MONTHYEARML11209B7092011-07-22022 July 2011 Submittal of Summary Report for Inservice Inspections (2R11) Project stage: Request ML11255A0322011-09-15015 September 2011 Plan for the Scoping and Screening Regulatory Audit Regarding the Limerick Generating Station, Units 1 and 2 License Renewal Application Review (TAC Nos. ME6555, ME6556) Project stage: Other ML11258A1092011-09-20020 September 2011 Plan for the Aging Management Program Regulatory Audit Regarding the Limerick Generating Station, Units 1 and 2 License Renewal Application Review Project stage: Other ML1134101442011-12-0707 December 2011 Response to NRC Request for Additional Information, Dated November 18, 2011 Project stage: Response to RAI ML11342A2052011-12-0909 December 2011 Scoping and Screening Methodology Audit Report Regarding the Limerick Generating Station, Units 1 and 2 Project stage: Other ML1133402312011-12-12012 December 2011 Request for Additional Information for Limerick Generating Station, Units 1 and 2 License Renewal Application-Scoping and Screening (TAC Nos. ME6555 and ME6556) Project stage: RAI ML11343A4382011-12-15015 December 2011 Requests for Additional Information for the Review of the Limerick Generating Station License Renewal Application (TAC ME6555, ME6556) Project stage: RAI ML11335A3172012-01-0505 January 2012 RAI for the Review of the Limerick Generating Station License Renewal Application (TAC Nos. ME6555, ME6556) Project stage: RAI ML11347A3602012-01-17017 January 2012 Requests for Additional Information for the Review of the Limerick Generating Station License Renewal Application (TAC Nos. ME6555, ME6556) Project stage: RAI ML11361A0832012-01-18018 January 2012 Requests for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555, ME6556) Project stage: RAI ML11361A0792012-01-24024 January 2012 Requests for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555, ME6556) Project stage: RAI ML11364A0992012-01-30030 January 2012 Requests for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555, ME6556) Project stage: RAI ML12163A7532012-01-31031 January 2012 2012/01/31 Limerick Lr - FW: Request for Additional Information for the Review of the Limerick Generation Station, Units 1 and 2 License Renewal Application (TAC Nos. ME6555 and ME6556) Project stage: Request ML12005A2512012-01-31031 January 2012 Request for Additional Information for the Review of the Limerick Generating Station Units 1 and 2 License Renewal Application (TAC Nos. ME6555, ME6556) TLAA 43 and 468 RAIs Project stage: RAI ML12018A0332012-02-14014 February 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555, ME6556) Rapb AMR2 RAIs Project stage: RAI ML12017A1592012-02-16016 February 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) Project stage: RAI ML12024A2312012-02-16016 February 2012 Requests for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) OE and Other RAIs Project stage: RAI ML1204703722012-02-16016 February 2012 Response to NRC Request for Additional Information, Dated January 17, 2012 Project stage: Response to RAI ML12019A1562012-02-17017 February 2012 Requests for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC ME6555 and ME6556) Project stage: RAI ML12018A0352012-02-23023 February 2012 Requests for Addtional Information for the Review of the Limerick Generating Station, Units 1 & 2, License Renewal Application (TAC ME6555 and ME6556) Project stage: Approval ML12059A3452012-02-28028 February 2012 Response to NRC Request for Additional Information, Dated January 30, 2012, Related to License Renewal Application Project stage: Response to RAI ML12018A3322012-02-28028 February 2012 Letter Aging Management Programs Audit Report Regarding the Limerick Generating Station, Units 1 and 2 (TAC NO.ME6555 & ME6556) Project stage: Other ML12065A2062012-03-0505 March 2012 Response to NRC Requests for Additional Information, Dated February 16, 2012, and February 17, 2012, Related to Renewal Application Project stage: Response to RAI