 0.435 LF6 0.1219 1.966 0.352 0.1580 1.998 0.395 0.3011 1.791 0.450 0.4200 1.029 0.501 HF7 0.0910 2.043 0.351 0.2628 2.048 0.391 0.8262 1.556 0.446 1.5355 0.763 0.600 LF7 0.2333 2.013 0.363 0.3498 1.793 0.431 0.8260 1.241 0.634 1.1542 0.656 0.673 10.0 Hz Motion Input Name PSA (q)

Log SD 25.0 Hz Input PSA (a) Median 100.0 Hz (PGA)

Log SD Input PSA (a)

Log Median SD Median HF3 0.0255 1.156 0.396 0.0230 0.915 0.339 0.0125 1.564 0.302 LF3 0.0255 1.165 0.342 0.0230 0.995 0.299 0.0125 1.740 0.281 HF4 0.0848 0.922 0.416 0.0874 0.621 0.348 0.0423 1.178 0.295 LF4 0.0848 0.920 0.344 0.0873 0.683 0.280 0.0423 1.330 0.249 HF5 0.2830 0.703 0.471 0.3431 0.381 0.400 0.1670 0.705 0.318 LF5 0.2020 0.770 0.355 0.2290 0.532 0.269 0.1010 1.144 0.230 HF6 0.9690 0.479 0.559 1.2801 0.237 0.437 0.6120 0.453 0.358 LF6 0.5210 0.580 0.441 0.5929 0.408 0.311 0.2610 0.892 0.277 HF7 2.5253 0.316 0.654 3.4200 0.168 0.487 1.6122 0.338 0.440 LF7 1.4314 0.378 0.550 1.6283 0.281 0.414 0.7155 0.624 0.393