ML12046A8992012-03-0909 March 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) Limerick App J RAIs Project stage: RAI ML12009A1352012-03-0909 March 2012 Summary of the Telephone Conference Call Held on December 14, 2011, Between the U.S. Nuclear Regulatory Commission and Exelon on Generation Company, LLC, Concerning Requests for Additional Information Pertaining to the Limerick 12-14-11 Tel Project stage: RAI ML1207303612012-03-13013 March 2012 Response to NRC Requests for Additional Information, Dated February 14 and February 16, 2012, Related to the Limerick Generating Station License Renewal Application Project stage: Response to RAI ML12080A1182012-03-20020 March 2012 Response to NRC Requests for Additional Information, Dated February 23 and March 9, 2012, Related to License Renewal Application Project stage: Response to RAI ML12074A0372012-03-22022 March 2012 Letter Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555, ME6556) Buried Piping and FP Follow Up Project stage: RAI ML12090A4892012-03-30030 March 2012 Response to NRC Request for Additional Information, Dated March 22, 2012 and Information Addressing Minor Errors or Omissions Related to License Renewal Application Project stage: Response to RAI ML12080A1902012-04-0505 April 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) BWR SCC Smp and Ctws Follow Up Project stage: RAI ML12066A0262012-04-0909 April 2012 February 9, 2012, Summary of Telephone Conference Call Held Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, Llc. Concerning Request for Additional Information Pertaining to the Limerick Project stage: RAI ML12089A3772012-04-13013 April 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6556 and ME6555) Fluence and FP Followup RAIs Project stage: RAI ML12104A1182012-04-13013 April 2012 Response to NRC Requests for Additional Information, Dated April 5, 2012, Related to License Renewal Application Project stage: Response to RAI ML12082A1552012-04-16016 April 2012 Requests for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) Project stage: RAI ML12095A3982012-04-17017 April 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos ME6555 and ME6556)TLAA Follow-up RAIs Project stage: RAI ML12025A0512012-04-20020 April 2012 Summary of Telephone Conference Call Held on January 18, 2012, Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Request for Additional Information Pertaining to the Limerick Generation 1-18-12 Te Project stage: RAI ML12059A0802012-04-20020 April 2012 February 17, 2012, Summary of Telephone Conference Call Held Between U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Request for Additional Information Pertaining to the Limerick 2-17-12 Telecon Summary Project stage: RAI ML12018A0232012-04-26026 April 2012 1/12/2012 Telecon Summary Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Requests for Additional Information Pertaining to the Limerick Generating Station, License Renewal Application Project stage: RAI ML12111A0342012-04-30030 April 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556)SCC RAIs Project stage: RAI ML12125A3342012-05-0404 May 2012 Responses to NRC Requests for Additional Information, Dated April 17, 2012, Related to the License Renewal Application Project stage: Response to RAI ML12128A4382012-05-0707 May 2012 Responses to NRC Requests for Additional Information, Dated April 30, 2012, Related to the License Renewal Application Project stage: Response to RAI ML12152A3092012-05-31031 May 2012 Responses to NRC Requests for Additional Information, Dated May 18, 2012, Related to the License Renewal Application Project stage: Response to RAI ML12139A0662012-06-0707 June 2012 4-30-12 Telecon Summary Project stage: Other ML12157A2122012-06-12012 June 2012 Requests for Additional Information for the Review of the Limerick Generating Stations, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) Ope Follow-up RAI Project stage: RAI ML12152A3052012-06-12012 June 2012 Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555, ME6556) Project stage: RAI ML12171A4872012-06-19019 June 2012 Responses to NRC Requests for Additional Information, Dated June 12, 2012, Related to the Limerick Generating Station License Renewal Application Project stage: Response to RAI ML12174A3292012-06-22022 June 2012 Response to NRC Request for Additional Information, Dated June 21, 2012, Related to License Renewal Application Project stage: Response to RAI ML12139A0612012-06-25025 June 2012 Summary of Telephone Conference Call Held on May 16, 2012, Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Requests for Additional Information Pertaining to the Limerick Generating Station, Lice Project stage: RAI ML12193A1282012-07-10010 July 2012 2012/07/10 Limerick Lr - FW: Limerick: Request for Additional Information for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC Nos. ME6555 and ME6556) Project stage: Request ML12181A4412012-07-10010 July 2012 RAI for the Review of the Limerick Generating Station, Units 1 and 2, License Renewal Application (TAC No. ME6555 and ME6556) Project stage: RAI 2012-03-22
[Table View] |
|
---|
Category:Meeting Summary
MONTHYEARML23320A2472023-11-17017 November 2023 Constellation - Summary of November 14, 2023, Public Pre-Application Meeting with Constellation Energy Generation, LLC on Adoption of TSTF-591 ML23263B1062023-09-22022 September 2023 R. E. Ginna Nuclear Power Plant - Constellation - Pre-Application Amse 9/18/2023 Meeting Summary ML23236A5132023-08-31031 August 2023 Summary of Meeting with Constellation Energy Generation, LLC Regarding Digital Modernization License Amendment Request ML23179A0012023-06-28028 June 2023 6/7/2023 - Annual Assessment Meeting for Pa/Md/Ny/Nj Nuclear Power Plants - Meeting Summary ML23156A2472023-06-0909 June 2023 Summary of Meeting with Constellation Energy Generation, LLC Regarding Digital Modernization License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23118A3752023-06-0909 June 2023 Summary of Audit Meeting with Constellation Energy Generation Concerning a Digital Instrumentation and Control Upgrade License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23145A0352023-05-31031 May 2023 Summary of May 17, 2023, Meeting with Constellation Energy Generation, LLC Regarding Digital Modernization License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23132A3082023-05-18018 May 2023 Summary of May 3, 2023, Audit Meeting with Constellation Energy Generation Concerning a Digital Instrumentation and Control Upgrade License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23076A0132023-05-12012 May 2023 March 15, 2023, Summary of Audit Meeting with Constellation Energy Generation Concerning a Digital Instrumentation and Control Upgrade License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23076A1042023-05-12012 May 2023 Summary of Audit Meeting with Constellation Energy Generation Concerning a Digital Instrumentation and Control Upgrade License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23121A0022023-05-12012 May 2023 Summary of March 29, 2023, Audit Meeting with Constellation Energy Generation Concerning a Digital Instrumentation and Control Upgrade License Amendment Request for Limerick Generating Station, Units 1 and 2 ML23076A2802023-03-28028 March 2023 Summary of February 23, 2023, Public Observation Meeting with Constellation Energy Generation, LLC Re. Proposed License Amendment Request to Modify 10 CFR 50.69 License Conditions ML23055A0352023-03-24024 March 2023 Summary of February 23, 2023, with Constellation Energy Generation, LLC on Proposed Changes to Emergency Plans to Revise Emergency Action Levels ML23030A0092023-02-10010 February 2023 January 10, 2023, Summary of Meeting with Constellation Energy Generation, LLC, on Planned Limerick Digital Modernization Project Installation Support License Amendment Request and Exemption Request ML23009A5872023-01-11011 January 2023 Summary of December 15, 2022, Meeting with Constellation Energy Generation, LLC on Potential Compliance with Certain Clauses of IEEE Standard 603-1991 in Limerick Digital Instrumentation and Controls License Amendment Requests ML22327A0192022-12-0606 December 2022 Summary of November 10, 2022, Meeting with Constellation Energy Generation, Lic on Acceptance Review of Limerick Digital Instrumentation and Controls License Amendment Requests ML22227A1112022-08-25025 August 2022 Summary of June 24, 2022, Public Observation Meeting with Constellation Energy Generation, LLC Proposed License Amendment Request to Modify 10 CFR 50.69 License Conditions ML22187A1462022-07-0606 July 2022 Joint Annual Assessment Meeting for Pa/Md/Nj/Ny Nuclear Power Plants - Meeting Summary ML22168A1922022-06-24024 June 2022 Summary of May 3, 2022, Public Observation Meeting with Constellation Energy Generation, LLC Re. Proposed License Amendment Request to Modify 10 CFR 50.69 License Conditions ML22038A0992022-02-23023 February 2022 Summary of January 11, 2022, Public Meeting with Exelon Generation Company, LLC Regarding Planned Digital Modernization License Amendment Request ML22021B2942022-02-0202 February 2022 Summary of December 7, 2021, Public Meeting with Exelon Generation Company, LLC Regarding Planned Digital Modernization License Amendment ML21333A1532021-11-30030 November 2021 Summary of November 16, 2021, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alternative to Extend the Inservice Inspection Interval ML21301A1612021-11-15015 November 2021 Summary of June 29, 2021, Public Meeting with Exelon Generation Company, LLC Regarding Planned Digital Modernization License Amendment Request for Limerick Generating Station, Units 1 and 2 ML21294A3692021-11-15015 November 2021 Summary of October 6, 2021, Public Observation Meeting with Exelon Generation Company, LLC Proposed License Amendment Request to Modify Emergency Diesel Generator and Emregency Core Cooling System Surveillance Requirements ML21300A2772021-11-0909 November 2021 Summary of October 20, 2021, Pre-Submittal Public Teams Meeting with Exelon Generation Company, LLC Regarding Planned Digital Modernization License Amendment Request ML21294A3792021-10-0606 October 2021 WCAP-17308 Implementation Licensing Amendment Request Pre-Submittal Meeting Presentation, October 6, 2021 ML21237A0412021-08-30030 August 2021 Summary of the July 27, 2021, Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Use Case OMN-28, ML21176A0822021-07-0606 July 2021 June 15, 2021, Summary of Meeting with Exelon Generation Company, LLC Vessel Nozzle Repair Related to a Planned Request for an Alternative Related to Reactor Pressure ML21139A1852021-06-22022 June 2021 Summary of Meeting with Exelon Generation Company, LLC Regarding Its Requested Alternative to Eliminate Certain Documentation Requirements for the Replacement of Pressure Retaining Bolting ML21123A1362021-05-13013 May 2021 Summary of March 16, 2021, Public Webinar with Exelon Generation Company, LLC Regarding Planned Digital Modernization License Amendment Request ML21071A1022021-03-24024 March 2021 Summary of the February 23, 2021, Meeting with Exelon Regarding a Future License Amendment Request Related to Implementing an Alternative Categorization Process Under the Requirements of 10 CFR 50.69 ML21011A2822021-01-21021 January 2021 Summary of January 6, 2021, Presubmittal Meeting Between the NRC and Exelon Generation Company, LLC Regarding Licensing Activities to Support the Planned Early Closures of Byron, Unit Nos. 1 and 2 and Dresden, Units 2 and 3 ML20351A2832020-12-18018 December 2020 Summary of Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Exemption to Reduce the Frequency of Updates to Its Inservice Testing and Inspection Programs ML20342A3522020-12-10010 December 2020 Summary of November 13, 2020, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alterantive to Certain Documentation Requirements for the Replacement of Pressure Retaining Bolting (EPID-L-2020-LRM-0102) ML20323A0332020-12-0101 December 2020 Summary of November 4, 2020, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alternative to Reduce the Frequency of Updates to Its Inservice Testing and Inspection Programs ML20197A2722020-07-15015 July 2020 2020 Beaver Valley, Calvert Cliffs, Limerick Peach Bottom, Susquehanna Annual Assessment Webinar Summary ML20175A2402020-06-30030 June 2020 Summary of June 12, 2020, Public Telephone Conference with Exelon Generation Company, LLC Regarding Planned Digital Modernization License Amendment Request ML20181A0002020-06-29029 June 2020 Summary of 6/24/20 Meeting with Exelon Generation Company, LLC Regarding Planned Request for Alternative to Supplemental Valve Position Indication Testing Requirements for Braidwood, Calvert Cliffs, Clinton, Limerick, Nine Mile, Peach Botto ML19326A3152019-12-0303 December 2019 Summary of November 18, 2019, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alternative to Supplemental Valve Position Indication Testing Requirements ML19326C3582019-12-0303 December 2019 Summary of November 20, 2019, Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Revise the Quality Assurance Program ML19191A1882019-07-0909 July 2019 Joint Annual Assessment Meeting (Webinar) for Pennsylvania Power Plants - Meeting Summary ML19162A0272019-06-21021 June 2019 Summary of June 4, 2019, Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Extend the Test Interval for Safety Relief Valves ML20108F0902019-04-20020 April 2019 April 15, 2020, Meeting Summary with Exelon Generation Company, LLC Regarding Planned Request to Defer Submittal of Owner'S Activity Report (Braidwood 2,Byron 2,Calvert Cliffs 1, LaSalle 1, Limerick 1, Nine Mile Point 2, Quad 2, R. E. Ginna ML19036A8832019-02-0707 February 2019 Summary of Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Use ASME Code Case N-879 ML18354B1712019-01-0202 January 2019 Summary of December 19, 2018, Meeting with Exelon Generation Company, LLC Regarding the Use of Boiling Water Reactor Vessel and Internals Project Guidelines ML18325A1712018-11-28028 November 2018 Summary of Meeting with Exelon Generation Company, LLC Regarding Planned Fleet License Amendment Request to Revise Technical Specifications for High Radiation Areas ML18297A1722018-10-26026 October 2018 Summary of Meeting with Exelon Generation Company, LLC Regarding Planned License Amendment Request to Adopt TSTF-427 ML18138A3442018-05-22022 May 2018 2018 Limerick Summary of Public Meeting and Attendance List ML18120A1772018-05-0101 May 2018 Summary of Meeting with Exelon Generation Company, LLC Regarding Draft Guidance for Emergency Response Organization Staffing ML18110A0122018-04-25025 April 2018 April 12, 2018, Summary of Meeting with Exelon Generation Company, Limerick, Units 1 and 2 - Regarding Their License Amendment Application for 10.CFR.50.69 Risk Informed Categorization of Structures Systems and Components. 2023-09-22
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555*0001 April 20, 2012 LICENSEE: Exelon Generation Company, LLC FACILITY: Limerick Generating Station
SUBJECT:
SUMMARY
OF TELEPHONE CONFERENCE CALL HELD ON JANUARY 18, 2012, BE1WEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND EXELON GENERATION COMPANY, LLC, CONCERNING REQUESTS FOR ADDITIONAL INFORMATION PERTAINING TO THE LIMERICK GENERATING STATION, LICENSE RENEWAL APPLICATION (TAC. NOS. ME6555 AND ME6556)
The U.S. Nuclear Regulatory Commission (NRC or the staff) and representatives of Exelon Generation Company, LLC held a telephone conference call on January 18, 2012, to discuss and clarify the staff's requests for additional information (RAls) concerning the Limerick Generating Station, license renewal application. The telephone conference call was useful in clarifying the intent of the staff's RAls. provides a listing of the participants and Enclosure 2 contains a listing of the RAls discussed with the applicant, including a brief description on the status of the items.
The applicant had an opportunity to comment on this summary.
, ;)
<:~:~c!12tz, Projects Branch 1 Senior Project Manager Division of License Renewal Office of Nuclear Reactor Regulation Docket Nos. 50-352 and 50-353
Enclosures:
- 1. List of Participants
- 2. List of Requests for Additional Information cc w/encls: Listserv
TELEPHONE CONFERENCE CALL LIMERICK GENERATING STATION LICENSE RENEWAL APPLICATION LIST OF PARTICIPANTS January 18, 2011 PARTICIPANTS AFFILIATIONS Robert Kuntz Nuclear Regulatory Commission (NRC)
Naeem Iqbal NRC Gene Kelly Exelon Generation Company, LLC (Exelon)
Christopher Wilson Exelon Albert Fulvio Exelon Ron Hess Exelon Dave Clohecy Exelon ENCLOSURE 1
ORAl 2.3.3.9-1 The staff notes that license renewal boundary drawing LR-M-22, Sheet 5, at location F3, shows the cable spreading room's fire walls and associated components including fire doors, fire dampers, and penetration seals as out of scope (Le., not colored in green). The staff requests that the applicant verify whether the cable spreading rooms fire walls and associated components are in the scope of license renewal in accordance with 10 CFR 54.4(a) and whether they are subject to an aging management review (AMR) in accordance with 10 CFR 54.21 (a)(1). The staff requested that, if these fire walls and associated components are excluded from the scope of license renewal and are not subject to an AMR, the applicant provide justification for the exclusion.
Discussion: The applicant indicated that the request is clear. This ORAl will be sent as a formal RAI.
ORAl 2.3.3.9-2 The following license renewal application (LRA) boundary drawings shows the following fire protection systems/components as out of scope (i.e., not colored in green):
LRA Drawing Systems/Coml2onents Location Fire water suppression systems associated with LR-M-22, Sheet 2 Safeguard Transformer (OAX103), Auxiliary H3 Transformer (10X102), and Spare Transformer (10X101)
Fire water suppression systems associated with LR-M-22, Sheet 2 Unit 1 Main Transformers (1AX101), (1BX101), and H4 (1CX101)
Fire water suppression systems associated with LR-M-22, Sheet 4 Safeguard Transformer (OBX1 03), and Auxiliary H3 Transformer (20X 102)
Fire water suppression systems associated with LR-M-22, Sheet 4 Unit 2 Main Transformers (2AX101), (2BX101), and H3 (2CX1 01)
The staff requests that the applicant verify whether the fire protection systems/components listed above are in the scope of license renewal in accordance with 10 CFR 54.4(a) and whether they are subject to an AMR in accordance with 10 CFR 54.21(a)(1). If they are excluded from the scope of license renewal and are not subject to an AMR, the staff requests that the applicant provide justification for the exclusion.
Discussion: The applicant clarified on the conference call that the drawings did not indicate structures within the scope of license renewal and that items discussed in the RAI are included in the scope of license renewal. The staff verified in the drawings that the drawings specifically noted that structures were not colored to annotate inclusion within the scope of license renewal and also verified the description in the LRA was adequate. Therefore, the staff will not issue this ORAl because sufficient information exist on the docket to satisfy the staff's concern.
ENCLOSURE 2
-2 ORAl 2.3.3.9-3 The source of water for the fire protection system at Limerick Generating Station, Units 1 and 2 is a pair of cooling tower basins, each of which has a capacity of 7,200,000 gallons. Section 9.5.1.6.7, Supplement No.2, NUREG-0991, "Safety Evaluation Report related to the operation of Limerick Generating Station, Units 1 and 2," dated October 1984, states that suction lines to the fire pump are arranged so that if one of the cooling towers becomes unavailable, the suction line can be switched to the functional tower.
The staff requests that the applicant verify whether the fire protection water supply components including suction lines to the fire pump and valves are in the scope of license renewal in accordance with 10 CFR 54.4(a) and subject to an AMR in accordance with 10 CFR 54.21(a)(1). If they are excluded from the scope of license renewal and not subject to an AMR, the staff requests that the applicant provide justification for the exclusion.
Discussion: The applicant clarified on the conference call that the drawings LR-M-9, Sheets 3, 8, and 9 highlight fire protection water supply components including suction lines to the fire pump and valves. The staff verified that the fire protection water supply components including suction lines to the fire pump and valves in question are highlighted and colored in green on the drawings LR-M-9, Sheets 3, 8, and 9. Therefore, the staff will not issue this ORAl because sufficient information exists on the docket to satisfy the staff's concern.
ORAl 2.3.3.9-4 LRA Tables 2.3.3-9 and 3.3.2-9 of the LRA do not include the following fire protection components:
- fire hose stations, fire hose connections, and hose racks
- fire protection water curtain systems in the reactor enclosures and hatchways
- floor drains for fire water
- passive components in fire protection water and foam solution storage tank heat exchangers
- fire retardant coating (fireproofing material) for structural steel members
- passive components in diesel driven fire pump engine
- passive components in lighting plant protection system (NFPA 78, Lighting Protection Code)
The staff requests that the applicant verify whether the fire protection components listed above are in the scope of license renewal in accordance with 10 CFR 54.4(a) and whether they are subject to an AMR in accordance with 10 CFR 54.21 (a)(1). If they are excluded from the scope of license renewal and are not subject to an AMR, the staff requests that the applicant provide justification for the exclusion.
Discussion: The applicant indicated that the request is clear. This ORAl will be sent as a formal RAI. This RAI will be renumbered and will be issued as RAI 2.3.3.9-2 to account for the deletion of ORAl 2.3.3.9-2 and ORAl 2.3.3.9-3 as discussed above.
ORAl 2.3.3.9-5 Section 2.4, "Scoping and Screening Results: Structures," of the LRA provides the scoping and screening results of various structures within the scope of license renewal and subject to an AMR. Further, Section 2.4 states that the fire barriers are evaluated separately with the Fire Protection System, LRA Section 2.3.3.9. LRA Table 2.3.3.9, includes fire barriers (doors), fire barriers (fire rated enclosures), fire barriers (for steel components), fire barriers (penetration seals), fire barriers (walls and slabs), that are supject to an AMR. The staff requests that the applicant provide a summary of the list of buildings or structures where fire barriers are credited, and the specific types of barriers at these locations in the plant's fire protection program.
Discussion: The applicant indicated that the request is clear. This ORAl will be sent as a formal RAI. This RAI will be renumbered and will be issued as RAI 2.3.3.9-3 to account for the deletion of ORAl 2.3.3.9-2 and ORAl 2.3.3.9-3 as discussed above.
SUBJECT:
Summary of Telephone Conference Call conducted on December 13, 2011 DISTRIBUTION:
HARD COPY:
DLR RF E-MAIL:
PUBLIC [or NON-PUBLIC, if applicable]
RidsNrrDlr Resource RidsNrrDlrRpb1 Resource RidsNrrDlrRpb2 Resource RidsNrrDlrRerb Resource RidsNrrDlrRarb Resource RidsNrrDlrRasb Resource RidsNrrDlrRapb Resource RidsNrrDlrRpob Resource RidsNrrPNILimerick Resource RidsOgcMailCenter Resource RKuntz DMorey LPerkins MSmith,OGC RConte, RI MModes, RI DiPaolo, RI NSielier, RI
LICENSEE: Exelon Generation Company, LLC FACILITY: Limerick Generating Station
SUBJECT:
SUMMARY
OF TELEPHONE CONFERENCE CALL HELD ON JANUARY 18, 2012, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND EXELON GENERATION COMPANY, LLC, CONCERNING REQUESTS FOR ADDITIONAL INFORMATION PERTAINING TO THE LIMERICK GENERATING STATION, LICENSE RENEWAL APPLICATION (TAC. NOS. ME6555 AND ME6556)
The U.S. Nuclear Regulatory Commission (NRC or the staff) and representatives of Exelon Generation Company, LLC held a telephone conference call on January 18, 2012, to discuss and clarify the staff's requests for additional information (RAls) concerning the Limerick Generating Station, license renewal application. The telephone conference call was useful in clarifying the intent of the staff's RAls.
Enclosure 1 provides a listing of the participants and Enclosure 2 contains a listing of the RAls discussed with the applicant, including a brief description on the status of the items.
The applicant had an opportunity to comment on this summary.
IRA!
Robert F. Kuntz, Senior Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket Nos. 50-352 and 50-353